Professional Documents
Culture Documents
Engineers
where
and
VSR m • max(VR _ 3 PH , VR _ SLG ) (2)
VR_3PH is the voltage developed at the differential relay for the maximum external three‐
phase fault
VR_SLG is the voltage developed at the differential relay for the maximum external single‐line‐
to‐ground fault
15800
VR _ SLG (0.6 0.4 • 2) 92 V
240
2. Calculate the secure voltage limit VSR, applying equation (2) and assuming a margin
factor of 2.
VSR 2 • 92V 184 V
where
VCT is the CT secondary voltage rating, e.g., 400V for a C400 CT at a full secondary winding
1. Calculate VD, assuming a 0.5 margin factor.
VD 0.5 • 400V 200V
87V 200 V
I MIN
I PKP m •
CTR (4)
where
900
I PKP 0.5 • 1.8 A
240
The minimum operating current in primary amperes for the bus protection system is estimated
using the equation below:
87
I OP n • I EX I MOV V • CTR
RS
(5)
where
The excitation current (IEX) at the voltage setting is read from the CT excitation curve
(Figure 2). Since there are four CTs in parallel, n = 4.
The MOV current, IMOV, at the voltage setting is obtained from the MOV characteristic (Figure
3). The MOV characteristic is given in peak volts and amperes so the quantities must be
converted to rms values using the √2. However, the voltage level is off the chart and
therefore can be neglected.
200V
I OP 4 • 0.04 A 0.0 • 240 62.4 APRIMARY
2000