You are on page 1of 2

4007ES CPU and Display Board

4007ES IDNAC PSU (Addressable)

Jumper Purpose Connector Purpose


Used to transfer files to or upload reports from the 4007ES using the Ethernet port on your laptop. This operation
J1 Ethernet Port P2 Serial Interface port is used for connection to remote services.
requires you to enable the Ethernet port by installing Service Mode Jumper J3.
Card Power and Communications connectors.
J2 USB Port Used to transfer files to or upload reports from the 4007ES. P3 & P4
Caution: Locking tabs are located up, on the top of the connectors.

LED Purpose
1 Ethernet connection LED (ON when connected, blinks with activity)
J3 Service Mode This jumper is normally positioned on only one of J3’s two pins. When installed, shorting the two pins, the Ethernet
2 Flashes once a second to show the CPU is processing
Jumper Port connection is enabled and a “SERVICE MODE JUMPER INSTALLED” trouble is generated.
3 Flashes once per polling cycle
4&5 Not used
6 Reset

SW1 Reset Switch - Cold Start. Clears Disables, Manual Overrides, and Logs
U11 - Contains the panel Serial Number and MAC address

© 2015 Tyco Fire Protection Products. All rights reserved. 579-1211


All specifications and other information shown were current as of document revision date and are subject to change without notice.
TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited.
Rev. A
4007ES CPU and Display Board
4007ES IDNAC PSU (Addressable)
Terminal Blocks on the 4007ES IDNAC PSU BOARD
TB Terminal(s) Purpose
1-4 IDNet
Aux/SNAC
1 5&6 Aux Power is Default, 24 volt non-resettable output
SNAC operation depends on the selected Point Type
7-10 RUI
2 1-5 IDNAC
1-3 Aux Relay 1
3
4-6 Aux Relay 2
4 1&2 Battery connection terminals
LEDS on the 4007ES IDNAC PSU BOARD
LED Color Behavior
LED 1 Comm Loss Y
LED 2 IDNAC TBL Y
LED 3 A Y
LED 4 B Y Power Supply Status LEDs
*See IDNAC table below
LED 5 C Y
LED 6 D Y
LED 7 RUI Y ON for Class A RUI trouble, otherwise OFF
LED 8 RUI OC Y Fast blink on short (overcurrent)
LED 9 IDNet Loop 3 Y A and/or B terminal short, or Class A open trouble
LED 10 IDNet Loop 2 Y A and/or B terminal short, or Class A open trouble
LED 11 IDNet Loop 1 Y A and/or B terminal short, or Class A open trouble
LED 12 IDNet Earth - Y Negative Earth Fault on IDNet
LED 13 IDNet Earth + Y Positive Earth Fault on IDNet
LED 14 IDNet TBL Y IDNet Channel Fail
LED 15 IDNet Comm Y ON when offline with Master, otherwise OFF
LED 16 AC Status G OFF on AC Fail, otherwise ON
* Power Supply Status LEDs
IDNAC A B C D Description
ON ON OFF OFF OFF IDNAC Channel Fail
ON OFF ON OFF OFF IDNAC Short Circuit
ON ON ON OFF OFF IDNAC Duplicate Device
ON OFF OFF ON OFF IDNAC Missing Device
ON ON OFF ON OFF IDNAC Extra Device
ON OFF ON ON OFF IDNAC Wrong Device
ON ON ON ON OFF IDNAC Controller Fail
ON OFF OFF OFF ON IDNAC Address Out of Range
ON ON OFF OFF ON IDNAC Isolator Trouble
ON OFF ON OFF ON IDNAC Overcurrent
ON ON ON OFF ON IDNAC Earth Trouble
Note: SW1 is used to scroll if there are multiple IDNAC Troubles
P Connectors on the 4007ES IDNAC PSU BOARD
P Purpose
1 RUI Class Selector. Default is Class A. For Class B operation,
move the two jumpers to short the top two pins.
2 IDNet+ Loop A Class. Default is Class A. For Class B operation,
move the two jumpers to short the top two pins.
4 Default – NAC Power Supply Online
Jumper removed NAC Power Supply Offline
5 Low Battery Cutout - * Canadian operation is not the default jumper setting
8 Default - IDNet Online
Jumper removed IDNet Offline
9 25V Regulator Jumpers 1-2, 3-4 default.
Remove Jumpers when using the 25V Regulator Module
10 AC power input connector
11 Connector for ribbon harness to optional city card or optional relay card
J connectors on the 4007ES IDNAC PSU BOARD
J Purpose
7 Communications and Power for Zone/Relay card(s)
10 IDNet 2 Loop expansion (first expansion IDNet card)
11 IDNet 3 Loop expansion (second expansion IDNet card)
15 Communications and Power for Zone/Relay card(s) or DCAI
16 Communications and Power for the retainer mounted CPU card
17 Communications and Power for a DACT card