Professional Documents
Culture Documents
Operation
and Maintenance Manual
TABLE OF CONTENTS
Page
CHAPTER ONE: GENERAL INFORMATION 1-1
CHAPTER ONE:
GENERAL INFORMATION
SHOCK HAZARD:
Connect this device to a proper ground connection in accordance with the National
Electrical Code. DO NOT under any circumstances remove the ground wire or ground
prong from any power plug. DO NOT use an extension cord with this equipment. Keep
the surface under the RO(s) free of water.
DEVICE LABELING:
Do not under any circumstances, remove any Caution, Warning or any other descriptive
labels from the devices until the conditions warranting the label are eliminated.
DO NOT OPERATE IN A FLAMMABLE ATMOSPHERE:
To avoid fire or explosion, do not operate this device in an explosive environment or near
flammable anesthetics.
1.3 Applications
The Millenium™ Reverse Osmosis (RO) System is designed to purify water by forcing
water through a semi-permeable RO membrane. Water purified by reverse osmosis has
had approximately 95% of the dissolved ions and approximately 99% of most other
contaminants removed. The quality of the purified water, referred to as product water or
permeate, depends on the quality of the feed water and normally is equal to or exceeds
AAMI standards. Such water is suitable for hemodialysis applications.
1.4 Contraindications
WARNING:
ZyzaTech Water Systems are not designed, sold, or intended for use in producing
water for injection
Furthermore, ZyzaTech's Water Systems are not intended to be used outside of the device
specifications and limitations, as outlined in this manual and other related materials.
DRAIN:
A drain outlet is required by the RO system. The drain must have a minimum
capacity of 2 gallons per RO per minute of continuous flow for as long as and as
often as the RO is operating.
TEMPERATURE:
The Millenium™ RO is normally connected to a cold water supply. The
performance specifications of the RO are based on 77°F (25°C) feed temperature.
Each degree Fahrenheit the feed water temperature falls, the RO product flow
decreases approximately 1.5%, and each degree Celsius drop, the product flow is
reduced by 3% (See Technote 113 in Appendix A for the “Temperature Correction
Factors” chart). In climates where the winter water temperature drops significantly
below 77°F it may be necessary to temper (heat) the water.
WARNING:
The temperature of the tempered water should be monitored closely with a
thermometer as high temperatures can damage the RO membranes and possibly
harm the patient. Refer to the inlet water requirements (Section 1.10.1) for the
maximum operating temperature for the Millenium™ RO.
CAUTION:
It is necessary to keep the RO from freezing to prevent serious damage to the RO
unit.
NOISE:
The RO unit does not generate significant noise levels. Hard walls may reflect
noise and will make the RO seem louder.
WATER PURITY:
Plumbing materials can significantly contribute to the contamination of the water.
Metallic pipes (with the exception of 316 stainless steel) must be eliminated once
the purification process has begun. Schedule 40 or 80 PVC pipes, polypropylene,
PVDF, and other FDA recommended materials are suitable for most grades of
purified water. Care must also be exercised in the choice of a thread sealant.
Teflon tape is suitable for all threaded connections in this system.
WARNING:
Ordinary pipe dope must be avoided since it may leach objectionable and
potentially dangerous impurities into the water.
Product Port:
The Product Port is a quick-disconnection port for the output of purified product
water. The port has a check valve that closes when there is no hose connected to
the fitting.
Waste Port:
The Waste Port is a quick-disconnection port for the output of concentrate or waste
to the drain. The port has a check valve that closes when there is no hose connected
to the fitting.
Percent Rejection Display:
The Percent Rejection Display is a 5 LED array that indicates how the RO
membranes are performing. The lights correspond to 99%, 95%, 90%, 85%, and
>70% rejection. The 99% light, when illuminated, indicates a need to evaluate the
RO system performance. RO units do not normally perform in excess of 99%;
verify this reading with an independent meter and take corrective action if
indicated. Some RO membranes will achieve this level of performance under
optimum conditions.
Product Water Total Dissolved Solids (TDS):
The Product Water Total Dissolved Solids (TDS) digital display indicates product
water purity in mg/L (ppm). It is temperature compensated to adjust the value of the
display with changing water temperature for better accuracy.
Less Than 0.5 mg/L Check System Lamp:
The Less Than 0.5 mg/L Check System lamp illuminates when the TDS reading is
0.5 mg/L or less. This indicates a need to evaluate the RO system performance.
RO units do not normally have this low product TDS. Verify this reading with an
independent meter and take corrective action if indicated. RO membranes may
achieve this level of performance under optimum conditions (good feed water).
Alarm Set:
The Alarm Set switch allows the operator to set the TDS levels at which the alarm
will sound. The alarm should be set at twice the initial TDS reading. If the set
point is exceeded, an audible alarm will sound.
Alarm Mute:
The Alarm Mute switch will mute the audible alarm for 30 - 45 seconds. A red
indicator lamp is displayed on the switch when the mute switch has been pressed.
Pretreatment Cart holds the Millenium™ RO and feedwater treatment equipment. The
cart has a bracket that provides for the attachment of prefilter cartridge housings. The
cart will hold any combination of two or three of the following tank sizes, .25 c.f., .47
c.f., or .60 c.f..
Carbon Filter Tanks remove chlorine/chloramine from the feed water, preventing
damage to the RO membrane and injury to patients. The filter incorporates a bed of
granular activated carbon. Three sizes of carbon tanks come in semi-automatic control
valve and exchange head styles.
WARNING:
Carbon is not regenerated and must be replaced when exhausted.
WARNING:
A suitable carbon filter should always be present as pretreatment for the RO unit in
order to prevent chlorine/chloramine damage to the thin film RO membrane and
harm to the patient. ZyzaTech strongly recommends the use of two carbon tanks,
used in a series configuration.
Softeners remove calcium, magnesium, and other scale producing contaminants from the
feed water. Their removal prevents the build-up of scale on the membrane surface. A
control valve drives the regeneration of the softener, and will remove the hardness ions
with a brine solution and rinse the ion exchange bed afterwards. The control valve is
normally governed by a semi-automatic time clock. There are three sizes of softener
tanks available.
Dealkalizers are used to lower the pH of alkaline feed water. Water with pH levels
above 8.5 with chloramines present can reduce the performance of the carbon filters and
thin-film membranes. A control valve drives the regeneration rinsing of the dealkalizer.
The control valve is normally governed by a semi-automatic time clock. There are three
sizes of dealkalizer tanks available.
1.10 Specifications:
1.10.1 Input Water Requirements
Minimum Maximum
Input flow Rate 2.0 GPM N/A
Temperature (water) 1.7°C (35°F) 32°C (90°F)
NOTE:
Operating at lower temperatures may make it impossible for the Millenium™ to
produce adequate permeate for the dialysis machine.
pH (operating) 4.0 11.0
TF Membranes
pH w/chloramines present (operating) 4.0 8.5
TF Membranes
pH (cleaning) 2.0 11.0
TF Membranes
Pressure, dynamic 30 PSI 100 PSI
1.10.2 Flow Rates
Product Flow based on the following conditions:
New Membranes
Operating Pressure: 190 PSI
Product Pressure: 1 PSI
Feed Water Temperature: 77°F (25°C)
1.10.4 Dimensions
Vertical Cabinet Horizontal Cabinet
Height 25 ½ inches 8 inches
Depth 15 inches 15 inches
Width 8 inches 25½ inches
Weight – Operating – 55 lbs.
1.10.5 Membrane Performance Characteristics
Salt rejection (TF Membranes): 95% minimum at initial testing at factory.
Test Solution: Inlet water 1000 PPM NaCl
Conductivity: 2000 micro mhos-cm
Operating Pressure: 190 PSI, ±10 PSI
Product Back pressure: 0 PSI
1.10.6 Environmental Requirement
Minimum Maximum
Ambient Temperature 4°C (39°F) 32°C (90°F)
Storage Temperature 2°C (36°F) 32°C (90°F)
Altitude N/A 10,000 feet
CAUTION:
This equipment must not be allowed to freeze. Irreparable harm to various
components, including RO membranes may result.
NOTE:
The user/operator should recognize that moisture can be caused by condensation
and is not necessarily an equipment leak. This equipment will function in the
presence of condensation.
1.11 Disposal
Disposal of this product or parts must be carried out according with local disposal codes.
NOTES:
CHAPTER 2:
INSTALLATION GUIDELINES AND INITIAL SYSTEM START-UP
valve allowing product flow. When the hose is disconnected, the product flow is
stopped.
4. Make sure that the inlet water valve switch and the RO pump power switch are in
the OFF position. Plug the power cord into a 115 VAC (220 VAC) grounded
outlet. Do not use an extension cord or an adapter.
5. Turn the water supply to the RO on.
6. Turn the operate/flush valve to the flush position.
7. Turn the inlet water valve switch on. Water will start to fill the RO. Allow the
RO to rinse to drain for five minutes after water begins to flow from the drain
line. The pump pressure gauge should indicate some pressure.
8. Turn the RO pump power switch on.
NOTE:
The operate/flush valve may need to be rotated part way towards the operate
position if the pump makes excessive noise.
9. Slowly turn the operate/flush valve to the operate position. Pump pressure should
not exceed 200 PSI. If 200 PSI is exceeded, adjust pump pressure on pump head
located inside the cabinet. See instructions in Figure 1 below:
Figure 1
10. Let the RO run for an additional 15 minutes or until the percent rejection and
TDS values have stabilized.
WARNING:
Ensure that TDS and membrane performance (% rejection) are normal for the
regions water quality. Consult your facility physician. An AAMI analysis and
bacteria test of the product water must be obtained and interpreted before using the
RO unit for hemodialysis treatment (refer to the Product Water Analysis procedure
and the Product Water Culture Procedure).
11. Set the product water TDS alarm limit switch as prescribed by the physician. The
switch is normally set to twice the initial TDS reading (or “next higher” setting) at
start-up.
WARNING:
The TDS alarm limit should not be moved from this setting unless instructed by a
physician.
12. After a minimum of 3 hours run time, disinfect and rinse the RO unit with an
approved disinfectant before using for hemodialysis treatment (refer to the
Formaldehyde and ‘RENALIN®’-type disinfection procedures in chapter four).
CAUTION:
New RO units with thin film membranes must be rinsed to drain with normal
pressures for a minimum of three (3) hours before exposure to disinfectants.
WARNING:
After disinfection, the product water must be verified free of residual disinfectant.
13. The RO product may be used in conjunction with hemodialysis treatment
equipment only after obtaining test results which validate compliance with
excepted standards.
• AAMI Product Water Panel
• Microbiological Culture (colony count) results
• Endotoxin (pyrogen) level testing (if applicable)
14. The Millenium™ RO is now ready for use.
In order to ensure that the RO is performing at or above AAMI (Association for the
Advancement of Medical Instrumentation) Standards, it is necessary to perform an
AAMI Water Quality Analysis test. For new units, the RO must be operated (rinsed to
drain) for at least two hours before taking a sample, to ensure that the membranes are free
of preservative or other contaminants which would invalidate the test.
WARNING:
There are many documented clinical risks in using less than AAMI Standard
product water (refer to Technote 103 in Appendix A, "AAMI Hemodialysis Water
Quality Standards").
NOTE:
Follow the procedures recommended by your water quality-testing laboratory if
they vary from the following steps.
Materials Required: Produce water sampling kit, sterile gauze, tape, and container (such
as a small bucket).
1. Ensure that all pre-RO devices are operating correctly and are performance
verified by the appropriate testing.
2. Connect the RO unit to the required utilities (feed water, drain, power).
3. Operate the RO unit with product and waste flows to drain for at least 15 minutes
after the product water quality has stabilized before drawing the water sample.
4. Hold the product line over the container and run product water for 60 seconds.
5. Aseptically remove the lid from the sample bottle and rinse the bottle twice with
RO product water.
6. Fill the bottle completely with RO product water and cap it immediately.
7. Fill out the laboratory requisition form. Ensure the requisition form has, at a
minimum, information to identify the facility or location of the RO, the serial
number or facility equipment number to ensure which RO was tested and name,
phone number and address of whom to contact.
8. Place the bottle and the completed requisition in the pre-addressed mailer and
mail it directly to the laboratory.
NOTE:
Total chlorine must be measured on-site. Tests for Chlorine/Chloramine (total
chlorine) are not typically reported on the AAMI Analysis. Chlorine and
chloramine dissipate from the water sample over time and reported results will be
inaccurate.
NOTES:
CHAPTER 3:
SYSTEM OPERATION
NOTE:
If the Millenium™ RO is to be stored for more than 24 hours (RO not being
operated), the RO should be stored in an approved disinfectant or storage solution
(Not ‘RENALIN®’ or other type oxidizing products). Refer to the disinfection or
storage procedure in this manual.
5. Disconnect from the utilities and store the RO.
NOTES:
CHAPTER FOUR:
ROUTINE MAINTENANCE
2. Add three drops of SAE 20 wt. non-detergent motor oil into the opening.
Threaded Connections:
1. Prior to performing this maintenance on any threaded fitting, release the pressure
on the piping/tubing system (i.e., turn off the pump, open a drain port, etc.)
2. Remove the connecting tubing.
3. Re-tape the pipe threads with 2 or 3 wraps of Teflon tape. (It is not necessary to
remove the old Teflon tape, although it may be advisable to do so if it is in very
bad shape).
4. Re-insert the threaded fitting into the opening and tighten hand tight. Be careful
to avoid cross threading. Tighten further using a wrench only if necessary, and
only about one-half turn.
5. Re-connect piping, pressurize, and inspect for leaks.
6. If the leak is still present, de-pressurize system again and tighten the fitting
another quarter-turn. Check again for leaks. (Over tightening can crack the
female fitting).
7. If the leak continues, it may be necessary to replace the male threaded fitting
and/or the female threaded fitting.
Tubing connections:
1. Prior to performing this maintenance on any tube fitting, release any pressure on
the tubing system (i.e., turn off the pump, open a drain port, etc.).
Foulants such as minerals, silt and organic substances may collect on the RO membrane
surface and cause the RO membrane to foul and diminish in its function. Many of these
foulants are prevented by proper selection of pretreatment equipment, while others are
treatable only with more sophisticated designs. Regardless of the foulant, it is essential
to clean the membrane promptly once cleaning is indicated. The longer a foulant is
allowed to remain in contact with the RO membrane, the more difficult it will be to
remove. In severe cases, repeated cleanings may be required.
NOTE:
Some foulants CANNOT be removed with cleaning and membrane performance
may not be fully restored. Observe the appearance of the cleaning solution before
discarding it. If the solution is heavily soiled, repeat the cleaning procedure with
fresh solution of the same type (high pH or low pH).
Routine cleaning of the RO membranes in conjunction with regular disinfection will keep
bacteria counts at a minimum and the RO membrane performance at its best. Cleaning
removes the silt, organic and mineral deposits that collect on the RO membrane surface
which, if left untreated, encourage bacterial growth and will eventually impair the RO
membranes' ability to perform. Disinfection kills most of the bacteria that may be present
in the system, but it does not remove the deposits on the membrane.
There are a variety of indications for cleaning membranes. The most common is a
reduced product flow rate. Remember that a reduction in inlet water temperature can also
result in a reduced flow rate. Refer to Technote 113 "Temperature Correction Factors" to
determine the reduction in flow that can be attributed to reduced water temperature.
Clean the membranes whenever the temperature compensated flow rate drops by 10%. A
loss in the membrane performance (percent rejection) or increase in TDS of the product
water may also be an indication to clean the membranes. A good preventative
maintenance practice is to clean the membranes on a quarterly basis, and more often if
needed.
CAUTION:
Membranes that have not been cleaned for a long time may actually incur damage
during cleaning as perforations are exposed that were masked by accumulations of
foulant. Regular maintenance cleaning is the best assurance of long membrane
service.
There are two types of cleaners available, a low pH cleaner (Calcium/Iron removal) and a
high pH cleaner (Silt/Organics removal). ZyzaTech provides these cleaners in liquid and
powdered form. The low pH cleaner attacks mineral scale deposits such as calcium,
magnesium and iron build-up, and should be used first. The high pH cleaner will remove
accumulated silt and organic matter from the RO membrane.
CAUTION:
The different cleaners must not be mixed together. Introduce the low pH cleaner
first, thoroughly rinse the system, and then use the high pH cleaner.
WARNING:
The solution is a mild irritant to eyes and skin. It is recommended that protective
gloves and eye protection be worn when handling the cleaner. Neither respiratory
protection nor special ventilation are required.
Materials Required:
Liqui-Clean 403™ – (Low pH liquid) - ZyzaTech Part No. 1228653 (1 Gal)
Liqui-Clean 211™ – (High pH liquid) - ZyzaTech Part No. 1228791 (1 Gal)
OR…
Calcium & Iron Cleaner (Low pH, powdered) - ZyzaTech Part No. 11271 (1 lb.)
Silt & Organics Cleaner (High pH, powdered) - ZyzaTech Part No. 12032 (1 lb.)
• high and low pH cleaner
• 2 Gallons pretreated water
• clean wide mouth container with volume of 2 ½ gallon or more
• pH test strips
• product rinse line (clear hose with male QD fitting on one end, open on the other)
• “DO NOT USE” warning labels (not provided by ZyzaTech)
• cleaning / disinfect log sheets
• most current log sheets for water quality comparison
CAUTION:
If using the powdered cleaner, ensure that it is completely dissolved before
allowing it into the RO. Undissolved granules circulating through the RO pump
may cause irreparable pump damage.
CAUTION:
Water to be used must be chlorine free or damage to the RO membranes may result.
4. Turn the RO pump power and inlet water valve switches off.
WARNING:
Label machine with appropriate warning signs such as "Do Not Use / Contains
Cleaner" to prevent use of the RO until it is properly rinsed.
5. Connect the disinfect hose quick-disconnect fitting to the disinfect port on the
RO. Place the open end in the cleaning solution.
6. Connect the product rinse line to the product port and place the open end in the
cleaning solution.
7. Place the open end of waste line in the cleaning solution.
1. Turn the Operate/Flush valve to the Flush position. The Flush mode will allow the
flow of cleaner only to the rejection side of the RO membrane to flush surface
particulates away. Very little or no product water will be made in flush mode.
2. Push and hold the disinfect switch to operate the RO pump for three minutes.
CAUTION:
Some pump noise (chattering) is normal in the flush position. Excessive pump
noise (chattering) can be damaging to the pump. The RO is in “flush” from the full
open (flush) position to just before the fully closed (operate) position. Adjust it by
partly closing the flush valve to reduce chattering of the pump.
CAUTION:
Check that there is waste flow within 10 seconds. If not, release the button (switch)
and verify that the disinfect-line is connected properly.
CAUTION:
Do not allow air or foam to be drawn into the RO system, as this will damage the
pump.
NOTE:
The cleaners will foam; this is normal. If using a closed container, provide a vent
to the atmosphere to relieve pressure.
3. Let the RO stand dormant with cleaning solution in it for thirty minutes.
4. Remove the waste hose from the cleaning solution and place it in the drain.
5. Using the disinfect switch, turn the RO on and flush approximately 1/2 gallon of
the solution to the drain. This prevents fouling the cleaning solution with the first
output after the dwell time.
6. Place the waste hose back in the cleaning solution container.
7. Using the disinfect switch, turn the RO on and operate it for five minutes.
8. Remove the product and waste hoses from the cleaning solution tank and place
them in the drain.
1. Using the disinfect switch, turn the RO on and run cleaning solution to the drain
until the container is empty. This aids in emptying the container of cleaning
solution.
CAUTION:
DO NOT ALLOW THE PUMP TO RUN DRY. As an alternative, the solution
may be poured in the drain.
2. Rinse and drain the cleaning solution tank and the hoses then let them air dry.
3. Disconnect the disinfect hose from the RO.
4. Ensure that the water supply to the RO unit is on. If it is partially closed, rotate
the operate/flush valve to the full flush position.
5. Place the inlet water valve switch in the on position. Let water flow to the drain
for one minute.
6. Rotate the operate/flush valve to the operate position.
7. Set the RO pump power switch in the ON position. Rinse for 20 minutes with the
Operate/Flush valve in the Operate position until the % rejection and TDS
monitors’ displays normalize (e.g. 'usual' % rejection and 'usual' TDS reading).
Refer to your operating log for 'usual' readings and compare to the pre-cleaning
values.
A. During this rinse period, rotate the Operate/Flush valve to the
Flush position briefly and then back to Operate three times to
build-up and release pump pressure. This aids in flushing the
cleaner from the system.
8. Test the product water for post-cleaning pH and compare it to the pre-cleaning pH
level. The values should be the same or very close to the pre-cleaning pH. If it is
not, continue rinsing in the Operate position until equalization of the value occurs.
9. When all of the parameters ( % Rejection, TDS, pH) have normalized, operate the
RO for an additional 20 minutes in rinse mode.
10. Repeat the cleaning procedure with the other pH cleaner. ZyzaTech recommends
using a low pH cleaner first, followed by a high pH cleaner after rinsing
thoroughly.
11. Turn the RO pump and inlet water valve switches OFF. Disconnect the product
rinse line, and drain and store it.
12. Reconnect the product line to its original connection.
13. Remove the “Do Not Use/Contains Cleaner” warning label.
14. The Millenium™ RO system is now ready for use.
BIOSAN™ is a liquid cleaner/descaler agent intended for use in removing mineral scale
and organic biofilm and is a short-term storage solution for RO water systems.
CAUTION:
BIOSAN™ is not intended for use in Hemodialysis Machines.
WARNING:
The solution is a mild irritant to eyes and skin. It is recommended that gloves
(latex/vinyl) and eye protection be worn when handling BIOSAN™. Neither
respiratory protection nor special ventilation are required.
Materials Required:
• 500 ml. BIOSAN™ cleaner
• 4500 ml. product water
• clean wide mouth container with volume of 2 ½ gallon or more
• pH test strips
• product rinse line (clear hose with male QD fitting on one end, open on the other)
• “DO NOT USE” warning labels (not provided by ZyzaTech)
• cleaning / disinfect log sheets
• most current log sheets for water quality comparison
CAUTION:
Water to be used must be chlorine free or damage to the RO membranes may result.
5. Connect the disinfect line quick-disconnect fitting to the disinfect port on the RO.
Place the other (open) end of the line in the cleaning solution.
6. Connect the product rinse line to the product QD port and place the other end of
the line in the cleaning solution.
7. Place the end of the waste line in the cleaning solution.
1. Rotate the Operate/Flush valve to the Operate position. This will allow the
BIOSAN™ to pass from the rejection side of the membrane through to the
product side of the membrane for total system exposure to the cleaning solution
once the RO is turned on in disinfect mode (step #2).
2. Push and hold the disinfect switch for three minutes. This will operate the RO
pump.
CAUTION:
Check that there is waste flow within 10 seconds. If not, release the disinfect
switch and verify that the disinfect line is connected properly.
CAUTION:
Do not allow air or foam to be drawn up into the RO unit, as this will damage the
pump.
NOTE:
Biosan™ will foam; this is normal. If using a closed container, provide a vent to
the atmosphere to relieve pressure.
3. Turn the Operate/Flush valve to the Flush position and hold the disinfect switch
for an additional 3 minutes. The Flush mode will allow the flow of cleaner only to
the reject side of the RO membrane to flush particles away. Very little or no
product water will be made.
CAUTION:
Some pump noise (chattering) is normal in the flush position. Excessive pump
noise (chattering) can be damaging to the pump. The RO is in “flush” from the full
open (flush) position to just before the fully closed (operate) position. Adjust by
partly closing the flush valve to reduce the chattering of the pump.
4. Allow the BIOSAN™ to dwell in the RO for a minimum of one hour.
NOTE:
Thin-film RO membranes: The Millenium™ RO unit may be stored in BIOSAN™
for up to one month.
5. Remove the waste and product lines from the cleaning solution and place them in
the drain.
4.3.2.3 BIOSAN™ Post-Cleaning Rinse Procedure
1. Using the disinfect switch, turn the RO on and run the cleaning solution to the
drain until the container is empty.
CAUTION:
DO NOT ALLOW THE PUMP TO RUN DRY. As an alternative, the solution
may be poured in the drain.
2. Disconnect the disinfect line from the RO.
3. Ensure that the water supply to the RO system is on. If it is partially closed, rotate
the operate/flush valve to the full flush position.
4. Push the inlet water valve switch to the on position. Let water flow to the drain
for one minute.
5. Rotate the Operate/Flush valve to the operate position.
6. Set the RO pump power switch in the ON position. Rinse for 20 minutes with the
Operate/Flush valve in the Operate position until the % rejection and TDS
monitor displays normalize (e.g. 'usual' % rejection and 'usual' TDS reading).
Refer to your operating log for 'usual' readings and compare to the pre-cleaning
values.
A. During this rinse period, rotate the Operate/Flush valve to the Flush position
briefly and then back to Operate three times to build-up and release pump
pressure. This aids in flushing the cleaner solution from the system.
7. Test the product water for post cleaning pH and compare it to the pre-cleaning pH
level. The values should be the same or very close to the pre-cleaning pH. If it is
not, continue rinsing in the Operate position until equalization of the value occurs.
8. When all of the parameters ( % Rejection, TDS, pH) have normalized, operate the
RO for an additional 20 minutes in rinse mode.
9. Turn the RO pump and inlet water valve switches OFF. Disconnect the product
rinse line, and drain and store it.
10. Reconnect the product line to its original connections.
11. Remove the 'Do Not Use/Contains BIOSAN™' warning label.
12. The Millenium™ RO System is now ready for use.
CAUTION:
New replacement thin film membranes must be rinsed to drain with normal
pressures for a minimum of six (6) hours before first exposure to formaldehyde, or
irreversible damage may occur. No mandatory pre-rinse of the membranes is
required for future disinfections.
WARNING:
Always wear rubber gloves, apron and facemask. Use proper ventilation during
disinfection and rinse-out. A face respirator with an organic cartridge to remove
formaldehyde fumes may be worn. DO NOT BREATHE FUMES OR ALLOW
FORMALDEHYDE TO COME IN CONTACT WITH SKIN OR EYES. Refer to
MSDS supplied by manufacturer of the formaldehyde or formalin product.
Materials Required:
• 800 ml. Formaldehyde, 37%
• 2 gallons pre treated or RO water
• clean wide mouth container with volume of 2 ½ gallon or more
• formaldehyde test kit
• product rinse line (clear hose with male QD fitting on one end, open on other)
• “DO NOT USE” warning labels or signs (not provided by ZyzaTech)
• cleaning / disinfect log sheets
• most current log sheets for water quality comparison
• proper protective body wear
WARNING:
Label the machine with appropriate warning signs such as "Do Not Use / Contains
Formaldehyde" to prevent use of the RO until it is properly rinsed.
4.4.1.1 Formaldehyde Pre-Disinfection Procedure
1. Push and hold the disinfect switch until the disinfectant has been drawn into the
machine.
CAUTION:
Check that there is waste flow within 10 seconds. If not, release the switch and
verify that the disinfect line is submerged in the solution and the QD is connected
correctly. Do not allow air to be drawn into the RO system, as this will damage the
pump.
2. Test for the presence of formaldehyde in the product line (the RO must be
running).
3. Release the disinfect switch.
4. Momentarily turn the inlet water valve switch on (approximately 5 seconds), then
turn it off again. This allows the water to rinse the disinfectant from the disinfect
line and quick-disconnect connection.
WARNING:
Failure to perform this step creates a potentially dangerous situation
(FORMALDEHYDE SPILLAGE) and prolongs the rinsing out of the disinfectant.
5. Disconnect the disinfect line from the quick-disconnect port.
6. Ensure that the FORMALDEHYDE warning label is clearly visible.
7. Remove the product rinse line and waste line from disinfect tank and RO.
8. Rinse the disinfect line and the disinfect tank with water to remove the
formaldehyde, and store it appropriately.
9. Allow the disinfectant solution in the RO to remain in contact for a minimum of
two hours, or, preferably, overnight.
NOTE:
The RO may be stored for up to one year at this time. If this is the case, a 0.5%
solution may be used instead of 4%.
4.4.1.3 Formaldehyde Post-Disinfection Rinse Procedure
1. Connect the product rinse line, input water and waste lines to the RO.
2. Ensure that the product rinse and waste lines are in the drain.
3. Turn the operate/flush valve to the flush position.
4. Turn on the inlet water valve and allow the system to rinse for 2 minutes.
5. Turn on the RO power switch and run the RO for 10 minutes.
CAUTION:
Some pump noise (chattering) is normal in the flush position. Excessive pump
noise (chattering) can be damaging to the pump. The RO is in “flush” from the full
open (flush) position to just before the fully closed (operate) position. Adjust it by
partly closing the flush valve to reduce the chattering of the pump.
6. Rotate the operate/flush valve to the operate position.
7. Turn RO pump power switch off for 1 minute. Turn the RO pump switch on for
2-3 minutes. This will aid in the rinsing out any trapped formaldehyde in the
Millenium™ RO.
8. Continue to rinse for an additional 5 minutes.
9. Check the product line for residual disinfectant with an appropriate test kit. If the
test is positive, continue to rinse until a negative test is obtained.
10. Disconnect the product rinse line and store it.
11. Remove the warning signs from the RO only after a negative test confirms the
absence of formaldehyde.
12. The Millenium™ RO System is now ready for use.
NOTE:
Success of the disinfection procedure may be ascertained by taking a water culture
after completion. See the Product Water Culture Procedure in this chapter.
Renalin®, Minncare™, Peracidin™ and others are trade names for compounds based
on Peracetic Acid and Hydrogen Peroxide compounds, and are common in dialysis
facilities. The products referred to in this procedure typically have 20% hydrogen
peroxide and 4% peroxacetic acid before dilution. Other products are available with
these same chemicals in different ratios; these are not acceptable for use in the
Millenium™ RO. Actril™ and other compounds with different combinations of
these chemicals must not be used on polyamide (thin-film) membranes. The name,
“Renalin®” will be used in this manual to refer to acceptable products.
CAUTION:
New replacement thin film membranes must be rinsed to drain with normal
pressures for a minimum of three (3) hours before first exposure to Renalin. No
mandatory pre-rinse of the membranes is required for future disinfections.
WARNING:
Follow all Material Safety Data Sheet (MSDS) precautions and OSHA Standards.
CAUTION:
‘RENALIN®’ is corrosive to most metals other than stainless steel. The
Millenium™ uses only compatible materials. ‘RENALIN®’ type products contain
oxidizing agents and are potentially damaging to thin film (polyamide) membranes.
It is imperative that all the precautions and instructions are followed correctly.
Failure to comply with these instructions, which incorporate instructions from the
membrane manufacturer, will jeopardize the system performance and the warranty.
Materials Required:
• correct amount of disinfectant, per manufacturers’ instructions
• 2 gallons RO water
• clean wide mouth container with volume of 2 ½ gallon or more
• product rinse line (clear hose with male QD fitting on one end, open on the other)
• “DO NOT USE” warning labels or signs (not provided by ZyzaTech)
• cleaning / disinfect log sheets
• most current log sheets for water quality comparison
CAUTION:
When ‘RENALIN®’ is to be used as a disinfectant, several preparatory steps are
required by ZyzaTech as well as the membrane manufacturer. Failure to comply
with these instructions, which incorporate instructions from the membrane
manufacturer, will jeopardize the system performance and warranty.
a. The system must be free of all incompatible materials.
b. Clean the membranes with an acid such as 0.1% HCl or 0.4% phosphoric
acids. Calcium and Iron Cleaner may be used as an alternate. It is essential
that all iron and other transition metals be removed from the membrane
surface.
CAUTION:
The RO system must be disconnected from the tempered water source (if present).
The solution temperature must be monitored closely. At temperatures above 25°
the ‘RENALIN®’ solution becomes very aggressive towards the RO membranes
and will damage them in a short period of time. The disinfection procedure will
raise the temperature of the solution. The operator must be prepared to add ice to
the solution or discontinue the procedure when the water temperature approaches
77ºF /25°C.
1. Read and understand the ‘RENALIN®’ disinfection procedure. Pay particular
attention to steps a and b in CAUTION statement above before initiating the
procedure.
2. Ensure the cleaning/disinfectant container is clean. Add two gallons (7.6 liters) of
RO permeate (product water) to the container.
3. Add 1.3 ounces (40 milliliters) of disinfectant concentrate to the container and
mix to prepare a 1:100 (1%) dilution.
WARNING:
Label the machine with appropriate warning signs such as "Do Not Use/ Contains
Disinfectant” to prevent use of the RO until properly rinsed.
4. Disconnect the dialysis machine from the RO product port and install the product
rinse line. Place the open end in the disinfectant solution container and ensure the
product valve is open.
5. Attach the quick-disconnect end of the disinfect line to the disinfect port of the
RO. Put the open end of the disinfect line in the disinfectant.
6. Disconnect the waste line from the drain connection and place the open end in the
disinfectant solution container.
CAUTION:
The operate/flush valve may need to be rotated partially closed, (towards the
operate position) if the pump makes excessive noise.
6. Rotate the operate/flush valve to the operate position.
7. Turn the RO pump power switch off for 1 minute. Turn the RO pump switch on
for 2-3 minutes. This will aid in the rinsing out of any potentially trapped
disinfectant in the Millenium™ RO.
8. Continue to rinse for an additional 5 minutes.
9. Check the product line for residual disinfectant with an appropriate test kit. If the
test is positive, continue to rinse until a negative result is achieved.
10. Disconnect the product rinse line and store it.
11. Remove the 'Do Not Use/Contains Disinfectant’ warning label. The
Millenium™ RO System is now ready for use.
FREQUENCY: Once a month or more often, depending upon culture results, and unit
protocol. We recommend before and after disinfection.
Materials Required:
• Bucket or similar container
• Sterile specimen container, such as Millipore (red) or 3M Commercial Standard
Plate count sampler, or a container your lab may require
RATIONALE: This procedure will help ensure that the microbial count of the product
(RO) water falls within the AAMI Hemodialysis Water Standard. The AAMI standard
maximum allowable concentration for bacteria in product water is 200 colony-forming
units. A bacterial count above the maximum level may be harmful to the hemodialysis
patient.
OTHER: Consult your lab to find out what type of sterile container to use and how
much product (RO) water is required to perform the test. Make certain that your
laboratory is informed of the correct procedure for performing a product water culture. A
"spread plate method" NOT a "calibrated loop" technique should be used, with tryptic
soy agar or equivalent agar, NOT blood or chocolate agar. If tested incorrectly, the
results may be inaccurate. The sample should be assayed within 30 minutes of obtaining
it, or refrigerated (5°C) immediately and assayed within a 24 hour period. Obtain the
samples wearing long sleeves and a mask to prevent contamination of samples, use a
“mid-stream” “clean catch” type procedure.
This procedure assumes the RO is connected to power and water, and is in operating
condition.
1. Connect the product rinse line to the product port. Place the other end in a drain.
2. Connect the waste line to the waste port. Place the other end in a drain.
3. Turn on the RO unit. Allow the RO unit to run for 10-15 minutes.
4. Remove the product rinse line from the drain.
5. Using aseptic technique, hold the product line over a container, and allow
approximately 100 cc of product (RO) water to flow to the drain (or allow product
water to flow for 30 seconds).
6. Maintaining aseptic technique, hold the product line over the sterile container
with the product water flowing.
7. Fill the container with RO product water. (If using commercial samplers, follow
the manufacturer's instructions.)
8. Aseptically cap the specimen container immediately.
9. Label the specimen appropriately with:
• Test to be performed - "culture / colony count"
• Sample source - product water/RO, machine serial number and room location
• Time and date sample obtained
• Person who obtained specimen
• Any other pertinent information or procedures your facility or lab requires
10. The samples should be assayed within 30 minutes of obtaining or refrigerated at
5° C immediately and assayed within a 24-hour period.
This storage procedure has been established to store Millenium™ RO machines. It is not
recommended that a unit be dormant longer than 24 hours without disinfectant. ROs that
have been left unused for more than 24 hours risk the possibility of colonizing bacteria
and exceeding acceptable limits. ROs to be stored should first be disinfected with one of
the procedures in this chapter. The RO should be stored in a location where it cannot
freeze or become overly hot.
CAUTION:
‘RENALIN®’ products (Renalin®, Minncare™, Peracidin™. etc.) are not
acceptable disinfectants for storage of systems. Exposure of more than 12 hours to
RENALIN® will result in irreversible damage to the membranes.
4.6.1 Formaldehyde Storage Procedure
WARNING:
Always wear rubber gloves, an apron and a facemask. If the room has ventilation,
use it. If not, wear a face respirator with an organic cartridge to remove
formaldehyde fumes. DO NOT BREATHE FUMES OR ALLOW
FORMALDEHYDE TO COME IN CONTACT WITH SKIN OR EYES Refer to
the MSDS supplied by the manufacturer of the formaldehyde/formalin product.
1. If formaldehyde is chosen to disinfect the RO, follow the instructions for
formaldehyde disinfection.
2. Do not rinse out after the disinfectant has been circulated in the machine.
3. Disconnect the disinfect line, the feed water line, the waste line, power and the
product line.
4. Coil the hoses and power cord, and cover the RO with a large plastic bag to
protect the RO from dust.
NOTE:
All ROs can be safely stored in 0.5 to 4 % formaldehyde for up to one year.
WARNING:
After storage, the RO unit must be completely rinsed of formaldehyde, and a
bacterial culture performed and interpreted before use. Perform AAMI analysis if it
has been one year or more since last done.
WARNING:
It is recommended that gloves (latex/vinyl and eye protection be worn when
handling BIOSAN™.
1. Disinfect and rinse the RO with an acceptable disinfectant.
2. Follow the BIOSAN™ procedure in this chapter.
3. Do not rinse the RO out after BIOSAN™ has been circulated in the RO.
4. Disconnect the disinfect line, waste line, feed water line, power and product line.
5. Coil the hoses and power cord, and cover the RO with a large plastic bag to
protect the RO from dust.
CAUTION:
The Millenium™ RO may be stored for up to one month in BIOSAN™. After one
month, if longer storage is needed, the Millenium™ RO may be rinsed and re-
packed with BIOSAN™.
WARNING:
After storage, the RO unit must be completely rinsed of BIOSAN™, and a bacterial
culture performed and interpreted before use. Perform AAMI analysis if it has been
one year or more since last done.
NOTES:
CHAPTER FIVE:
TROUBLESHOOTING
Table of Contents
SECTION TITLE PAGE
c. See 5.1.6
d. See 5.1.7
3. Thermal overload trips
a. Verify line voltage and motor amperage draw.
b. Disassemble pump/motor at clamp and inspect coupler for wear.
c. Pump pressure too high (see 5.2.2).
5.3 Motor Runs Hot
1. Pump/motor binding.
a. Remove pump head and try restarting motor.
b. Inspect pump and motor coupling for wear.
c. Clean any debris or liquid from connection area.
d. See 5.5
e. Replace pump.
2. Fan obstructed or inoperative.
a. Verify no debris is obstructing fan vent.
b. Verify fan operation.
3. Excessive current draw.
a. Verify that flow rates and pressures are within RO specifications.
b. Check motor/pump coupling for alignment.
c. Confirm amperage draw with meter.
d. Motor insulation shorted, replace motor.
4. Voltage too low.
a. Check voltage against serial label and motor label, correct condition.
5.4 Water Produced While RO is Off
Low water temperatures, fouled membrane elements, or inadequate pump pressure can
cause low product flow. A partial blockage of the feed stream (dirty pre-filter) can also
result in low product water flow by causing the pump to draw a strong vacuum.
Similarly, an obstruction (defective check valve) in the product flow path may cause
reduced flow.
1. Pump pressure too low.
a. See 5.5
2. Low feed water temperature.
a. Verify product production with Tech Note 121 Temperature Correction.
b. Install or adjust temperature blending valve.
3. Membrane fouled or scaled.
a. Review trend analysis logs for flow.
b. Clean membrane with both high and low pH cleaners.
c. If flow is not recoverable, replace membrane.
4. Center tube of ROMA collapsed from operating at high temperatures.
a. Correct temperature problem.
b. Replace membrane.
5. Check softener pretreatment for brackish (high salt) water.
a. Check inlet water for high conductivity.
b. Check water softener for proper function.
c. Regenerate softener.
d. Check supply water for hardness and conductivity.
5.9 Product Flow Too High
1. Rejection Satisfactory
A. Pump pressure too high.
a. Adjust pressure regulator setting to specifications.
B. Feedwater temperature too high.
a. Adjust temperature blending valve.
b. Correct plumbing error that allows the cold water to be heated.
C. Quick disconnect tubing connections not in correct port.
a. Verify QD connections.
2. Rejection Unsatisfactory
A. Waste flow too low.
a. Check waste flow rate.
b. Check for blockage or kink in waste line.
c. Quick disconnect not connected completely.
B. High pH and chlorines in feed water.
a. Check feedwater for higher than 8.5 and the presence of chloramines.
1. General information: Any leak from any part of the system should be corrected as
soon as possible. Left unattended, leaks can cause secondary damage
necessitating expensive repairs.
2. Refer to the Maintenance Procedures for Leak Repair.
NOTES:
CHAPTER SIX:
DRAWINGS
FRONT VIEW
PUMP/MOTOR
SIDE VIEW
INPUT MANIFOLD
FLOW
AIR
ROMA ASSEMBLY
WASTE MANIFOLD
FAN
MAIN MANIFOLD
REAR VIEW
Millenium RO
(Component Layout)
Millenium RO
(Disinfect View)
Millenium RO
(Flow Schematic)
6-6
110VOLTS
Millenium RO
INLET WATER RO PUMP PUMP POWER
VALVE SWITCH POWER SWITCH MOTOR SUPPLY
6-7
220VOLTS
Millenium RO
INLET WATER RO PUMP PUMP POWER
VALVE SWITCH POWER SWITCH MOTOR SUPPLY
14693c - 29 Mar- 02
PC BOARD DISPLAY PC BOARD
6-8
Millenium RO
SONALERT
POWER
SUPPLY
(% REJECTION)
12312
21080
20204
20205
20203
30005
12310
ELECTRICAL CONTROL PANEL
12315
30010
20012
110VOLTS
30010
20120
12311
1 2 3 4 5 6 7 8 9 10
Millenium RO
(Electrical Layout, 60Hz)
MOTOR CORD
J
110VOLTS
POWER CORD O
SOLENOID WIRES
AND PROBE WIRE CORD
1 2 3 4 5 6 7 8 9 10
K L MN
ELECTRICAL CONTROL BOX
B) FAN WIRE.
E) SOLENOID WIRE.
L M KN
F) POWER CORD WHITE.
ELECTRICAL CONTROL PANEL
G) MOTOR CORD WHITE (P/N 14712).
H) FAN WIRE.
I) SOLENOID WIRE.
Millenium RO
(Wire Connections, 60Hz)
12312
21080
20204
20205
20203
30005
12310
ELECTRICAL CONTROL PANEL
12315−1
30010
20120
30010
220VOLTS
20290
30010
20290
12311
1 2 3 4 5 6 7 8 9 10
Millenium RO
(Electrical Layout, 50Hz)
MOTOR CORD
J
220VOLTS
POWER CORD O
SOLENOID WIRES
AND PROBE WIRE CORD
1 2 3 4 5 6 7 8 9 10
K L MN
ELECTRICAL CONTROL BOX
B) FAN WIRE.
E) SOLENOID WIRE.
L M KN
F) JUMPER WIRE
ELECTRICAL CONTROL PANEL
G) MOTOR CORD WHITE (P/N 14712).
H) FAN WIRE.
I) SOLENOID WIRE.
Millenium RO
(Wire Connections, 50Hz)
40569
40090
40574 41152
40739* 40070
40569
40241
14770
Millenium RO
(Input Manifold 50/60Hz)
14765
40568
12131
40564 40569 40563
40566
40564
42047
1228224
40218 40602
40568
12131 20178
Millenium RO
(Main Manifold)
14738
40976
40976
40976
40218
40976
40976
40570
40218
Millenium RO
(Waste Manifold)
40569
40570
14774
OS1228070
OR
40179A
(INSIDE)
12102
(HOUSING)
40742
40570 40569
Millenium RO
(ROMA Assembly)
50112
14493
41566 41566
42014
TO HOLE
IN RO
CABINET
Millenium RO
(Flush Valve Assembly)
TOOLS REQUIRED:
1. FLAT BLADE SCREWDRIVER.
2. 3/4" WRENCH OR EQUIVALENT.
3. TOWEL.
PROCEDURE:
1. TURN OFF POWER AND WATER TO UNIT.
2. OPEN FRONT COVER AND EXPOSE PUMPHEAD.
3. REMOVE ACORN NUT. NOTE: DO NOT LOSE WASHER.
4. USE SCREWDRIVER AND TURN SCREW AS SHOWN. CLOCKWISE TO INCREASE PRESSURE, COUNTER
CLOCKWISE TO DECREASE PRESSURE. EACH 90° ROTATION WILL CHANGE PRESSURE ABOUT 25 PSI.
5. REPLACE WASHER (IF IT CAME OFF) AND ACORN NUT.
6. TURN ON WATER AND POWER AND THEN CHECK PRESSURE READING. REPEAT AS NECESSARY.
DECREASE
INCREASE
WASHER
Millenium RO
(Pump Pressure Adjustment Procedure)
NOTES:
CHAPTER SEVEN:
SPARE PARTS LIST
Millenium RO System
SPARE PARTS LIST
NOTE: Part Numbers are subject to change and should be verified when ordering
spare parts.
CLEANERS
1228653 Cleaner, Liqui-Clean403™,1gal., Low pH, liquid
1228791 Cleaner, Liqui-Clean211™,1gal., High pH, liquid
10230 Membrane Cleaner, BIOSAN™, 1 gal., liquid
11271 Membrane Cleaner, Calcium/Iron, 1 lb., Low pH, powdered
12032 Membrane Cleaner, Silt/Organic, 1 lb., High pH, powdered
TESTS
50033 Hardness Test Kit
14604 Silt Density Index (SDI) Test Kit
11656 Total Chlorine Test Kit
70001 Water Test Kit, AAMI Standards
OPTIONAL
12128 Pre-filter Housing Assembly
40694 O-ring, Pre-filter (9 7/8”)
40695 Filter, 1 Micron, 9 7/8"
40696 Filter, 5 Micron, 9 7/8"
40698 Filter, Carbon, 9 7/8"
NOTES
APPENDIX A:
TECHNOTES / LOG SHEETS
APPENDIX A
Millenium™ RO System by ZyzaTech Water Systems
APPENDIX A
Millenium™ RO System by ZyzaTech Water Systems
TechNotes
In this section, you will find a variety of information related to your ZyzaTech equipment
and to dialysis water use in general.
APPENDIX A
Millenium™ RO System by ZyzaTech Water Systems
APPENDIX A
Technote 102
RECOVERY
In the operation of a reverse osmosis system, It can be easily deduced that a 10% recovery will
most of the dissolved ionic material and cause an increase of approximately 10% in the
organics are blocked by the membrane and TDS of the waste water relative to the
passed to the drain with the waste water. The feed. We can also see that a 50% recovery will
product water, with the concentration of cause the TDS in the waste to be approximately
impurities reduced, is then suitable for use in double that of the feed, as we will have almost
whatever application for which the system is all of the dissolved material in half of the water
designed. going to the drain.
To clarify the relationship between system An additional factor called 'polarization' results in
performance and the water flow parameters, a further concentration of the dissolved material
some of the nomenclature commonly used at or near the membrane surface within the
should be defined. The terms 'product', module assembly. It is primarily a function of
'effluent', and 'permeate' are all applied to the the transverse flow of water through the
purified water. The supply water is usually membrane and increases with higher recoverys.
called 'feed' , 'supply' or 'input'. 'Waste', 'brine', This factor is reduced by brine recirculation
and 'concentrate' are all used to refer to the within the system but may give an increase in
water passing over the membrane on the feed TDS within the module of from 25% to 100%.
or input side carrying the dissolved and
suspended material to the drain. Some of the impurities requiring removal by
reverse osmosis have a saturation characteristic
The waste flow to the drain must be sufficient to which can result in precipitation and scaling on
carry away the removed material and prevent the membrane surface, blocking the flow of
either mechanical plugging or precipitation on product water and eventually disabling the
the feed side of the membrane. For system. The most frequently encountered
convenience in working with these systems, the materials of this type are iron and calcium. For
ratio of the product water to the input water is this reason, almost all reverse osmosis
most commonly used as an operating manufacturers set a limit of 0.05 ppm for iron in
parameter. This ratio is called 'yield', 'recovery', the feed water.
or 'conversion' and is usually expressed in a
percentage. This can be stated mathematically Calcium scaling as calcium carbonate is a
a s: complex function of temperature, hardness, TDS
alkalinity and pH, and can be analyzed by
RECOVERY (%) = 100 PRODUCT FLOW means of the Langlier equations. This
FEED FLOW determination takes into account the
concentration factors discussed above and
As the sum of the product and waste is equal to provides a reasonable margin of safety as long
the feed. The equation can also be written as: as the waste flow is adequate.
APPENDIX A
APPENDIX A
This page intentionally left blank.
APPENDIX A
Technote 103
AAMI HEMODIALYSIS WATER
QUALITY STANDARDS
Aluminum 0 .0 1
Arsenic 0 .0 0 5
Barium 0 .1
Cadmium 0 .0 0 1
Calcium 2 (0.1 mEq/L)
Chloramines 0 .1
F re e c h l o ri n e 0 .5
Chromium 0 .0 1 4
Copper 0 .1
F l u o ri d e 0 .2
Lead 0 .0 0 5
Magnesium 4 (0.3 mEq/L)
Mercury 0 .0 0 0 2
Nitrate (as N) 2
Potassium 8 (0.2 mEq/L)
Selenium 0 .0 9 7
Silver 0 .0 0 5
Sodium 70 (3 mEq/L)
Sulfate 100
Zi n c 0 .1
APPENDIX A
This page intentionally left blank.
APPENDIX A
Technote 104
NOMINAL REJECTION
CHARACTERISTICS OF REVERSE
OSMOSIS MEMBRANES
APPENDIX A
This page intentionally left blank.
APPENDIX A
Technote 111
WATER QUALITY
CONVERSION TABLE
Note: Parts per million (PPM), is commonly considered equivalent to milligrams per liters (mg/L).
APPENDIX A
This page intentionally left blank.
APPENDIX A
TechNote 113
TEMPERATURE CORRECTION
ZyzaTech Water Systems
FACTORS FOR THIN-FILM
MEMBRANES
Feedwater Temperature
°C °F TCF 1/TCF
2 3 5 .6 .4 4 2 2 .2 6
3 3 7 .4 .4 5 9 2 .1 8
4 3 9 .2 .4 7 6 2 .1 0
5 4 1 .0 .4 9 5 2 .0 2
6 4 2 .8 .5 1 5 1 .9 4
7 4 4 .6 .5 3 4 1 .8 7
8 4 6 .4 .5 5 4 1 .8 0
9 4 8 .2 .5 7 5 1 .7 4
10 5 0 .0 .5 9 6 1 .6 8
11 5 1 .8 .6 1 7 1 .6 2
12 5 3 .6 .6 4 0 1 .5 6
13 5 5 .4 .6 6 4 1 .5 0
14 5 7 .2 .6 8 8 1 .4 5
15 5 9 .0 .7 1 3 1 .4 0
16 6 0 .8 .7 3 8 1 .3 5
17 6 2 .6 .7 6 4 1 .3 0
18 6 4 .4 .7 9 0 1 .2 7
19 6 6 .2 .8 1 8 1 .2 2
20 6 8 .0 .8 4 6 1 .1 8
21 6 9 .8 .8 7 5 1 .1 4
22 7 1 .6 .9 0 5 1 .1 0
23 7 3 .4 .9 3 6 1 .0 7
24 7 5 .2 .9 6 7 1 .0 3
25 7 7 .0 1 .0 0 1 .0 0
Product flow rate at 25°C x TCF= Product flow rate at other temperatures.
Product flow rate at other temperatures x (1/TCF)= Product flow rate at 25°C.
APPENDIX A
This page intentionally left blank.
APPENDIX A
TechNote 115
ZyzaTech Water Systems
USEFUL FORMULAS
1 g a llo n = 3 . 7 8 5 l i t e rs
1 grain per gallon = 17.1 mg/liter
1 m g / l i te r = 1 ppm (parts per million)
1 micromho/cm = .4 mg/liter as NaCl
.65 mg/liter as ion
.5 mg/liter as CaCO3
1
Conductivity (micromho/cm) = Resistivity (megohm-cm)
1
Resistivity (megohm-cm) = Conductivity (micromho/cm)
RO SIZING EQUATION:
Total the flow needed for hemodialysis equipment, re-use equipment and other water
uses. For a recirculating loop add 1 GPM to the total flow requirements to meet the
minimum standard of 1.5 ft/sec through the loop.
APPENDIX A
This page intentionally left blank.
APPENDIX A
Technote 119
MOST COMMONLY ASKED
QUESTIONS
Cleaning is the removal of foulants from the feed side of the RO membrane. There are two
types of cleaners, high pH (7.5-11) and low pH (2.0-4). High pH cleaners remove silt and
organics that clog or foul the membrane, and low pH cleaners strip the mineral scale build-up
and biofilm (from bacteria) that prevent the membrane from functioning adequately. Cleaners
aid in the control of microbes by stripping the membrane free of deposits that bacteria can
adhere to, but they themselves do not kill bacteria like a disinfectant does.
Disinfection decreases and controls microbial levels in the complete system both feed and
product side of the membrane and the fluid pathway.
Routine cleaning of the membranes (approximately every quarter) along with regular
disinfection (approximately once a month) together in large central systems will expand the life
of the RO membrane and control bacteria counts in the system. It is recommended to disinfect
portable systems once a week, or if the system has not been in use for more than forty eight
hours. The membranes in portable units should be cleaned every quarter or more often as
recommended.
Temperature of the feed water: Incoming water temperature greatly affects the amount of
product water made. RO membranes are rated on an ideal source water temperature of 77°F
(25°C). For every 1 degree F lower the feed water temperature is, the product flow is reduced
by 1.5%. Temperature blending valves are commonly used on large water systems to maintain
the incoming water around 77°F, and for small portable RO machines, larger, or more
membranes are used to compensate for seasonal water temperature fluctuations.
APPENDIX A
Cleanliness of the RO membrane: Foulants such as silt, organics and mineral scale deposits
can cover portions of the feed water side of the membrane. These foulants can clog the
membrane and obstruct the water from passing through, thus decreasing production of RO
permeate.
Low city/source feed water pressure: It is common for municipal water systems to have various
difficulties. These problems sometimes affect the incoming flow pressure to the RO machine.
Either reduced feed water pressure or no feed water pressure can be the result. A booster
pump, sometimes coupled with a bladder tank, can reduce the risk of deficient water supply. A
storage tank can help in a no water situation for large RO systems. In small, portable RO units,
it is best to not use the system until the feed water reaches at least 25 PSI. Decreased flow
through the system will cause undo wear and tear on the pump.
The length of time between carbon exchange or rebedding is dependent upon the amount of
chlorine/chloramines present in the source water. How often the carbon is changed is best
determined by testing for chlorine/chloramine presence before each patient shift. Based on the
test results, a pattern can be identified and a routine established to change the tanks before
they become exhausted. However, when break through occurs, the carbon is exhausted and
n e e d s t o b e re p l a c e d .
In addition to chlorine/chloramines, carbon will also remove organics from the incoming water,
and is therefore a perfect medium for bacteria to proliferate. It can also become fouled by dirt
and suspended particles, thus reducing the efficacy of the carbon. It is a common practice to
backwash carbon to clear it of this matter and prevent channeling of the carbon bed so that the
water is exposed to more surfaces, which renders the carbon more efficient. However, this
does not renew the carbon; when it is exhausted it must be replaced.
Since bacteria growth is a problem in the carbon tanks, it is recommended that they be changed
every three to six months (even if they are not exhausted), or more often before they break
t h ro u g h .
An RO membrane, which has adequate pretreatment, which is cleaned and disinfected routinely
and is maintained well, will last on an average from 3-5 years in a large system, and 1-2 years
in a portable system. Along with maintenance, the quality of the source water also determines
the life span of the membrane. A higher solute concentrated source water will have more wear
on the membrane than a lower ionic supply water.
Thin film (TF) membranes are more durable than cellulose acetate (CA) membranes. TF
membranes have a longer life on a wider variety of feed water quality and have a greater range
for pH tolerance than CA membranes do.
APPENDIX A
5. Is it a good idea to store purified water?
There are advantages in a storage tank system. For instance, a smaller RO unit can be used
instead of upgrading the size of the RO system when a dialysis center is expanded. If water
supply interruption is a problem, there is product water available to furnish the dialysis systems.
There are some cases in which it is not feasible to install a direct feed system. For example, a
dialysis facility that is limited on space, or a center which has the RO system reside on a lower
floor than the patient treatment area.
Storage tank water distribution systems have disadvantages that are not inherent to direct RO
feed systems (no storage tank). Storage systems require extra maintenance and monitoring
plus the added expense of the storage tank and a distribution pump. Additional time is required
in cleaning, sanitizing, monitoring and maintaining the system. T h e ri s k o f b a c t e ri a l
contamination is greater because of the potential stagnation and because the surface area of
the product water is exposed to atmosphere.
6. Why does ZyzaTech typically design their water systems with the softener before
the carbon tank?
Either the softener or the carbon tank can be placed first in the pretreatment flow path (the FDA
Manual and the film picture the carbon tank primary). ZyzaTech designs the system with the
softener before the carbon in dialysis applications, because of the reduced risk of bacteria
exposure. Carbon tanks are primarily used for the removal of chlorine/chloramines and will
therefore eventually experience microbial growth, because chlorine/chloramines are what
prevents microbial growth from occurring. If the carbon tank is first in line, the softener will be
exposed to de-chlorinated water which will allow for greater microbial growth in the softener,
thus allowing both the carbon tank and softener to become contaminated at the same time.
However, if the softener is first, it is exposed to chlorinated water and the bacteria will be
minimized. Bacteria and endotoxins are rejected by the RO membrane at a rate of 99%+, but
the more the membrane is exposed to bacteria, the higher the chance for the microbes to
adhere and possibly "grow through" the membrane.
The down side designing the system with the carbon first is that the softener resin beads are
harmed by chlorine, thus the life of the softener may be shortened a few years, depending upon
the level of chlorine the softener resin is exposed to. Large system softeners generally last 10
to 15 years, therefore the damage is insignificant when compared to the microbial contamination
problem.
APPENDIX A
This page intentionally left blank.
Technote 120
GLOSSARY OF TERMS
APPENDIX A
Adsorption: Adsorption is the binding of a molecule to a surface (solid or liquid) by non-specific physical
forces. For example, the removal of free chlorine and chloramines by activated carbon is through
the mechanism of adsorption.
Algae: A group of single-celled plants which includes both sea water and fresh water varieties.
Alkalinity: A measurement of the quantity of chemicals present in water which can neutralize acids.
These include carbon dioxide, bicarbonate, carbonate and hydroxides. See also titratable
alkalinity.
Aluminum sulfate: An aluminum salt commonly used as a flocculant by municipal water treatment
facilities.
Bacteria: Bacteria are single cell microorganisms capable of replicating on their own. They can be
divided into two broad categories, aerobic (requiring oxygen) and anaerobic (not requiring
oxygen). Bacteria can live in a very broad range of habitats. Some, for example pseudomonads,
can thrive in environments containing a very low level of nutrients. These bacteria are frequently
slime producers and are a major problem in water treatment systems. Other bacteria, which
adhere to surfaces, secrete a gelatinous material which serves to protect the bacteria from
chemical disinfectants. This combination of bacteria and their protective coating is sometimes
referred to as biofilm. The concentration of bacteria in water is commonly given in terms of
colony forming units (cfu) per ml. A colony forming unit is a viable bacterium able to replicate to
form a whole colony when incubated in a given environment.
Cellulose Acetate: A synthetic polymer derived from naturally occurring cellulose and widely used in the
fabrication of membranes. The polymers used for water purification membranes may be
diacetate, triacetate or blends of these materials.
Chloramines: Chemicals used to disinfect municipal water. They are formed by reacting ammonia and
free chlorine and may occur naturally when free chlorine combines with ammonia arising from the
breakdown of vegetation. Chloramines are strong oxidants which are highly toxic in hemodialysis
applications.
Coagulant: A chemical which causes dispersed colloidal particles to become destabilized thereby aiding
in their removal during municipal water treatment. Aluminum and iron salts are commonly used
APPENDIX A
for this purpose.
Coagulation: A practice common in municipal water treatment in which a chemical (coagulant), most
commonly alum, is added to water in order to destabilize colloidal particles by neutralization of
their electrical charges. Coagulation is used, together with flocculation, as a process for colloid
removal.
Colloid: Undissolved, submicron-sized suspended particles which are well dispersed in a solution and
will not readily settle out on standing.
Compaction: The undesirable physical compression of a reverse osmosis or ultra filtration membrane
which results in reduced flux rates. The phenomenon is accelerated at higher temperatures and
pr es s ur es .
Conductivity: The ability of an aqueous solution to carry electric current depends on the presence of
ions in the solution. Conductivity is a quantitative measure which describes this ability. Solutions
of inorganic ions are relatively good conductors (and exhibit high conductivity), whereas solutions
of organic molecules are rather poor conductors (and exhibit low conductivity). Highly purified
water is also a poor conductor. Conductivity is expressed in units of Siemen/cm (also known as
mhos/cm). Conductivity measurements are frequently encountered in monitoring the
performance of reverse osmosis equipment. Conductivity is temperature dependent and should
be measured with a temperature-compensated meter. The usual reference temperature is 25°C.
Conductivity measurements are sometimes used to estimate total dissolved solids in water.
While convenient, this practice is imprecise. (See also resistivity.)
Deionization: Removal of ions from water by exchange with other ions associated with fixed charges on
a resin.
Dialysis Dementia: A severe, often fatal encephalopathy which has been attributed to accumulation in
the brain of aluminum from dialysate prepared with inadequately purified water and/or aluminum
containing phosphate binders.
APPENDIX A
Empty Bed Contact Time: The empty bed contact time (EBCT) is used as a measure of how much
contact occurs between particles, such as activated carbon, and water as the water flows through
a bed of the particles. As the EBCT increases, the time available for the particles to adsorb
solutes from the water also increases, as does the amount of solute removed from the water
during its transit through the bed. EBCT is calculated from:
EBCT = Vm/Q
where Vm is the volume of particles in the bed and Q is the volumetric flow rate. A consistent set
of units must be used when calculating EBCT with this equation. For example, if Vm is given in
ft3, then Q must be expressed in ft3/min for the EBCT to have units of minutes. Values of Q can
be converted from other units, such as GPM, to ft3/min using the conversion factors.
Endotoxin: Bacterial lipopolysaccharide, a substance released from the cell walls of gram-negative
bacteria when the organism is broken down.
Feed Water: Water entering a purification system or an individual piece of purification equipment, such
as an ultrafilter or reverse osmosis system.
Flocculation: A practice common in municipal water treatment in which destabilized colloidal particles
are formed into larger particles (flocs), usually by stirring. The floc is removed from the water by
settling or filtration. The process may also incorporate the addition of such compounds as
synthetic polyelectrolytes which increases the size of the flocs, thereby making them more easily
removed by settling or filtration. Removal of colloids by flocculation is done in combination with
coagulation.
Flow Velocity: The flow of fluid at any point in a water treatment system may be expressed
quantitatively in two ways, either in terms of the volume of fluid passing the point in a given time
(volumetric flow rate) or in terms of the velocity with which fluid passed the point (flow velocity).
The flow velocity (V) depends on the geometry of the conduit through which the fluid flows and is
related to the volumetric flow (Q) by:
V = Q/A
where A is the cross-sectional area of the conduit. As an example, the table below shows the
volumetric flow rate as a function of flow velocity in PVC schedule 80 pipes of different diameters.
(The values in the table are based on actual, rather than nominal, pipe diameters.) Note that for
such calculations, it is essential that consistent units be employed. Thus, the term Q would be
expressed as ft3/sec and A as ft2 to yield V as ft/sec.
APPENDIX A
APPENDIX A
Fluidization: A flowing liquid impinging on a bed of particles imparts some of its momentum to each
particle. The imparted momentum is in the direction of the fluid flow. The particles are held to
the floor of their container by gravity and to each other by adhesive forces. If the fluid flow is
upward through the bed of particles, and if the transfer of momentum from the fluid to the
particles is sufficient to overcome both the gravitational and the adhesive forces, the particles
become suspended, or fluidized, in the fluid stream.
Fluoride: A salt of hydrofluoric acid which may occur naturally in water supplies or be added by
municipal processes for the prevention of dental cavities. Fluoride is considered toxic in the
hemodialysis setting and has been implicated with renal bone disease.
Flux Rate: The rate per unit of area at which water passes through a semi-permeable membrane, such
as those used for ultra filtration or reverse osmosis.
Fouling: The deposition of insoluble materials, such as bacteria, colloids, oxides and water-borne
debris, onto the surface of a reverse osmosis or ultra filtration membrane. Fouling is associated
with decreased flux rates and may also reduce the rejection rates of reverse osmosis
membranes.
Fulvic Acids: Acidic substances which are found in humic (organic) soils and which may become
suspended in water.
Fungus: A parasitic plant which produces no chlorophyll and is dependent on other life forms for its
existence.
Grains of Hardness: Although the theoretical hardness of water is the sum of the concentrations of all
metallic ions, other than the alkali metals, it is commonly expressed as the equivalent
concentration of calcium carbonate in grains. Ionic concentrations can be expressed in terms of
their combining potential (Eq/L), the number of moles present (mol/L), or their masses in any of
several conventions. In the English system masses are expressed in terms of pounds
(avoirdupois) which contain 7000 grains each. Although considered outdated in most of the
world, the US water purification industry continues to express hardness in units of grains/gal
expressed as calcium carbonate. Grains/gal expressed as calcium carbonate can be converted
into metric units (mg/L) by multiplying the former by 17.1. Grains/gal expressed as calcium
carbonate can also be converted into mEq/L of a univalent ion, such as sodium (Na+) by
multiplying by 0.342. Care must be taken in using these conversion factors to size equipment
based on ion exchange principles since the ionic content of the water will depend on the type of
ions present as well as their total mass.
Hardness: Hardness was originally defined as a measure of the ability of water to precipitate soaps
made from fatty carboxylic acids. These "soaps" precipitated in the presence of calcium and/or
magnesium ions. Today, hardness is used to describe the total concentration of calcium and
magnesium, expressed as mg/L of calcium carbonate. It is generally calculated from
measurement of calcium and magnesium ion concentrations, using:
Heinz Body: A small, round inclusion within a red blood cell resulting from the release of hemoglobin
following injury to the cell by toxic or oxidative substances, such as chloramines.
Hemolysis: The destruction of red blood cells and the subsequent release of hemoglobin into the
plasma.
Hemolytic Anemia: An anemia resulting from the destruction of red blood cells.
APPENDIX A
APPENDIX A
Homogeneous membranes: See membranes.
Hydrolysis: A chemical process resulting from reactions with water; frequently used in reference to the
breakdown of polymers.
Hydrophobic: Pertaining to a substance which does not readily absorb water ("water-hating").
Ion: An atom or molecule having either a positive or negative electrical charge. Positively charged ions
are referred to as cations and ions having a negative charge are termed anions.
Ion Exchange: Ion exchange is based on the principle of electroneutrality, that is, charged species are
stable only when they exist as balanced pairs of positive and negative charges. Ion exchange
resins, the materials used to carry out the process of ion exchange, are particles which contain
fixed charges on their surface. To maintain electroneutrality, each of these charges has an ion of
equal and opposite charge held to it; these ions are called counter ions. The counter ions are
mobile and can leave the fixed charge if some other counter ion is available to replace it. The
replacement ion must be of the same charge as the initial counter ion in order to maintain
electroneutrality. The initial counter ion is established by washing the resin with a concentrated
solution of the desired counter ion. For example, the softener resins are cation exchangers
containing carboxylic acids on their surfaces. If these resins are washed with strong NaCl
solutions, the predominant cation in solution is Na+ and it will become the counter ion. In use, the
perfusing water will provide competing counter ions, such as Ca2+. Because of the preference of
carboxylic acids for Ca2+ over Na+ in dilute solutions, the water will be depleted of Ca2+ in
exchange for the Na+ initially present.
Langelier Saturation Index: The precipitation of calcium and magnesium carbonates in water
purification systems is a serious cause of system failure. The insolubility of these compounds are
a complex function of the pH of the water, the dissolved carbon dioxide content, the carbonate
content, the presence of other salts, and the temperature. The Langelier Saturation Index is a
method of predicting whether or not carbonate deposits will form under given conditions.
Calculation of the Langelier Saturation Index is complex and will not normally be done by
hemodialysis personnel. Reverse osmosis vendors may use the index in determining the
maximum recovery and rejection rates that can be obtained from a reverse osmosis system
before carbonate deposits will seriously reduce water quality and recovery. It should be noted
that the utility of such determinations is limited to those situations in which a softener is not used
as part of the pre-treatment scheme for reverse osmosis.
Lignin: A polysaccharide found in the cell walls of plants; a breakdown product of decaying vegetation
which may be present in surface water supplies.
Limulus amebocyte lysate (LAL): An extract from horseshoe crabs which forms a gel or clot in the
presence of bacterial endotoxin and is widely used for quantitative measurements of these
substances.
APPENDIX A
Membranes: Membranes are thin films made with structures designed to provide selective transport of
solutes. In general, the selectivity of a membrane is based on its ability to pass or exclude
species according to their size. Membrane structures may become homogeneous or
asymmetric. Homogeneous membranes have structures which are uniform in cross-section, at
lease to a magnification of 100 x . Most homogeneous membranes have been developed for
micro-filtration and hemodialysis.
Membranes reduce not only the flow of undesirable solutes, but also the flow of solvent. In order
to minimize the reduction in solvent flow, asymmetric membranes have been developed. These
membranes are made with asymmetric cross-sections, that is, they consist of two parallel layers.
The resistance to flow of the skin layer, which gives the membrane its filtration selectivity, is
minimized by reducing its thickness. The resistance to flow of the thicker support layer, which
provides structural strength, is minimized because of its open pore structure. These different
layers may be made from the same material, as in asymmetric cellulose acetate membranes, or
from different materials, as in thin-film composite membranes.
Membranes used in water treatment equipment are fabricated in two forms, as flat sheets or as
hollow fibers.
Microcytic Hypochromic Anemia: An anemia characterized by small red blood cells containing a
reduced amount of hemoglobin.
Microporous: In the context of water purification, membranes having an average pore size which is
between 0.1 and 1.0 microns in diameter.
Nitrate: An anion comprised of one nitrogen atom and three oxygen atoms. Nitrates are considered
toxic in hemodialysis water and are also harmful to infants when consumed orally.
Osmotic Pressure: When a solution, such as salt water, is separated from pure water by a membrane
which is impermeable to the salt, a flow of water will occur from the pure water to the salt
solution. The driving force for this flow is called the osmotic pressure and its magnitude depends
on the number of salt particles in the solution. Note that the osmotic pressure depends on the
number of particles and not on the total mass of particles. For example, 1 g/L of a small solute,
such as sodium chloride, will exert a greater osmotic pressure than 1 g/L of a large solute, such
as a protein. For water to flow from the salt solution to the pure water, the solution must be
exposed to a hydrostatic pressure greater than its osmotic pressure. This is the principle of
reverse osmosis.
Osteodystrophy: Abnormal bone development which, in renal patients, may be attributed to parathyroid
gland dysfunction and is characterized by high serum phosphorus and alkaline phosphate and
low serum calcium levels.
Osteomalacia: A softening of bone due to an accumulation of osteoid and reduced mineralization which
may cause fractures with minimal stress.
Osteoporosis: Demineralization of bone which may cause fractures with minimal stress.
Oxidants (oxidizing agents): Chemicals which provide oxygen and accept an electron in an oxidation-
reduction reaction. Free chlorine and chloramines are oxidants which are widely used for
disinfection.
APPENDIX A
Ozone: An extremely active oxidizing agent which consists of three oxygen atoms. It is formed by the
action of a high voltage electrical field on oxygen or air.
pH: Water (H2O) can dissociate into two ions: hydrogen (H+) and hydroxyl (OH). These ions can also
be added to water in combination with other oppositely charged ions. Thus, a solution of
hydrochloric acid added to water provides both H+ and the chloride anion, Cl-. The concentration
of H+ in the water is a measure of water's acidity and the concentration of OH-, a measure of its
alkalinity.
To simplify quantitation of H+ differences, where numbers with a wide range of exponents are
encountered, scientists devised a logarithmic scale called pH. The pH values range from 1 to 14.
A pH value of 7 is considered neutral. Lower values of pH indicate acidic conditions and higher
pH values indicate alkaline conditions. Because pH is a logarithmic scale, an increased of 1 pH
unit corresponds to a ten-fold change in acidity.
Phenols: Weak aromatic acids which are indicative of industrial pollution of water supplies. When
combined with chlorine, they produce an objectionable taste and odor. However, while indicative
of pollution, phenols themselves are not known to be hazardous to hemodialysis patients.
Polyamide: A synthetic polymer of the nylon family used in the fabrication of reverse osmosis and ultra
filtration membranes.
Polysulfone: A synthetic polymer used in the fabrication of reverse osmosis and ultra filtration
membranes which are characterized by extreme thermal stability and chemical resistance.
Polyvinyl Chloride (PVC): A thermoplastic material produced by the polymerization of vinyl chloride.
Used extensively in the U.S. for piping, food packaging, and injection molded plastic parts. PVC
is the most common pipe material used in the U.S. for dialysis applications.
Potassium Permanganate: An oxidizing agent commonly used for the regeneration of manganese
greensand iron filters and occasionally used as a disinfectant.
Pressure Drop: Expenditure of a certain amount of energy is required for a fluid to flow through any
channel, such as a pipe, particle bed, or membrane. The pressure at any point is a measure of
the energy content of the fluid at that point. Since some of this energy is expended in flowing to a
second point downstream, the pressure at the downstream point is less than at the original point.
The amount of energy expended, and hence the decrease in pressure (or pressure drop), is
dependent on the flow rate and viscosity of the fluid, and the size and shape of the channel.
Pressure drops are usually expressed in terms of lb/in2 or PSI, or in the SI system, kPa
(kilopascals) or Kg/cm2. Pressure drop is sometimes referred to colloquially as "delta P".
Product Water: The purified water stream from purification equipment, such as reverse osmosis units
and ultra filters.
Pyrogenic Reactions: A physical response to the presence of endotoxin in the blood stream which is
characterized by fever and occasionally, chills or shaking rigors.
Pyrolysis: A breakdown process which occurs when organic matter is subjected to elevated
APPENDIX A
temperatures.
Recovery (percent recovery): A measurement applied to reverse osmosis and ultra filtration equipment
which characterizes the ratio of product water to feed water flow rates. The measurement is
descriptive of reverse osmosis or ultra filtration equipment as a system and not of individual
membrane elements. Expressed as a percentage, recovery is defined as:
Rejection (percent rejection): A measure of the ability of a reverse osmosis membrane to remove
salts. Expressed as a percentage, rejection is defined as:
ROMA: Reverse osmosis membrane assembly includes vessel housing, end caps, internal inter
connecting parts, o-rings and the RO membrane.
Salt Passage Rate: A measurement of the passage of salts through a reverse osmosis membrane. Salt
passage is related to rejection by:
Scaling: In reference to reverse osmosis equipment, scaling is the precipitation of sparingly soluble
salts, such as calcium carbonate, onto the surface of a membrane. Scaling is associated with
decreased flux and reduced reverse osmosis rejection rates.
Sedimentation: The process by which solids are separated from water by gravity and deposited on the
bottom of a container or` basin.
Silt Density Index: The silt density Index (SDI) is a measure of the ability of water to foul a membrane or
plug a filter. SDI is measured using an apparatus which typically consists of an inlet pressure
regulator and pressure gauge followed by a filter holder containing a 0.45 micron microporous
membrane filter. Commercial test kits, complete with instructions on how to calculate the index,
are available.
Sterilization: A physical or chemical process that reduces the number of organisms to a safe
predetermined level.
APPENDIX A
Superficial Velocity: The velocity of a fluid flowing through a tank containing a bed of particles is
described in terms of the superficial velocity. The superficial velocity is defined as the velocity
which would be achieved by the fluid if it flowed at the same volumetric flow rate through the tank
when it was empty of particles. Mathematically, the superficial velocity (Vs) is given by:
Vs = Q/A
where Q is the volumetric flow rate and A is the cross-sectional area of the empty tank. For
example, if an ion exchange tank has a cross-sectional area of 640 cm2 and water is pumped
through it at a rate of 64 cm3/sec, the superficial velocity is 64/640 or 0.1 cm/sec. The actual
velocity at the surface of any particle may be greater or less than the superficial velocity because
flow will not be uniform throughout the bed and because the particles occupy some of the cross-
section. Nevertheless, engineers have found it useful to calculate superficial velocities in this
manner to aid in estimating mass transfer between a flowing liquid and the stationary surfaces of
a particle. (See also Empty Bed Contact Time.)
Surge Tank: A type of pressurized water storage vessel also known as a bladder tank. Used almost
exclusively on residential well water systems, they provide a small amount of pressurized water
to downstream valves or equipment without requiring a pump. When installed on a piston type
pump, they reduce violent pressure spikes. Surge tanks typically have large areas of stagnation
that offer opportunistic bacteria a favorable environment for multiplication.
Titratable Alkalinity: When certain anions, such as carbonate (CO3-), are dissolved in water, they bind
hydrogen ions (H+) and thus shift the water equilibrium (see definition of pH) to produce free
hydroxyl ions (OH-). This excess concentration of OH- is termed alkalinity. Titratable alkalinity
can be measured by determining the amount of H+ (in mEq or mmol) which must be added to
water to restore the pH to 7.0, the condition of neutrality where [H+] = [OH-].
Total Dissolved Solids (TDS): The sum of all organic, inorganic and ionic contents in a solution
(excluding all dissolved gasses). Since a TDS meter cannot measure organic content of water,
most TDS readings are an approximation. TDS measurements are widely used in the water and
waste water industries to monitor final water quality. The TDS meter derives its' values from
resistivity and conductivity measurements of the product water.
Total Organic Carbon: Organic compounds dissolved in water are characterized by their carbon
content. Total organic carbon is the mass of carbon present in a water sample, excluding the
carbon present as CO2 and/or carbonates. The values are determined by catalytically oxidizing
(burning) all dissolved carbon (after CO2/CO3- removal by acidification) to CO2. The resulting
CO2 may be measured directly by infra-red absorption, or it may be reduced in a furnace with
hydrogen to form methane, which is measured by flame ionization detectors.
Turbidity: Turbidity is a measure of the presence of colloidal matter in the water that remains
suspended. Suspended matter in a water sample, such as clay, silt, or finely divided organic
and/or inorganic material will scatter the light from an incident light beam. The extent of
scattering is expressed in Jackson or Nephelometric turbidity units (JTU and NTU, respectively).
Ultra filters: A membrane based filtration system in which the pore sizes range from 0.001 to 0.1
microns.
Virus: The smallest infectious microorganism, made of RNA or DNA in a protein shell and which grow
only in other, living cells.
APPENDIX A
This page intentionally left blank.
APPENDIX A
TechNote 140
Equipment Maintenance Log
Date Performed Monthly Annual Bacteria AAMI Cleaning Disinfections Results Comments
By Maintenance Maintenance Testing Analysis Performed Performed Verified
P e r f or m e d Performed (Pass/Fail) (Pass/Fail) (Cleaner used) (Disinfectant used) By
TN140a 1 07-Dec-01
nd
Osmonics / ZyzaTech Water Systems ► 7848 S. 202 Street ► Kent, Washington 98032 ► (206) 395-2200 or (800) 633-3080
APPENDIX A
This page intentionally left blank.
APPENDIX A
TechNote 141
Pretreatment System Log
CARBON TANK(S) SOFTENER
Date Tested City Water Carbon Carbon Carbon City Softener Salt Results Comments
By Total Water Hardness Tank Verified
Chlorine Tank(s) Tank(s) Tank(s) Hardness (Output) Fille d By
Free Cl2 Total Cl2 Chloramines
TN141a 1 07-Dec-01
nd
Osmonics / ZyzaTech Water Systems ► 7848 S. 202 Street ► Kent, Washington 98032 ► (206) 395-2200 or (800) 633-3080
APPENDIX A
This page intentionally left blank.
APPENDIX A
TechNote 142
Equipment Operation Log
Date Tested Filter Filter Membrane Membrane % TDS Product Wa s t e Waste Results Comments
By In p u t Ou t p u t In p u t Ou t p u t Rejection GPM GPM Recirc. Reviewed
(LPM) (LPM) GPM By
TN142a 1 07-Dec-01
nd
Osmonics / ZyzaTech Water Systems ► 7848 S. 202 Street ► Kent, Washington 98032 ► (206) 395-2200 or (800) 633-3080
APPENDIX A
This page intentionally left blank.
APPENDIX A
TechNote 143
Cleaning / Disinfections Log
CLEANING DISINFECTIONS
Date D o ne Pre Pre % Pre Post Post % Post Disinfec- Presence Rinse Absence Review Comments
By TDS Rejec- Product TDS Rejec- Produc t a nt Test Performed Test By
tion pH tion t used (Positive) By Negative
pH
APPENDIX A
TN143a 1 07-Dec-01
nd
Osmonics / ZyzaTech Water Systems ► 7848 S. 202 Street ► Kent, Washington 98032 ► (206) 395-2200 or (800) 633-3080
APPENDIX A
Technote 133
MEMBRANE REPLACEMENT
AND START-UP INSTRUCTIONS
RO membranes can come with two types of outer sealing mechanisms, brine seal and cage
wrapped.
The brine seal type (traditional) membrane is used on tape and fiberglass-wrapped (outer
covering) style membranes. The brine seal is used to seal the membrane to the inner surface of
the housing. This forces the water to pass through the layers of the membrane rather than
bypass around the outside of the membrane. The brine seal is always installed at the inlet end
o f th e h o u s i n g .
The cage wrapped (sanitary) membrane is also referred to as a "full fit". The outer wrapping is
a plastic mesh that extends the full length of the membrane. This is the seal for the membrane
and the housing. The mesh design allows a small amount of water to flush the outside,
preventing trapping of contaminants. The cage style membrane can be installed either end first.
New membranes are shipped in polyethylene bags. Please inspect all membranes prior to
loading for physical damage that may have occurred during shipping.
APPENDIX A
MEMBRANE AND HOUSING REFERENCE DRAWINGS
APPENDIX A
This page intentionally left blank.
APPENDIX A
TechNote 144
Cleaning Log
PRE CLEANING POST CLEANING
Date D o ne Cleaner Pre Pre % Pre Pre Recirculat Post Post % Post Post Review Comments
By Used TDS Rejec- Product Product ion TDS Rejec- Product Product By
tion pH Flow tion pH Flow
Solution
Temperature
TN144a 1 07-Dec-01
nd
Osmonics / ZyzaTech Water Systems ► 7848 S. 202 Street ► Kent, Washington 98032 ► (206) 395-2200 or (800) 633-3080
APPENDIX A
This page intentionally left blank.
APPENDIX A
ZyzaTech Water Systems, Inc. - Limited Warranty
APPENDIX B:
WARRANTY
APPENDIX B
nd
Osmonics, Kent Operations (ZyzaTech Water Systems) 7848 S. 202 Street Kent, Washington 98032
(253) 395-2200 or (800) 633-3080
ZyzaTech Water Systems, Inc. - Limited Warranty
APPENDIX B
nd
Osmonics, Kent Operations (ZyzaTech Water Systems) 7848 S. 202 Street Kent, Washington 98032
(253) 395-2200 or (800) 633-3080
LIMITED WARRANTY
KENT OPERATIONS
Warranty Terms:
Subject to the terms and conditions set forth hereinafter, Seller (ZyzaTech Water Systems, Inc. or any of its
authorized subsidiaries) warrants to the original purchaser (hereinafter the “Buyer”) that the products
manufactured by Seller are free from defects in material and in workmanship for six (6) months or 1000
hours, whichever comes first, for portable equipment and accessories, and twelve (12) months for stationary
equipment and accessories from the Warranty Commencement Date (as defined below) only when used
strictly in accordance with the applicable operating instructions and within the range of the operating
conditions specified by Seller for each such product. This Warranty does not extend to equipment or
components manufactured by others into which a Seller product has been incorporated or to equipment or
components which have been incorporated into a Seller product but, if allowable, Seller hereby assigns,
without warranty, to the Buyer its interest, if any, under any warranty made by the manufacturer of such
equipment or component. This Warranty does not cover disposable items such as fuses, lamps, filters,
cartridges or other such disposable items which must be replaced periodically under the normal and
foreseeable operating conditions of the goods warranted hereby.
Warranty Commencement Date:
The Warranty Commencement Date for each Seller product shall be the later of the date of: (1) receipt by the
Buyer, or (2) the date of installation at the Buyer’s premises provided that such installation must occur within
three (3) months of shipment from the Seller’s manufacturing facility in Kent, Washington. In no event shall
the Warranty Commencement Date exceed three (3) months from shipment from Seller’s manufacturing
facility in Kent, Washington. The Buyer shall provide proof of purchase in order to exercise rights granted
under this Warranty. If requested by ZyzaTech, the Buyer must also provide proof of the installation date.
Proof of installation shall be returned by Buyer to Seller within thirty (30) days after installation by virtue of
supplying a Warranty Validation Card supplied with each Seller product fully completed and signed in ink by
Buyer and the authorized installer of the product. To exercise rights hereunder, Buyer must also provide to
Seller a copy of a laboratory bacterial test showing compliance with AAMI standards immediately following
installation of the products sold hereunder.
Warranty Service:
SELLER’S OBLIGATION UNDER THIS WARRANTY IS LIMITED TO REPAIR OR REPLACEMENT (AT
SELLER’S SOLE OPTION) OF ANY PRODUCT, OR COMPONENT THEREOF, PROVED TO BE
DEFECTIVE IN MATERIAL OR WORKMANSHIP WITHIN THE COVERED WARRANTY PERIOD. The
Buyer, at the Buyer’s risk and expense, shall be responsible for returning such product or component, upon
obtaining a Return Material Authorization (RMA) from Seller, freight prepaid, and in conformance with any
special packaging and shipping instructions set forth on the operating documentation or RMA instructions, or
as otherwise reasonably required, to the Seller’s address set forth below, together with (1) RMA number
issued by Seller at Buyer’s request; (2) proof of purchase and, if necessary, proof of installation date; (3) a
description of the suspected defects; (4) the serial number of the Seller product alleged to be defective; and
(5) a description of the type of water pretreatment equipment which has been utilized in connection with the
product, if any. Seller shall, in Seller’s reasonable discretion, be the sole judge of whether a returned product
or component is defective in material or workmanship. Repaired or replaced products or components shall be
returned to the Buyer by the Seller, freight prepaid by Seller, via UPS ground or best way surface freight. In
genuine emergency situations, Seller will (at Seller’s sole option) forward replacement parts to Buyer without
waiting for authorized return of the questionable part(s). In such cases, Buyer will issue a purchase order or
other payment guarantee prior to shipment. If the returned part is found to have been misused or abused, the
Buyer will be invoiced and pay for the price of the part, plus any freight charges. If the defective part is not
received by Seller within thirty (30) days, the Buyer will be invoiced for the replacement part(s) provided. This
Warranty does not cover or include labor and/or travel to the Buyer’s premise or location or any other
location. Charges will be made for the usual and customary Seller costs and associated expenses incurred
by Seller in providing Warranty Service at any location other than Seller’s factory at the address set orth
Date of Start-Up:
Name of facility:
Location or department:
Contact person at facility:
Address:
City: State: Zip Code:
Telephone Number: Fax Number:
RO Start up Information:
Pre-filter PSI Pump PSI Feed Water Waste Flow Rate
Product Product Water Quality
Temp. in Recirc.
In p u t Output Supply Waste PSI TDS % Rej. Flow Rate Waste Product
°C &/or °F
Central RO n/a
System
Portable RO n/a n/a
System
Authorized Printed
Signature: Name:
APPENDIX B
nd
Osmonics, Kent Operations (ZyzaTech Water Systems) 7848 S. 202 Street Kent, Washington 98032
(253) 395-2200 or (800) 633-3080
nd
Osmonics, Kent Operations (ZyzaTech Water Systems) 7848 S. 202nd Street Kent, Washington 98032
(253) 395-2200 or (800) 633-3080
Call (253) 395-2200 for additional information, (800) 633-3080 in the U.S., or visit www.osmonics.com
nd
Osmonics, Kent Operations (ZyzaTech Water Systems) 7848 S. 202nd Street Kent, Washington 98032
(253) 395-2200 or (800) 633-3080