Bulletin Nokia NI 211001 Ed01 «Eltek Temp Sensor»


Project: Mwingz
Activity: Ni Deploy Swap
Emergency: Normal
Publication date: 01/10/2021
Applicable From:
Expiration: NA
Attachment: NA
Product: Eltek
Sub-product: NA
Model: NA
Version : NA

Context:

The Eltek’s temp probe are coming preinstalled in the cabinet. Do not move the position of the sensor. On a site
Mwingz FLM has received high temp alarms? So they went for an intervention and found out temp sensor was
installed on wrong position.

Action to take:

The temperature probe in new Eltek racks/cabinets is pre-mounted attached to the bottom/back of the
powercore, behind the rectifiers.

This should not be moved, as it is the position defined by Eltek.