Landline: +237233711104 or a marecrion ‘Admin: info@bindendt.com Service: bindendt@amail.com ADDRESS: BP 469, Limbe- RegNo:TPPRR/RC/LBE/2014/8/0645 CAMEROON, CENTRAL AFRICA Tox No:M0514120911758 Cell 1237-676174124, +237656055094 ( BINDE website: nu bindendtcom 3” SS 316 G EXPANSION PIPE PNEUMATIC TEST CERTIFICATE AS PER DECREE NO AR 00 NMIDT Di OF AUGUST 5th, Certificate * 19/08/20-01 Date: 18/08/2021 INSPECTION SITE: ‘CLIENT REQUESTING INSPECTION: BINES WORKSHOP COSL SEEKER FEATURES OF TRANSPORTING VESSEL | ‘Type: 3° SS G Expansion Pipe Air FLANGE RATING: ASTM 105/PN16 ‘Transported fluid: oe een DESIGN CODE: ASME SEC VII DIV. DESIGN PRESSURE (MAWP) ‘Test pressure :1.2xWP Work Details: Test Volume: N/A INSPECTION TYPE: PNEUMATIC START OF TEST Date: 19/08/2020 Pressure: Opsi. Temperature: 15°. Fluid: Air End Of Test Date: 18/08/2020, Pressure: 150.7psi_ Temperature: 17°C, Total Soak in Time : 30min, MANOMETERS Make: WIKA: 90259480-2-91 Calibration date: 22/05/17 ‘As per procedure # BINDE-14-001, pressure was introduced in the hose in a step wise pattern, at increments of 14.5psi, and carried out preliminary soaking for Smin. to achieve a stable pressure until test pressure is attained at 150psi and soaked for 30min. Observations: No pressure drop and or leaks were alerted during the 30minutes pneumatic exercise, Results: The Expansion pipe is serviceable. Client COSL SEEKER Carried out by: GIDEON MENGO: Position