Data sheet

____________________________________________________________________________________________________________________

SecuriFire
BX-OI3
Output/input module for
SecuriLine eXtended
Beginning with edition number 20-2100001-01-02

The BX-OI3 output/input module can be used as either O/I module


or as detector/detection zone for connecting special detectors.

It meets the SecuiLine eXtended specification for operation on the


Fig. 1 BX-OI3
ring circuit of the SecuriFire fire detection system.
____________________________________________________________________________________________________________________

Description
The BX-OI3 can be connected to the SecuriLine eXtended ring cir- SecuriLine eXtended (X2)
cuit of the SecuriFire fire detection system. Terminal Designation Description
The BX-OI3 can be used as either an O/I module (1 relay output, 2 1 L1 Data A
monitored inputs, 1 opto-isolator) or as detector/detection zone for 2 GND GND A
connecting special detectors. 3 GND GND B
Input 1 can be programmed as checkback. 4 L2- Data B
Addressing and parameter assignment for the BX-OI3 is performed 5 SHLD Screen
with PC software via the fire alarm control panel. 6 SHLD Screen
The BX-OI3 includes a short-circuit isolator. In the event of wire
breakage or a short-circuit, this functionality ensures that the fault Relay output (X3)
is localised and at the same time maintains the full operability of Terminal Designation Description
the ring circuit. 1 NC Data A
2 COM GND A
Interfaces 3 NO GND B

Areas of application
Use as O/I module
 1x relay output for actuating fire incident control (e.g. lift control
system)
 2x monitored inputs for polling potential-free contacts (e.g.
*)

sprinklers)
 1 opto-isolator input for polling external voltages (e.g. 5 V, 12 V)

Use for connecting special detectors


 1x relay output for resetting the special detector
 2x monitored inputs for polling the alarm and fault contact
Fig. 2 BX-OI3 interfaces  1x opto-isolator input for monitoring the voltage supply of the
special detector

Inputs (X1) * Input is always implemented as monitored, i.e. termination resis-


Terminal Designation Description tance and alarm resistance are always required.
1 VEXT+ Monitored ext. Power supply
2 IN3+ Input 3+
3 IN3- Input 3-
4 IN2+ Input 2+
5 IN2- Input 2-
6 IN1+ Input 1+
7 IN1- Input 1-

Securiton AG Alpenstrasse 20 3052 Zollikofen Switzerland T 811 128 en f 1/7


Data sheet

To be able to connect a special detector (aspirating smoke detec- Planning


tor, line type smoke detector etc.) to the BX-OI3, it must have at
Use as O/I module
least one potential-free contact each for alarm and fault. Resetting
the special detector is done by interrupting the voltage supply via
the BX-OI3 relay output. If a suitable reset input is available on the It is imperative that the technical data are strictly ob-
special detector, it can be actuated directly via the relay outputs. served.
The voltage supply of the special detector is monitored via the
opto-isolator input. This also enables connecting devices whose
fault contact does not become active when there is no power sup-
 Inputs 1 and 2 can be operated as monitored or unmonitored
ply.
inputs when using termination and alarm resistance in each
case.
Use for connecting special detectors
 The maximum number of BX-OI3s per ring depends on the total
In principle, any special detector can be connected to the BX- number of connected detectors and modules, on the line length
OI3 provided it has two potential-free contacts for alarm and fault and on the wire cross-section of the concerned ring.
and that it can be reset by interrupting its voltage supply or via its
own reset input. To ensure reliable operation, each special detec-
tor has to be checked and then implemented with a fixed defined Use for connecting special detectors
parameter set in SecuriFire Studio. The following table shows the
checked special detectors to be connected and the parameter sets
 If the BX-OI3 is used to connect a special detector, a corre-
of the SecuriFire Studio to be used (SecuriFire Studio V2.1).
sponding detector address must be designated for it in Securi-
Fire Studio. As a result, the BX-OI3 is shown and operated like
Parameter-Set in Studio Manufacturer designation
an automatic detector on the indication and control map of the
ARDEA IP65 / EX Setronic ARDEA IP65 S-SF
fire alarm control panel (e.g. MG 14/7). Multiple BX-OI3s can be
and ARDEA EEX S
grouped into a detection zone in order to simplify operation.
ARDEA J ECO 25/50
 During first-time commissioning the fixed predefined parameter
ASD 51x Securiton SecuriRAS ASD 51x set of the connected special detector must be assigned to the
PM-5MPX Det-Tronics BX-OI3 via SecuriFire Studio from a selection list. If your special
IR-flame detector PM-5MPX detector is not listed, please contact the Securiton support cen-
U7698B Det-Tronics tre.
IR- flame detector U7698B  The maximum number of special detectors per ring is identical
MINIBOOM Setronic Miniboomerang 2S to the maximum possible number of BX-OI3s. This depends on
RAS 51B Securiton the total number of connected detectors and modules, on the
RAS 51B and RAS 52B line length and on the wire cross-section of the concerned ring.
RAS 54 Securiton RAS 54  Only four different types of special detectors can be connected
RAS 51B/53B Securiton RAS 51B/53B per ring. If they are already planned in SecuriFire Studio, these
SPB-E Hochiki SPB-E four special detectors appear in the selection list for this ring.
ADW 511 Securiton Transafe  Because most special detectors have high power requirements,
ADW 511 And ADW 511A a power requirement calculation should always be carried out
UNILASER XL Kidde-Deugra for the fire alarm control panel. If it is determined that direct
UNILASER & RAS XL power supply from the power supply unit of the FACP is not
MHD/TSC Securiton possible, then either another FACP or an external power supply
SecuriSense MHD535 unit must be used.
U7652B/WMX5000 UV/IR- flame detector  If an external power supply unit is used, ensure that country-
Det-Tronics U7652B specific standards and directives concerning battery capacity,
Minimax WMX5000 approval (e.g. VdS) etc. are observed.
ILIA Setronic ILIA
SPB 651 Securiton If power is supplied directly to the special detectors from the power
Sprinker-test box SPB 651 supply unit of the FACP, some special detectors can be operated
BSD 535 Securiton only a few hundred metres from the fire alarm control panel due to
SecuriBeam BSD 535 their high quiescent current (dependent on the wire cross-section
of the supply lines and the minimum operating voltage).
LISTEC Listec sensor cable

The BX-OI3 can be mounted up to 30 m from the spe-


cial detector and interface of the special detector.

2/7 T 811 128 en f BX-OI3


Data sheet

Connection examples ADW 511/ADW 511A (ADW 511 parameter set)

GND GND
L1 L2
The voltage supply of the special detector is monitored
SHLD SHLD

GndExt5

GndExt4

GndExt3

GndExt2

GndExt1
by means of an opto-isolator on the BX-OI3 output/input

VExt5

VExt4

VExt3

VExt2

VExt1
module. This also enables connecting devices whose

B5-PSU
B6-PSU
fault contact does not become active when there is no X2

BX-OI3
1
power supply. When connecting the voltage supply, en-

SHLD
SHLD

L1
L2
GND
GND
sure that it is conveyed from the power supply unit via

Relay
the reset contact of the BX-OI3 directly to the special

External power

Input 3
Input 2
Input 1
detector and then from this back to the voltage monitor

supply unit
on the BX-OI3. Only in this way can it be ensured that

+ -
also the voltage supply between BX-OI3 and special de-

Vext+

COM
IN3+

IN2+

IN1+
IN3-

IN2-

IN1-

NO
NC
tector is monitored. 1 1
X1 X3
Use as O/I module
GND GND
L1 L2
SHLD SHLD
GndExt5

GndExt4

GndExt3

GndExt2

GndExt1
VExt5

VExt4

VExt3

VExt2

VExt1

180 

180 

180 
180 
B5-PSU
B6-PSU

X2
BX-OI3

1
SHLD
SHLD

L1
L2
GND
GND

10
11
12
13
14
15
16
17
18
1
2
3

5
6
7
8
9
4
Relay

Power supply 24V


External power

ra

ra
Input 3
Input 2
Input 1

a
r

r
supply unit

Alarm relay

Fault relay
+ -

Vext+

COM
IN3+

IN2+

IN1+
IN3-

IN2-

IN1-

NO
NC

X1
1
X3
1
ADW 511
Actuation of
ADW 511A
fire incident controls

180 
Fig. 5 Connection: ADW 511/ADW 511A
180 
monitored
Polling of
potential-free contacts

not monitored

-
Monitoring of
+ external voltages

Fig. 3 Use as O/I module

ASD 51x (ASD 51x parameter set) RAS 51B and RAS 52B (RAS 51B parameter set)

GND GND GND


GND
L2 L1 L2
L1
SHLD SHLD
GndExt5

GndExt4

GndExt3

GndExt2

GndExt1

SHLD SHLD
GndExt5

GndExt4

GndExt3

GndExt2

GndExt1

VExt5

VExt4

VExt3

VExt2

VExt1
VExt5

VExt4

VExt3

VExt2

VExt1

B5-PSU
B6-PSU
B5-PSU
B6-PSU

X2
BX-OI3

X2
BX-OI3

1
1
SHLD
SHLD

L1
L2
GND
GND
SHLD
SHLD

L1
L2
GND
GND

Relay
Relay

External power

Input 3
Input 2
Input 1
External power

Input 3
Input 2
Input 1

supply unit
supply unit

+ -
+ -

Vext+

COM
IN3+

IN2+

IN1+
IN3-

IN2-

IN1-
Vext+

COM

NO
IN3+

IN2+

IN1+

NC
IN3-

IN2-

IN1-

NO
NC

1 1
1 1
X1 X3 X1 X3
180 

180 

180 

180 
180

180

180 

180 

11
12
13

15

17
10

14

16

18
1
2
3
4
5
6
7
8
9
15

13
20
19

14

12
11
10

1
2
ra

24V
24V
ra

a
r

ra

ra
a
r
Reset +

a
a
Reset -

r
Alarm relay

Fault relay

Power supply

Fault relay
Power supply

Alarm relay

ASD 515 RAS 51B


ASD 516
Fig. 6 Connection; RAS 51B und RAS 52B
Fig. 4 ASD 51x connection

BX-OI3 T 811 128 en f 3/7


B5/B6-DXI2 (X2)

4/7
B6-BCU (X12)
V4
G4
C4
L4
V3

Ring 2

X1

Miniboomerang
BX-OI3 G3

X2
B5-PSU Vext+
IN3+ C3
B6-PSU

L2
1 L1
IN3- Input 3 L3

GND
GND

SHLD
SHLD
V2

BX-IM4
X2
VExt5 IN2+
GndExt5 IN2-
Input 2 SHLD G2
Data sheet

External power
VExt4 IN1+ C2
supply unit Input 1 SHLD
GndExt4 IN1- L2
L2
VExt3 V1
Ring 1

Power + - GND

Input 4
Input 3
Input 2
Input 1
supply G1

X3
Fault relay Alarm relay GndExt3

1
NC C NO NC C NO _ + VExt2 NC GND C1
L1

1
8 7 6 5 4 3 2 1 GndExt2 COM Relay L1

IN3+
IN2+
IN1+

IN4-
IN3-
IN2-
IN1-
VExt1 NO

IN4+ 1
GndExt1

X1
B5-PSU

180 
180 
B6-PSU
180  180  VExt5
RAS XL (UNILASER XL parameter set)

Exernal power GndExt5


VExt4
supply unit

L1
GndExt4

X1
GND

SHLD
180 
180 
180 
180 
180 
180 
180 
180 
180 
180 
180 
BX-OI3 VExt3

1
Vext+ + -
IN3+ GndExt3

Fig. 7 Connection; RAS XL


CM NO CM NO CM NO CM NO CM NC NO CM NC NO
Input 3 VExt2

MINIBOOMERANG (MINIBOOM parameter set)


IN3-
GndExt2

X2
IN2+
Input 2 VExt1
IN2- SHLD
Pre Pre Al 1 Al 2 Stö Isolate GndExt1

Fig. 8 Connection; MINIBOOMERANG


IN1+ SHLD Al 1 Al 2 Trouble
IN1-
Input 1
L2
GND

X3
External PSU Power Power

RAS XL

1
NC GND Network Display Status out in
_ _ _ _ _ _

1
COM Relay L1 + + 0V 24V _ + + + + +
NO

2 x 2 x 0,8

screened
screened

1 x 4 x 0,8

max. 20 m
External Display

GND
L2
SHLD
max. 1000 m
B5-PSU
B6-PSU

T 811 128 en f
VExt5
External power GndExt5
VExt4
supply unit GndExt4
VExt3
+ - GndExt3
VExt2
RTX GndExt2
+ Power supply 24V VExt1
_

Boomerang or ARDEA
ARDEA J
GndExt1

transmitter TX
Screen NA 180 
JP A Fault relay C 180 

RRX NC
JP B
+ NA 180 
_

TX/RX
Receiver
ARDEA J
Alarm relay C 180 

receiver RX
Screen

BOOMERANG
NC
L1

X1
GND

SHLD

INT8BA BX-OI3
1

Vext+
IN3+
IN3- Input 3
JP A - delay time relay
X2

IN2+
IN2-
Input 2 SHLD
immediately 30 s 60 s 90 s
IN1+ SHLD
IN1-
Input 1
JP B - ialways remove L2
GND
X3
1

NC GND

Fig. 9 Connection; ARDEA and BOOMERANG


1

COM Relay L1
NO
ARDEA and BOOMERANG (ARDEA IP65/Ex parameter set)

GND
L2
SHLD

BX-OI3
Data sheet

ECO 25/50/80 (ARDEA J parameter set) REK 511 (ASD 51x parameter set)

GND GND GND GND


L1 L2 L1 L2
SHLD SHLD SHLD

GndExt5

GndExt4

GndExt3

GndExt2

GndExt1
SHLD
GndExt5

GndExt4

GndExt3

GndExt2

GndExt1

VExt5

VExt4

VExt3

VExt2

VExt1
VExt5

VExt4

VExt3

VExt2

VExt1

B5-PSU
B6-PSU
B5-PSU
B6-PSU

X2 X2

BX-OI3
BX-OI3
1 1

SHLD
SHLD

L1
L2
GND
GND
SHLD
SHLD

L1
L2
GND
GND

Relay
Relay

External power

Input 3
Input 2
Input 1
External power

Input 3
Input 2
Input 1

supply unit
supply unit

+ -
+ -

Vext+

COM
IN3+

IN2+

IN1+
IN3-

IN2-

IN1-

NO
NC
Vext+

COM
IN3+

IN2+

IN1+
IN3-

IN2-

IN1-

NO
NC
1 1
1 1 X1 X3
X1 X3

MEA 720
(max. 5 mA)

RNA
St
RA- 180 
Al
RA+ 180 
180 
SSD MRP

NC C NO
RE- 180 

180 
RE+ 180  515-xS 915

Al
LOOP

+
5
LOOP+ 180 

+ G N D (NC) C (NO)
St-

180 
0V

REL
ECO 0V

St
Al+

Base contact
3

GND 3
+24V

_
2

OUT

IN
+
1

+
Fig. 10 Connection; ECO 25/50/80
REK 511

Fig. 11 Connection; REK 511

d-List, 1 detection zone per sensor cable (LISTEC parameter set)

B5-PSU
B6-PSU
VExt5
External power GndExt5
VExt4
- ST3/3 supply unit GndExt4
PWR

SCU 800 ST3/2 + - VExt3


GndExt3
+ ST3/1 VExt2
BR 2 GndExt2
1 VExt1
GndExt1
LG 2
180  NC 2
L1
SHLD

GND
FAULT

X1

BX-OI3
180 

NO 3 Vext+
1

IN3+
IN3- Input 3
C 4
X2

IN2+
LG 1 IN2-
Input 2 SHLD
A 5 IN1+
Input 1 SHLD
AL 1

IN1-
L2
C 6 GND
X3

4 x 180 NC GND
1

A 7 COM Relay L1
1
AL 2

NO

C 8
SHLD

GND
L2

+ 9
EXR

- 10

Fig. 12 Connection; d-List 1 detection zone

BX-OI3 T 811 128 en f 5/7


Data sheet

d-List, 2 detection zones per sensor cable (LISTEC parameter set)

B5-PSU
B6-PSU
VExt5
External power GndExt5
VExt4
- ST3/3 supply unit GndExt4

PWR
SCU 800 ST3/2 + - VExt3
GndExt3
+ ST3/1 VExt2
BR 2 GndExt2
1 VExt1
GndExt1
LG 2
180  NC 2

L1
SHLD

GND
FAULT

X1
BX-OI3
180 
NO 3 Vext+

1
IN3+
IN3- Input 3
C 4

X2
IN2+
LG 1 IN2-
Input 2 SHLD
A 5 IN1+
Input 1 SHLD
AL 1

IN1-
L2
C 6 GND

X3
NC GND

1
A 7 COM Relay L1
AL 2

1
NO

C 8

SHLD

GND
L2
+ 9
EXR

L1
SHLD

GND
-
X1

10
Vext+
BX-OI3
1

IN3+
Relay print IN3- Input 3
1
X2
IN2+
IN2-
Input 2 SHLD
180 
180 

2 IN1+
Input 1 SHLD
IN1-
4 x 180 L2
3 GND
X3

NC GND
1

LG 1 4 COM Relay L1
1

NO
SHLD

GND
L2

Fig. 13 Connection; d-List 2 detection zones

Article numbers / spare parts


Short designation Art. number CH Art. number
BX-OI3 Output/input module 115.249 774 20-2100001-01-03
GEH MOD IP66 IP66 map case for BX-OI3 403.239 917 FG020234
MM SM M20 M20 step nipple 428.242 578 MM000181
MM ANB M16 M16 mounting screw union -- MM000185
MM GM M16 M16 counter-nut -- MM000186

6/7 T 811 128 en f BX-OI3


Data sheet

Technical data
Function Output/input module
Operating voltage 12 to 30 VDC
Power consumption (module’s power consumption only) 0.55 mA
Signal transmission Serial data transmission, 2-line technology
Protection type 66 with map case IP
Ambient temperature -20 to +60 °C
2
Connection Screw terminals max. 1.5 mm
VdS approval G210133
EU certificate of conformity (EN 54-17/18) 0786-CPD-21011
Dimensions (H x W x D) 67 x 67 x 20 mm

Relay output 1 Pc.


Relay Bistable, one coil
Type of contact Change-over contact
Switching voltage 230 V
Switching current 0.1-2000 mA
Breaking capacity 60 (0.25 A at 230 V) W
Switching frequency max. 3.125 Hz
(a relay can change its state every 160 ms per ring, provided no other command has to be performed)
2
Connection Screw terminals max. 2.5 mm

Monitored inputs 2 Pc.


Connection IN1- and IN1+, IN2- and IN2+, potential-free contacts
Polling current 10 mA
Polling voltage 3-6 V
Termination resistance 180 Ω
Alarm resistance 180 Ω
Line resistance Max. 30 Ω
Polling impulse 100 μs
Polling cycle 66 ms
Input filter 10 μs
Periodic duration >8 s
(switching states which last longer than 330 ms and whose repetition time is greater than 8 s are recorded)
Line length Max. 30 m
2
Connection Screw terminals max. 1.5 mm

Opto-isolator input 1 Pc.


Connection IN3- and IN3+, potential-dependent signals
Voltage range 0 to 30 V
Input resistance 4,900 Ω
Input current Max. 6 mA
Galvanic separation By opto-isolator
Line length Max. 1,000 m
2
Connection Screw terminals max. 1.5 mm

Input voltage monitoring 1 Pc.


Connection IN3- and VEXT
Voltage range 0 to 30 V
Input resistance 10 kΩ
Monitoring current Approx. 1.9 at 24 V mA
Galvanic separation By opto-isolator
Line length Max. 1,000 m
2
Connection Screw terminals max. 1.5 mm

BX-OI3 T 811 128 en f, 24.07.2015 Rd 7/7


First edition: 26.11.2010 Bed/ksa
The product specifications contained in this document are subject to change without notice.
© Copyright by Securiton