Professional Documents
Culture Documents
Syllabus:
Bond between masonry unit and mortar, tests for determining flexural and shear bond strengths, factors affecting
bond strength, effect of bond strength on compressive strength, orthotropic strength properties of masonry in
flexure, shear strength of masonry, test procedures for evaluating flexural and shear strength.
Since masonry consists of a large number of individual units jointed together with mortar so as to form one
mass, it is necessary to lay the units in such a way that, under load, the units act jointly. It is necessary that
quality of materials used (brick and mortar), and construction technique workmanship should be sound.
Nature of Bond:
The resistance of masonry to tensile or shear stresses is dependent on the bond between mortar and
masonry units.
The mechanism of bond between unit and mortar is incompletely understood but is known to be
influenced by a large number of factors.
It will be clear from this that the problem of masonry bond is extremely complex and most investigations
so far have been of a phenomenological nature, applying to specific combination of materials.
However, some more fundamental work has been reported in which the physical and chemical nature of
the brick mortar interface has been studied.
Experiments on interaction between brick material and cement paste have shown that this is critically
affected by the formation of a micro-layer of ettringite (3CaS𝑂4. A𝑙2 𝑂3.3CaO.31𝐻2 𝑜) at the clay-cement
interface, and by the respective mean diameters of the pores of the brick and of the micro-crystals of the
ettringite.
It is necessary for the pore size of the brick material to be greater than 0.05mm for a mechanical bond to
be formed, and also for the cement to be properly hydrated behind the ettringite layer, despite the
withdrawal of some of the water by suction from the brick.
lf the brick is dry, and has a high suction rate, there will be a partially hydrated zone in the cement paste,
in a depth of several millimeters, and possessing poor mechanical strength.
The movement of water between the brick and the mortar, and the resulting effects on the development
of the mechanical bond between these components, was shown to be considerably affected by their
specific surfaces and capillary dimensions.
It is possible on the basis of these observations to obtain some indication of the likely behavior of cement
mortars, which would, however, also be influenced by such other parameters as the compaction of the
mortar, its cement content and water retentivity.
The effects of water movement on bond between various combinations of mortar and unit have been
studied and concluded that a primary cause of poor bond in clay masonry is the presence of an unduly
high proportion of fine material at the mortar/brick interface. In the case of calcium silicate bricks, poor
bond results from the presence of too many fine pores in the bricks.
Studies of both cement and cement-lime pastes were done and conclusion was that the bond was
mechanical in nature, and that bond strength seems to develop from the interlocking of hydration
products growing on the surface and in the pores of the brick material.
The presence of lime appeared to have beneficial effects in reducing micro cracking at the interface and
in producing a more continuous structure of hydration products on the brick surface.
The investigations described above indicate that the brick/mortar bond is mechanical in nature.
The determination of the shear bond strength of masonry has attracted considerable attention in recent years
and the many different tests which have been proposed have been reviewed. The simplest tests have employed
a couplet specimen consisting of a pair of bricks joined together by a single mortar joint. Such couplet specimens
give rise to the problem of trying to ensure that the result at shear force acts in the plane of the joint, necessitating
the use of rather complicated fixtures to bring this about. A triplet specimen of the type shown in figure below,
on the other hand, overcomes this disadvantage and is easy to prepare. It is necessary, however, to ensure that
bending effects are minimized. As shear strength is dependent on the level of normal stress across the joint, a
modification of the triplet test is to apply such a stress to the triplet specimen so that this relationship can be
determined. This takes the form of Mohr-coulomb equation:
𝜏 = 𝜏𝑜 + 𝜇𝑓𝑛
Where,
𝜏𝑜 𝑖𝑠 𝑡ℎ𝑒 𝑠ℎ𝑒𝑎𝑟 𝑏𝑜𝑛𝑑 𝑠𝑡𝑟𝑒𝑛𝑔𝑡ℎ 𝑤𝑖𝑡ℎ 𝑧𝑒𝑟𝑜 𝑝𝑟𝑒 − 𝑐𝑜𝑚𝑝𝑟𝑒𝑠𝑠𝑖𝑜𝑛 𝑎𝑛𝑑 𝜇 𝑖𝑠 𝑎 𝑞𝑢𝑎𝑠𝑖
− 𝑖𝑛𝑡𝑒𝑟𝑛𝑎𝑙 𝑓𝑟𝑖𝑐𝑡𝑖𝑜𝑛 𝑓𝑎𝑐𝑡𝑜𝑟
Evaluation of the relationship requires measurement of the shear strength at various levels of pre-compression
In an alternative procedure, a triplet is first tested without pre-compression and the failed specimen is then
placed on an inclined plane apparatus to determine the coefficient of friction. This method appears to give results
in good agreement with the method requiring tests at various levels of pre-compression and has the advantages
of being simpler to carry out and of not requiring expensive special equipment.
In this table, besides using different mortars, some bond enhancing techniques have also been used. These
techniques are in the nature of modifications like better frogs, cement slurry or epoxy applications. From the
table, it is clear that 1:6 cement mortar has the poorest flexural bond strength of 0.088 MPa. Richer mortar like
1:4, or combination mortars like cement-soil mortars or cement-Iime mortars give better results, even when the
mortar strength is moderate. Use of better frogs, cement slurry coatings or epoxy coating enhance the bond
strengths to values in the range of 0.15 MPa to 0.39 MPa. The studies by Gumaste (2004) showed similar results.
His work also showed that when mortar becomes very weak like cement soil- sand mortar of proportion 1:15:5,
the flexural bond strength is exceedingly low at 0.03 MPa and the mortar strength itself is 0.86 Mpa. This makes
it clear that for wind and earthquake loading it is important to use richer mortars or combination mortars of
adequate strength. Some results on flexural bond strength was also obtained by Bhandari using a modulus of
rupture test. These results are also presented in Table above flexural bond strength values obtained by all the
researchers are similar shear bond strength were also determined. Sarangapani used a brick triplet test with and
without pre-compression while Bhandari used a brick couplet test without pre-compression. When masonry walls
are in compression their shear strength is substantially higher.
The shear strength of masonry is important when considering wall panels subject to lateral forces and structural
forms such as diaphragm and fin walls where there is the possibility of vertical shear failure between the
transverse ribs and flanges during bending. Shear failure is most likely to be due to in-plane horizontal shear
forces, particularly at the level of damp-proof courses. The characteristic shear strength is dependent on the
mortar strength and any pre-compression which exists.
In BS 5628: Part 1: 1992, Clause 25 linear relationships are given for the characteristic shear strength and the pre-
compression as follows:
a) Shear in a horizontal direction in a horizontal plane
Mortar Designations (i) and (ii)
𝑓𝑣 = 0.35 + 0.6 𝑔𝐴
≤ 1.75 𝑁/𝑚𝑚2
𝑀𝑂𝑟𝑡𝑎𝑟 𝐷𝑒𝑠𝑖𝑔𝑛𝑎𝑡𝑖𝑜𝑛𝑠 (𝑖𝑖𝑖)𝑎𝑛𝑑 (𝑖𝑉)
𝑓𝑣 = 0.15 + 0.6 𝑔𝐴
≤ 1.4 𝑁/𝑚𝑚2
Where:
𝑓𝑣 is the characteristic shear strength in the horizontal direction in the horizontal plane (see Figure 2 of the
code),
𝑔𝐴 is the design vertical load per unit area of wall cross-section due to the vertical loads calculated for the
appropriate loading conditions specified in Clause 22.
(b) Shear in bonded masonry in the vertical direction in the vertical plane
For brick:
Mortar Designations (i) and (ii)
𝑓𝑣 = 0.7 N/mm2
Mortar Designations (iii) and (iv)
𝑓𝑣 = 0.5 N/mm2
For dense aggregate solid concrete block with a minimum strength of 7 N/𝑚𝑚2 :
Mortar Designations (i) and (ii)
𝑓𝑣 = 0.7 N/𝑚𝑚2
Mortar Designations (iii) and (iv)
𝑓𝑣 = 0.5 N/𝑚𝑚2
The design shear strength is obtained by applying the partial safety factor ‘𝛾𝑚𝑣 ′ (see section 1.5), given in Clause
27.4 of the code and hence:
𝑓
Design shear strength of masonry = 𝛾 𝑣
𝑚𝑣
Where,
𝛾𝑚𝑣 = 2.5 when mortar not weaker than designation (iv) is used, and = 1.25 when considering the probable effects
of misuse or accidental damage.
In the case of wall panels which are subject to lateral loads and restrained by concrete supports, the shear forces
can be transmitted by metal wall ties. The characteristic shear strength of various types of tie which are engaged
in dovetail slots in structural concrete are given in Table 8 of the code. As with masonry, the design values can be
obtained by applying a partial safety factor ‘𝛾𝑚 ’ as given in Clause 27.5, i.e.
𝛾𝑚 = 3.0 under normal conditions and
= 1.5 when considering the probable effects of misuse or accidental damage.