Professional Documents
Culture Documents
BEM High Mark Sample 70
BEM High Mark Sample 70
Pages
1 Introduction 1-2
LE
2 Technical Content
2.3.3 Daylight 7
3 Analysis
LE
4 Integration and Analysis under IBs 19-20
References 23-28
MP
Appendices
Control 39
Speed Control 40
ii
Appendix 8A: Detail Information for the Chiller Unit 41
Analyzer 42
LE
Appendix 10: Power Meter 44
Chart 47
Occupancy 50
LE
MP
SA
iv
1 Introduction
From the past few years, more people are interested in the topic of the Intelligent
Buildings (IBs) since it can improve the functionality of the built environment. One of
LE
the paramount things is that the IBs is the application of technology. It improves the
comfort, safety and quality of life. By using this technology, it improves environmental
Addy (2014) mentioned that for designing a new building or doing building
resources and improve systems efficiency. When some automatic technologies are
MP
applied to the building systems, which is called Smart Buildings or Intelligent Buildings
According to the European IBs Group, the definition of IBs is creates an environment
which maximizes the effectiveness of the building occupants while at the same time
and facilities. In July 1983, IBs became a reality. After that, it was developed to have
an automation service, using local area networks, digital private automatic branch
SA
Also, Cempel (2012) mentioned that IBs will be considered for three fundamental
factors: (i) healthy environment, (ii) low energy consumption and (iii) good
management. Now a day, being a building services engineer is not an easy job because
it needs to design, develop and manage the new technologies into the new or existing
systems.
1
Huang (2008) said that the lighting system, building management system (BMS) and
heat, ventilation and air conditioning (HVAC) system will be considered for the
intelligent system operation. It can make good use of it. Both systems will be integrated
LE
and share their information for centralized controlling, monitoring and management. It
can reduce the workload for the facilities management office. If these two systems have
an integration, the energy use for the lift can be more efficient and convenient.
lighting system, it is 19%. If this case can improve, it can reduce a lot of energy.
2
2 Technical Content
Lagace (2011) indicated that intelligent buildings index (IBI) is to assess that how the
LE
level of the IBs is achieved. All existing construction of the building must be to separate.
Dorf (1998, p. 213) mentioned that the range of IBI is between 1 to 100, which is shown
that the level of the IBs. If the building gets a score from 80 to 100, it can get distinction
buildings. The score from 60 to 79.9 can get credit buildings; From 50 to 59.9 of the
score can get fair buildings. If from 1 to 49.9 of the score, it shows that the building
Different items have their weights for each module of the IBs (Appendix 2).
Global warming is a critical issue in the whole world due to urban development,
greenhouse gas emissions and human activities (Bulkeley & Betsill, 2013). It refers to
climate change which means the increase in temperature and relates to human activities
SA
that lead to higher levels of greenhouse gases emission in the atmosphere (Bradley,
2011). According to Coley (2008), global warming occurs due to a build-up of carbon
dioxide and other greenhouse gases in the atmosphere and the use of carbon-based fossil
fuels emanate the majority of pollutants. It creates impacts from sea level rise to
Houghton (2009) stated that carbon dioxide is the main greenhouse gas that is
emission of carbon dioxide means more blanketing is provided and leads to a higher
temperature. Besides, Black and Weisel (2010) mentioned that electricity is mostly
LE
produced from fossil fuels, such as coal, oil and natural gas. Electrical technology is
developing rapidly and humans rely on fossil fuelled power mainly for appliances like
Kayakutlu & Mercier-Laurent (2017) stated that energy efficiency is the golden
redesigning and upgrading the processes of energy use, developing energy management
and control systems, optimizing power generation, heating and cooling system, and
Houghton (2009) suggested that various ways for energy saving: turn off lights when it
is not needed, turn down the thermostat by one or two degrees and apply more
separated heating, air conditioning and ventilation systems. Integrated building design
connected the opportunities for energy saving and the synergies between many aspects
of the overall design. Moreover, it is necessary to minimize the amount of energy used
for lighting to achieve energy efficiency (Hall, 2010). Apart from using energy efficient
lamps or LEDs, luminaries and the whole lighting system can influence the energy
4
2.2.3 Energy Conservation
Energy conservation refers to the quantity of energy use under efficiency ways (Xu &
Cheung, 2014). It relates to the reduction of energy by using few energy services and
LE
adjusting human behaviours. According to Law (2013), energy conservation requires a
limited demand for energy which has to be supplied efficiently. The energy demand
includes cooling, heating, air circulation, refrigerant and water; while the energy
supply includes temperature and flow, efficient plans and systems, timing control and
Gardner & Stern (1996) mentioned that there are two types of human activity that can
MP
be related to energy conservation, which are efficiency activities and curtailment
activities. Efficiency activities refer to one-shot activities and represent the purchase of
energy efficient equipment, such as adoption and insulation of appliances with higher
achieve the effectiveness of energy consumption (Su & Thomson, 2016). In order to
SA
maintain both energy conservation and human comfort, the ideal solution is to utilize
the centralized cooling system. Waters (2003) also stated that both internal and external
lighting systems should be provided by appropriate lamps with sufficient controls for
5
2.3 Lighting System
Bernard (2004, p. 12) indicated that it cannot work in the dark without light. For
buildings, lighting system is very important, but it is a part of the building system. It is
LE
19% of the energy consumption in a modern office building.
To provide a good quality lighting system, Hall (2010) said that it needs to consider
provide a good quality lighting system, it will affect the working environment and the
workers. After years and years, lighting system engineer has been designing a lot of
equipment and new methods to reduce energy for a lighting system to develop low
MP
energy or passive lighting system. Good low energy or passive lighting system is not
just about providing the best quality visual environment, but it can minimize the impact
The following items are the common technologies applied in our daily life for low
Borer (1994) mentioned that it is a digital control lighting protocol, which is developed
by the lighting industry to be an open standard. For open standard, it can be connected
There are some advantages if we install DALI, such as universal voltage input, precise
dimming curve, individual addressable lighting control and monitor systems, as well as
offer maximum flexibility and functionality. Also, the DALI standard is the
6
International Electrotechnical Commission (IEC) 62386. It can be easily installed and
LE
2.3.2 Light-Emitting Diode (LED)
Hamsira (2014, p. 96) said that a light-emitting diode is a two-lead semiconductor light
source. Also, it is popular lighting equipment. It is applied in our day for a while,
especially LED Multifaceted Reflector (MR) 16 and reflector lamps. LED high bay
fixture can reduce around 83% energy consumption compared to the traditional
incandescent lamp. Also LED has a useful life of 30,000 to 50,000 hours or even longer.
It is longer than a typical incandescent lamp, which only has around 1,000 hours only.
MP
It can find that the price per lumen and the price per wattage. LED MR16 lamps and
luminaires show that the price of LED MR16 lamps and luminaires are very much
higher than conventional lamps and luminaires. The price per lumen is higher than the
2.3.3 Daylight
Lau (2011) said that daylight is free and environment-friendly. If we can make good
SA
use of it, it can reduce the electric light. On the other words, it can fulfil the low energy
or passive lighting system. The most building can receive daylight from the sun through
the window in the daytime, but it has some disadvantage when applying daylight.
The biggest issue is whether, if it is raining, it will become useless. It may affect the
lighting system sensors. While applying daylight into the lighting system, the
calibrations for all the sensors after installation are required. (Appendix 6).
7
2.4 Heat, Ventilation and Air Conditioning Control
Lehman (2011) said that HVAC control can combine with another system. Also, the
cooling load temperature difference calculation method had been applied for a long
LE
time. However, engineers will spend a lot of time on calculation and some of the
information may not be suitable for now. It was tedious and not efficiency. Bill (2011)
pointed out that before personal computers were widely available, simple procedures
were even more important to have, as doing calculations by hand is slow and tedious.
Using personal computer and software to calculate cooling and heating load can reduce
human errors, time and cost. Not only that, it can provide much accuracy loading
MP
information. Using software, engineers can consider the outdoor environment while
having a design. Also, BMS can connect to the observatory to have real-time
especially the personal computer and engineering software, it has changed our daily life,
Huang (2008, p. 67) indicated that for the intelligent HVAC system, it should have the
SA
following items: (i) network; (ii) sensor for automatic control the chiller, air handling
units and other HVAC equipment; (iii) pump flow; (iv) indoor and outdoor temperature
and (v) humidity different. It should be connected to the central control monitor system
so that engineers can get the first-hand data for system analysis. For one more step,
engineers can modify the system while maintaining the services, such as below:
8
i. Adjust indoor air quality
LE
On the other side, engineers can manage and recover the energy, which is mean the
energy consumption can be reduced thanks to the intelligent HVAC system. For
example, engineers can use a heat-recovery chiller to reclaim the heat from the
any mechanical and electrical services. Every service will be getting stronger when
meeting BMS. The reason is BMS predominate all of the condition of the services in
the building. It knows what are the best things for each service. This action just like our
human brain, but the difference controls all building services not feet or legs.
Bushby (1998) mentioned that all design services also want to maintain the factor in
the comfort zone and provide a suitable condition for human or some equipment. BMS
SA
smoke detection system, security system and escalator. Therefore, the BMS seems like
a manager who groups up all services and manages easily. Taking action and operations
is the most important point in this system. It also forms group monitoring, group control
and makes optimize the service. BMS can connect to the observatory to have real-time
monitoring of the outdoor environment. It has changed our daily life, help engineers in
designing and real-time monitoring. There is a huge difference between designing and
combines the technology of computer and logic control system and application on
electrical and mechanical equipment in building services. BMS use much of computer
LE
technology and the maintenance team or management office must keep the good
computer condition. When the system failed, it needs to provide much workforce to
Kibert (2014) said that controlled lighting and mechanical systems can save much
energy and minimize building’s energy consumption. Lighting control modes include
MP
on/off control, scheduling, occupancy detection and dimming. More advanced schemes
include daylight harvesting, task tuning and demand response. Daylight harvesting
involves measurement of how much ambient light is present and harnessing ambient
light to reduce the amount of artificial lighting required to keep the amount of light at
a preset level.
Task tuning involves adjusting the light output in accordance with the function or tasks
which will be performed in the lighted area. Demand response is the dimming of
SA
lighting output in response to signals from the utility. Intelligent lighting control
Natural daylight ‘harvesting’ can make people happier, healthier, and more productive.
And with the reduced need for electric light, a great deal of money can be saved on
energy. Lau (2011, p. 53) mentioned that nearly every commercial building is a
potential energy saving project, where the electric lighting systems can be designed to
10
be dimmed with the availability of daylight. Up to 75% of lighting energy consumption
can be saved. In addition, by reducing electric lighting and minimizing solar heat gain,
LE
2.5.2 Chiller Plant Control by BMS
There is sequencing control by BMS for the chiller plant to control the chiller units,
chilled water pumps with Variable Speed Drive (VSD), by-pass system and modulating
valve. Therefore, the system helps to maintain better control for the chiller plant to
avoid any misuse of energy to generate the cooling load. According to the building load
requirement to add or drop the chiller unit to provide a suitable condition to the user
MP
and save the energy at the same time. There is the designated detail control sequence
for equipment to start or stop and the control flow chart to have better control for the
There are some skills to save more energy such as operating the chiller unit with the
part load because it is more efficient than using full load. It means operating two chiller
units by 50% part load are more efficient than operating one chiller unit by 100% full
For the VSD, by-pass system and modulating valve, it can be controlled by BMS to
adjust the percentage of power and water flow rate in order to adjust the condition for
the chiller plant to change the temperature as required and save more energy which is
According to Appendix 10, all the instantaneous data will be collected by the sensors
such as temperature, the status of the equipment, power meters and timer to have correct
11
feedback in order to control the chiller plant. It can also show the status of the chiller
unit, such as the operation percentage of the compressor, the condition and running
hours. There is a point list for the data collection for all the equipment and sensors
LE
(Appendix 11).
Besides, the set point for the chiller unit can be changed according to the ambient
temperature by BMS outdoor temperature sensors, which refers to the higher set point
in the winter and lower set point in the summer to suit the thermal comfort for the users
for easy controlling and monitoring. The data will be interfaced to repeater station via
fax link instantaneously. The setpoint can be changed by remote control from another
12
3 Analysis
3.1 Design of the Low Energy or Passive Lighting System and HVAC System
under IBs
LE
It cannot work without network. The network is like a bridge, which can connect the
gateway, Direct Digital Control (DDC) and Central Control and Monitoring System
(CCMS).
Taylor (2014) indicated that DDC will connect the field equipment, such as sensors,
valves, air handling units and exhaust air fans. Engineers can control all the equipment
MP
by DDC and set up a program for the IBs. The IBs will take over the control and operate
the whole system automatically. If there are any incidents happened, the IBs system can
send a message to engineers and facilities management workers so that it can monitor
Schuetter (2014) said that DALI will be applied in the IBs system. It has a universal
voltage input, precise dimming curve and other functions. The most important thing is
DALI can be connected by lighting hubs and gateways allow connection into BMS,
SA
which means engineers can control the lighting system by using the BMS. DALI can
provide central configuration and feedback for maintenance. It can also provide an
People spend most of the time in the office, home or shopping centre. Indoor Air
Quality (IAQ) is being more important than before. In order to improve air quality, the
13
Hong Kong Government publishes a guideline, which is called IAQ. When engineers
design the new HVAC system, their design should be under the IAQ guideline.
LE
Lehman (2011) mentioned that in the morning, the outdoor temperature is lower than
the indoor temperature. Engineers can turn on the air handling unit and the fresh air
damper is fully open so that the fresh air can get into the indoor environment. It can
reduce the indoor temperature, improve the IAQ and save energy which means it can
reduce the cooling load for some of the rooms in buildings (Appendices 15 & 16).
The air conditioning system capacity is designed for the prepared spare situation. Most
MP
of the operation is the partial load, because of the variables like a solar load, the quantity
of occupancy, temperature, daylighting equipment and hold the variable loadings. The
design deviation may cause serious fluctuation or imbalance because in most operating
conditions, design the capacity is bigger than the real capacity. Without the control
system, it becomes unstable. There will be a hot or cold air zone. The benefits of using
a control system are maintaining thermal comfort and good IAQ, providing safe
operation of the plant and reducing energy use with the labour cost.
SA
Simpson (2003) said that control is defined as the heating, cooling ventilation and air
conditioning to start, stop and adjust. Involves three different steps to control the HVAC
system, such as measurement variables and data collection, processing and other
information data, and lead to control action. The function is composed of sensors,
control device and control equipment control sequence can be found as follows
(Appendix 17).
14
3.3.1 Open Loop Control Valve
Ma (2009) said that the controller can control and operate the actuator and the timer. It
LE
heating element. The timer is set by the operator and in the operation of the circuit. The
timer will open or close the actuator to adjust the temperature to the set point (Appendix
18).
Wang (2008) mentioned that most HVAC control valves are controlled by adjusting the
flow of hot or chilled water, so its size, characteristics and selection of the equipment
element is opened or closed by the actuator through preset timing equipment. The
temperature has a wide range which is not stable and constant because of the changes
at the steady state. In order to have a more accurate control, it is desirable to hold the
3.3.2 Sensors
Spataru (2012) mentioned that the sensor measures the average of the data and provides
an accurate and repeat the way to change the conditions of the controller. The variables
data monitor like temperature, pressure, relative humidity and water flow rate have to
calibration of the expansion and electrical properties of gas and metal (Appendix 21).
15
Humidity sensor - The percentage of all kinds of detecting methods are used to check
and monitor the relative humidity by resistance, capacitance, impedance and frequency
changes. Changes in fabric size and humidity are used as a measuring element, It can
LE
provide the variation of resistance and moisture absorption. The corresponding polymer
(Appendix 22).
Flow sensor - The liquid flow can be measured by the flow sensor by the cross-sectional
area of the pipeline or the fluid in the pipe or tube obtained. The commonly used method
for measuring liquid flow including a differential pressure flow restriction, volume
MP
sensor, flow sensor, turbine flow sensor, magnetic sensor and ultrasonic flow sensor.
The position of the sensor is the key to have good control. The device cannot be put
under the sun or on the material surface. Otherwise, the data is inaccurate. In the piping
system, the sensor has to be arranged and related to the fluid position. In some cases,
the average unit is used to measure the average variables reading such as in a big zone
3.3.3 Controller
Sun (2005, p. 91) said that the controller receives the signal from the sensor, the input
instruction set, the logic of control and generates for the output signal. It can be passed
through to a control device or other logic control to have a function. The type of
controller has electrical, pneumatic, electronic or electronic digital. The signal can be a
other range in the controller. The disadvantage of the output voltage is that the voltage
signal distorts more long distance than the current signal. The output current modulation
16
range is 4 to 20 mA.
The controller usually requires feedback from the sensor. Some of the input circuits
LE
receive a Resistance Temperature Detector (RTD) sensors such as BALCO or platinum
and other elements, including the thermistor sensor input circuit. The controller setpoint
Taylor (2014) indicated that the control valve is used to keep the space temperature by
changing the chilled water flow rate. The valve should be two positions or adjust the
MP
three port configuration. The bidirectional valve has two ports, for the control of flow
rate of the variable flow system. The three-way valve has three ports, and it can be used
in hybrid the bypass pipeline or transfer service. The by-pass (transfer) applications are
often used in the constant flow system in the whole coil is in full flow because part of
system load conditions does not need. By controlling the flow of the terminal unit is
usually through the use of a motorized modulating valve. There are two basic levels:
the three-way valve and mixing valve. The selected type of valve has determined the
position in the system (Appendix 23). It can have a by-pass system between the return
SA
and supply for the water pipework or air pipework. It can save energy and easy to
control the quality of the final supply water to avoid high water pressure and water
It can install the carbon dioxide (CO2) sensor (Appendix 24) for the measuring the index
in the office and using the VSD (Appendix 25) to control the frequency of air handling
unit or other equipment to operate. Also, it can control the operation percentage of the
17
chilled water pump to control the water flow rate to comply with the different situation
for the chiller plant to save more energy. VSD creates the harmonic current which
affects the efficiency. Therefore the harmonic current will be eliminated by the
LE
harmonic filter (Appendix 26).
operation installed in buildings. BMS controls and monitors different mechanical and
electrical equipment such as air ventilation, lighting, electrical power systems, fire
services system and security systems. Generally, BMS consists of both software and
MP
hardware. The software programme is usually be configured in an intelligent automatic
manner which can be specified using some tools like C-bus, Profibus, and BACnet.
Nowadays, vendors can produce BMS for buildings that integrate different internet
Robb (1996) said that BMS is a critical component for management in energy efficiency.
Apart from controlling the building’s environment, the system is also linked to access
control to enter the building. On the other hand, another security system CCTV is also
SA
commonly be used. In some cases, motion detectors can be adapted to a security system
as well.
According to Appendix 27, BMS can be applied air conditioning, electric power,
plumbing and drainage, lift, fire alarm system and security. This application can save
time and money, increase productivity, improve reliability and lead to effective
18
4 Integration and Analysis under IBs
Addy (2014) said that new technology had been widely adopted in many different
LE
configurable. It is important to connect with the observatory to obtain information
including the weather condition in the present and upcoming week. It is important to
implement a green interior design. The sensor can be installed the window lamp and
Nidditch (2001) mentioned that for the office which would be used for a different
purpose, can set out different lighting and air-conditioning mode to suit each purpose.
MP
For example, when there is a meeting, the lighting will fully open and air-conditioners
will automatically be turned on. A sensor can detect people’s body temperature to
maintain a comfort level. For the reception and corridor area, it is better to apply a focal
design with solar energy. Besides, an electronic actuator can be installed in the radiator
and connected to a temperature sensor near the door. This sensor can ensure the lights
and air-conditioners be automatically switched off when the last person leaves the
office.
SA
Cempel (2012) mentioned that energy performance is a broad concept and the
The energy performance index is together with an energy baseline which are keys to
system assists data integration, reduction in the manpower and error (Hamsira, 2014)
19
If a detector detects the fire occurs, the fire service control panel will send the signal to
the BMS, it will shut down and control all the air-conditioning equipment, power
LE
The security management system acts as a security guard. The security manager can
easily control every camera through the central control room. It can manage and view
the video at different zones on some workstation. It can zoom out a specific area on a
separate monitor for detail look. Also, the alert system can increase the security level
by deterring the malicious behaviour, as with visual and sound alarm which can alert
manually adjust other CCTV to check the situation of that particular area. The CCTV
will record the daily activities for future record finding. If a criminal happens, video
and event report can be viewed to find out the security problem.
SA
20
5 Conclusion & Recommendations
To conclude, BMS can control many important items in a building, like air-
conditioning, electric power, lifts and illumination level. It assists to save time and
LE
money, increase productivity, improve reliability and lead to effective monitoring. As
mentioned in chapter 1, more than 65% energy is used for the air conditioning and
IBs is a new technology which has been widely adopted in networks to achieve a self-
organized of setpoint. The system can assist the data integration and reduction in
manpower and error. It can offer various functions for building control and management,
MP
which can reduce the building maintenance cost and increase the building lifetime.
The purpose of using the BMS and applying IBs in daily life is to create a more
management to improve the buildings by achieving the advantages of BMS and IBs.
Since energy saving is very important to slow down the effects from the global warming,
Apart from that, there are some items which can be improved such as the type of cables,
sensors and communication methods. The twisted pair cables should be used for
interfacing in order to avoid the interference. Also, the sensors which are highly
sensitive and more accurate can reduce the error and the reaction time, to ensure the
action can respond immediately to the BMS station. Besides, the BACnet high-level
language for all equipment. Also, the high-efficiency chillers or chilled water pump can
the above technology and improve for the whole building life cycle, including initial
cost, rehabilitation cost and maintenance cost by assumption with 3% net present value
LE
(Appendix 30). Also, it can minimize the emission of greenhouse gases, in order to
enhancement, IBs will become a trend and being linked with the future life.
MP
SA
22
References
Abrahamse, W., Steg, L., Vlek, C. & Rothengatter, T. (2005) A Review of Intervention
LE
Psychology 25:273-91.
IT, security and building controls. security Technology & Design Magazine.
MP
Binet, A. (2006) The development of intelligence system. USA: Applied Energy.
Brunel University.
SA
Massachusetts press.
Bulkeley, H. & Betsill, M. (2013) Cities and Climate Change. USA: Routledge Ltd.
23
Bushby, S. (1998) Communication gateways friend or foe. USA: ASHRAE Journal,
40(4): 50-3
LE
Cempel, W. (2012) Intelligent building reengineering: adjusting life and work
Dorf, R. (1998) Modern Control System, 8th edn, Menlo Park, USA: California:
Addison-Wesley.
Electrical and Mechanical Services Department. (2018) EMSD: Home (1) [Online].
2018].
SA
Gardner, G. T. & Stern, P.C. (1996) Environmental Problems and Human Behavior.
Hall, M. R. (2010) Material for energy efficiency and thermal comfort in buildings.
24
Hamsira, S. (2014) Through ASHRAE JOURNAL: 2014 AHSRAE Technology
LE
Houghton, J. (2009) Global Warming The Complete Briefing 4th Ed. UK: Cambridge
University Press.
Huang, G. (2008) Enhancing the reliability of chiller sequencing control using fused
ASHRAE.
Buildings International 3.
Lehman, L. (2011) How sensory design brings value to buildings and their
25
Martinich, A. (1995) The concept of Intelligence building. USA: Applied Energy
LE
building cooling water systems prior to implementation. USA: Applied Energy,
86(5): 712-21.
Philp, R.B. (2012) Environmental issues for the twenty-first century and their
JOURNAL, ASHRAE.
26
Simpson, R. (2003) Lighting control: technology and applications, Oxford: Focal
Press.
LE
Spataru, C. (2012) Through Intelligent Buildings International 3: Intelligent
systems for monitoring energy use and occupancy. UK: The use of intelligent
Springer Nature.
MP
Sun, J. (2005) Optimal control of building HVAC&R systems using complete
Taylor, S. (2014) How to Design & Control Waterside Economizers. USA: ASHRAE
JOURNAL, ASHRAE.
SA
Wills, J. (2004) Will HVAC control go wireless. USA: ASHRAE Journal, 46(7): 46-
52.
27
Wong, J. (2005) Intelligent building research: a review. UK: Automation in
LE
Xu, Q.H. & Cheung, W. (2014) China Energy Policy in National and International
MP
SA
28
Appendices
LE
MP (Source from Environmental Protection Department, 2016)
SA
29
Appendix 2: IBI Model and Weighting
LE
MP
SA
Luminous Efficacy
LE
LED A19 lamp (warm white) 78
white) 67
white) 93
MP LED high/low-bay fixture
(warm white) 90
High-intensity discharge
High-intensity discharge
Halogen 20
Incandescent 15
31
Appendix 4: Sampling of Lumen Output Data
LE
(Source from HK Engineer, 2017)
MP
SA
32
Appendix 5: Price for a Different Type of Lamp
LE
MP
(Source from HK Engineer, 2017)
SA
33
Appendix 6: Common and Recommended Light Levels Indoor
Illumination
Activity
(lux, lumen/m2)
LE
Public areas with dark surroundings 20 - 50
LE
MP
SA
35
Appendix 7B: Chiller Sequencing Control
LE
MP
SA
36
Appendix 7C: Chiller Start / Stop Sequencing Control
LE
MP
SA
37
Appendix 7D: Chilled Water Pump Request Sequencing Control
LE
MP
SA
38
Appendix 7E: Chilled Water Pump Start / Stop Sequencing Control
LE
MP
SA
39
Appendix 7F: By-pass Valve Control and Chiller Water Pump Speed Control
LE
MP
SA
LE
MP
(Source from Self-created, 2018)
SA
41
Appendix 8B: Detail Information for the Chiller Unit by Power Analyzer
LE
MP
(Source from Self-created, 2018)
SA
42
Appendix 9: Percentage of Set Point to be Controlled by BMS
LE
MP
SA
LE
MP
SA
44
Appendix 11: Point List for BMS
LE
MP
(Source from Self-created, 2018)
SA
45
Appendix 12A: Chiller Supply Temperature Set Point Reset
LE
MP
(Source from Self-created, 2018)
SA
46
Appendix 12B: Chiller Supply Temperature Set Point Reset Flow Chart
LE
MP
SA
47
Appendix 13: Remote Repeater Station
LE
MP
(Source from Self-created, 2018)
SA
48
Appendix 14: IBs Connection Diagram
LE
MP
(Source from Building Automation, 2017)
SA
49
Appendix 15: Thermal Environmental Conditions for Human Occupancy
LE
MP
(Source from ASHRAE 55, 2017)
SA
50
Appendix 16: Ventilation for Acceptable Indoor Air Quality
LE
MP (Source from ASHRAE 62.1, 2017)
SA
51
Appendix 17: Heating System Control Loop Diagram
52
Appendix 18: Temperature vs Time Diagram
LE
(Source from Self-created, 2018)
MP
SA
53
Appendix 19: Improved Temperature vs Time diagram
54
Appendix 20: Sensors
LE
(Source from Self-created, 2018)
MP
SA
55
Appendix 21: Temperature Sensors
LE
MP
SA
56
Appendix 22: Humidity Sensors
LE
MP
(Source from Self-created, 2018)
SA
57
Appendix 23: Three Port Control Valve
58
Appendix 24: CO2 Sensors
LE
MP (Source from Self-created, 2018)
SA
59
Appendix 25: Variable Speed Drive
LE
MP
SA
60
Appendix 26: Active Harmonic Filter
LE
MP
(Source from Self-created, 2018)
SA
61
Appendix 27: Different Type of Service Controlled by BMS
LE
MP
(Source from Self-created, 2018)
SA
62
Appendix 28: Detail of BMS Controlling Elements
LE
MP
(Source from Self-created, 2018)
SA
63
Appendix 29: Table of Energy Saving by Intelligent Technology
LE
power meter
traditional system
MP
Lighting 35% Dimming system and
motion sensor
64
Appendix 30: Financial Tables – Net Present Value
LE
MP
SA
65