You are on page 1of 44

4010ES

Gregg Lupaczyk
Derek Knerr
Alex Andrews
International Trade Controls and Restrictions
This training material may contain information or technology the export or re-export of which is restricted by U.S. laws and regulations. By viewing this training material, the
recipient agrees to the following: (1)) the recipient's use of the contents of this training material shall comply with all applicable laws, rules and regulations, including, without
limitation, U.S. international trade laws and regulations, and (ii) the recipient may not transfer or otherwise export or re-export any information or technology contained in this
training material except in full compliance with the export controls administered by the U.S. and other countries and any applicable import and use restrictions.

1
4010ES

4010ES 2 Bays for the International Market


• 1000 Devices over 4 Channels
– IDNet+ or Mx devices
– Compatible with all IDNet devices including Quick
Connect
– Compatible with MX devices supported by the
4100ES
• Full Networking
• Option Cards
– 11 blocks size option card slots
– BNIC, DACT, SafeLINC, RS232, VESDA
– Network, City Connect, TrueInsight
– IDNet+, MX Loop, 25VDC,
– 8-zone Card (1 max), Alarm Relay
– Remote InfoAlarm
• 2 Bay 4100ES Size Cabinet
– Internal 50AH batteries
4010ES

4010ES Base System Components


• CPU with 2 GB Compact FLASH
• Direct connect 2x40 UI with membrane keypad
• 248 device, 2-loop isolated IDNet+ channel Style
4 or Style 6
• 8A Power Supply
• Battery Charger (50Ah)
• 4 NACs (Class A)
• One AUX Relay & One AUX PWR (2A)
• Style-7 RUI
• Three block size option card slots (One 4 x1 0
card and 1 4 x 5 card OR three 4 x 5 cards)
• Mounting space for TrueInsight “Perle” box
without using up an option card block.
4010ES Point Capacities
• IDNet+ devices
– 248 Devices
– Dual Isolated Circuit
• VESDA Points
– 127
– One VESDA HLI card
• Network Externals
– 100 Points
• Annunciator Points
– 2000
– Panel LEDs and External Graphic Modules
• Keyboard Devices CPU Card
– 5 DACT, SafeLINC etc. LED Module
• Up to 5 Printers
• Up to 20 Option Card Addresses TrueInsight
Remote
– Combination of Internal and External (RUI)
Option Cards Gateway
– MSS /IDNet+ count as 2 addresses
4
User Interface - Standard
Can also be
programmed SYSTEM IS NORMAL
Yellow

 2X40 Operator Interface


• Available in English and French Silkscreen (select models)
 Same as 4100ES except 2 programmable keys / LEDs removed.
 Slide in Labels for programmable keys

5
Slide in Label Locations

CPU Card Slide in


Label Location

48 LED Slide In Label Locations

6
Electrical

7
Electrical Approach
• Use the same Core as 4100ES CPU and SPS
– minimizes software effort
• Cost reduce features not needed
• Remove harnessing where we can
• Remove expansion supply requirement (lower R&D effort)
• Remove sheet metal where we can
• Maximize option card space
• Leverage 4100ES Option Cards

8
CPU Card Overview
• Combination of 4100ES CPU Card, Motherboard, and User Interface
– Cost reduced with some features removed

• Sold pre-installed in top level 4010ES PIDs or as a service part.


– Two versions (depends on which 4010ES ordered)
• CPU Card w/2X40 Display (0566-861) - 2X40 LCD, Piezo and
Membrane Interface installed
• CPU Card for InfoAlarm (0566-888) – No LCD, Piezo or Membrane
Interface

9
CPU Card Features
• Membrane Keypad Controller (depopulated for InfoAlarm )
• Piezo built in (depopulated for InfoAlarm )
• 2X40 Display (depopulated for InfoAlarm)
• Compact Flash
• Style 7 RUI Circuit (Same wiring and limitations as 4100ES CPU
Motherboard)
• 4100 COMMs (internal slave comm)
• 30 Day Battery Backed History Logs
• Ethernet Service Port
• Serial Service Port (kept for TrueInsight Remote Gateway)
• Cold Start Switch

10
4010ES CPU Card Notable Deletions
• Removed Service Modem Interface
• Removed 8V power (was on motherboard)
• Removed CFIG Swap Button (not needed with the advent of Ethernet
Service Port)
• Removed 2 Programmable buttons and their corresponding LEDs
(membrane keypad)
• Removed City Circuit Interface
– must use MSS / MSSI city circuit interface option
• Removed 4100 Comm / Download Jumper for service troubleshooting
– not needed since Automated test interface does the same thing for field
captures

11
4010ES CPU Card (0566-861 picture, back)
Piezo RUI Enable Jumper
Reset Switch Compact RUI Shield Jumper
2X40 Display
and LED Flash

RUI LEDs

RUI Interfac

Serial Chip
Cold Start Battery Ethernet Service
Serial
Switch Bootloader Keypad Jumper Power / Port and LEDs
Service
Interface Comms
LEDs Port

Note:  CPU Card for InfoAlarm is the same but without LCD, piezo, and membrane
12
interface circuits populated
CPU Card Switches

13
CPU Card Jumpers

14
CPU Card LEDs (non-UI LEDs)

15
CPU Card Connections (Internal)

16
CPU Card Connections (External)
• RUI Interface
– Style 4 or Style 7 Wiring
• If Style 4 wiring is used, must have Pri-
Sec loop back on terminal block
– Short and open detection
– Same wiring guidelines as 4100ES RUI
circuitry
– Wiring gets terminated from the CPU card to
the left side of the box for strain relief
– 4010ES RUI Supports
• 4009T
• 4009TPS
• 24 I/O Graphic Annunciator
• 4010 Remote LCD Annunciator
• Remote InfoAlarm

17
Main System Slave (MSS) Overview
• Redesign of 4100ES SPS with added features
• Sold pre-installed in top level 4010ES PIDs or as a service part.
– Two versions
• MSS IDNet (MSSI) (0566-876) - includes a single channel 2 loop
IDNet+ circuit
• MSS (MSS) (0566-878) - IDNet circuit depopulated (MX systems)

18
MSS Features
• 8A of available power - excludes 2X40 CPU current draw and MSS current draw
– 48 LED Module, InfoAlarm, NAC power, IDNet peripherals current Draw must
be subtracted from the available 8A
• Four 3A Class A NACs (No option module required for Class A)
– Remember, you still have only 8A of available power.
• Battery Charger, up to 110Ah batteries (UL) and 50Ah (ULC) can be charged.
Batteries may need external battery box for larger batteries.
• Aux Relay (2A, 32V)
• Aux Power (2A Max)
• Standby Power, 5A Max (Same as SPS)
• Single Channel, Two Loop IDNet+ Circuit
• Mounting space for City Circuit, or Alarm Relay Module
– Ordered and installed separately
• Earth Detection (10K Ohm minimum)

19
Main System Slave w/ IDNet (0566-876)
Canadian Battery Cutout Jumper Address
To Bridge Switch Status
Rectifier LEDs
Battery
Connecti IDNet
on Jumper
City or s
Relay
Option IDNet
Modul Status
Earth
e
Detect

Jumpe
Auxilia
rry
Relay
Auxilia IDNet+ Loop A and
NACs 1-4 B
ry
Note: MSS without IDNet is the same without the IDNet circuitry populated.
Power
20
MSS Switches and Jumpers
• ADDRESS SWITCH
– Set the slaves RUI address to the programmer’s
assigned address

• Jumpers

21
MSS LEDs

22
MSS Mounting and Internal Connections
Harness
• MSS Mounts directly PDI, Top (not
Bay Block C only (No shown)
harnesses) connects
left side of
• MSS can be replaced easily
AC block
without removing Rectifier
and Transformer
• Provided Harness connects
Battery to MSS (Fused
Harness) with standard with
standard spade lugs
• Bridge Connection connects
to Rectifier

Connects Connects
Label next to to Bridge to AC
Bridge Rectifier Rectifier Block
shows Molex
23
connections Connectio
MSS Field Wiring

• NACs – Same wiring requirements as SPS NACs


– 4 Class A NACs
• 3A maximum each for special application appliances (8A maximum
total MSS)
– See Tech Pub for which appliances are special apps.
• 2A for 24VDC regulated appliances (4A maximum total MSS)
– Protocols supported
• TrueAlert Non-Addressable
• Conventional (Free Run / Sync)
• Wheelock
– Can be used for Aux power
• Same as 4100ES SPS (2A max)

24
MSS Field Wiring (cont.)
• IDNet+ Circuit
– Same wiring requirements as 4100-3107 IDNet+ card.
• 2 Loops instead of 4 loops.
• Compatible with all IDNet devices the 4100ES is compatible with
including Quickconnect (QC1 and QC2).
• When configured as Class B, can have 4 circuits per loop or 8 circuits
across both loops
• Aux Relay
– Same interface as the 4100ES SPS (2A, 32V)
• Aux Power
– Same as 4100ES SPS (2A max)

25
City / Relay Card Mounting

26
Top Bay and Expansion Bay PDIs Overview
• Similar to 4100ES PDI cards except
– No Audio Support
– Signal Power is bussed from bay to bay (no expansion supply needed)
• 5A Limitation of Signal Power in Second Bay (connector limitation)
• No Signal Power limitation in Top Bay
– Plugging cards used in the 4100ES into a 4010ES PDI will not damage the
card or PDI
• Exception – Power Supplies – not supported in software and
hardware may be damaged.
– Card power is 4A (includes Dead Front card power, MSS Limitation)

27
Top Bay and Expansion Bay PDIs Overview (cont.)

Top Bay – 0566-880

Expansion Bay – 0566-882

28
PDI Connections

4" x 5" Slave


To Dead Card Block
MSS
Block A
Front (CPU) To front door (CPU Card)
Harness TBD

(4 Pin)
Spare / 4 14 14

Close
Spare Core-4
Connector 4 Top Bay PDI

6 14 14

To
Nippled Block D
Block B
Expansion 4" x 5" Slave 4" x 5" Slave
Standard system: Top Bay PDI only
Expansion System: Top and Expansion PDI

Card Block Card Block


Bay (6 pin) 0734-052

4" x 5" Slave 4" x 5" Slave 4" x 5" Slave 4" x 5" Slave
Card Block Card Block Card Block Card Block

Block A Block C Block E Block G

6 14 14 14 14
Expansion Bay PDI
Close Nippled
Box (no SIG 4 14 14 14 14
Spare / power)

Block B Block D Block F


Close 4" x 5" Slave 4" x 5" Slave 4" x 5" Slave
Block H

4" x 5" Slave


Card Block Card Block Card Block
Nippled Card Block

Notes:
"4" Denotes the "Core-4" Microfit Connector
"6" Denotes the “Core-6” Microfit Connector
"14" Denotes the Minifit Connector used for PDI access by slave cards and other
modules

29
Optional Modules Installed Inside the Panel
Option Cards (Local)
4010-9901 0743-888 Flat Vesda HLI
* 4010-9902 0743-928 Flat Network Card
4010-9903 0743-929 Modem Physical Bridge Style 4
4010-9904 0743-931 Modem Physical Bridge Style 7
* 4010-9905 0743-930 TCP/IP Physical Bridge Style 4
4010-9906 0743-932 TCP/IP Physical Bridge Style 7
4010-9818 0742-100 Network Card Media Module - Wired
4010-9819 0742-101 Network Card Media Module - Fiber
4010-9907 0743-890 IDNet+
4010-9908 0743-973 4 Point Flat Aux Relay Module
4010-9909 0743-974 City Connect Module w/ disconnect switches
4010-9910 0743-975 City Connect Module
4010-9911 0743-976 Alarm Relay Module
4010-9912 0743-982 Serial DACT
* 4010-9913 0743-977 SafeLinc
4010-9914 0743-978 Building Network Interface Card
4010-9915 0743-979 BacPac Grid Connect Module
* 4010-9916 0743-980 25V Regulator Module
4010-9917 0743-970 MX Loop Card
4010-9918 0743-981 Dual RS232 Module
4010-9919 0743-990 TrueInsight Remote Service Gateway
* Comes with 8V converter
* 4010-9920 0743-983 8 Zone Initiating Device Circuit - Class B Module
Comes with 8V converter
* 4010-9921 0743-984 8 Zone Initiating Device Circuit - Class A Module

Items with * have mechanical or electrical changes discussed in this presentation. All
other modules function and install exactly the same as 4100ES equivalent versions. 30
8 Zone IDC (Class B and Class A)
• Only vertical Cards used in the 4010ES
– Electronics and connections are identical to 4100ES system.
– Mounting is largely the same
• Mounts in top bay only (1 or 2 bay systems, uses Blocks A and B)
• Limit of 1 per system
– Kit comes with 8VDC power supply and Zone Card w/ motherboard

31
8 Zone IDC Module

32
8 Zone IDC Mounting

33
8 Zone IDC Harnessing

34
Power Limited Wiring
• One Bay Panel
would be the
same except the
expansion area is
removed

35
Compatible Options (outside the box)
Fiber Modem
Red Fiber Modem Expansion Cabinet w/ Left Port Modem – Single
4190-9021 0743-720 Mode

4190-9022 0743-721 Beige Fiber Modem Exp Cabinet w/ Left Port Modem - Single Mode
4190-9023 0743-717 Right Port Modem for Exp Cabinet – Single Mode
4190-9024 0743-722 Red Fiber Modem Exp Cabinet w/ Left Port Modem – Multimode
4190-9025 0743-723 Beige Fiber Modem Exp Cabinet w/ Left Port Modem - Multimode
4190-9026 0743-719 Right Port Modem for Expansion Cabinet – Single Mode
Remote Power / Notification
4009-9201 0636-867 4009A 120V SPI: 050-091 for accessories
4009-9202CA 0636-988 4009A 120V ULC listed model SPI: 050-091 for accessories
4009-9301 0636-868 4009A 240V SPI: 050-091 for accessories
4009-9401 0636-968 4009T TrueAlert Controller 120V SPI: 050-094 for accessories
4009-9402CA 0637-244 4009T TrueAlert Controller 120V w/ Low Battery Cutout SPI: 050-094 for accessories
4009-9501 0637-450 4009T TrueAlert Controller 240V SPI: 050-094 for accessories
0746-069 Order with 4009-9813 and a
2975-9230 Beige 4009 TPS Cabinet single TPS. SPI: 050-094
0746-070 Order with 4009-9813 and a
2975-9229 Red 4009 TPS Cabinet single TPS. SPI: 050-094
0743-801 Only usable with 2975-9229 or
4009-9813 Transponder Interface Card 2975-9230. SPI: 050-094
0742-659 Only usable with 2975-9229 or
4100-5120 120V Domestic TrueAlert Power Supply 2975-9230.
0742-660 Only usable with 2975-9229 or
4100-5121 120V Canadian TrueAlert Power Supply 2975-9230.
0742-661 Only usable with 2975-9229 or
4100-5122 220-240V International TrueAlert Power Supply 2975-9230.
36
Compatible Options (outside the box, cont.)

Remote Annuncition
4100-9401 0743-187 Remote Unit Interface Panel w/FUI – Red – Domestic & Canadian
English
4100-9402 0743-188 Remote Unit Interface Panel w/FUI – Beige – Domestic & Canadian
English
4100-9421 0743-189 Remote Unit Interface Panel w/FUI – Red – Canadian French
4100-9422 0743-190 Remote Unit Interface Panel w/FUI – Beige – Canadian French
4100-9441 0743-191 Remote Unit Interface Panel w/FUI – Red – International
4100-9442 0743-192 Remote Unit Interface Panel w/FUI – Beige – International
4606-9102 0748-696 4010ES RUI LCD Annunciator (English)
*
4606-9102CF 0748-697 4010ES RUI LCD Annunciator (French)
4100-7401 N/A 24 Point I/O Graphic Module (requires mounting cabinet)
64 Switch and 64 LED Driver Module with 32 on-board LED drivers
SPI: See 050-070 for
4100-7402 N/A (requires mounting cabinet)
configuration options.
4100-7403 N/A 32 Point LED Driver Module (requires mounting cabinet)
4100-7404 N/A 32 point Switch Input Module (requires mounting cabinet)

37
4010ES RUI LCD Annunciator
• Same as 4100ES RUI LCD annunciator (cost reduced version)
– 3 Programmable Keys and LEDs instead of 4.

38
Software

39
The old 4010 is a far distant relative of the
4010ES – There are no similarities
• Old 4010 software was totally abandoned. None of it was used for 4010ES.

• 4010ES software is the same source code as the 4100ES.


– 4010ES code will go through more than 9,500 Automated Tests prior to each release.
– Increased usage = more field testing. Defects will be found and fixed sooner.
– A single code base is easier to maintain. One fix resolves 4100ES and 4010ES.
– Multiple Languages are now supported (carry over from 4100ES)

• A single bin file is downloaded into either a 4100ES or a 4010ES.

• There is nothing to prevent downloading 4100ES jobs into 4010ES panels


and vice versa. However, panel software will compare CPU card type and Job
type. If they do not align, the panel will crash with ‘Invalid CPU Type’ error.

40
4010ES vs. 4100ES
• 4010ES Differentiation:
– Limited to 20 addressable slaves and e-slaves.
– Limited to 10 RUI annunciators.
– Limit of 3 optional cards in CPU bay. If a 4x10 card is used, limit is 2 optional
cards.
– Limited to 100 external network points. No limit on public network points.
– No Audio or Signal cards.
– Limited selection of Monitor, Relay, Annunciator, Interface, and Power options
(mostly due to form fit).
– Uses different LCD Annunciator than 4100ES or old 4010.
– New cards: MSSI, MSS, 4010IDNet+, 4010LCD, 48 LED Module.
– 4010ES limited to the 2 loop IDNet+ on MSSI.
– International 4010ES allows up to 4 MX Loop or 4010IDNet+ cards (IDNet+ circuit
on the MSSI counts against the limitation).

41
4010ES vs. 4100ES (cont.)
• 4010ES Noteworthy Similarities:
– No device restrictions on IDNet. All 4100ES IDNet devices
are available on 4010ES (including Isolators Modules,
Isolator Bases, Quickconnect 1 and Quickconnect 2
devices..
– Full 4120 network capability (public and external points).
• Supports Global Ack
– Vesda availability.
– Computer port and TrueInsight compatible.
– InfoAlarm is available.

42
4010 to 4010ES Upgrade
• Items that will not be translated to 4010ES:
– Custom Control.
– System Options and Access Levels.
– Network and Site Info.
– User List and User Pseudos.
– Class A Adaptor Card for NACs, Battery Meter Modules, and Expansion Power
Supply.
– DACT Programming
• The ES Programmer is not used to program the DACT

• Special case items:


– The Virtual NAC card (17) does not exist in the 4010ES. 4009A points will be
translated to points and subpoints on the IDNet+ card.

43
4010 to 4010ES Upgrade (cont.)
• 4010 IDNet device translation restrictions:
– LATSUPV for ION will not be translated.
– SUPVMON for ION will not be translated.
– LATSUPV for QSPHOTO will not be translated.
– SUPVMON for QSPHOTO will not be translated.
– SUPREL for RIAM will not be translated.
– SWATER for RIAM will not be translated.
– QRPHOTO will be translated to QSPHOTO on 4010ES.
– Labels for multi-point devices (e.g. 4009 points) may not appear in the 4010ES job.
– Devices at addresses 249 and 250 will not be translated as these addresses are reserved for IDNet+ Isolators.

• Upgrade existing 4010 job.


– No need to export anything from old 4010 programmer.
– Select ‘Upgrade Legacy 4010’ under File menu item.

• All items that do not translate will be noted in the output as conversion
progresses.

44