TUTORIAL :- FAULT CURRENT DISTRIBUTION IN TRANSFORMERS
Questions
Consider an earth fault at F on the high voltage (H) side of the auto transformer
shown below and calculate the current distribution in the transformer windings and
the neutral currents at the source and transformer earthing-points.
All impedances are referred to the 100kV winding, ie. to V3. 700KV phase to
phase.
Earth Fault on
Phase A
Transformer winding voltages
Vu = 100KV, V, = SOKV, Vy = 5OKV
‘Transformer impedances
X= 120hms, X, = -3ohms, Xr = 28 ohms
The source on the low voltage (L) side of the transformer is solidly earthed and
has the following equivalent sequence impedances, each considered as purely
reactive :-
Xs1 = Xsq = 20ohms, Xgoq = 10 ohms
Ifthe source on the low voltage (L) side of the transformer is unearthed, calculate
the new current distribution,
TuTosPage 2
Xy = 120; 100kV B-N H
Earth Fault on
Phase A
Xq =X = 200
X.= 102
50kV @ -N
SOKV B-D
The sequence networks for the system can be drawn as follows:-
NoPage 3
For an earth fault at F, the total sequence impedances to the fault are :-
2, = 28 ohms
Z_ = 29 ohms
B= 12+ et = 17.6 ohms
Interconnection of the sequence networks:~
3
= =p = OXI 13308
Current in high voltage winding equals the fauit current
Tay = Iz = Tyo = 13308
Twa = Jan + Jno + Ino = 39908
The tertiary winding has only zero sequence current flowing in it
(0.2 1; referred to high voltage side
Tro
0
0.2 x 22 x 1; referred to tertiary voltage
0.2 x 2 x 1330 = 532A
Currents in the low voltage connections are calculated as follows :-
Iu = hi = hh x z referred to low voltage
100
= 100 = 26608
1330 x Gy = 266
4100 100
= 0. = 1330 x 100 =
yy = 08 X Tp x Gy = 0.8 x 1930 x FO = 21284
TuUTOSPage 4
Ta = ha + hha + luo = 2660 + 2660 + 2128 = 7448A
= ay + alia + hho = @+a)hy tho = “litho
u
-2660 + 2128 = -532A.
Tuc = (a + a) uy + Ing = 832A. /
3
Sho = Z x 2128
63844
Current from earth into neutral of source on low voltage side
Current in the fault = 3149 = 39904
Current from earth into neutral of transformer = Slo ~3lyo = 3(1330 - 2128)
= -3 x 798 = -2394A
The rest of the current distribution follows and is given below. Note that a balance
of ampere tums is obtained in each phase between the three sections of winding;
each section of winding having the same number of turns.
Current Distribution
Ss
——
3458 3990 ~
TUTOSPage 5
For the case of an unearthed source on the low voltage side of the transformer,
the positive and negative sequence impedances remain the same as for the
earthed case but the zero sequence impedance network changes to:
No
Tro
> Xqo = 280.
Tro
Kyo = 122
Fo
For an earth fault at F, the total sequence impedances to the fault are -
Z; = 29 ohms, Z, = 29ahms, Z, = 40 ohms.
100 x 10°
= 102
aa 0A
h=kh=h= *
High voltage winding current :~
Iya = 3ly = 30608
Tertiary winding current :-
100
= 100 = 204
Tro = In x Gy = 20408
Currents in low voltage connections -
Ta = lr + Tz + Yo = 40808
= “ly + ho = 20408
u
TUTOSPage 6
Tyg = -2040A
Current from earth into neutral of the transformer = ly = 3060A
Current distribution :-
TUTos