REMOTE CONTROL RC-EX3

INSTALLATION MANUAL

PJZ012D120
201705
Contents
1. Safety precautions……………………………………………………… 4

2 . Accessories & Prepare on site………………………………………… 5

3. Installation place………………………………………………………… 6

4. Installation procedure…………………………………………………… 6

5. Main/Sub setting when more than one remote controls are used………… 8

6. Functions and menu items of the remote control………………………… 9

7. Main item……………………………………………………………… 11

8. Power on and initial setting…………………………………………… 13

9. Installation settings and test run……………………………………… 15

10. R/C function settings………………………………………………… 18

11. IU settings…………………………………………………………… 21

12. Service & Maintenance……………………………………………… 29

13. Select the language………………………………………………… 33

−3−
1. Safety precautions
●Please read this manual carefully before starting installation work to install the unit properly.
Every one of the followings is important information to be observed strictly.
WA R N I N G Failure to follow these instructions properly may result in serious consequences such as death, severe injury, etc.
C A U T I O N Failure to follow these instructions properly may cause injury or property damage.
It could have serious consequences depending on the circumstances.
●The following pictograms are used in the text.
Never do. Always follow the instructions given.

●Keep this manual at a safe place where you can consult with whenever necessary. Show this manual to installers when moving or repairing the
unit. When the ownership of the unit is transferred, this manual should be given to a new owner.

WA R N I N G
●C
 onsult your dealer or a professional contractor to install the unit.
Improper installation made on your own may cause electric shocks, fire or dropping of the unit.
● Installation work should be performed properly according to this installation manual.
Improper installation work may result in electric shocks, fire or break-down.
● Be sure to use accessories and specified parts for installation work.
Use of unspecified parts may result in drop, fire or electric shocks.
● Install the unit properly to a place with sufficient strength to hold the weight.
If the place is not strong enough, the unit may drop and cause injury.
● Be sure to have the electrical wiring work done by qualified electrical installer, and use
exclusive circuit.
Power source with insufficient and improper work can cause electric shock and fire.
● Shut OFF the main power supply before starting electrical work.
Otherwise, it could result in electric shocks, break-down or malfunction.
● Do not modify the unit.
It could cause electric shocks, fire, or break-down.
● Be sure to turn OFF the power circuit breaker before repairing/inspecting the unit.
Repairing/inspecting the unit with the power circuit breaker turned ON could cause electric shocks or injury.
● Do not install the unit in appropriate environment or where inflammable gas could generate,
flow in, accumulate or leak.
If the unit is used at places where air contains dense oil mist, steam, organic solvent vapor, corrosive gas (ammonium,
sulfuric compound, acid, etc) or where acidic or alkaline solution, special spray, etc. are used, it could cause electric shocks,
break-down, smoke or fire as a result of significant deterioration of its performance or corrosion.
● Do not install the unit where water vapor is generated excessively or condensation occurs.
It could cause electric shocks, fire, or break-down.
● Do not use the unit in a place where it gets wet, such as laundry room.
It could cause electric shocks, fire, or break-down.
● Do not operate the unit with wet hands.
It could cause electric shocks.
● Do not wash the unit with water.
It could cause electric shocks, fire, or break-down.
● Use the specified cables for wiring, and connect them securely with care to protect electronic
parts from external forces.
Improper connections or fixing could cause heat generation, fire, etc.
● Seal the inlet hole for remote control cable with putty.
If dew, water, insect, etc. enters through the hole, it could cause electric shocks, fire or break-down.
If dew or water enters the unit, it may cause screen display anomalies.

−4−
WA R N I N G
● When installing the unit at a hospital, telecommunication facility, etc., take measures to
suppress electric noises.
It could cause malfunction or break-down due to hazardous effects on the inverter, private power generator, high frequency
medical equipment, radio communication equipment, etc.
The influences transmitted from the remote control to medical or communication equipment could disrupt medical activities,
video broadcasting or cause noise interference.
● Do not leave the remote control with its upper case removed.
If dew, water, insect, etc. enters through the hole, it could cause electric shocks, fire or break-down.

CAUTION
● Do not install the remote control at following places.
(1) It could cause break-down or deformation of remote control.
・Where it is exposed to direct sunlight
・Where the ambient temperature becomes 0 °C or below, or 40 °C or above
・Where the surface is not flat
・Where the strength of installation area is insufficient
(2) M oisture may be attached to internal parts of the remote controller, resulting in a display failure.
・Place with high humidity where condensation occurs on the remote controller
・Where the remote controller gets wet
(3) A ccurate room temperature may not be detected using the temperature sensor of the remote controller.
・Where the average room temperature cannot be detected
・Place near the equipment to generate heat
・Place affected by outside air in opening/closing the door
・Place exposed to direct sunlight or wind from air conditioner
・Where the difference between wall and room temperature is large
● To connect to a personal computer via USB, use the dedicated software.
Do not connect other USB devices and the remote controller at the same time.
It could cause malfunction or break-down of the remote controller/personal computer.

2 . Accessories & Prepare on site


Following parts are provided.
Accessories R/C main unit, wood screw (ø3.5 x 16) 2 pcs, Quick reference
Following parts are arranged at site. Prepare them according to the respective installation procedures.
Item name Q’ty Remark When the cable length is longer than
100 m, the max size for wires used
Switch box
in the R/C case is 0.5 mm2 . Connect
For 1 piece or 2 pieces (JIS C8340 or 1
them to wires of larger size near
equivalent)
the outside of R/C. When wires are
Thin wall steel pipe for electric These are not required when connected, take measures to prevent
appliance directly on a wall. As required installing directly on a wall. water, etc. from entering inside.
(JIS C8305 or equivalent)

Lock nut, bushing (JIS C8330 or equivalent) As required ≦ 200 m 0.5 mm2 x 2-core

Necessary to run R/C cable on ≦ 300m 0.75 mm2 x 2-core


Lacing (JIS C8425 or equivalent) As required ≦ 400m 1.25 mm2 x 2-core
the wall.
Putty Suitably For sealing gaps ≦ 600m 2.0 mm2 x 2-core
Molly anchor As required
See right table when longer than
R/C cable (0.3 mm2 x 2 pcs) As required
100 m

−5−
3. Installation place
Secure the installation space shown in the figure. Installation space
For the installation method, “embedding wiring” or “exposing
30mm
30mm
wiring” can be selected. Wiring
配線

For the wiring direction, “Backward”, “Upper center” or “Upper left”


can be selected. 30mm
30mm 30mm
30mm

Determine the installation place in consideration of the installation


method and wiring direction.

R/C temperature sensor

120mm
Secure minimum spaces for disassembling the case.

120mm
Upper left and Upper right sides
……30mm or more
Bottom side…120mm or more
If using L-shaped screwdriver, 50mm or more is
available.

4. Installation procedure
Perform installation and wiring work for the remote controller according to the
following procedure. PCB side (Viewed from rear)
Dimensions (Viewed from front)
18.3
18.3
83.5
120
83.5

Fixing固定穴
holes
120

センサー
Sensor USBUSB
port 端子 block
Terminal
37
37 23
23 23
23 19
19
120
120

To remove the upper case from the bottom cases of R/C


· Insert the tip of flat head screwdriver or the like in the recess at the lower part of
R/C and twist it lightly to remove. It is recommended that the tip of the screwdriver
be wrapped with tape to avoid damaging the case.
Take care to protect the removed upper case from moisture or dust.
Conduit
電線管
Wall

Locknut
ロックナット
In case of embedding wiring
Switch
スイッチ
(When the wiring is retrieved “Backward”) box
ボックス

① Embed the switch box and the R/C wires beforehand.


Seal the inlet hole for the R/C wiring with putty. Bushing
ブッシング
50 パテでシール
Seal with putty
すること
8

200
R/C
リモコcable
ン配線

−6−
下ケース配線穴
② When wires are passed through the bottom case, fix the bottom case at 2 places on the switch box. 電線管

上side
Upper 上 上 上side
Upper
ロックナット
Switch box for Switch box for
1 pcs 2 pcs スイッチ
ボックス
ねじ取付部のねCutじ取付部の
out the thin
wall
薄肉部分を 薄肉部分を part at the
screw mounting
下ケース
Bottom case 下ケース 下ケース ブッ シング
下ケース
Bottom case ナイフ等で、 ナイフ等で、
section with a
50 切りとって knife
切りと the like パテでシール
orって
からねじを か らね じ を すること
8 before tightening
しめてくだ しめて くだ
the screw.
さい。 さい。
200

Downside 下 下 下
Downside リモコン配線
配線取出口
Wire outlet 配線取出口 配線取出口 配線取出口 Wire outlet
③ Connect wires from X and Y terminals of R/C to X and Y terminals of indoor unit. R/C
wires (X, Y) have no polarity. Fix wires such that the wires will run around the terminal
screws on the top case of R/C. Wiring hole on
下ケース配線穴
④ Install the upper case with care not to pinch wires of R/C. bottom case
Cautions for wire connection
Use wires of no larger than 0.5 mm2 for wiring
running through the remote control case. Take care
not to pinch the sheath.
Tighten by hand (0.7 N·m or less) the wire
connection.
If the wire is connected using an electric driver, it
may cause failure or deformation.
In case of exposing wiring
(When the wiring is taken out from the “upper center” or “upper left” of R/C)
① Cut out the thin wall sections on the cases for the size of wire. 上面中央の場合

When taking the wiring out from the upper center, open a hole before separating the upper and bottom cases. This will reduce risk of
damaging the PCB and facilitate subsequent work.
When taking the wiring out from the upper left, take care not to damage the PCB and not to leave any chips of cut thin wall inside.

Upper center Upper left


上面左の場合
上面中央の場合 Bottom
下ケース case
Upper
上ケース case

上面左の場合
下ケース
上ケース

② Fix the bottom R/C case on a flat surface with two wood
screws.
③ In case of the upper center, pass the wiring behind the
bottom case. (Hatched section) 120mm 190 mm
120
左側の場合mm (for retrieving
190mm
④ Connect wires from X and Y terminals of R/C to X and Y (for retrieving wire wire from upper
中央の場合center)
from upper left)
terminals of indoor unit. R/C wires (X, Y) have no polarity.
Fix wires such that the wires will run around the terminal
8

screws on the top case of R/C.


⑤ Install the top case with care not to pinch wires of R/C.
⑥ Seal the area cut in ① with putty.

−7−
5. Main/Sub setting when more than one remote controls are used
Up to two units of R/C can be used ○: operable ×: not operable
R/C operations Main Sub R/C operations Main Sub
at the maximum for 1 indoor unit or 1 Run/Stop, Change set temp, Service setting Installation Installation date ○ ×
Change flap direction, Auto swing, Change fan speed opera- ○ ○ settings Company information ○ ○
group. tions Test run ○ ×
High power operation, Energy-saving operation ○ ○
One is main R/C and the other is sub Silent mode control ○ ×
Static pressure adjustment ○ ×
Change auto-address ○ ×
R/C. Useful functions Individual flap control ○ × Address setting of main IU ○ ×
Anti draft setting ○ × IU back-up function ○ ×
Operating range is different depending Timer ○ ○ Infrared sensor (motion sensor)
○ ×
on the main or sub R/C. Favorite setting
Weekly timer



×
setting
R/C function Main/Sub of R/C ○ ○
Home leave mode ○ × settings Return air temp ○ ×
External ventilation ○ ○ R/C sensor ○ ×
Indoor unit
室内ユニット
Select the language ○ ○ R/C sensor adjustment ○ ×
Energy-saving setting ○ × Operation mode ○ ×
X Y R/C cable (無極性)
リモコン線 Filter Filter sign reset ○ ○ ºC / ºF ○ ×
(No polarity) User setting Initial settings ○ ○ Fan speed ○ ×
Administrator Permission/Prohibition External input ○ ×
○ ×
X Y X Y settings setting Upper/lower flap control ○ ×
Outdoor unit silent mode
R/C
リモコン R/C
リモコン timer
○ × Left/right flap control ○ ×
“Main”
「親」 “Sub”
「子」 Setting temp range ○ ×
Ventilation setting ○ ×
Auto-restart ○ ×
Temp increment setting ○ ×
Auto temp setting ○ ×
Set the “Main” and “Sub” as Set temp display ○ ○
Auto fan speed ○ ×
R/C display setting ○ ○
described at Section 8. Change administrator
IU settings ○ ×
○ ○ Service & IU address ○ ○
password
Maintenance Next service date ○ ×
F1/F2 function setting ○ ○
Operation data ○ ×
Error display Error history ○ ○
Display/erase
○ ×
anomaly data
Reset periodical
○ ○
check
Saving IU settings ○ ×
Special settings Erase IU address ○ ×
CPU reset ○ ○
Restore of default
○ ×
setting
Touch panel calibra-
○ ○
tion
Indoor unit capacity display ○ ×

Advice: Connection to personal computer


It can be set from a personal computer via the USB port (mini-B).
Connect after removing the cover for USB port of upper case.
Replace the cover after use.
Special software is necessary for the connection.
For details, view the web site or refer to the engineering data.

USB端子
USB port
カバー
Cover

Advice: Initializing of password


Administrator password (for daily setting items) and Input password

service password (for installation, test run and maintenance) are used. Input the administrator password.

○ The administrator password at factory default is “0000”. This setting can be changed (Refer to Delete

User's Manual).
Set

Back
If the administrator password is forgotten, it can be initialized by holding down the [F1] and [F2]
Input 4 digit number & tap [Set]

switches together for five seconds on the administrator password input screen.
○ Service password is “9999”, which cannot be changed.
When the administrator password is input, the service password is also accepted.
[F1] [F2] switch

−8−
6. Functions and menu items of the remote control
Names and functions of sections on the R/C (Operating section)

⑤ LCD (With backlight)

Menu
16:14 (Mon)

Direction
Cooling Set temp

Timer

Now stopping.

F1: High power F2: Energy-saving

③ F2 switch
④ Operation lamp
⑥ USB port (mini-B)
① Run/Stop switch
② F1 switch

Touch panel system, which is operated by tapping the LCD screen with a finger, is employed for any operations other
than the ① Run/Stop, ② F1 ③ F2 switches.

① Run/Stop switch tapped while the backlight is turned off, the backlight
only is turned on. (Operations with switches ①, ②
 ne push on the button starts operation and another
O
and ③ are excluded.)
push stops operation.
⑥ USB port
② F1 switch ③ F2 switch
USB connector (mini-B) allows connecting to a
 his switch starts operation that is set in F1/F2
T personal computer.
function setting. For operating methods, refer to the instruction
④ Operation lamp manual attached to the software for personal
This lamp lights in green (yellow-green) during computer (remote control utility software).
operation. It changes to red (orange) if any error
occurs.
Operation lamp luminance can be changed.
⑤ LCD (With backlight)
A tap on the LCD lights the backlight.
The backlight turns off automatically if there is no Note
operation for certain period of time. When connecting to a personal computer, do not connect
Lighting period of the backlight lighting can be simultaneously with other USB devices.
changed. Please be sure to connect to the computer directly, without going
If the backlight is ON setting, when the screen is through a hub, etc.

−9−
Names and functions of sections on the R/C (Display)
*All icons are shown for the sake of explanation.
① Clock, Room name display
② Icon display
TOP screen
MEETING1 ③ Menu button
Menu
14:00 (Mon)
⑤ Change set temp
Direction button
④ Change operation Auto Set temp
mode button ⑥ Change flap
direction button
⑧ Timer button Timer ⑦ Change fan speed
button
⑨ Message display
In operation for running.
⑩ F1 , F2 switch
F1: High power F2: Energy-saving function display

① Clock, Room name display ④ Change operation mode button


Displays the current time and the room name.  isplays the operation mode which is selected currently.
D
② Icon display Tap this button to change the operation mode.
⑤ Change set temp button
 ach icon is displayed when one of following settings is
E
going on.  isplays the temperature which is set currently. Tap this
D
button to change the set temperature.
When the demand When setting is made ⑥ Change flap direction button
control is effective. from the sub R/C.  isplays the flap direction which is selected currently.
D
When the 3D auto flow operation is enabled, 3D auto
display will appear. Tap this button to change the flap
When the When the periodical direction.
central control (Optional) is inspection is necessary. ⑦ Change the fan speed button
running.
D
 isplays the fan speed which is selected currently. Tap this
button to change the fan speed.
During the ventilation When ”filter sign” is up. ⑧ Timer button
operation.  isplays simplified contents of the timer which is set
D
currently.
(When two or more timers are set, contents of the timer
When the Permission/ When the peak-cut
which will be operated immediately after is displayed.)
Prohibition setting is made. timer is set. Tap this button to set the timer.
⑨ Message display
When the weekly  tatus of air conditioner operation and messages of the
S
timer is set. R/C operations etc. are displayed.
⑩ F1 , F2 switch function Display
③ Menu button  isplays the function that is set for each F1 , F2
D
switch.
When setting or changing other than the following④-⑧,
The function for these switches can be changed in F1/F2
tap the menu button. Then menu items are displayed, select
function setting
one and set.

−10−
7. Main item

Main menu
Basic operation
Run…………………………………………………………………………………………… 8
Stop…………………………………………………………………………………………… 8
Change operation mode…………………………………………………………………… 9
Change set temp…………………………………………………………………………… 9
Change flap direction……………………………………………………………………… 10
Change the fan speed……………………………………………………………………… 13
F1, F2 switch operation……………………………………………………………………… 13
High power operation……………………………………………………………………… 14
Energy-saving operation…………………………………………………………………… 21
Silent mode control………………………………………………………………………… 64
Useful functions
Individual flap control………………………………………………………………………… 27
Anti draft setting……………………………………………………………………………… 31
Timer……………………………………………………………………………………………
Set ON timer by hour……………………………………………………… 39
Set OFF timer by hour…………………………………………………… 40
Set ON timer by clock……………………………………………………… 41
Set OFF timer by clock…………………………………………………… 41
Confirm……………………………………………………………………… 42
Favorite setting……………………………………………………………………………… 49
Weekly timer………………………………………………………………………………… 42
Home leave mode…………………………………………………………………………… 46
External ventilation………………………………………………………………………… 32
Select the language……………………………………………………………………………
Energy-saving setting Please refer to
User’s manual.
Sleep timer…………………………………………………………………………………… 21
Peak-cut timer……………………………………………………………………………… 22
Automatic temp set back…………………………………………………………………… 25
Infrared sensor (motion sensor) control…………………………………………………… 26
Filter
Filter sign reset……………………………………………………………………………… 28
User setting
Initial settings………………………………………………………………………………… 33
Clock setting……………………………………………………………… 33
Date & time display………………………………………………………… 34
Summer time……………………………………………………………… 35
Contrast…………………………………………………………………… 35
Backlight…………………………………………………………………… 36
Controller sound…………………………………………………………… 36
Operation lamp luminance………………………………………………… 37
Administrator settings……………………………………………………………………… 51
Permission/Prohibition setting…………………………………………… 52
Outdoor unit silent mode timer…………………………………………… 53
Setting temp range………………………………………………………… 54
Temp increment setting…………………………………………………… 56
Set temp display…………………………………………………………… 56
R/C display setting………………………………………………………… 57
Change administrator password………………………………………… 62
F1/F2 function setting……………………………………………………… 63

−11−
Main menu
Service setting
Installation settings
Installation date…………………………………………………………… 15
Company information……………………………………………………… 15
Test run……………………………………………………………………… 15
Static pressure adjustment………………………………………………… 16
Change auto-address……………………………………………………… 16
Address setting of main IU………………………………………………… 16
IU back-up function………………………………………………………… 16
Infrared sensor (motion sensor) setting………………………………… 17
R/C function settings
Main/Sub of R/C…………………………………………………………… 18
Return air temp…………………………………………………………… 18
R/C sensor………………………………………………………………… 18
R/C sensor adjustment…………………………………………………… 19
Operation mode…………………………………………………………… 19
ºC / ºF……………………………………………………………………… 19
Fan speed………………………………………………………………… 19
External input……………………………………………………………… 19
Upper/lower flap control…………………………………………………… 20
Left/right flap control……………………………………………………… 20
Ventilation setting………………………………………………………… 20
Auto-restart………………………………………………………………… 20
Auto temp setting………………………………………………………… 20
Auto fan speed…………………………………………………………… 20
IU settings
Fan speed setting………………………………………………………… 21
Filter sign…………………………………………………………………… 22
External input 1…………………………………………………………… 22
External input 1 signal……………………………………………………… 22
External input 2…………………………………………………………… 22
External input 2 signal……………………………………………………… 22
Heating thermo-OFF temp adjustment…………………………………… 23
Return temperature adjustment…………………………………………… 23
Fan control in cooling thermo-OFF……………………………………… 23
Fan control in heating thermo-OFF……………………………………… 23
Anti-frost temp……………………………………………………………… 23
Anti-frost control…………………………………………………………… 23
Drain pump operation……………………………………………………… 24
Keep fan operating after cooling is stopped……………………………… 24
Keep fan operating after heating is stopped…………………………… 24
Intermittent fan operation in heating……………………………………… 24
Fan circulator operation…………………………………………………… 24
Control pressure adjust…………………………………………………… 24
Auto operation mode……………………………………………………… 25
Thermo. rule setting……………………………………………………… 27
Auto fan speed control…………………………………………………… 27
IU overload alarm………………………………………………………… 28
External output setting…………………………………………………… 28
Service & Maintenance
IU address………………………………………………………………… 29
Next service date………………………………………………………… 29
Operation data……………………………………………………………… 29
Error display………………………………………………………………… 30
Saving IU settings………………………………………………………… 31
Special settings…………………………………………………………… 32
Indoor unit capacity display……………………………………………… 32
Contact company
Please refer to
Contact company…………………………………………………………………………… 15
User’s manual.

−12−
8. Power on and initial setting
Set the main and sub R/C units according to the display at the power on.
・ Main/Sub setting not performed => (1)
・ Main/Sub setting performed => (2)
⑴ When the main and sub are not yet set,
①⇒② Main/sub input screen is displayed.
When tapping the Main or Sub button, initial setting starts.
If any wrong button has been tapped by mistake, the setting can be changed after the end of the initializing operation. (10. R/C
function setting④)
When using two remote controllers for one IU or one group, if the first one is set for the Main , the second is set for the
Sub automatically.

① Start screen ② Main/sub set input


Caution
When only one unit of R/C is
used, tap the Main button.
Select main or sub remote control. In the state of initial setting, if
Version :
either one of buttons ([Main]/[Sub])
Program ID :
Main Sub is not tapped, it keeps the screen
unchanged.

Main The screen changes to ③⇒④⇒⑤.


Sub The screen changes to ①⇒⑧⇒⑤.

③ IU search on ④ IU info acquisition on ⑤ TOP screen

Menu
16:14 (Mon)

Cooling Direction
Set temp
Searching IU Loading IU settings.

Will finish 1230 seconds later. Timer

Now stopping.

F1: High power F2: Energy-saving

The red LED will blink if communication is


not established in ten minutes.

−13−
(2) When the main and sub are set

⑥ Set continue acknowledge ⑦ Initialize acknowledge ⑧ Initialize set on

Do you want to save up the previous Do you want to restore default


settings of R/C before power ON? R/C setting?
R/C is initializing.

Yes No Yes No

Yes The screen changes to ⑧⇒⑤. Yes The screen changes to ①⇒②.
No The screen changes to ⑦. No The screen changes to ⑥.
If the screen is not tapped for more than After the initializing, it returns to the
15 seconds, the Yes (Continue) is default state.
selected and the display changes to the
screen of ⑤.

−14−
9. Installation settings and test run
TOP screen Menu ⇒ Service setting ⇒ Installation settings ⇒ Service password

① Installation settings menu #1 ② Installation settings menu #2 ③ Installation date


Installation settings Installation settings
Installation date 3 Address setting of main IU 13 Installation date

Company information 4 IU back-up function 14

Test run 7 Infrared sensor setting 17 dd mm yy


Static pressure adjustment 10

Change auto-address 11

Next Back Previous Back


Set Back
Select the item. Select the item. Set the date.

The selected screen is displayed. The selected screen is displayed. Select the date with ▲ ▼ buttons,
and tap the Set button.

④ Company information ⑤ Enter the Company ⑥ Enter the Phone No.


Company information Company Set
Company 5 Phone No.
Number Alphabet
Phone No. 6
カナ 漢字 汉字
Delete

Set
Back Delete Next Back
Back
Select the item. Input the name & tap [Set]. Input the phone No & tap [Set].

Enter the company information. Enter the company name using up to Enter the phone number of the company
26 one-byte characters and then tap using up to 13 characters and then tap the
the Set button. You can enter Set button.
alphanumeric, Japanese Kana, Kanji,
Cyrillic, or Chinese characters.

⑦ Test run ⑧ Cooling test run ⑨ Drain pump test run


Test run
Cooling test run 8 Cooling test run Drain pump test run

Drain pump test run 9


Start
Compressor Hz fixed operation
When tapping [Start], test run starts Run Stop
for 30 min. at 5°C in cooling.
Finish-condition of test run is follows.
Passage of 30 min./Stop the IU/Change "Set temp",
"Operation mode" on the TOP screen.
Back
Back Back
Select the item. Select the item.

The selected screen is displayed. This can be operated while cooling is Drain pump can be operated
stopped. When the room temperature independently.
is too low to start the cooling test run, it
operates for 30 minutes by decreasing the
set temperature to 5°C.

−15−
⑩ Static pressure adjustment ⑪ Change auto-address ⑫ Change auto-address

Finish
Static pressure adjustment Change auto-address Change auto-address
IU address OU address

IU address OU address
AUTO No.0
No.2

Pa
Set
Set

Change Next Back


Back Back Ⅱ
Tap ▲▼ to set the value of Pa. Select the IU address to be changed. Tap ▲▼ to set address & [Set].

This is operable in case of connecting


duct type IU equipped with the external In case of Multi series (KX) models, the IU addresses registered with the auto-address
static pressure adjustment function. Select setting method can be changed with this function.
the external static pressure and tap the This function changes the OU address for each IU. Select an IU and,
Set button. Ⅰ When an indoor unit is selected and the Change button is tapped, the display
changes to the Change auto-address screen ⑫ .
Ⅱ Tap the Set button to return to the screen ⑪ and display the new address.
Ⅲ Tap the Finish button to register the new address.

⑬ Address setting of main IU

Address setting of main IU

Cancel

Set

Back
Tap ▲▼ to set address & [Set].

In case of Multi Series (KX) models, it is


possible to let indoor units (Sub IUs) follow
the operation mode (Heating, cooling) of
the indoor unit (Main IU). Set the address
of the Main IU to the Sub IUs The Sub IUs
to which the Main IU address is set follow
the Main IU settings.

In case of 2 sets of indoor units (2 groups) connected to one R/C, it is available to perform
⑭ IU Back-up function back-up operation with them.
1. IU rotation: Operate 2 sets of indoor units alternately at every set time of operation
IU back-up function
interval.
IU rotation Disable Details 15
2. IU capacity back-up: When the temp difference between the set temp and the actual
IU capacity back-up 16
room temp is higher than the set temp diff., 2 sets of indoor units operate.
Disable Details
3. IU fault back-up: If one of the IU has a fault and stops, the other one starts operation.
IU fault back-up Disable Select Enable / Disable (tapping Disable changes to Enable ) and tap the Enter
button to confirm the settings.
Enter Back
Select the item.

−16−
⑮ Rotation details ⑯ Capacity back-up details

Set the time for changeover Set the temp diff. for back-up

Set Set
hours

Back Back
Set the time. Tap ▲▼to set temp & tap [Set].

In IU rotation function, the timer to changeover the operation of The difference between the setting temperature for a change
2 indoor units is set. between one unit and two units for capacity back-up and room
The timer can be set within the range of 10 to 990 hours in incre- temperature is set.
ments of ten hours. The temperature can be set within the range of 2 to 5 °C in
After the time is changed, tap Set for temporary setting. increments of 1 °C.
After temporary setting, return to the IU Back-up function screen After the temperature is changed, tap Set for temporary
and tap Enter . setting.
After temporary setting, return to the IU Back-up function screen
and tap Enter .

Back-up control restrictions


1. The back-up control is unavailable when the operation mode is "Auto". When the back-up control is set for the air conditioner that
specifies "Auto" for the operation mode, the operation mode changes to "Cooling" automatically.
2. When the rotation control is set, the fault back-up control will be enabled automatically. In this case, the fault back-up control cannot
be disabled alone. When the rotation operation is disabled, the fault back-up control will also be disabled.
3. When the capacity back-up control is set, the fault back-up control will be enabled automatically. In this case, the fault back-up control
cannot be disabled alone. When the capacity back-up control is disabled, the fault back-up control will also be disabled.
4. It is also possible to enable the fault back-up control alone.
5. The home leave mode, warming up and external input cannot be set together with the back-up control.
6. While the rotation or fault back-up control is set, either of the two target indoor units (two groups) will operate. Both units will not
operate at the same time.
7. An indoor unit having younger address will start the operation first in each control.

⑰ Infrared (motion) sensor setting

Infrared sensor setting


Disable
・ For customers who adapt a motion sensor, please proceed the setting shown on
Enable
the left and enable the indoor unit to be used to detect the activity amounts of
persons.
When the infrared (motion) sensor is disabled, activity amounts of persons will not
be detected and thus the infrared sensor control (power saving and auto-off) will
Back
not be performed.
Select the item.
・ The infrared (motion) sensor cannot be enabled for the indoor unit older than FDT-
VG or FDT-KXZE1.
Select Enable / Disable for the infra-
When the infrared (motion) sensor setting is tapped, "Invalid request." will be
red sensor of the indoor unit connected to displayed.
the R/C.

−17−
10. R/C function settings Advice: It is valid when unit stops.

TOP screen Menu ⇒ Service setting ⇒ R/C function settings ⇒ Service password

① R/C function settings menu #1 ② R/C function settings menu #2 ③ R/C function settings menu #3
R/C function settings R/C function settings R/C function settings
Main/Sub of R/C 4 ºC / ºF 13 Ventilation setting 18

Return air temp 5 Fan speed 14 Auto-restart 19

R/C sensor 6 External input 15 Auto temp setting 20

R/C sensor adjustment 9 Upper/lower flap control 16 Auto fan speed 21

Operation mode 12 Left/right flap control 17

Next Back Previous Next Back Previous Back

Select the item. Select the item. Select the item.

The selected screen is displayed.

④ Main/Sub of R/C

Main/Sub of R/C
Main
Sub

Back
Select the item.

Use this when changing the Main/Sub


setting of R/C.

Thermo. rule is applied based on the temperature detected with the return air temp sensor of
⑤ Return air temp IU.
When plural indoor units are connected to one R/C, the return air temp applied to the thermo.
Return air temp
rule can be selected.
Individual
1.  Individual :Thermo. rule is applied based on the return air temp of each IU. When plural
Master IU units are connected to one R/C, it is based on the return air temp of the main unit.
Averaged temp
2.  Master IU :Thermo. rule is applied based on the return air temp of IU having the
youngest address out of IUs connected.
If there are several sets of plural units each of which is connected to one R/C, it is based on
Back the IU having the youngest address out of the main units of each plural units.
Select the item.
3.  Averaged temp :Thermo. rule is applied based on the average of return air
temperatures of IUs connected.

⑥ R/C sensor You can change IU main unit return air temperature sensor to the R/C side.
Disable The Indoor temp display changes to the temperature measured by the
R/C sensor sensor at the main unit. ⇒ ⑦
Disable
Enable The Indoor temp display changes to the temperature measured by the R/C
Enable side sensor. ⇒ ⑧
Enable(Heating only)
Enable(Heating only) The Indoor temp display changes to the temperature measured
Enable(Cooling only)
by the R/C side sensor during heating only.
Enable(Cooling only) The Indoor temp display changes to the temperature measured
Back
Select the item. by the R/C side sensor during cooling only.

−18−
⑦ TOP screen (sensor at main unit) ⑧ TOP screen (sensor at R/C) ⑨ R/C sensor adjustment
MEETING1 MEETING1 R/C sensor adjustment
Menu Menu
16:00 (Mon) 16:00 (Mon)
Adjustment in cooling 10
Direction Auto Direction Adjustment in heating 11
Auto Set temp Set temp

Timer Timer
Room Room (R/C)

In operation for running. In operation for running. Back

F1: High power F2: Energy-saving F1: High power F2: Energy-saving Select the item.

When the R/C sensor is disabled, the TOP When the R/C sensor is enabled, the TOP You can adjust the R/C sensor detection
screen displays "Room ○ °C". screen displays "Room (R/C) ○ °C". temperature.
Adjustment in cooling ⇒⑩
Adjustment in heating ⇒⑪

⑩ Adjustment in cooling ⑪ Adjustment in heating ⑫ Operation mode

Adjustment in cooling Adjustment in heating Operation mode


Tap ▲▼ to set offset value. Tap ▲▼ to set offset value. Auto Disable Enable

Cooling Disable Enable

Set Set Heating Disable Enable

Dry Disable Enable

Back Back Set Back


Select the item.

The R/C sensor detection temperature The R/C sensor detection temperature Enable or Disable can be set for
during cooling operation can be corrected. during heating operation can be corrected. each operation mode.
Set the value within the range of -3 to +3. Set the value within the range of -3 to +3. If the cooling or heating is disabled, the
auto is also disabled.

⑬ °C/°F ⑭ Fan speed ⑮ External input

ºC / ºF Fan speed External input


4-speed Individual
3-speed All units
(Hi-Lo)
2-speed
(Hi-Me)
2-speed
1-speed

Back Back Back


Select the item. Select the item. Select the item.

Select the unit of temperature displayed Fan speed can be changed to the selected Set the range to apply the external input
on the R/C. one. received through CNT of either one IU
It may not be available to select some to plural indoor units connected in one
of fan speeds depending on indoor unit system
models. Individual This is applied only to the
IU receiving CNT input.
All units This is applied to all indoor
units connected.

−19−
⑯ Upper/lower flap control ⑰ Left/right flap control ⑱ Ventilation setting

Upper/lower flap control Left/right flap control Ventilation setting


Stop at fixed position Fixed position stop Disable
Stop at any position Stop at any position Interlocking
Independent

Back Back Back


Select the item. Select the item. Select the item.

Stop at fixed position The upper/ Fixed position stop The left/right Set this when a ventilation device is
lower flap can be set to stop at one of four flap can be set to stop in eight different connected.
positions. patterns. Disable No ventilation device is
Stop at any position The flap can Stop at any position The flap can connected.
be set to stop at any position immediately be set to stop at any position immediately Interlocking Ventilation is interlocked
after operating the R/C switch. after operating the R/C switch. with the Run/Stop of air conditioner and
operate the Ventilation output.
Independent If the ventilation is selected
from the menu, only the ventilation device
is operated or stopped independently.

⑲ Auto-restart ⑳ Auto temp setting  Auto fan speed

Auto-restart Auto temp setting Auto fan speed


Enable Enable Enable
Disable Disable Disable

Back Back Back


Select the item. Select the item. Select the item.

If the unit stops during operation, Enable Auto can be selected on the Enable Auto can be selected on the
Enable It returns to the state before room temperature setting screen. fan speed setting screen.
the power failure as soon as the power Disable Auto selection switch will not Disable Auto selection switch will not
supply is restored (After the end of the be displayed on the room temperature be displayed on the fan speed setting
primary control at the power on). setting screen. screen.
Disable It stops after the restoration of
power supply.

−20−
11. IU settings Advice: It is valid when unit stops.

TOP screen Menu ⇒ Service setting ⇒ IU settings ⇒ Service password

① IU select #1 ② IU select #2 ③ Loading

Menu Menu
IU select IU select

Loading. Wait a while.

All units Next Back All units Previous Back


Select an IU address. Select an IU address.

When plural indoor units are connected, they are displayed on the screen. The display changes to ④ after receiving
000 to 015 Individual settings are performed for indoor units. data from the IU.
All units The same setting applies to all units.

④ IU setting menu #1 ⑤ IU setting menu #2 ⑥ IU setting menu #3


IU settings IU settings IU settings
Fan speed setting 9 External input 2 signal 16 Anti-frost temp 21

Filter sign 10 Heating thermo-OFF temp adjustment 17 Anti-frost control 22

External input 1 11 Return temperature adjustment 18 Drain pump operation 23

External input 1 signal 13 Fan control in cooling thermo-OFF 19 Keep fan operating after cooling is stopped 24

External input 2 14 Fan control in heating thermo-OFF 20 Keep fan operating after heating is stopped 25

Next Back Previous Next Back Previous Next Back

Select the item. Select the item. Select the item.

The selected screen is displayed.

⑦ IU setting menu #4 ⑧ IU setting menu #5


⑭ ⑨ Fan speed setting
IU settings IU settings
Intermittent fan operation in heating 26 Auto fan speed control 44 Fan speed setting
Standard
Fan circulator operation 27 IU overload alarm 45
Setting 1
Control pressure adjust 28 External output setting 46
Setting 2
Auto operation mode 29

Thermo. rule setting 40

Previous Next Back Previous Back


Back
Select the item. Select the item. Select the item.

Set the fan speed tap for the IU. Refer to


the engineering data for details.

−21−
⑩ Filter sign Standard

Filter sign
No display None
No display
Setting 1 180Hr
Setting 1

Setting 2 Setting 2 600Hr


Setting 3

Setting 4 Setting 3 1,000Hr


Back
Select the item. Setting 4 1,000Hr Operation stop

Set the time to display the filter sign.

⑪ External input 1 #1 ⑫ External input 1 #2 ⑬ External input 1 signal

External input 1 External input 1 External input 1 signal

Run/Stop Forced thermo-OFF Level input


Permission/Prohibition Temporary stop Pulse input

Cooling/Heating Silent mode

Emergency stop
Setting temperature shift

Next Back Previous Back Back


Select the item. Select the item. Select the item.

Set the control at the time when the signal is input to the external input 1 (CNT) of IU. Set the signal type to input to the external
Refer to the engineering data for details. input 1 (CNT) of IU.
Refer to the engineering data for details.

This is operable when the IU equipped with the external input 2 is connected. Refer to the engineering data for details.

⑭ External input 2 #1 ⑮ External input 2 #2 ⑯ External input 2 signal

External input 2 External input 2 External input 2 signal

Run/Stop Forced thermo-OFF Level input


Permission/Prohibition Temporary stop Pulse input

Cooling/Heating Silent mode


Emergency stop
Setting temperature shift

Next Back Previous Back Back


Select the item. Select the item. Select the item.

−22−
⑰ Heating thermo-OFF temp adjustment ⑱ Return temperature adjustment ⑲ Fan control in cooling thermo-OFF

Heating thermo-OFF temp adjustment Return temperature adjustment Fan control in cooling thermo-OFF
Tap ▲▼ to set offset value. Tap ▲▼ to set offset value. Low
Set fan speed

Intermittent
Set Set
Stop

Back Back Back


Select the item.

Adjust the temperature for judging to make Adjust the main return air temperature Set the fan speed at the cooling thermo-
thermostat ON or OFF during heating sensor detection temperature. OFF.
operation. Adjustable range is -2°C / -1.5°C / -1°C / Low The fan runs at the low speed.
Adjustable range is 0°C / +1°C / +2°C / 0°C / +1°C / +1.5°C / +2°C. Set fan speed The fan runs at the
+3°C. same speed as that during the thermo-ON
operation.
Intermittent Cycles of Lo fan operation
for 2 minutes and stop for 5 minutes are
repeated.
Stop The fan is stopped.

⑳ Fan control in heating thermo-OFF  Anti-frost temp  Anti-frost control

Fan control in heating thermo-OFF Anti-frost temp Anti-frost control

Low Temp Low Enable


Set fan speed Temp High Disable

Intermittent

Stop

Back Back Back


Select the item. Select the item. Select the item.

Set the fan speed at the heating thermo- Select the anti-frost control temperature. Set the fan control during the anti-frost
OFF. control.
Low The fan runs at the low speed. Enable The fan speed increases
Set fan speed The fan runs at the during the anti-frost control.
same speed as that during the thermo-ON Disable The fan speed does not
operation. change during the anti-frost control.
Intermittent Cycles of Lo fan operation
for 2 minutes and stop for 5 minutes are
repeated.
Stop The fan is stopped.

−23−
 Drain pump operation  Keep fan operating after cooling is stopped  Keep fan operating after heating is stopped

Drain pump operation Keep fan operating after cooling is stopped Keep fan operating after heating is stopped

Standard (in cooling & dry) No setting No setting

Operate in standard & heating Setting 1 Setting 1

Operate in heating & fan Setting 2 Setting 2

Operate in standard & fan Setting 3 Setting 3

Back Back Back


Select the item. Select the item. Select the item.

Standard (in cooling & dry) Select the residual fan operation time Select the residual fan operation time
Operates in cooling and dry modes. period after stopping and the thermo-OFF period after stopping and the thermo-OFF
Operate in standard & heating in cooling mode. in heating mode.
Operates in cooling, dry and heating No setting Residual fan operation not No setting Residual fan operation not
modes. performed. performed.
Operate in heating & fan Operates Setting 1 0.5 hours Setting 1 0.5 hours
in all modes. Setting 2 2 hours Setting 2 2 hours
Operate in standard & fan Setting 3 6 hours Setting 3 6 hours
Operates in cooling, dry and fan modes. *Residual time may vary.

 Intermittent fan operation in heating  Fan circulator operation  Control pressure adjust

Intermittent fan operation in heating Fan circulator operation Control pressure adjust
Stop Disable Standard
Stop for 20 min & run for 5 min Enable Type1
Stop for 5 min & run for 5 min

Back Back Back


Select the item. Select the item. Select the item.

Set this when operating the fan as a circulator. Set the control pressure when connecting the
Select the fan control after the residual fan operation following
Disable During the fan operation, the fan outdoor air conditioning unit to the Multi (KX)
stop and thermo-OFF in heating mode.
runs continuously. System.
Stop Intermittent fan operation is not done.
Enable During the fan operation, the Standard Normal
Stop for 20 min & run for 5 min
fan runs and stops based on the difference Type1 When all operating IUs are in this
Check the operating conditions at every 25 min and run the fan
between temperatures detected with the R/C mode, the control pressure value is changed.
for 5 min.
sensor and the return air sensor.
Stop for 5 min & run for 5 min
Check the operating conditions at every 10 min and run the fan
for 5 min.

−24−
Auto 1 T he temp difference between the
 Auto operation mode  Auto rule selection
set temp and the actual room
Auto operation mode temp switch cooling and heating.
Auto rule selection 30 Auto rule selection
Auto 2 The temp difference between the
Auto 1
Auto 1 details 31
set temp and the actual room
Auto 2
Auto 2 details 32
temp/outdoor temp switch cooling
Auto 3
Auto 3 details 33
and heating.
Auto 3 The actual room temp and
Back outdoor temp switch cooling and
Back
Select the item. Select the item. heating.

The method of switching between cooling and heating in the auto operation mode
can be selected from three options.
Set the condition for each method.

[Set temp - Temp switching


 Auto 1 details to cooling] < [Indoor return air (Sample)

Cooling operation
Auto 1 details temp]
Temp switching to cooling 34
⇒ Operation mode: Cooling
Temp switching to heating 35

Cooling operation
Temp switching to heating
Thermo-OFF
[Set temp + Temp switching
to heating] > [Indoor return air
Indoor temp

Room
temp] setting

⇒ Operation mode: Heating

Temp switching to cooling


Back
Heating operation

Thermo-OFF
Select the item.

Set the temperatures switching to cooling and

Heating operation
heating.
Switching temperatures can be set within the ◆ Switching between cooling and heating can be set after thermo-OFF at least for 5 minutes.
range of 1°C to 4°C. ◆ When temp switching to cooling and temp switching to heating are set to 3 °C.

“[Set temp - Temp switching (Sample)


 Auto 2 details
to cooling] < [Indoor return air Forced thermo-OFF

Auto 2 details temp]” and “[Outdoor temp, Outdoor temp set for cooling Selection range

Temp switching to cooling 34


cooling] < [Outdoor air temp]” Switching to Thermo-OFF Cooling opera-
Temp switching to heating 35
⇒ Operation mode: Cooling heating
Temp
tion

Outdoor temp setting to limit in cooling 36 Setting


室Room

Temp
内吸込

“[Set temp - Temp switching


Outdoor temp setting to limit in heating 37 Switching to
cooling
absorption
温度 temp

Thermo-OFF Temp
to cooling] > [Indoor return air
Heating opera-
Back temp]” and “[Outdoor temp, tion

Select the item. cooling] > [Outdoor air temp]” Forced thermo-OFF

⇒ Operation mode: Heating


Set the temperatures switching to cooling Outdoor temp set for heating Selection range

and heating and the outdoor temp settings


to limit in cooling and heating. Outdoor temp

◆ The temp switching to cooling/heating is 4 °C,


the outdoor temp setting to limit in cooling is 19 °C, and the outdoor temp set-
ting to limit in heating is 18 °C.

−25−
“[Indoor temp, cooling] < (Sample)

 Auto 3 details Forced thermo-OFF


[Indoor return air temp]” and
Auto 3 details “[Outdoor temp, cooling] <

Indoor temp set for cooling Selection range


Outdoor temp set for cooling Selection range
Outdoor temp setting to limit in cooling 36
[Outdoor air temp]”
Outdoor temp setting to limit in heating 37
⇒ Operation mode: Cooling

Forced thermo-OFF
Indoor temp set for heating Selection range
Indoor temp switching to cooling 38

Room absorption temp


Cooling opera-
Indoor temp switching to heating 39
“[Indoor temp, heating] > tion

[Indoor return air temp]” and


Back “[Outdoor temp, heating] > Heating
operation
Select the item. [Outdoor air temp]”
⇒ Operation mode: Heating
Set the outdoor temp settings to limit in Outdoor temp set for heatingSelection range
Forced thermo-OFF

cooling and heating and the indoor temp


settings to limit in cooling and heating.
Outdoor temp
◆ The outdoor temp setting to limit in cooling is 19 °C, the outdoor temp setting to
limit in heating is 20 °C,
the indoor temp switching to cooling is 18 °C, and the indoor temp switching to
cooling is 25 °C.

 Temp switching to cooling  Temp switching to heating  Outdoor temp set for cooling

Temp switching to cooling Temp switching to heating Outdoor temp set for cooling
Tap ▲▼ to set offset value. Tap ▲▼ to set offset value. Tap ▲▼ to set offset value.

Set Set Set

Back Back Back

Set the temperature switching to cooling Set the temperature switching to heating Set the outdoor temperature for cooling
with Auto 1 and Auto 2. with Auto 1 and Auto 2. with Auto 2 and Auto 3.
The temperature can be set within the The temperature can be set within the The temperature can be set within the
range of 1 to 4 °C. range of 1 to 4 °C. range of 10 to 30 °C.

 Outdoor temp set for heating  Indoor temp set for cooling  Indoor temp set for heating

Outdoor temp set for heating Indoor temp set for cooling Indoor temp set for heating
Tap ▲▼ to set offset value. Tap ▲▼ to set offset value. Tap ▲▼ to set offset value.

Set Set Set

Back Back Back

Set the outdoor temperature for heating Set the indoor temperature for cooling with Set the indoor temperature for heating with
with Auto 2 and Auto 3. Auto 3. Auto 3.
The temperature can be set within the Indoor temp, cooling: Can be set within the The temperature can be set within the
range of 10 to 22 °C. range of 18°C to 30°C. range of 10 to 30 °C.

−26−
 Thermo. rule setting  Standard/Outdoor temp basis
Thermo. rule setting
Standard/Outdoor temp basis 41 Standard/Outdoor temp basis
Standard
Cooling offset 42

43
Outdoor temp basis
Heating offset

Back
Back
Select the item. Select the item.

Set the room temperature control, thermostat ON/OFF switching method and condition.
Standard The thermostat judges based on the indoor temperature and set tempera-
ture.
Outdoor temp basis The thermostat judges based on the outdoor temperature and
the cooling and heating offset values.
The room temperature setting will be disabled.

 Cooling offset  Heating offset  Auto fan speed control

Cooling offset Heating offset Auto fan speed control


It is effective only when "Outdoor temp It is effective only when "Outdoor temp Auto 1
basis” is selected for thermostat control. basis” is selected for thermostat control.
Auto 2

Set Set

Back Back Back


Select the item.

The thermostat judges based on the outdoor temperature and the cooling and heating Set the switching range of the fan tap at
offset values. the auto fan speed setting.
(a) C
 ooling offset: The thermostat judges based on [Outdoor temp - Cooling offset value] Auto 1 The fan tap is changed in the
during cooling. range of High ⇒ Medium ⇒ Low.
The thermostat trips ON when [Indoor temp] > [Outdoor temp - Cooling offset value]. Auto 2 The fan tap is changed in
This value can be set in the range of 0°C to 10°C. the range of Powerful high ⇒ High ⇒
(b) H
 eating offset: The thermostat judges based on [Outdoor temp + Cooling offset Medium ⇒ Low.
value] during heating.
The thermostat trips ON when [Indoor temp] < [Outdoor temp + Cooling offset
value].
This value can be set in the range of 0°C to 5°C.

−27−
 IU overload alarm  External output function  External output function #1

IU overload alarm
IU overload alarm External output function External output function

External output 1 Operation output


External output 2 Heating output

キャンセル
Cancel External output 3 Compressor ON output
Set
External output 4 Inspection (Error) output
Cooling output

Back Back 次ペー


Next ジ Back
Tap ▲▼ to set temp & tap [Set]. Select the item.

When the room temperature differs to Select the output destination to change and then select the function to be allocated to the
some extent from the setting temperature selected output.
at 30 minutes after the start of operation, The following shows output connectors and defaults.
the overload alarm signal is transmitted External output 1 CNT-2 Operation output
from the external output (CNT-5). External output 2 CNT-3 Heating output
External output 3 CNT-4 Compressor ON output
External output 4 CNT-5 Inspection (Error) output
Refer to the engineering data for details.

 External output function #2  External output function #3

External output function External output function

Fan operation output 1 Heater output


Fan operation output 2 Free cooling output
Fan operation output 3 Indoor unit overload alarm output
Defrost/oil return output
Ventilation output

前ペー ジ
Previous 次ペー
Next ジ Back 前ペー ジ
Previous Back

−28−
12. Service & Maintenance
TOP screen Menu ⇒ Service setting ⇒ Service & Maintenance ⇒ Service password

① Service & Maintenance #1 ② Service & Maintenance #2 ③ IU address


Service & Maintenance Service & Maintenance
Check
IU address 3 Special settings 29
IU address
IU address Name of IU OU address
Next service date 5 Indoor unit capacity display 34

Operation data 7

Error display 15

Saving IU settings 26

次ペー
Next ジ Back 前ペー ジ
Previous Back
次ペー
Next ジ Back
Select the item. Select the item.

The selected screen is displayed. The selected screen is displayed. When 8 or more units are connected,
further data are displayed on the next
page. When the Check button is tapped
after selecting an IU address, the fan of
the selected IU can be operated. ⇒④

④ Check run mode ⑤ Next service date ⑥ Service message

Check run mode Next service date

Usage time 1 years & 9 months


Next check 10 / 2020
dd mm yy Company
Fan operation Run Stop Phone No.

No setting Set Back


Back
動作を選択
Tap [Run] to して ください。
check. Set the date.

Run Tap this button to start the fan When next service date is entered, messages are displayed at the start/stop of operation
operation. on the service month.
Stop Tap this button to stop the fan Contents are reset if the next service date is updated.
operation. If the No setting button is tapped, messages are not displayed.

⑦ Operation data #1 ⑧ Operation data #2 ⑨ Operation data #3

Update Update Update


Operation data Operation data Operation data
IU OU IU OU IU OU
Item Data Disp. Item Data Disp. Item Data Disp.
Operation mode Cooling IU heat exch. temp 2 IU EEV opening Check
Set temp IU heat exch. temp 3 IU operation Hrs.
Return air temp IU fan speed 5-speed Supply air temp
R/C temp Required Hz Outdoor air temp
IU heat exch. temp 1 Answer Hz OU heat exch. Temp 1

Display 次ペー
Nextジ Back Display 前ペー ジ
Previous 次ペー
Next ジ Back Display 前ペー ジ
Previous Next Back
Select 6 items for display & tap [Display]. Select 6 items for display & tap [Display]. Select 6 items for display & tap [Display].

After read the indoor unit data, the operation data at the time of reading are displayed. Tapping the Update button to update the data.
To automatically update data and display, up to six items can be selected. Tapping the Display button after selecting six items
changes the display to ⑭ .

−29−
⑩ Operation data #4 ⑪ Operation data #5 ⑫ Operation data #6

Update Update Update


Operation data Operation data Operation data
IU OU IU OU IU OU
Item Data Disp. Item Data Disp. Item Data Disp.
OU heat exch. Temp 2 Comp bottom temp Protection control
Compressor Hz Current OU fan speed 5-speed
High pressure SH control 63H1
Low pressure SH Defrost
Discharge pipe temp TDSH Comp. running Hrs

Display Previous Next Back Display Previous Next Back Display Previous Next Back
Select 6 items for display & tap [Display]. Select 6 items for display & tap [Display]. Select 6 items for display & tap [Display].

⑬ Operation data #7 ⑭ Individual display ⑮ Error display


Error display
Update
Operation data Operation data Error history 16
IU OU Operation mode Cooling
Display anomaly data 17
Item Data Disp. Set temp
OU EEV 1 opening Erase anomaly data 24
OU EEV 2 opening Return air temp
R/C temp Reset periodical check 25

IU heat exch. temp 1


IU heat exch. temp 2
Display Previous Back Back
Back
Select 6 items for display & tap [Display]. Select the item.

Automatically updates and displays the six


selected items.

⑯ Error history (Sample) ⑰ Display anomaly data #1 ⑱ Display anomaly data #2

Delete
Error history Display anomaly data Display anomaly data
Time IU ErrorCode IU ErrorCode OU IU ErrorCode OU
6:57 PM Item Data Item Data
6:57 PM Operation mode Cooling IU heat exch. temp 3
6:57 PM Set temp IU fan speed 5-speed
Return air temp Required Hz
IU heat exch. temp 1 Answer Hz
IU heat exch. temp 2 IU EEV opening

Next Back Previous Next Back


Back

Date and time when error occurred, IU The operation data obtained just before the occurrence of an error are displayed.
address and Error Code are displayed.
Tap the Delete button to delete the
error history.

−30−
⑲ Display anomaly data #3 ⑳ Display anomaly data #4  Display anomaly data #5

Display anomaly data Display anomaly data Display anomaly data


IU ErrorCode OU IU ErrorCode OU IU ErrorCode OU
Item Data Item Data Item Data
IU operation Hrs. Compressor Hz Current
Supply air temp High pressure SH control
Outdoor air temp Low pressure SH
OU heat exch. Temp 1 Discharge pipe temp TDSH
OU heat exch. Temp 2 Comp bottom temp Protection control

Previous Next Back Previous Next Back Previous Next Back

The operation data obtained just before the occurrence of an error are displayed.

 Display anomaly data #6  Display anomaly data #7  Erase anomaly data

Display anomaly data Display anomaly data Erase anomaly data


IU ErrorCode OU IU ErrorCode OU
Item Data Item Data
OU fan speed 5-speed OU EEV 2 opening
63H1 Yes
Defrost
Comp. running Hrs
OU EEV 1 opening

Previous Next Back Previous Back


Back
Select the item.

The anomaly data is erased.

 Reset periodical check  Saving IU settings  Automatic saving


Saving IU settings
Reset periodical check Save IU settings Automatic saving
Do you want to reset the periodical check? Saving automatically at the set time.
Automatic saving 27

Transfer the saved data 28 AM

Yes Set

Back No setting Back


Back
If yes, tap [Yes] Select the item. Tap ▲▼to set clock time & tap [Set].

The time count is reset by resetting the Save IU settings All settings of the Set the time when the automatic saving is
periodical check. IUs connected to the R/C are saved in the performed everyday.
R/C. If the No setting button is tapped, the
 Transfer the saved data Automatic saving Set the time automatic saving is not performed.
when the automatic saving is performed
IU select everyday.
Transfer the saved data The
IU setting data saved in the R/C are
transferred to an indoor unit.

Next Back Advice


Select an IU address. Have you ever lost setting contents
after replacing an IU board?
If an IU to which the saved date is When IU settings are saved in the R/
transferred is selected, the Transfer C, the saved data can be written to
the saved data acknowledge screen is IU using "Transfer the saved data".
displayed. Tap [Yes] to transfer the data.

−31−
Erase IU address Memory of the IU
 Special settings  Touch panel calibration
address for multi (KX) unit is erased.
Special settings
CPU reset Microcomputers of IU and
Erase IU address Touch panel calibration
OU connected are reset (State of restoration
CPU reset
after power failure).
Restore of default setting
Restore of default setting Settings on Start
Touch panel calibration 30
R/C and IU connected are initialized (State of
factory default).
Back
Touch panel calibration Use this Back
Select the item. If Yes, tap [Start].
to correct when the display and the touch
The selected screen is displayed. position are not matched.

 Touch panel calibration #1  Touch panel calibration #2  Touch panel calibration #3

Tap [+] on the lower right. Tap [+] on the upper left.

Tap center of [+] & check screen position.

Cancel Redo Finish

Use this when the display and the touch position are not matched.
Tap the center of [+] and check the deviation from the display.
Finish ⇒ Calibration is completed.

 Indoor unit capacity display

Indoor unit capacity display


IU address Capacity

Next Back

Capacities of IUs connected to the R/C are


displayed.
When seven units or more are connected,
tap the Next button to view all.
These items may not be displayed
depending on the combination of IUs and
OUs.

−32−
13. Select the language
TOP screen Menu ⇒ Useful functions ⇒ Select the language

① Select the language


Select the language

Set Next Back

Select the language

The menu for select the language is


displayed.
Select the language to be displayed on the
R/C and tap the Set button.
You can select from the following
languages:
English/German/French/Spanish/Italian/
Dutch/Turkish/Portugal/Russian/
Polish/Japanese/Chinese

−33−