Eltek rectifier cabinet

Eltek rectifier cabinet SW

Eltek

SW was used to control the cabinet


operation such as , battery charging,
maximum current ,low voltage for batteries
disconnecting ,batteries voltage reconnecting ,boosting voltage ,available
phases voltage and loads

Eltek SW working
1- On first time working we need to add site then new network
appears then connect

Eltek SW working
2- SW opened as follows and we working over SW as visual check not
to change any values

Eltek SW working
3- first power system opened
It indicates site ID and cabinet serial no

Eltek SW working
4- Mains
It indicates every phase voltage

Eltek SW working
5- rectifiers
It indicates no of rectifiers modules-and start up delay of rectifier if needed

Eltek SW working
6- loads
It indicates loads and fuse status working or not

Eltek SW working
7- Batteries
It indicates current batteries voltage-battery current-batteries temp-no of strings

Eltek SW working
8- System configuration
It indicates reference voltage,boosting voltage,battery disconnecting and battery connecting
voltage

Eltek SW working
9- Alarms overview
Current alarms

Eltek SW working
9- Alarms overview
On alarms over view we open outputs column so check box of alarms appears

Eltek SW working
If any quantity to be changed we need to work over SW as per access
Then we need to used password as 0003

Eltek SW working
SW for current limit value we have equation for this value as follows
current limit value=0.3x battery Strings capacity x no of strings

Eltek acceptance concerns


1- cabinet working over one fan as no A/C so its not available to be
housing also for batteries

Eltek acceptance concerns


2- only 2battery temp. sensors on cabinet ( so it is available only to
control 2 housing batteries cabinets

Eltek acceptance concerns


3- main and priority loads not available as relay was missing

Eltek acceptance concerns


4- First configuration was available for Eltek team only