Abstract—In previous years, a lot of experimental work was depend upon its insulation properties and it is very important
done on the factors that affect the breakdown voltage of to evaluate the condition of insulation. In pure oil the
transformer oil but recently software techniques for optimization breakdown voltage is higher, as the oil aging process starts,
gained so much attention. The basic purpose is to analyze the the breakdown voltage decreases because of number of factors
behavior of the properties that affect the breakdown voltage, to [3]. Not every particle is pollutant, adding nanoparticles
optimize the results according to the requirement and to enable enhance the breakdown strength while adding copper particles
the researcher to predict results before the experimental work. decreases the breakdown strength [4]. The characteristic
As we know, if the applied electric field is provided above a behavior of the factors is observed with 10mm gap length as
certain limit even for few nano-seconds it could lead to the increasing gap length decreases the breakdown strength [5].
breakdown of transformer oil. There are certain factors and Minimum gap length of almost 5mm shows the linear
dielectric properties that affect the breakdown strength of
characteristic behavior of breakdown curves whereas the
transformer oil and compromising the throughput of the
maximum gap length is 50mm [6].
electrical system. The optimization technique used for this
purpose is Genetic Algorithm because of its good results, Dielectric insulating oils have been used as a liquid
simplicity, and ease of use. It can deal with multiple variables at a insulator in transformers. In presence of electric field, E the
time. The considered factors that affect the breakdown voltages current in insulating oil is highly affected by the impurities
are temperature, permittivity, tan δ, viscosity, velocity of the present in the oil [6]. Similarly, the breakdown strength have
particles. The gap length is considered as 10mm and the factors been studied that it is the maximum amount at which the
are optimized around breakdown voltage of 50KV. Generally, oil maximum electric field is achieved without the breakdown
having breakdown less than 50KV requires oil reconditioning.
[7]. Many factors have been discussed in different research
Considering these factors are leads to analyze many other factor
affecting the breakdown voltage.
papers which are affecting the breakdown voltage of
transformer oil such as electric permittivity [6].
Keywords— breakdown voltage, permittivity, temperature, Different approached to find the breakdown voltage of oil
transformer oil, viscosity are well explained according to IEC 60156 standard [7].
Whereas, the transformer oil having a breakdown of less than
I. INTRODUCTION 50KV needs oil reconditioning and various methods for
transformer maintenance are explained [2]. The breakdown
It has been observed that power transformers use the oil as under uniform electric field studies such that the particles get
a dielectric insulator or either as a cooling material. aligned in the space between the electrodes, and the charge on
Breakdown voltage of transformer oil is a very important the particles is increased to the extent that the particles itself
factor for measuring the dielectric strength of transformer oil. fly apart from the alignment and suddenly the charge on the
Basically, breakdown voltage is the minimum voltage at particle reduced [8]. Breakdown mechanism in liquid
which insulation small portion starts conducting, insulator dielectrics has been well explained, and the research has been
becomes electrical conductor and lost the properties as an done on breakdown voltage in liquid dielectric is more
electrical insulator whereas breakdown strength is the significant and higher in an alternating or non-uniform field as
maximum applied voltage at which the insulator withstand to compared to constant field [8][9].
its properties. The life span of transformer is directly affected
by the breakdown voltage of transformer oil. The numerical
method for finding breakdown voltage is discussed in [1]. It is II. METHODOLOGY
very important to not operate transformer beyond its specified Basic objective is to maximize the breakdown voltage
breakdown voltage or it will damage the transformer according to IEC 60296 standard by considering different
electrical, physical, mechanical and chemical properties. factors that affect the breakdown voltage. By considering the
There are several ways to maintain and monitor transformer constraints of the factors, breakdown voltage is optimized
oil properties [2]. The life and health of transformer highly around 50KV discussed below in each section. Suggested
=
6
Equation (2) represents the relation of with E but the
relation could not be clearly seen because of differential
relation. A comprehensible relation in with breakdown is
shown in Figure 3. Optimized value of E is 48KV/Cm,
r=40μm, V=107mm/s, B=48KV.
The effect of E applied on an electron has been discussed.
Under small electric field there is no significant difference in
particle movement but under higher electric field there is
significant change in the movement of the electron [8].
Velocity of the particle increases with the increasing electric
field. Basically, E is the cause which changes the V of the
Figure 2: Un-optimized and optimized results of particle. If the particle is massive or if there are huge number
of particles, the work done by the electric field on them (to
breakdown and temperature
accelerate them) will be taken from the energy of the electric
In Figure 3. Similar behavior of temperature and field. In such a case the electric field becomes weaker as the
velocity of the massive particle/the huge number of particles is
breakdown was observed on experimental basis that the
increased. That effect can be ignored for a small particle. This
temperature and breakdown have direct relation at lower equation for the relationship of V and B is a differential
temperature with gap length 5mm [9]. equation. So the optimized and un-optimized results show a
different story altogether. The result is that as V increases,
breakdown decreases. This is not evident from the equation rapidly on lower temperature because of presence of foreign
but derivative function has produced this relationship. A liquid molecule. Loaded transformer increases the temperature
similar increasing trend of velocity with increasing E was resulting in increasing the solubility of that liquid globule.
observed but at lower limits of E, and it was clearly mentioned Permittivity depends upon the type of polarization in a
that same trend could not be obtained at higher value of E material. It is whether electronic polarization, orientation
[19]. polarization or ionic ionization depending upon whether the
electron density varies or the electric dipoles vary in presence
C. Viscosity of E [6]. The breakdown phenomenon usually starts with a
It is the resistance follow by the liquid. The viscosity of very small size bubble evolution in transformer oil decreases
oil is measured by many standards i-e SAE (Society of the dielectric strength [3]. The dielectric strength or
Automotive Engineers). The more the SAE number the higher breakdown voltage will decrease by increasing bubble size
will be viscosity of oil. Viscosity usually decreases with the [3].The presence of the particles increases the bubble
rise in temperature as the intermolecular forces between generation. The liquid globule has its own permittivity which
molecules of the oil decreases. The more viscous is the oil, the is effecting the breakdown voltages. Under the influence of
stronger will be intermolecular forces. It does not simply electric field the globule may elongate to the shape of a
depends upon intermolecular forces or temperature but it is spheroid. The ratio of longer to shorter globule ß increases
also dependent on the size and shape of particle. The greater with increasing electric field [17]. In Equation (3), the
the viscosity is the less will be effect of particles on the permittivity of bubble was kept to be 1=1, =43dynes/cm,
breakdown [4]. Viscosity does not have markable effect on =1.85 was placed in Equation (4) and Equation (5) to find the
non-polar liquids whereas it does have effect on polar liquids. constants G and H. optimized value of E is 51KV/Cm,
Viscosity and breakdown have a direct relation [16]. In r=2.26μm, 2 =2.3, B=51.3KV.
Equation (2) the optimized value of =13 at B=48KV.
√
= 600 (3)
−
1 cosh
= −1 (4)
− 1 ( − 1)