SecuriFire
BX-OI3
Output/input module for
SecuriLine eXtended
Beginning with edition number 20-2100001-01-02
Description
The BX-OI3 can be connected to the SecuriLine eXtended ring cir- SecuriLine eXtended (X2)
cuit of the SecuriFire fire detection system. Terminal Designation Description
The BX-OI3 can be used as either an O/I module (1 relay output, 2 1 L1 Data A
monitored inputs, 1 opto-isolator) or as detector/detection zone for 2 GND GND A
connecting special detectors. 3 GND GND B
Input 1 can be programmed as checkback. 4 L2- Data B
Addressing and parameter assignment for the BX-OI3 is performed 5 SHLD Screen
with PC software via the fire alarm control panel. 6 SHLD Screen
The BX-OI3 includes a short-circuit isolator. In the event of wire
breakage or a short-circuit, this functionality ensures that the fault Relay output (X3)
is localised and at the same time maintains the full operability of Terminal Designation Description
the ring circuit. 1 NC Data A
2 COM GND A
Interfaces 3 NO GND B
Areas of application
Use as O/I module
1x relay output for actuating fire incident control (e.g. lift control
system)
2x monitored inputs for polling potential-free contacts (e.g.
*)
sprinklers)
1 opto-isolator input for polling external voltages (e.g. 5 V, 12 V)
GND GND
L1 L2
The voltage supply of the special detector is monitored
SHLD SHLD
GndExt5
GndExt4
GndExt3
GndExt2
GndExt1
by means of an opto-isolator on the BX-OI3 output/input
VExt5
VExt4
VExt3
VExt2
VExt1
module. This also enables connecting devices whose
B5-PSU
B6-PSU
fault contact does not become active when there is no X2
BX-OI3
1
power supply. When connecting the voltage supply, en-
SHLD
SHLD
L1
L2
GND
GND
sure that it is conveyed from the power supply unit via
Relay
the reset contact of the BX-OI3 directly to the special
External power
Input 3
Input 2
Input 1
detector and then from this back to the voltage monitor
supply unit
on the BX-OI3. Only in this way can it be ensured that
+ -
also the voltage supply between BX-OI3 and special de-
Vext+
COM
IN3+
IN2+
IN1+
IN3-
IN2-
IN1-
NO
NC
tector is monitored. 1 1
X1 X3
Use as O/I module
GND GND
L1 L2
SHLD SHLD
GndExt5
GndExt4
GndExt3
GndExt2
GndExt1
VExt5
VExt4
VExt3
VExt2
VExt1
180
180
180
180
B5-PSU
B6-PSU
X2
BX-OI3
1
SHLD
SHLD
L1
L2
GND
GND
10
11
12
13
14
15
16
17
18
1
2
3
5
6
7
8
9
4
Relay
ra
ra
Input 3
Input 2
Input 1
a
r
r
supply unit
Alarm relay
Fault relay
+ -
Vext+
COM
IN3+
IN2+
IN1+
IN3-
IN2-
IN1-
NO
NC
X1
1
X3
1
ADW 511
Actuation of
ADW 511A
fire incident controls
180
Fig. 5 Connection: ADW 511/ADW 511A
180
monitored
Polling of
potential-free contacts
not monitored
-
Monitoring of
+ external voltages
ASD 51x (ASD 51x parameter set) RAS 51B and RAS 52B (RAS 51B parameter set)
GndExt4
GndExt3
GndExt2
GndExt1
SHLD SHLD
GndExt5
GndExt4
GndExt3
GndExt2
GndExt1
VExt5
VExt4
VExt3
VExt2
VExt1
VExt5
VExt4
VExt3
VExt2
VExt1
B5-PSU
B6-PSU
B5-PSU
B6-PSU
X2
BX-OI3
X2
BX-OI3
1
1
SHLD
SHLD
L1
L2
GND
GND
SHLD
SHLD
L1
L2
GND
GND
Relay
Relay
External power
Input 3
Input 2
Input 1
External power
Input 3
Input 2
Input 1
supply unit
supply unit
+ -
+ -
Vext+
COM
IN3+
IN2+
IN1+
IN3-
IN2-
IN1-
Vext+
COM
NO
IN3+
IN2+
IN1+
NC
IN3-
IN2-
IN1-
NO
NC
1 1
1 1
X1 X3 X1 X3
180
180
180
180
180
180
180
180
11
12
13
15
17
10
14
16
18
1
2
3
4
5
6
7
8
9
15
13
20
19
14
12
11
10
1
2
ra
24V
24V
ra
a
r
ra
ra
a
r
Reset +
a
a
Reset -
r
Alarm relay
Fault relay
Power supply
Fault relay
Power supply
Alarm relay
4/7
B6-BCU (X12)
V4
G4
C4
L4
V3
Ring 2
X1
Miniboomerang
BX-OI3 G3
X2
B5-PSU Vext+
IN3+ C3
B6-PSU
L2
1 L1
IN3- Input 3 L3
GND
GND
SHLD
SHLD
V2
BX-IM4
X2
VExt5 IN2+
GndExt5 IN2-
Input 2 SHLD G2
Data sheet
External power
VExt4 IN1+ C2
supply unit Input 1 SHLD
GndExt4 IN1- L2
L2
VExt3 V1
Ring 1
Power + - GND
Input 4
Input 3
Input 2
Input 1
supply G1
X3
Fault relay Alarm relay GndExt3
1
NC C NO NC C NO _ + VExt2 NC GND C1
L1
1
8 7 6 5 4 3 2 1 GndExt2 COM Relay L1
IN3+
IN2+
IN1+
IN4-
IN3-
IN2-
IN1-
VExt1 NO
IN4+ 1
GndExt1
X1
B5-PSU
180
180
B6-PSU
180 180 VExt5
RAS XL (UNILASER XL parameter set)
L1
GndExt4
X1
GND
SHLD
180
180
180
180
180
180
180
180
180
180
180
BX-OI3 VExt3
1
Vext+ + -
IN3+ GndExt3
X2
IN2+
Input 2 VExt1
IN2- SHLD
Pre Pre Al 1 Al 2 Stö Isolate GndExt1
X3
External PSU Power Power
RAS XL
1
NC GND Network Display Status out in
_ _ _ _ _ _
1
COM Relay L1 + + 0V 24V _ + + + + +
NO
2 x 2 x 0,8
screened
screened
1 x 4 x 0,8
max. 20 m
External Display
GND
L2
SHLD
max. 1000 m
B5-PSU
B6-PSU
T 811 128 en f
VExt5
External power GndExt5
VExt4
supply unit GndExt4
VExt3
+ - GndExt3
VExt2
RTX GndExt2
+ Power supply 24V VExt1
_
Boomerang or ARDEA
ARDEA J
GndExt1
transmitter TX
Screen NA 180
JP A Fault relay C 180
RRX NC
JP B
+ NA 180
_
TX/RX
Receiver
ARDEA J
Alarm relay C 180
receiver RX
Screen
BOOMERANG
NC
L1
X1
GND
SHLD
INT8BA BX-OI3
1
Vext+
IN3+
IN3- Input 3
JP A - delay time relay
X2
IN2+
IN2-
Input 2 SHLD
immediately 30 s 60 s 90 s
IN1+ SHLD
IN1-
Input 1
JP B - ialways remove L2
GND
X3
1
NC GND
COM Relay L1
NO
ARDEA and BOOMERANG (ARDEA IP65/Ex parameter set)
GND
L2
SHLD
BX-OI3
Data sheet
ECO 25/50/80 (ARDEA J parameter set) REK 511 (ASD 51x parameter set)
GndExt5
GndExt4
GndExt3
GndExt2
GndExt1
SHLD
GndExt5
GndExt4
GndExt3
GndExt2
GndExt1
VExt5
VExt4
VExt3
VExt2
VExt1
VExt5
VExt4
VExt3
VExt2
VExt1
B5-PSU
B6-PSU
B5-PSU
B6-PSU
X2 X2
BX-OI3
BX-OI3
1 1
SHLD
SHLD
L1
L2
GND
GND
SHLD
SHLD
L1
L2
GND
GND
Relay
Relay
External power
Input 3
Input 2
Input 1
External power
Input 3
Input 2
Input 1
supply unit
supply unit
+ -
+ -
Vext+
COM
IN3+
IN2+
IN1+
IN3-
IN2-
IN1-
NO
NC
Vext+
COM
IN3+
IN2+
IN1+
IN3-
IN2-
IN1-
NO
NC
1 1
1 1 X1 X3
X1 X3
MEA 720
(max. 5 mA)
RNA
St
RA- 180
Al
RA+ 180
180
SSD MRP
NC C NO
RE- 180
180
RE+ 180 515-xS 915
Al
LOOP
+
5
LOOP+ 180
+ G N D (NC) C (NO)
St-
180
0V
REL
ECO 0V
St
Al+
Base contact
3
GND 3
+24V
_
2
OUT
IN
+
1
+
Fig. 10 Connection; ECO 25/50/80
REK 511
B5-PSU
B6-PSU
VExt5
External power GndExt5
VExt4
- ST3/3 supply unit GndExt4
PWR
GND
FAULT
X1
BX-OI3
180
NO 3 Vext+
1
IN3+
IN3- Input 3
C 4
X2
IN2+
LG 1 IN2-
Input 2 SHLD
A 5 IN1+
Input 1 SHLD
AL 1
IN1-
L2
C 6 GND
X3
4 x 180 NC GND
1
A 7 COM Relay L1
1
AL 2
NO
C 8
SHLD
GND
L2
+ 9
EXR
- 10
B5-PSU
B6-PSU
VExt5
External power GndExt5
VExt4
- ST3/3 supply unit GndExt4
PWR
SCU 800 ST3/2 + - VExt3
GndExt3
+ ST3/1 VExt2
BR 2 GndExt2
1 VExt1
GndExt1
LG 2
180 NC 2
L1
SHLD
GND
FAULT
X1
BX-OI3
180
NO 3 Vext+
1
IN3+
IN3- Input 3
C 4
X2
IN2+
LG 1 IN2-
Input 2 SHLD
A 5 IN1+
Input 1 SHLD
AL 1
IN1-
L2
C 6 GND
X3
NC GND
1
A 7 COM Relay L1
AL 2
1
NO
C 8
SHLD
GND
L2
+ 9
EXR
L1
SHLD
GND
-
X1
10
Vext+
BX-OI3
1
IN3+
Relay print IN3- Input 3
1
X2
IN2+
IN2-
Input 2 SHLD
180
180
2 IN1+
Input 1 SHLD
IN1-
4 x 180 L2
3 GND
X3
NC GND
1
LG 1 4 COM Relay L1
1
NO
SHLD
GND
L2
Technical data
Function Output/input module
Operating voltage 12 to 30 VDC
Power consumption (module’s power consumption only) 0.55 mA
Signal transmission Serial data transmission, 2-line technology
Protection type 66 with map case IP
Ambient temperature -20 to +60 °C
2
Connection Screw terminals max. 1.5 mm
VdS approval G210133
EU certificate of conformity (EN 54-17/18) 0786-CPD-21011
Dimensions (H x W x D) 67 x 67 x 20 mm