Professional Documents
Culture Documents
LIQUID CHILLERS
INSTALLATION, COMMISSIONING,
OPERATION AND MAINTENANCE
STYLE E
REFRIGERANT TYPE: R22, R407C, R134A
035L02374-GB2 (05/02)
GB
035L02374-GB2 (05/02) I- i
TABLE OF CONTENTS
2.4 Condensers 2.1 4.13 Power Section Volt Free Contacts 4.11
2.6 Power and Control Panels 2.2 4.15 Connection Schematics 4.13
7.1 General Requirements 7.1 9.1 Flow Rate/Pressure Drop Charts 9.1
11 DE-COMMISSIONING, DISMANTLING
AND DISPOSAL
This manual and the Operating Instructions for the All the scheduled maintenance operations detailed
Micro Based Control System contain all the in this manual must be performed at the specified
information required for correct installation and times by suitably trained and qualified personnel.
commissioning of the unit, together with operating
and maintenance instructions. The manuals Failure to satisfy any of these conditions will
should be read thoroughly before attempting to automatically void the warranty.
operate or service the unit.
1.3 Safety
All procedures detailed in the manuals, including
installation, commissioning and maintenance Standards for Safety
tasks must only be performed by suitably trained
and qualified personnel. LCHM/LCHHM Series Chillers are designed and
built within an EN ISO 9001 accredited design and
The manufacturer will not be liable for any injury or manufacturing organisation and, within the limits
damage caused by incorrect installation, specified in this manual, are in conformity with the
commissioning, operation or maintenance essential health and safety requirements of the
resulting from a failure to follow the procedures and following European Union Directives:
instructions detailed in the manuals.
Machinery Directive (89/392/EEC)
1.2 Warranty Low Voltage Directive (73/23/EEC)
The warranty is limited to free replacement and 1.4 Responsibility for Safety
shipping of any faulty part, or sub-assembly which
has failed due to poor quality or manufacturing Every care has been taken in the design and
errors. All claims must be supported by evidence manufacture of York Chillers to ensure that they
that the failure has occurred within the warranty meet the safety requirements listed in the previous
period, and that the unit has been operated within paragraph. However, the individual operating or
the design parameters specified. working on any machinery is primarily responsible
for:
All warranty claims must specify the unit model,
serial number and order number. These details are Personal safety, safety of other personnel, and the
printed on the unit identification plate. machinery
1- 2 035L02374-GB2 (05/02)
Structural support of the unit must be provided as The unit must be earthed. No installation or
indicated in these instructions. Failure to provide maintenance work should be attempted on
proper support may result in injury to the operator, electrical equipment without first switching off,
or damage to the equipment. isolating and locking-off the main power supply
and any control supplies. Work on live equipment
Mechanical Strength must only be carried-out by suitably trained and
qualified personnel. No attempt should be made to
The unit is not designed to withstand loads or gain access to internals of the control panel, wiring
stresses from adjacent equipment, pipework or or other electrical enclosures during normal
structures. Additional components must not be operation of the unit.
mounted on the unit. Any such extraneous loads
may cause structural failure and may result in injury
LCHM LCHHM
to the operator, or damage to the equipment.
General Access
Each unit has one or two independent pressure Refrigerants and Oils
systems each comprising a compressor, water
cooled condenser (WL units) or receiver tank Refrigerants and oils used in the unit are generally
(AL-R units), cooler vessel and interconnecting non-toxic, non-flammable and non-corrosive, and
copper pipework. Each system contains refrigerant pose no special safety hazards. Use of gloves and
vapour and liquid under pressure, release of which safety glasses are, however, recommended when
can be a danger and cause injury. The user should working on the unit. Build up of refrigerant vapour,
ensure that care is taken during installation, from a leak for example, does pose a risk of
operation and maintenance to avoid damage to the asphyxiation in confined or enclosed spaces and
pressure system. No attempt should be made to attention should be given to good ventilation. For
gain access to the component parts of the pressure more comprehensive information on safety
system other than by suitably trained and qualified precautions for use of refrigerants and oils, refer to
personnel. the Materials Safety Data tables provided.
In case of emergency the control panel is fitted with The following labels are fixed to each unit to give
an emergency stop button (LCHM) or stop switch instruction, or to indicate potential hazards which
(LCHHM) which, when operated, removes the may exist.
electrical supply from the control system and the
microprocessor controller. On LCHM units the White symbol on b lu e
button, once pressed, requires key release. On background
LCHHM units the switch can be pad-locked in the
off position. A facility is available to connect a For safe operation - read the
remote emergency stop device for the same Instructions first
purpose. The unit emergency stop button or switch
is red on a yellow back plate.
Refrigerant Data:
Toxicity Low.
In contact with skin Liquid splashes or spray may cause freeze burns. Unlikely to be hazardous
by skin absorption. R22 may be slightly irritant and liquid has a degreasing
effect. Thaw affected areas with water. Remove contaminated clothing
carefully - may adhere to skin in case of freeze burns. Wash affected areas
with plenty of warm water. If symptoms occur (irritation or blistering) obtain
medical attention.
In contact with eyes Vapour has no effect. Liquid splashes or spray may cause freeze burns.
Immediately irrigate with eyewash solution or clean water for at least 10
minutes. Obtain immediate medical attention.
Ingested Highly unlikely to occur -but should this occur freeze burn will occur. Do not
induce vomiting. Provided patient is conscious, wash mouth with water and
give about 250 ml (0.5 pint) to drink. Obtain immediate medical attention.
Further medical advice Symptomatic and supportive therapy is indicated. Cardiac sensitisation
has been described which may, in the presence of circulating
catecholamines such as adrenalin, give rise to cardiac arrhythmias and
subsequent arrest following exposure to high concentrations.
Long term exposure R22 A lifetime inhalation study in R407C, R134a A lifetime inhalation
rats and mice give a small excess in study in rats has shown that
salivary gland tumours in male rats exposure to 50,000 ppm resulted in
only at 50,000 ppm. 10,000 ppm benign tumours of the testis. This is
showed no effect. This information not considered to be of relevance to
suggests t hat R 22 does not humans exposed to concentrations
represent a carcinogenic hazard to at or below the occupational
humans. exposure limit.
Occupational exposure limits R22 Recommended limit: 1000 ppm R407C, R134a Recommended
v/v - 8 hr TWA 1250 ppm v/v - 12 hr limit: 1000 ppm v/v - 8 hr TWA.
TWA.
Conditions to avoid Use in presence of naked flames, red hot surfaces and high moisture
levels.
035L02374-GB2 (05/02) 1- 7
Hazardous reactions May react violently with sodium, potassium, barium and other alkali and
alkaline earth metals. Incompatible materials: Magnesium and alloys
containing more then 2% magnesium.
Hazardous decomposition products R22 Halogen acids formed by R407C, R134a Halogen acids by
thermal decomposition. t her mal decomposi t i on a n d
hydrolysis.
Storage Keep containers dry and in a cool place away from fire risk, direct sunlight,
and all sources of heat such as radiators. Keep at temperatures not
exceeding 45°C.
Spill/leak procedure Ensure suitable personal protective clothing and respiratory protection is
worn. Provided it is safe to do so, isolate the source of the leak. Allow small
spillages to evaporate provided there is suitable ventilation.
Large spillages: Ventilate area. Contain spillages with sand, earth or any
suitable absorbent material. Prevent liquid from entering drains, sewers,
basements and work pits since vapour may create a suffocating
atmosphere.
Containers Fire exposed containers should be kept cool with water sprays. Containers
may burst if overheated.
Fire fighting protective equipment Self contained breathing apparatus and protective clothing must be worn in
fire conditions.
Classification Non-hazardous
In contact with skin Minimally irritating. No first aid necessary. Exercise reasonable personal
cleanliness including cleansing exposed skin areas several times daily with
soap and water. Launder soiled work clothes at least weekly.
In contact with eyes As with most foreign materials flush Flush eyes with eyewash solution or
with plenty of eyewash solution or clean water for 15 minutes and
clean water. consult a physician.
Ingested Non-toxic. No first aid considered May cause nausea and diahorrhea.
necessary. Obtain immediate medical attention.
1- 8 035L02374-GB2 (05/02)
Inhalation If oil mist is inhaled, remove to fresh air and consult a physician.
Hazardous decomposition Oxides of carbon, aldehydes and Not fully. Analogous compounds
ketones, combustion products of evolve carbon monoxide, carbon
nitrogen, sulphur. dioxide and other unidentified
fragments when burned. Burning
fluid may evolve irritating/noxious
fumes.
Respiratory protection Use in well ventilated areas. Use in well ventilated areas -
ventilate locally.
Protective clothing Not necessary but goggles or face Goggles or face shield should be
shield recommended. worn. Gloves not necessary, but
recommended, especially for
prolonged exposure.
Spill / Leak procedure Wear suitable protective equipment, especially goggles. Stop source of
spill. Use absorbent materials to soak up fluid (i.e. sand, sawdust, and
commercially available materials).
Disposal Incinerate the oil and all associated wastes in an approved facility in
accordance with local laws and regulations governing oily wastes.
Fire extinguishing data Flash point over 180°C. Use water Flash point over 300°C. Use dry
spray, dry chemical, carbon dioxide chemical, carbon dioxide or foam.
or alcohol foam. Water or foam may Spraying water on hot or burning
cause frothing. liquid, may cause frothing or
splashing.
If a leak or spill has not ignited use water spray to disperse the vapours and
to provided protection for persons attempting to stop the leak.
Containers Fire exposed containers should be kept cool with water sprays.
Fire fighting protective equipment Self contained breathing apparatus should be worn in fire conditions.
035L02374-GB2 (05/02) 1- 9
Health Hazard & First Aid Toxicity Index <10 to NES713 Issue 3 (1991) : Non-hazardous, non-toxic.
No first aid necessary.
Handling / Use / Disposal No special handling precautions required. Dispose of according to local
laws and regulations governing non-biodegradable non-hazardous solid
wastes.
2 PRODUCT DESCRIPTION
York LCHM/LCHHM Liquid Cooled and Remote Suction and discharge valves are high quality,
Air Cooled Chillers are delivered completely non-flexing, stainless steel. The pistons are
assembled with all interconnecting refrigerant aluminium alloy with two piston rings. The
piping and internal wiring, ready for field connecting rods are aluminium alloy with integral
installation. bearing surfaces on both ends. Cylinder liners are
removable.
Prior to delivery each unit is pressure tested,
evacuated and charged with a refrigerant (WL, Compressor Lubrication
WL-HP and WL-HR units) or nitrogen (AL and ALR
units) holding charge, and includes an initial oil The lubrication is force-fed by a reversible oil pump
charge. After assembly an electrical function test is which supplies oil to all crankshaft and bearing
performed to ensure correct operation. surfaces through a fine mesh stainless steel filter.
The compressor housing is cast iron. It contains: The water baffles are constructed from galvanised
removable cylinder heads with internal muffling, steel to minimise corrosion. The removable heads
suction and discharge service valves, crankcase allow access to the internally enhanced, seamless
sight glass and heater, oil and suction strainers, copper tubes. Vent and drain connections are
an d int er nal re l i e f va l ve co n fo rming to included.
ASHRAE/ANSI Standard 15 Safety Code.
The cooler is insulated with 19 mm closed cell type
Crankshaft insulation.
All control and motor starting equipment necessary Common Input Supply + Mains Isolation
for the unit operation are located in galvanised (LCHHM only)
steel enclosures manufactured to IP33 protection.
The power and logic sections are fully factory wired Factory fitted fused door interlocked isolators
and function tested during manufacture. (switch-disconnector-fuse type), one per power
Components are mounted on galvanised steel section, plus interconnecting wiring and terminals
back plates in separate power or control to allow connection at a single point. Available with
compartments, each having a separate galvanised B.S. or D.I.N. fuses. A gland plate extension box is
steel access door. All doors are hinged and included with this option to allow additional space
lockable. for cable spreading.
Each power section contains a 380/400V power One (LCHM) or two (LCHHM) single refrigerant
group formed by the compressor contactors and circuit/dual 2-pass or 3-pass coolant circuit
incoming terminals or switch disconnector fuse condenser(s), fitted instead of the standard
(option), overloads and fuses. A 220/230V control condenser(s), to allow heat rejection or recovery
group is formed by control fuses, residual current via two separate liquid systems. Design is
device, compressor timer, compressor current generally as per the standard unit condensers
transformer and relay boards. except for a higher design pressure on the
refrigerant side.
Control Panel - Logic Section
Liquid Receiver (AL units only)
The logic section door has mounted on it the Micro
Based Control System keypad and display. The Remote Air Cooled units can be fitted with a single
l og ic c ont r ol co mp a rt me n t co n t a i n s the section (LCHM) or dual section (LCHHM) liquid
microprocessor board, power supply board, optical refrigerant receiver complete with relief valve(s)
isolation board and, if fitted, electronic expansion built to pressure vessel code.
valve controllers. For details refer to the Operating
Instructions for the Micro Based Control System High Pressure Condenser (LCHHM - WL only)
supplied with the chiller.
A high pressure condenser can be supplied for
units, using R22 or R407C; to allow operation with
condenser leaving water temperatures above the
normal maximum of 40°C for R22 or 35°C for
R407C. This option includes oversized motor(s)
and electrical starters.
035L02374-GB2 (05/02) 2- 3
Set of level adjustable spring vibration isolator Hand held printer for obtaining print-outs of the unit
mounts with mounting holes for fixing to operating and history data from the Micro Based
foundations. Control System.
2.8 Nomenclature
LC H M 115 W L xx 50 E
York Liquid Chiller Design Level (Style)
H = Single Compressor
50 = 380/400/415-3-50
HH = Dual Compressor
Option Code
Microprocessor Controlled
HR = Heat Recovery
HP = High Pressurre
Model Size
Condenser
W = Liquid Cooled
York UK Manufactured
A = Remote Air Cooled
Range of Models
Related Drawings
3 TRANSPORTATION, HANDLING
AND STORAGE
3.2 Inspection
Remove any transit packing and inspect the unit to LCHM - Single Compressor Units
ensure that all components have been delivered
and that no damage has occurred during transit. If
any damage is evident, it should be noted on the Prior to moving the unit ensure that the installation
carrier’s freight bill and a claim entered in site is suitable for installing the unit, and is capable
accordance with the instructions given on the of supporting the weight of the unit and all
advice note. associated services.
■ The isolators should be loosely attached to the The flow switch used must have gold plated
holes provided in the unit feet using the lock contacts for low voltage/current operation.
screw in the top of the mount main levelling Paddle type flow switches suitable for 10 barg
bolt. Levelling of the unit is accomplished by working pressure and having a 1" N.P.T.
turning the levelling bolt and then tightening connection can be obtained from York as an
the lock screw. accessory for the unit. Alternatively a
differential pressure switch sited across an
■ To maintain isolator efficiency, no mechanical orifice plate may be used, preferably of the
ties should be made to the building and flexible high/low limit type.
connectors should be used for all piping.
■ The liquid pump(s) installed in the pipework
On LCHHM units two mounts are located system(s) should discharge directly into the
side by side at each mounting foot of the unit heat exchanger section of the system. The
unit. The centre line distance between pump(s) require an auto-starter (by others) to
each mount is 80 mm. be wired to the control panel. For details refer
to “Electrical Connection”.
4.4 Pipework Connection
■ Pipework and fittings must be separately
General Requirements supported to prevent any loading on the heat
exchanger(s). Flexible connections are
The following piping recommendations are recommended which will also minimise
intended to ensure satisfactory operation of the transmission of vibrations to the building.
unit(s). Failure to follow these recommendations Flexible connections must be used if the unit is
could cause damage to the unit, or loss of mounted on anti-vibration mounts as some
performance, and may invalidate the warranty. movement of the unit can be expected in
normal operation.
The maximum flow rate and pressure
drop for the cooler and condenser must ■ Pipework and fittings immediately next to the
not be exceeded at any time. Refer to heat exchangers should be rea d ily
Section 9 for details. de-mountable to enable cleaning prior to
operation, and to facilitate visual inspection of
■ The water must enter the heat exchanger(s) the exchanger nozzles.
by the inlet connection. The inlet connection
for the cooler is at the same end as the ■ Each heat exchanger must be protected by a
refrigerant pipework connections. The inlet strainer, preferably of 40 mesh, fitted as close
connection for a heat recovery condenser is as possible to the liquid inlet connection, and
the bottom liquid connection. provided with a means of local isolation.
■ A flow switch must be installed in the customer ■ The heat exchanger(s) must not be exposed to
pipework at the outlet of the cooler as shown in flushing velocities or debris released during
the arrangement diagrams, and wired back to flushing. It is recommended that a suitably
the control panel using screened cable. For sized by-pass and valve arrangement is
details refer to “Electrical Connection”. This is installed to allow flushing of the pipework
to prevent damage to the cooler caused by the system. The by-pass can be used during
unit operating without adequate liquid flow. maintenance to isolate the heat exchanger
without disrupting flow to other units.
Flow Switch
Flanged Connection
4- 4 035L02374-GB2 (05/02)
Key
Strainer
Pressure Tapping
Flow Switch
Flanged Connection
035L02374-GB2 (05/02) 4- 5
Standard Connections
Standard Threaded
Coolers, condensers and liquid receiver vessels For primary cooling of WL units, condensers are
are each protected against internal refrigerant side usually piped in conjunction with a cooling tower,
over-pressure and fire by refrigerant relief valves. although in some cases they can be cooled by well
The pressure relief valve is set at design pressure water.
of the system and has discharge capacity required
by relevant standard. On coolers the relief valve(s) For LCHM and LCHHM units it is necessary to
are mounted on the end of the vessel, one per control coolant flow and/or temperature into the
refrigerant circuit. On condensers and receiver condenser to maintain refrigerant pressure as
tanks the relief valve(s) are mounted on top of constant as possible to ensure satisfactory
vessel body. operation of the refrigerant expansion valve(s).
D5 = C x L
Where:
D = minimum pipe internal diameter in centimetres
L = length of pipe in metres
C = constant given in table below
035L02374-GB2 (05/02) 4- 7
With LCHM units it is possible, if desired, to control For a cooling tower system the simplest forms of
the condenser water inlet temperature / flow control are to use fan cycling fan speed control, or
directly from the unit refrigerant pressure. air damper control, with the tower having a
thermostat in its sump. This will ensure stable
The refrigerant pressure can either be used to condenser water temperature sensing at design
control cooling tower effectiveness by controlling conditions and should be adjusted to ensure a
fans or dampers on the tower, or to control condenser water entering temperature of not lower
condenser flow using a three way bypass valve as than 21°C to 24°C at later ambient conditions.
shown below.
If these methods are not available or a cooling
The aim is to maintain a stable discharge pressure tower is not the source of cooling water, then a
as low as possible, but at least 5.2 bar above three way valve recirculation system can be used
suction pressure on R22 and R407C units and at with control based on condenser inlet water
least 4.0 bar above suction pressure on R134a temperature as shown below. In this case the
units. This can be done at a fixed value above the objective is to maintain the inlet cooling water
highest expected suction pressure or by also temperature as low as possible although still
measuring suction pressure and using differential observing the minimum limit of 21°C to 24°C.
control. In either case water flow and temperature
limits must also be observed.
General
The condenser should be designed to provide ■ To avoid the risk of discharge gas pulsation's
sufficient subcooling at its outlet to ensure that no causing undesired noise within the building, a
'flashing' will occur in the liquid line to the unit, or in suitably sized discharge gas muffler may be
the filter/drier and liquid valves on the unit itself. fitted in the discharge line near the unit. A
Liquid subcooling should be 4°C to 10°C on arrival slight loss of performance may, however,
at the unit. result at full load.
LCHM and LCHHM units perform a 'pump-down' Incorrectly or badly designed and/or
cycle whenever a compressor starts. If the optional installed pipew ork systems m a y
liquid receiver tank has not been ordered with the invalidate unit warranty.
unit, it is important to ensure that for each system
the remote condenser and liquid line volume is at
least 1.65 times the liquid volume of the operating Refrigerant Connections
refrigerant charge.
Units are supplied with a nitrogen holding charge.
When the unit has been located in its final position, This should be relieved carefully via the
the refrigerant system pipework can be connected. compressor suction service valve connections and
Pipework and fittings MUST be separately the liquid line stop valve service connection.
supported and not cause any loading on the unit.
Flexible connections are recommended and will Discharge Line
also minimise transmission of vibrations to the
building. Flexible connections MUST be used if the Remove the clamp bolts on the compressor
unit is mounted on anti-vibration mounts as some discharge service valve and slide the flange over
movement of the unit can be expected in operation. the discharge line pipe. Remove the brazing collar
careful from the gasket and braze to the discharge
Pipework Design line. Oil the gasket with appropriate refrigerant oil
and reassemble the joint.
The following notes give guidance but should not
be considered exhaustive:
On AL units the liquid line connection is made at the The following connection recommendations are
liquid line service valve. Pipework can be brazed intended to ensure safe and satisfactory operation
directly onto the valve taking care to protect the of the unit(s). Failure to follow t h e se
valve from excess heat which may cause recommendations could cause harm to persons, or
distortion. damage to the unit, and may invalidate the
warranty.
On AL-R units the liquid connection is made to the
liquid receiver vessel at the brazing stub on top of No additional controls (relays, etc.)
the vessel. Care should be taken to avoid debris should be mounted in any section of
falling into the vessel when making this connection the control panel. Power and control
wiring not connected to the Control
Connection Sizes Panel should not be run through the
System 1 System 2 Control Panel. If these precautions are
Model Disch. Liquid Disch. Liquid not followed it could lead to a risk of
All units AL units AL-Runits All units AL units AL-Runits
LCHM electrocution. In addition, electrical
60 2 5/8" 1 3/8" 2 1/8" - - - noise could cause malfunctions, or
R22 / 70 2 5/8" 1 3/8" 2 5/8" - - -
R407C 85 2 5/8" 1 5/8" 2 5/8" - -
damage the unit and its controls.
100 3 1/8" 1 5/8" 3 1/8" - - -
115 3 1/8" 1 5/8" 3 1/8" - - -
After connection do not switch on
55 2 5/8" 1 3/8" 2 1/8" - - -
R134a 65 3 1/8" 1 5/8" 2 5/8" - - - mains power to the unit. Some internal
75 3 1/8" 1 5/8" 2 5/8" - - - components are live as soon as mains
LCHHM
140 2 5/8" 1 3/8" 2 5/8" 2 5/8" 1 3/8" 2 5/8" is switched on, and this must only be
R22 / 170 2 5/8" 1 3/8" 2 5/8" 2 5/8" 1 3/8" 2 5/8" done by authorised persons.
R407C 200 3 1/8" 1 5/8" 3 1/8" 2 5/8" 1 3/8" 3 1/8"
230 3 1/8" 1 5/8" 3 1/8" 3 1/8" 1 5/8" 3 1/8"
90 2 5/8" 1 3/8" * 2 5/8" 1 3/8" * ■ The main Off/Auto unit selector switch on the
R134a 110 2 5/8" 1 3/8" * 2 5/8" 1 3/8" *
130 3 1/8" 1 5/8" 2 5/8" 3 1/8" 1 5/8" 2 5/8"
front of the control panel has been sealed in
150 3 1/8" 1 5/8" 2 5/8" 3 1/8" 1 5/8" 2 5/8" the off position at the factory.
All connections are Female for brazing to the given O.D. size of copper pipe. This seal must remain in place
* Refer to York Basildon for these connection sizes.
preventing running of the unit
until commissioned by
System Testing authorised personnel. If the
seal has been removed before
All newly installed pipework must be pressure/leak commissioning then it must be
tested to national code requirements (normally reported to the Basildon
1.1 x Design Working Pressure) then fully Factory Quality Manager
evacuated before charging. Refer to the Section 5 otherwise warranty may be
for correct charging methods. invalidated.
4-10 035L02374-GB2 (05/02)
4.12 Power Wiring LCHHM Standard Units and Units with Switch
Disconnector Fuse*
LCHM and LCHHM units are suitable for
380/400 volt, 3 phase, 50 Hz nominal Standard units and units fitted with optional switch
supplies only. disconnector fuse require two-off 3 phase
Minimum allowable voltage 342 V. separately fused 3 wire supplies plus earth, with
Maximum allowable voltage 440 V. one supply to be connected to each of the two
system power sections of the control panel. Also
All electrical wiring should be carried out in required is a separate control supply connected to
accordance with local regulations. Route properly customer terminals in the centre common power
sized cables (based on installation conditions and section of the panel.
currents given in electrical data tables) to site
drilled holes in the Control Panel gland plate as All three supply cables should enter via site drilled
specified below. gland plate in the bottom of the centre common
power section. The 3 phase supplies can then be
In accordance with EN 60204 it is the responsibility routed to their respective input terminals in each of
of the user to install overcurrent protection devices the power sections, number 1 to the left and
between the supply conductors and the customer number 2 to the right.
input supply terminals on the unit.
Connect each of the two main 3 phase supplies to
To ensure that no eddy currents are set up in the
the customer terminal blocks, or optional switch
metal gland plate the cables forming each 3 phase
disconnector fuse, located in the two separate
power supply must enter via the same hole in the
power sections of the control panel using lug sizes
gland plate. If separate entries for each cable
detailed in the Technical Specification Section.
forming the 3 phase supplies are used, the metal
gland plate must be replaced by a non-metallic
Connect earth wires to the main protective earth
gland plate, with due regard given to sealing the
terminals, using M10 lugs, in each power section.
panel to IP33.
On standard units connect a 220/230 V single
All sources of supply to the unit must
phase control supply to the control switch
be taken via a common point of
disconnector in the centre main common power
isolation (not supplied by York).
section with bare wire ends of maximum cable size
4 mm. For details refer to the Technical
Specification Section (customer control circuit
LCHM Standard Units and Units with Switch supply data). Also connect an earth wire to the
Disconnector Fuse* protective earth terminal using an M4 lug.
Standard units and units fitted with an optional
On units fitted with a 3 wire supply option* connect
switch disconnector fuse require a 3 phase 4 wire
two phases (380/400 V) to the control switch
supply plus earth. One phase and the neutral are
disconnector in the centre main common power
used internally to derive the 220/230 V control
section with bare wire ends of maximum cable size
supply. On units fitted with a 3 wire supply option*
4 mm². For details refer to Technical Specification
an internal transformer is used to create the
Section (customer control circuit supply data). Also
220/230 V control circuit supply and therefore no
connect an earth wire to the protective earth
neutral connection is required.
terminal using an M4 lug.
All cables should enter via the site drilled gland
plate on the right side of the control panel and be *Fitted as standard on CE units
connected to the 3 phase supply customer terminal
block or the optional switch disconnector fuse
terminals. For details of lug sizes, refer to section 9.
Connect the earth wire to the main protective earth
terminal, using an M10 lug.
Units with Common Input Supply and 4.13 Power Section Volt Free Contacts
Isolators
All wiring to the power section volt free contacts
Units fitted with the common input supply option requires a supply, maximum 254 V, provided by
require one 3 phase and neutral supply plus earth the customer. The customer must take particular
only. If a 3 wire mains supply option is fitted**, no care deriving the supplies for the volt free terminals
neutral is required. Under the centre power section with regard to a common point of isolation. These
of the control panel is a cable spreader box which circuits when used must be fed via the common
should be used to separate the cores of large point of isolation so that the voltage is removed
multi-core cable prior to connection to the when the common point of isolation to the unit is
customer main terminal block. The cable should opened.
enter the spreader box through a site drilled gland
plate on the left hand side of the box. In accordance with EN 60204 it is recommended
that the customer wiring to these terminals uses
**Fitted as standard with common input supply orange wires. This will ensure that circuits not
option on CE units switched off by the unit supply disconnecting
device are distinguished by colour, so that they can
Connect the 3 phases to the main customer easily be identified as live even when the unit
terminal block located in the centre power section disconnecting device is off.
of the control panel using M16 lugs. If no 3 wire
supply option is fitted, also connect neutral to the The unit volt-free contacts are rated at 125 VA. All
main neutral terminal block using an M12 lug. inductive devices (relays) switched by the unit
volt-free contacts must have their coil suppressed
Connect an earth wire to the main protective earth using standard R/C suppressors.
terminal located in the centre power section of the
control panel using an M10 lug. Chilled Liquid Pump Starter
Control Transformer Primary Voltage Terminals 33 and 34 close to start chilled liquid
Tappings pump. This contact can be used as a master
start/stop for the pump in conjunction with the daily
The 3-wire control transformer is mounted behind start/stop schedule. If no schedule is set, and the
the control panel. It is important to check that the customer has master control of the pump, the unit
correct primary tapping has been used: contact must be used to override the customer
master start/stop so that the York contact can start
■ With the supply to the unit isolated remove the the pump in the event of a low temperature liquid
lid to the transformer box. condition.
Each system has a voltage-free change over Remove the link from terminals 11 and 14 LCHM
contact which will operate to signal an alarm and LCHHM No. 1 system and terminals 12 and 15
condition whenever a system locks out, or there is LCHHM No. 2 system and connect remote
a power failure. To obtain system alarm signal, switch(es) to provide remote run/stop control if
connect alarm circuit to volt free terminals 31 and required.
32 (close on alarm) or 30 and 32 (open on alarm)
for LCHM and LCHHM No. 1 system. For LCHHM Remote Print
No. 2 system terminals 38 and 39 (close on alarm)
or 37 and 39 (open on alarm). Closure of suitable contacts connected to
terminals 18 and 13 will cause a hard copy printout
4.14 Logic Section Connections of Operating Data/Fault History to be made if an
optional printer is connected to the RS 232 port.
All wiring to the logic section terminal block is
nominal 30 Vdc and must be run in screened cable, Remote Lead/Lag (LCHHM)
with the screen earthed at the panel end only. Run
screened cable separately from mains cable to If manual lead/lag control is required, closure of
avoid electrical noise pick-up. Use the gland plate suitable contacts connected to terminals 13 and 19
on the back of the control panel, to connect directly will cause system 2 to operate in lead. Open
into the logic section to avoid mains cable. contacts will cause system 1 to be in lead.
The voltage free contacts must be suitable for Remote Set Point Offset
30 Vdc (gold contacts recommended). If the
voltage free contacts form part of a relay or Timed closure of suitable contacts connected to
contactor, the coil of the device must be terminals 13 and 17 (PWM contacts) will give
suppressed using a standard R/C suppressor. The remote offset function of the chilled liquid set point
above precautions must be taken to avoid if required. This function cannot be used if “Remote
electrical noise which could cause a malfunction or Unload” function is required.
damage to the unit and its controls.
Remote Unloading
The length of cable to these terminals
must not exceed 7.5 m unless an optional The Micro Based Control System is capable of
input isolator kit is fitted. remote unloading (or pull-down demand limiting) in
two steps. The first step of unloading is achieved
The optional input isolator kit uses 15 Vdc by closing suitable contacts connected to terminals
(not 30 Vdc). 16 and 13. The second step of unloading is
achieved by closing suitable contacts connected to
Flow Switch terminals 17 and 13. Note: the first step contacts
must be closed before the second step contacts
A chilled liquid flow switch of suitable type must be are closed. For details of compressor load steps
connected to terminals 10 and 13 to provide given by these contacts, refer to the Micro Based
adequate protection against loss of liquid flow. Control System Manual. This function cannot be
used if “Remote Set point Offset” is required.
035L02374-GB2 (05/02) 4-13
LCHM Units
+5V
GND
RS232
RXD LOGIC POWER
TXD SECTION SECTION
DSR
DTR
INPUT
SECTION
3 4
PE
N
30 31 32 33 34 35 36
13 10 11 14 12 15 16 13 13 17 18 13 13 19 20 13
REMOTE 3-PHASE + NEUTRAL
EMERGENCY 50 Hz 380/400 V
STOP DEVICE
OPEN CHILLED
ON LIQUID
ALARM PUMP
STARTER
CHILLED LIQUID
FLOW SWITCH
REMOTE REMOTE TEMP REMOTE
RUN UNLOAD RESET PRINT
INTERLOCK OR CLOSE RUN CONTACT
(REMOVE LINK REMOTE
3 WIRE CONTROL SUPPLY
ON (CONDENSER
IF CONTACT FITTED) UNLOAD OPTION ALARM PUMP/FAN
STARTER)
U W 3 4
PE
REMOTE
EMERGENCY
2-PHASE 50 Hz STOP DEVICE
˜
380/400V
4-14 035L02374-GB2 (05/02)
LCHHM Units
CONTROL PANEL
No.1 POWER LOGIC SECTION No.2 POWER
+5V SECTION SECTION
GND
RS232
RXD
TXD
DSR
DTR
U V W N U 3 4 U V W
PE PE N L PE
REMOTE
EMERGENCY
3˜ 50Hz 1˜ 50Hz STOP 3˜ 50Hz
380/400V 220/230V DEVICE 380/400V
SCR
No.1 CHILLED COMMON No.2
SYSTEM LIQUID RUN SYSTEM
CLOSE PUMP SIGNAL CLOSE
ON STARTER ON
ALARM ALARM
3 4 N U V W U W 3 4
INPUT SECTION
N U V W
CABLE
SPREADER
BOX
PE N PE
REMOTE REMOTE
EMERGENCY 3N~50Hz OMIT NEUTRAL EMERGENCY
STOP DEVICE 380/400V IF 3 WIRE OPTION 2˜ 50Hz STOP DEVICE
ALSO FITTED 380/400V
035L02374-GB2 (05/02) 5- 1
5 COMMISSIONING
Inspection: Inspect unit for installation damage. If Do not liquid charge with static water in any of the
found take action and/or repair as appropriate. heat exchangers. Care must also be taken to liquid
charge slowly to avoid excessive thermal stress at
Remote Condenser Systems the charging point. Once the vacuum is broken,
charge into the condenser coils with the full
All units require a suitable remote refrigerant operating charge as given on the unit data plate
condenser system. Verify that the system has been and the Section 9 of this manual, (including
installed correctly and that the condenser has additional condenser charge for AL units).
discharge pressure control capable of maintaining
a reasonably stable working pressure. Valves: Open the compressor suction and
discharge, and the liquid line service valves on
both systems (CCW).
Compressor oil: Compressor lubrication systems Control Transformer: The 3-wire control
must be primed prior to first time start-up. Only the transformer is mounted behind the control panel. It
correct type of oil must be used as given by unit is important to check that the correct primary
d ata plat e/ label s a n d i s a s fo l l o ws for tapping has been used:
LCHM/LCHHM standard units:
■ With the supply to the unit isolated remove the
Refrigerant Compressor Oil lid to the transformer box.
R22 York grade C
R407c York grade H ■ Check that the tapping used conforms to the
R134a York grade H site supply voltage. The two tappings are 342 -
424 V and 360 - 440 V.
To prime each compressor - connect a York hand
oil pump (part no. 470-10654-000) to the 1/4" Switch Settings: Ensure that the black handled
compressor oil priming valve with a length of clean unit switch on the display door and the micro board
hose or copper line, but do not tighten the flare nut. system switches S2 and S3 in the logic section are
Using clean oil of the correct type, pump oil until all set to "0" (OFF). For LCHM units ensure the
air has been purged from the hose then tighten the emergency stop button is reset. For LCHHM units
nut. Stroke the oil pump 10 times (delivering set the red handled control circuit switch
approximately 1,5 litres) to prime the oil system. disconnector/emergency stop device on the lower
The oil level should be between the middle of the centre section door to "1" (ON). For units fitted with
lower and middle of the upper sight glasses. If it is switch disconnector fuse devices the power
necessary to add oil, continue to stroke the pump section doors must be closed and the devices set
until the correct level is achieved. to "1" (ON). The customers disconnection devices
can now be set to ON.
Isolation/protection: Verify that all sources of
electrical supply to the unit are taken from a single The machine is now live!
point of isolation. For units not fitted with a switch
disconnector fuse check that the maximum
recommended fuse sizes given in the Technical
Data section have not been exceeded.
The unit is fitted with an under voltage
Control panel: Check panel to see that it is free of relay and it may take between 5 to 10
foreign materials (wire, metal chips, etc.) and clean seconds for its contacts to close and
out if required. energise the units electronics, including
the display.
Power connections: Check the customer power
cables are connected to the unit incoming Crankcase heaters: Verify the compressor
terminals. Ensure that connections of power crankcase heaters are energised. The compressor
cables within the panel to contactors, terminal crankcase heaters must be on for at least 24
blocks or switch disconnector fuse, and external HOURS prior to start-up to ensure all refrigerant
connection to compressors are tight. liquid is driven out of the oil.
Earthing: Verify that the units protective
terminal(s) are properly connected to a suitable
earthing point. Ensure that all unit internal earth
connections are tight.
Water/Glycol system(s): Verify that the chilled Control supply: Verify the control centre display is
water system has been installed correctly, and has illuminated. If an electronic expansion valve option
been commissioned with the correct direction of is fitted, the `power to expansion valve’ on the
water flow through the cooler. Inlet should be at the valve controllers (in the logic section) should pulse
refrigerant pipework connection end of the cooler. to indicate the 24 volt supply is on to these items.
With water flowing, (it may be necessary to bypass
the unit pump control if this is connected) purge air HP cut-out reset: Check that the hand reset
from the top of the cooler using the ¼" angle valve mechanical high pressure cut-outs mounted on the
mounted on the top of the cooler body. unit are reset.
On WL units, verify that the hot water system has EEV controller settings (if fitted): Loosen the four
be en ins t all e d co rre ct l y, a n d h as been screws holding the Danfoss controller to its base
commissioned with the correct direction of water and remove by pulling the handle. Check that the
flaw through the condenser(s). Inlet should be at refrigerant setting is correct for the refrigerant used
the condenser connection nearest the bottom of in the unit and that the MOP value is set for 5,8 barg
the vessel. With water flowing, (it may again be for R22 or 3,8 barg for R134a as applicable. Set the
necessary to bypass the unit pump control if this is (-BS2 (-) -BS1) temperature differential on the
connected) purge air from the condenser(s) using controllers to 9°C and check that the Tn (time
the ¼" angle valve mounted on the top of water integration) value is set to 200 seconds and the Kp
head. (amplification factor) value is set to 1,0. The `TQ
Power’ light will be pulsing indicating that the valve
Flow rates and pressure drops must be actuator is ready for operation and the `beyond
within the limits given in Section 9 of this neutral zone’ (∆∇) light will be on.
manual. Operation outside of these limits
is undesirable and could cause damage. EEV sensors (if fitted): Check that the electronic
Pressure drop should not be used to expansion valve sensor -BS1 is coated with heat
determine flow rate. conductive compound (013-00890-000) and is
firmly to the bottom of the sensor pocket. Sensor
Flow switch: Verify a chilled water flow switch is -BS2, located on the suction line, should also be
correctly fitted in the customer’s pipework on the coated in the heat conductive compound and
cooler outlet, and wired into the control panel logic should be securely strapped to the suction pipe.
section Opto-isolator board terminals 10 and 13
using screened cable. Programmed options: Verify that the options
factory programmed into the Microprocessor
Temperature sensor(s): Ensure the leaving water Control Centre are in accordance with the
temperature sensor is coated with heat conductive customers order requirements by pressing the
compound (part no. 013-00890-000) and is `Options’ key on the keypad and reading the
inserted in the bottom of the water outlet sensor settings from the display. Refer also to the
pocket of the cooler. This sensor also acts as the Microprocessor Based Control System Manual for
freeze protection thermostat sensor and must notes and explanation of messages.
always be in the water OUTLET sensor pocket.
5- 4 035L02374-GB2 (05/02)
Programmed settings: Ensure the system cut-out 5.2 First Time Start-up
and operational settings are in accordance with the
instructions given in the Microprocessor Based During the commissioning period there
Control System Manual and with operational should be sufficient heat load to run the
requirements by pressing the ‘Program’ key. The unit under stable full load operation to
chilled liquid temperature control settings need to enable the unit controls, and system
be set according to the unit model and required operation to be set up correctly and a
operating conditions. The following tables give commissioning log taken. Read the
suggested settings: following section in conjunction with the
Microprocessor Based Control System
LCHM Units LCHHM Units Manual, then proceed step by step as
Water / Glycol Range follows:
4 6 8 4 6 8
through Cooler / °C
Rate Sensitivity / °C/min 3 4 4 2 3 4
Interlocks: Verify that water is flowing through the
Control Range / °C 2.5 3.7 4.4 1.3 1.9 2.5
cooler and on WL units through the condenser(s)
Rate Control Temperature / °C 5 5
(unless the unit chilled liquid pump and condenser
Anti-recycle Timer / s 300 300
liquid pump start control is being used, in which
case just ensure the pump supplies are on).
Additional settings for units operating on glycol with Ensure that any remote run interlocks are in the run
a cooler leaving temperature below 4.5°C: position and that the run schedule requires the unit
to run or is overridden.
Glycol leaving
-10 -7.5 -5 -2.5 0 2.5
temperature / °C System switches: Place the ‘Sys 1’ and ‘Sys 2’
Leaving liquid
-14 -11.5 -9 -6.5 -4 -1.5 switches on the microprocessor board to the ON
temp. cut-out / °C
position - see operating sequence in the
Suction pressure cut-out / barg
R22 1.52 1.79 2.07 2.34 2.62 2.97
Microprocessor Control Centre Manual.
R407C 1.56 1.84 2.14 2.43 2.73 3.09
R134a 0.42 0.58 0.73 0.9 1.1 1.32 Start-up: Remove the locking device from the unit
switch which prevents unauthorised starting of the
unit before commissioning. Press the ‘Status’ key,
Date & time: Programme the date and time by first then turn the unit switch to the "1" position to start
ensuring that the CLK jumper J18 on the the unit (there may be a few seconds delay before
microprocessor board is in the ON position (top two the first compressor starts because of the
pins). Then press the ‘Clock Set Time’ key and set anti-recycle timer). Be ready when each
the date and time (see Microprocessor Based compressor starts to switch the unit off
Control System Manual). immediately if any unusual noises or other adverse
conditions develop. Also refer to the Micro Based
Start/Stop schedule: Programme the daily and Control System Manual for the normal operating
h ol id ay s t ar t / sto p b y p re ssi n g th e ‘Set sequence of the unit from start-up.
Schedule/Holiday’ key (see Microprocessor Based
Control System Manual). Oil pressure: When a compressor starts, press
the relevant ‘System Pressures’ key and verify that
Set-point and Remote offset: Set the required oil differential pressure is developed immediately.
leaving chilled liquid temperature set-point and If oil pressure does not develop the automatic
control range (see table above for recommended controls will shut down the compressor (see the
control ranges). If remote temperature reset Micro Based Control System Manual for the flow
(offset) is to be used, the maximum reset must be chart of the automatic oil pressure safety system).
programmed by pressing the ‘Remote Reset Under no circumstances should a restart attempt
Temp’. key (see Microprocessor Based Control be made on a compressor which does not develop
System Manual). oil pressure immediately. Switch the unit switch to
the "0" position (OFF).
035L02374-GB2 (05/02) 5- 5
Refrigerant flow: When a compressor starts a Electronic expansion valve adjustment (if
flow of liquid refrigerant will be seen in the liquid line fitted): Electronic expansion valves, when fitted,
sight glass. After several minutes operation, and are set for 9°C difference between the -BS2 and
providing a full charge of refrigerant is in the -BS1 sensors during preparatio n f o r
system, the bubbles will disappear and be replaced commissioning and should be adjusted to their
by a solid column of liquid. running setting only when steady operation has
been established. During pull down the `TQ Power’
General operation: Check the system operating light will pulse rapidly and the `beyond neutral
parameters are normal by selecting the various zone’ (∆∇) light will be on. When steady operation
readouts of pressure, temperature, etc. is reached the ∆∇ light will go out and the `within
neutral zone’ (SP) light will illuminate indicating
Superheat: Check the compressor suction that the difference between -BS2 and -BS1 is
superheat value only when pull down is complete within 1°C of the setting.
and steady full load operation has been
established. It is also important that there are no The actual superheat value at the compressor will
bubbles showing in the liquid line sight glass. still be quite high and the expansion valve
Suction line temperature should be measured on controller setting should be reduced 1°C at a time,
the copper line about 150 mm before the normally to a value of 6°C, until the correct value of
compressor service valve. Suction pressure measured superheat is achieved. The valve
should be measured at the compressor service should be allowed to stabilise for at least 5 minutes
valve with a suitably calibrated gauge. Suction between adjustments before rechecking the value
superheat at the compressor should be between of superheat.
5°C and 6°C for R22 and R134a, and between 4°C
and 5°C relative to the `dew’ temperature for Subcooling: Check the amount of subcooling
R407C. Discharge line temperature should not leaving the condenser coils only when pull down is
exceed 80°C during normal operation. complete and steady full load operation has been
established. It is also important that all fans are
Thermal expansion valve adjustment: Thermal running, giving full airflow across the condenser
expansion valves are factory set and should not coils. Liquid line temperature should be measured
need adjustment. If the superheat is out of range, on the copper line between the liquid line service
however, the expansion valve adjusting screw valve and the filter/drier. Liquid pressure should be
should be adjusted no more than 1 turn at a time measured at the liquid line service valve with a
(`in’ to increase superheat, `out’ to decrease suitably calibrated gauge. Liquid subcooling
superheat), allowing at least 10 minutes for the should be between 4°C and 10°C for R22 and
valve to stabilise before rechecking the value of R134a, and between 4°C and 8°C relative to the
superheat. ‘bubble’ temperature for R407C. If necessary, add
or remove refrigerant to obtain the correct level of
subcooling. Do not overcharge the unit.
5- 6 035L02374-GB2 (05/02)
6.6 Shutdown
The LCHM and LCHHM range of liquid chillers Operating conditions: read the operating
have been designed to operate continuously pressures and temperatures at the control panel
provided they are regularly maintained and using the display keys and check that these are
operated within the limitations given in this manual. within the operating limitations given this manual.
Each unit should be included in a routine schedule
of daily m a i n te n a n ce ch e cks by the Compressor oil level: Check the compressor oil
operator/customer, backed up by regular service level after the compressor has been operating on
inspection and maintenance visits by a suitably "FULL LOAD" for approximately 15 minutes. The
qualified Service Engineer. maximum acceptable operating oil level is the
middle of the top sight glass and the minimum
It is entirely the responsibility of the owner to acceptable operating oil level is the middle of the
prov ide f or th e se re g u l a r ma i n t enance bottom sight glass. When the compressor is
requirements and/or enter into a maintenance operating for long periods at "PART LOAD" the
agreement with York International service level may fall as far as the middle of the bottom
organisation to protect the operation of the unit. If sight glass but should not fall below this level.
damage or a system failure occurs due to improper
maintenance during the warranty period, York shall Do not overfill the PC compressor with oil
not be liable for costs incurred to return the unit to as this could cause damage to the
satisfactory condition. compressor.
The Safety Section of this manual Maximum Acceptable Operating Oil Level
should be read carefully before
at t em p ti n g any m a i n tenance
operations on the unit. This section
should be read in conjunction with the
Micro Based Control System Manual.
The maintenance operations detailed in the following table should be carried out on a regular basis by a
suitably qualified Service Engineer. It should be noted that the interval necessary between each `minor’
and `major’ service can vary depending on, for instance, application, site conditions and expected
operating schedule. Normally a `minor’ service should be carried out every three to six months and a
`major’ service once a year. It is recommended, however, that York Service is contacted for
recommendations for individual sites.
Standard Units
MAJOR SERVICE
SERVICE SCHEDULE MINOR SERVICE
All items under Minor Service plus:
Unit general: Check thermal insulation Check main structure
Check vibration isolators Check paint-work
Refrigerant systems general: Check relief valves Change filter/drier cores
Check fusible plugs Check solenoid valves
Check for pipework damage
Check for leaks
Check moisture indicator
Check suction superheat
Check liquid subcooling
Compressors: Check oil level Check big ends
Check oil pressure Check sump for white metal
Check unloader operation Check suction valves and springs
Check crankcase heater Check discharge valves and springs
Check condition of oil Check cylinder sleeves
Check suction strainer
Check oil filter
Check pistons and rings
Change compressor oil
Evaporator: Check water flow Check water pH / glycol strength
Check water pressure drop
AL air cooled condensers: Check for airflow obstructions Brush fins
Check fins Check fan motor bearings
Check fans and fan guards
Power & Control system general: Check panel condition Check all connections
Check mains and control wiring Check compressor contactors
Check sensor locations Check sensor / transducer calibration
Check mechanical HP cut-outs Check motor protectors
Check emergency stop Check contactor contacts
Check residual current devices
Microprocessor controls: Check fault history Check ambient cut-out function
Check program settings Check LTL cut-out function
Check HP / LP cut-out functions Check low oil pressure function
Check pump-down function
Check load / unload function
There is no corrosion on the refrigerant side therefore in-service inspection on the refrigerant side is not
necessary. For the water side, if the water used is treated in accordance with Section 4.5, in-service
inspection is not necessary. In the design of the vessels used in the unit, a 1 mmcorrosion allowance has
been used to consider slight corrosion on the water side. This allowance is sufficient to cover the lifetime
of the unit.
York International believes that periodic in service proof testing (e.g.; hydro tests) is not required.
However, York International recognises that national regulations may require such testing to be
conducted.
035L02374-GB2 (05/02) 8- 1
8 TROUBLE SHOOTING
No supply to -T3. Check emergency stop switch fuses -F1 and -F4 (when
fitted), -F13 (LCHM), -F1 (LCHHM) and -F4.
No 24 V ac supply to power board. Check wiring from -T3 to power board and fuse -F3.
No +12 V output from power board. Replace power board or isolate excessive load on the
board.
NO RUN PERM displayed No liquid flow through the cooler. Ensure that liquid pumps are running, valves are correctly
set and flow is established.
Flow switch contacts are not made. Check the flow switch is functional and is installed as per
the manufacturers instructions.
Remote cycling device open. Check cycling devices connected to terminals 11 & 14
(SYS 1) and 12 & 15 (SYS 2) on the opto interface board
are closed.
OIL TEMP INHIBIT displayed Oil temperature has not reached Use the oil temperature display key to confirm that the oil
working temperature following temperature is slowly rising. The warning message should
power-up. clear when the oil temperature has reached the correct
working temperature.
Compressor crankcase heater not Check the operation of the heater. Measure the current
working. drawn by the heater (should be 1A).
Unit is not unloading. Check the electrical supply to the unloader valve
solenoids.
Check the compressor unloads correctly.
Excessive refrigerant charge. Check for signs of air in the refrigerant system(s).
Check sub-cooling is correct.
Too much refrigerant in the oil. Check crankcase heater operation and output (current
should be in excess of 1 amp).
Check operation of expansion valve for liquid flooding
(especially during unloading steps).
Measured pressure incorrect. Check suction pressure transducer calibration and wiring.
SYS # C U R R EN T/ M P / H P X Compressor current too high or too Check compressor mains supply, fuses, contactors and
displayed low. wiring. Check mains supply voltage is within tolerance.
Measured current is incorrect. Check for defective current transformer (resistance should
be between 55 and 60 Ohms).
Check calibration resistor is correctly fitted.
Leak on low pressure side of system. Check low pressure side for air/liquid leaks.
Measured pressure incorrect. Check suction pressure transducer calibration and wiring.
SYS # CURR LIMITING displayed High compressor motor current has Check liquid temperature is within operating limits. Check if
activated unloading. ambient air temperature is above operating limits.
See also SYS # CURRENT/MP/HPX
(See Section 5 for Valve Adjustment) Measurements should be made on controller base
with the controller removed:
Electronic Expansion Valve and Controller
base connections ■ Supply voltage should measure 24 Vac + 10%
across terminals 1 and 2.
Voltage supply too low. Temporarily set S2-S1 knob on controller to 18°C,
check TQ power lamp lights up constantly, then
check supply at terminals 77 & 78 on actuator is 24
Vac +/- 10%.
Valve capacity Sensors swapped over. Check sensors are wired correctly.
low - actuator
cold Broken or short circuited sensor cable or Check sensors are located correctly: -BS1 firmly in
sensor out of calibration / out of position. bottom of cooler pocket and -BS2 strapped on
suction line.
Defective NTC resistor in valve actuator. Check NTC resistance from controller base.
Defective actuator heater element. Check heater resistance from controller base.
V a lve does Defective NTC resistor circuit. Check NTC resistance from controller base.
not close
Defective controller / incorrect set-up. Remove controller from base and check if valve
now closes.
Broken or short circuited sensor cable or Check sensor resistance at controller base.
sensor out of calibration / out of position. Check sensors are located correctly: -BS1 firmly in
bottom of cooler pocket and -BS2 strapped on
suction line.
035L02374-GB2 (05/02) 9- 1
9 TECHNICAL DATA
Condenser Water Pressure Drops (A) Condenser Water Pressure Drops (B)
CONDENSER WATER PRESSURE DROP kPa
Heat Recovery Condenser (HR) 2-Pass Heat Recovery Condenser (HR) 3-Pass
Water Pressure Drops Water Pressure Drops
CONDENSER WATER PRESSURE DROP kPa
CONDENSER WATER FLOW RATE l/s CONDENSER WATER PRESSURE kPa CONDENSER WATER FLOW RATE l/s
A Correction Factor
B Mean Glycol Temperature through Cooler
C Concentration W/W
035L02374-GB2 (05/02) 9- 3
General Limitations
Minimum Maximum
ELECTRICAL Mains ( 380 / 400 / 415 V - 3ph - 50 Hz Nominal ) : 342 V 440 V
SUPPLY Controls ( 220 / 230 / 240 V - 1ph - 50 Hz Nominal ) : 198 V 254 V
Chilled Water Leaving Temperature : R22 & R134a models : 4.0 °C 10 °C
R 407C models : 6.0 °C 10 °C
Chilled Glycol Leaving Temperature : R22 & R134a models : - 6 °C 10 °C
R 407C models : - 2 °C 10 °C
WATER / Chilled Liquid Temperature Range through Cooler : 3.3 °C 8 °C
GLYCOL Standard Condenser R22 models : 30 °C 41 °C
SYSTEMS Liquid Leaving Temperaure : R134a models : 30 °C 55 °C
R407C models : 30 °C 35 °C
High Pressure Condenser and Heat Recovery R22 models : 30 °C 52 °C*
Condenser Liquid Leaving Temperature : R134a models : 30 °C 55 °C*
R407C models : 30 °C 49 °C*
Evaporator & Condenser Water / Glycol Pressure at Unit : - 10 barg
High Pressure Side Design Pressure : WL Units : - 20.7 barg
WL-HR,WL-HP,AL,ALR Units : - 27.6 barg
REFRIGERANT Operating Discharge Pressure (AL Units): R22 models : 13.0 barg 24.1 barg
SYSTEM(S) R134a models : 8.0 barg 17.9 barg
R407C models : 13.0 barg 24.1 barg
Low Pressure Side Design Pressure : All models : - 20.7 barg
AIR TEMPERATURE SURROUNDING UNIT 4.4 °C 46 °C
* In excess of 49 °C for R22 units, 52 °C for R134a units and 46 °C for R407C units the flow rate must be guaranteed
steady within +/-10% at 5.5 °C range to avoid nuisance HP cutout trips.
Compressor Limitations
Minimum Maximum
Compression Ratio : - 9.5 : 1
Discharge Pressure : - 27.9 barg
Suction Pressure (operating) : - 8.5 barg
Differential Pressure : - 22.5 barg
Oil Pressure (above suction pressure) : 1.4 bar ** -
Oil Temperature (at oil pump suction) : - 70 °C
Suction Gas Superheat : 2.8 °C -
Discharge Gas Temperature : - 135 °C
** 1.4 bar provides bearing protection but is insufficient to operate oil pressure actuated unloading
system on PC compressors which may require up to 4.2 bar.
9- 4 035L02374-GB2 (05/02)
0.28
GLYCOL FACTOR (l/s) °C / kW AT
RECOMMENDED CONCENTRATION
0.27
CONCENTRATION BY WEIGHT %
CONCENTRATION BY WEIGHT %
RECOMMENDED
CONCENTRATION
0.25
RECOMMENDED
CONCENTRATION 0.24
0.23
FREEZING
TEMPERATURE
0.26
CONCENTRATION BY WEIGHT %
CONCENTRATION
CONCENTRATION BY WEIGHT %
0.23
RECOMMENDED
CONCENTRATION
FREEZING
TEMPERATURE
Pressure drop correction factors for Pressure drop correction factors for
Ethylene glycol solutions Propylene glycol solutions
1.50
CORRECTION FACTOR
% CONCENTRATION
CORRECTION FACTOR
% CONCENTRATION
Correction Factors
Ethylene Glycol Propylene Glycol
% By Weight
Capacity Factor Comp. Input Factor Capacity Factor Comp. Input Factor
10 1.045 1.020 1.070 1.025
20 1.020 1.010 1.040 1.015
30 1.000 1.000 1.000 1.000
40 0.970 0.990 0.950 0.985
50 0.940 0.980 0.900 0.970
Sound levels are for fully loaded unit. SPL values are adjacent to compressors
(SWL values are based on measurements to ISO 3744 or ISO 3746)
AL-R operating weight & charge are based on receiver tank filled to 10% of pump down capacity.
Pump down capacity is based on 80% of receiver volume.
035L02374-GB2 (05/02) 9- 7
Sound levels are for fully loaded unit. SPL values are adjacent to compressors
(SWL values are based on measurements to ISO 3744 or ISO 3746)
AL-R operating weight & charge are based on receiver tank filled to 10% of pump down capacity.
Pump down capacity is based on 80% of receiver volume.
9- 8 035L02374-GB2 (05/02)
Sound levels are for fully loaded unit. SPL values are adjacent to compressors
(SWL values are based on measurements to ISO 3744 or ISO 3746)
AL-R operating weight & charge are based on receiver tank filled to 10% of pump down capacity.
Pump down capacity is based on 80% of receiver volume.
035L02374-GB2 (05/02) 9- 9
Sound levels are for fully loaded unit. SPL values are adjacent to compressors
(SWL values are based on measurements to ISO 3744 or ISO 3746)
AL-R operating weight & charge are based on receiver tank filled to 10% of pump down capacity.
Pump down capacity is based on 80% of receiver volume.
9-10 035L02374-GB2 (05/02)
Notes:
1 Fuse sizes given are for the maximum rating permitted. Lower rated fuses can be used based on load and
inrush values under actual installation and operational conditions.
2 Compressor models are named as follows:
PC (compressor type) X (No. of cylinders) X (4=long stroke, 3=short stroke) X (No. of unloading pairs of cylinders) -X (motor size code)
3 Nominal rating conditions are:
WL units 6.7°C chilled water leaving temperature, 35°C condenser water leaving temperature
WL-HR units 6.7°C chilled water leaving temperature, 45°C condenser water leaving temperature
AL and AL-R units 6.7°C chilled water leaving temperature, 50°C saturation temperature at compressor discharge
4 Maximum rating conditions are:
R22: WL units 10°C chilled water leavig temperature, 40°C condenser water leaving temperature
WL-HP and WL-HR units 10°C chilled water leavig temperature, 52°C condenser water leaving temperature
AL model 60 8°C chilled water leavig temperature, 60°C saturation temperature at compressor discharge
Other AL and AL-R units 10°C chilled water leavig temperature, 60°C saturation temperature at compressor discharge
5 When selecting cable sizes for LCHHM units fitted with the common input supply option, the sum of the current values
for both compressors should be considered.
035L02374-GB2 (05/02) 9-11
Notes:
1 Fuse sizes given are for the maximum rating permitted. Lower rated fuses can be used based on load and
inrush values under actual installation and operational conditions.
2 Compressor models are named as follows:
PC (compressor type) X (No. of cylinders) X (4=long stroke, 3=short stroke) X (No. of unloading pairs of cylinders) -X (motor size code)
3 Nominal rating conditions are:
WL units 6.7°C chilled water leaving temperature, 35°C condenser water leaving temperature
WL-HR units 6.7°C chilled water leaving temperature, 45°C condenser water leaving temperature
AL and AL-R units 6.7°C chilled water leaving temperature, 50°C saturation temperature at compressor discharge
4 Maximum rating conditions are:
R134a: WL and WL-HR units 10°C chilled water leavig temperature, 55°C condenser water leaving temperature
AL and AL-R units 10°C chilled water leavig temperature, 60°C saturation temperature at compressor discharge
5 When selecting cable sizes for LCHHM units fitted with the common input supply option, the sum of the current values
for both compressors should be considered.
9-12 035L02374-GB2 (05/02)
Notes:
1 Fuse sizes given are for the maximum rating permitted. Lower rated fuses can be used based on load and
inrush values under actual installation and operational conditions.
2 Compressor models are named as follows:
PC (compressor type) X (No. of cylinders) X (4=long stroke, 3=short stroke) X (No. of unloading pairs of cylinders) -X (motor size code)
3 Nominal rating conditions are:
WL units 6.7°C chilled water leaving temperature, 35°C condenser water leaving temperature
WL-HR units 6.7°C chilled water leaving temperature, 45°C condenser water leaving temperature
AL and AL-R units 6.7°C chilled water leaving temperature, 50°C saturation temperature at compressor discharge
4 Maximum rating conditions are:
R407C: WL units 10°C chilled water leavig temperature, 35°C condenser water leaving temperature
WL-HP and WL-HR units 10°C chilled water leavig temperature, 49°C condenser water leaving temperature
AL and AL-R units 10°C chilled water leavig temperature, 55°C saturation temperature at compressor discharge
5 When selecting cable sizes for LCHHM units fitted with the common input supply option, the sum of the current values
for both compressors should be considered.
035L02374-GB2 (05/02) 9-13
DSV
PS
RV 1/2” FL. ZCMTB
RV 1/2” FL. CP
SSV
COMP IS LSV
LIQUID RCF
CONDENSER
YLLSV WATER
INLET Y
CLR CDR
CDR
LIQUID
TEV/YEEV
WL A B C D E F G G1 H J K L1 L2 X Y
55 2725 860 1740 320 32 195 720 720 940 508 275 315 235 4" N.B.¹ 2½" N.B.²
60 2600 860 1740 320 32 195 720 720 940 508 275 315 235 4" N.B.¹ 2½" N.B.²
65 2725 885 1740 320 32 195 720 720 940 508 275 315 235 4" N.B.¹ 3" N.B.²
70 2610 860 1740 320 32 195 720 720 940 508 275 315 235 6" N.B.¹ 3" N.B.²
75 2725 885 1740 320 32 195 725 725 940 508 275 315 235 4" N.B.¹ 3" N.B.²
85 2640 875 1785 375 32 200 605 710 890 470 300 340 260 6" N.B.¹ 3" N.B.²
100 2640 875 1785 375 32 200 605 710 890 470 300 300 300 6" N.B.¹ 4" N.B.³
115 2640 875 1785 375 32 200 605 710 890 470 300 300 300 6" N.B.¹ 4" N.B.³
Connections: ¹ Victaulic, ² Threaded female taper to BSPT / ISO R7 / DIN 2999, ³ Flanged with face dimensions to BS 4504 PN10 / ISO 7005 / DIN 2502
035L02374-GB2 (05/02) 9-15
DSV
LSV
RCF
COMP IS HEAT
YLLSV RECOVERY
OR MAIN
CONDENSER
WATER
CLR CDR CONNECTION
Y
TEV/YEEV
WL-HR A B C D E F G G1 H J K L M N X Y
55 2995 920 1825 340 32 170 720 720 940 530 350 275 205 75 4" N.B.¹ 2½" N.B.²
60 2995 910 1845 340 32 195 720 720 940 560 375 275 205 75 4" N.B.¹ 2½" N.B.²
65 3045 1000 1850 370 32 170 720 720 940 560 375 265 220 75 4" N.B.¹ 3" N.B.²
70 3045 986 1845 370 32 195 720 720 940 560 375 265 220 75 6" N.B.¹ 3" N.B.²
75 3045 1000 1850 370 32 170 725 725 940 560 375 265 220 75 4" N.B.¹ 3" N.B.²
85 3045 990 1855 410 32 195 605 710 890 545 375 265 220 75 6" N.B.¹ 3" N.B.²
100 3065 1020 1880 375 32 195 605 710 890 545 375 260 230 75 6" N.B.¹ 4" N.B.³
115 3065 1020 1880 375 32 195 605 710 890 545 375 260 230 75 6" N.B.¹ 4" N.B.³
Connections: ¹ Victaulic, ² Threaded female taper to BSPT / ISO R7 / DIN 2999, ³ Flanged with face dimensions to BS 4504 PN10 / ISO 7005 / DIN 2502
WL-HR P R S T Y2
55 102 102 275 64 2½" N.B.¹
60 102 102 256 64 2½" N.B.¹
65 114 114 262 64 3" N.B.¹
70 114 114 262 64 3" N.B.¹
75 114 114 262 64 3" N.B.¹
85 114 114 262 64 3" N.B.¹
100 127 137 239 70 3" N.B.¹
115 127 137 239 70 3" N.B.¹
Connections: ¹ Victaulic
9-16 035L02374-GB2 (05/02)
LCHM 55 - 115 AL
DSV
DSV PS
ZCMTB
CP
RV 1/2” FL. SSV
LSV
RCF
COMP IS YLLSV
CLR
TEV/YEEV
AL A B C D E F G G1 H J K L1 L2 X
55 2700 860 1740 320 32 190 720 720 940 510 275 2 5/8" OD ² 1 3/8 OD ² 4" N.B.¹
60 2600 860 1740 320 32 190 720 720 940 510 275 2 5/8" OD ² 1 3/8 OD ² 4" N.B.¹
65 2700 885 1740 320 32 190 720 720 940 510 275 3 1/8" OD ² 1 5/8 OD ² 4" N.B.¹
70 2600 860 1740 320 32 190 720 720 940 510 275 2 5/8" OD ² 1 3/8 OD ² 4" N.B.¹
75 2700 885 1740 320 32 190 590 725 940 510 275 3 1/8" OD ² 1 5/8 OD ² 4" N.B.¹
85 2640 875 1785 375 32 200 605 710 890 470 300 2 5/8" OD ² 1 5/8 OD ² 6" N.B.¹
100 2640 875 1785 375 32 200 605 710 890 470 3003 3 1/8" OD ² 1 5/8 OD ² 6" N.B.¹
115 2640 875 1785 375 32 200 605 710 890 470 3003 3 1/8" OD ² 1 5/8 OD ² 6" N.B.¹
Connections: ¹ Victaulic, ² Female for Brazing
035L02374-GB2 (05/02) 9-17
DSV DSV
PS
RV 1/2” FL.
ZCMTB CP
RV 1/2” FL. SSV
LSV
COMP IS RCF
LR YLLSV
LR
CLR
TEV/YEEV
Pump Down
AL-R A B C D E F G G1 H J K L1 L2 X Capacity
60 2700 860 1740 320 32 190 720 720 940 460 275 2 5/8" OD ² 2 1/8" OD ² 4" N.B.¹ 92 kg
70 2700 860 1740 320 32 190 720 720 940 460 275 2 5/8" OD ² 2 5/8" OD ² 4" N.B.¹ 132 kg
85 2715 880 1785 375 32 200 605 720 890 470 300 2 5/8" OD ² 2 5/8" OD ² 6" N.B.¹ 132 kg
100 2715 880 1785 375 32 200 605 710 890 470 300 3 1/8" OD ² 3 1/8" OD ² 6" N.B.¹ 162 kg
115 2715 880 1785 375 32 200 605 710 890 470 300 3 1/8" OD ² 3 1/8" OD ² 6" N.B.¹ 162 kg
Connections: ¹ Victaulic, ² Female for Brazing
9-18 035L02374-GB2 (05/02)
1-DSV
1-ZCMTB
Ps1 Ps2
CP
2-ZCMTB
RV 1/2” FL. 1-YLLSV
2-SSV
1-SSV
COMP1 IS
1-LSV RCF
COMP2
1-RCF
LSV
CDR 2-YLLSV
CLR
WATER
INLET R
WL A B C D E J K L P R
90 2890 1265 855 925 1500 8 1215 1860 6" N.B.¹ 4" N.B.²
110 2890 1265 855 925 1500 8 1215 1860 6" N.B.¹ 4" N.B.²
Connections: ¹ Victaulic, ² Flanged with face dimensions to BS 4504 PN10 / ISO 7005 / DIN 2502
When Door Interlocked Isolator Option fitted, Add 30 mm to dimension B
035L02374-GB2 (05/02) 9-19
1-ZCMTB
Ps1 Ps2
CP
2-ZCMTB
1-YLLSV
1-SSV 2-SSV
1-LSV COMP1 IS
RV 1/2” FL. 1-RCF COMP2 2-YLLSV
WATER 2-LSV
OUTLET 2-RCF
R
CLR CDR RV 1/2” FL.
(R22/407c WL-HP 5/8” FL.)
YEEV
WL A B C D E E1 F J K L M N P R
130 2905 1275 855 925 1525 1380 65 1380 1950 260 230 6" N.B.¹ 4" N.B.¹
140 2905 1195 855 925 1525 1380 95 1380 1950 260 230 6" N.B.¹ 4" N.B.¹
150 2905 1275 825 815 1525 1380 90 1380 1950 260 230 8" N.B.¹ 4" N.B.¹
170 2905 1240 825 815 1525 1380 120 1380 1950 260 230 8" N.B.¹ 4" N.B.¹
200 3135 1240 825 1170 1630 1390 120 1390 1950 255 240 8" N.B.¹ 6" N.B.¹
230 3240 1240 825 1270 1630 1390 120 1390 1950 255 240 8" N.B.¹ 6" N.B.¹
Connections: ¹ Victaulic
When Door Interlocked Isolator Option fitted, Add 30 mm to dimension B
9-20 035L02374-GB2 (05/02)
RV 5/8” FL.
1-DSV
1-SSV
Ps1 Ps2
1-ZCMTB 2-ZCMTB
1-YLLSV CP
1-SSV
RV 1/2” FL. 1-LSV
COMP1 IS COMP2
2-SSV
1-RCF 2-LSV
2-RCF
2-YLLSV
TEV/YEEV
WL-HR P R S T Y2
130 115 115 265 65 3" N.B.¹
140 115 115 265 65 3" N.B.¹
150 115 115 265 65 3" N.B.¹
170 115 155 265 65 3" N.B.¹
200 260 115 115 114 260 65 70 3" N.B.¹
230 130 135 260 70 3" N.B.¹
Connections: ¹ Victaulic
035L02374-GB2 (05/02) 9-21
LCHHM 90 - 230 AL
1-DSV
1-DSV 2-DSV
1-ZCMTB
1-YLLSV Ps1 CP Ps2 2-ZCMTB
1-SSV
RV 1/2” FL. 1-LSV
COMP1 IS 2-SSV
1-RCF COMP2
2-LSV
2-RCF
2-YLLSV
CLR 1-LSV
TEV/
YEEV
AL A B C D E F J M P R U V1 V2 W X Y
90 2890 1265 855 925 1500 1185 95 1 3/8 OD ² 6" N.B.¹ 1 3/8 OD ² 1410 160 160 670 2 5/8" OD ² 2 5/8" OD ²
110 2890 1265 855 925 1500 1185 1185 1 3/8 OD ² 6" N.B.¹ 1 3/8 OD ² 1410 160 160 670 2 5/8" OD ² 2 5/8" OD ²
130 2740 1275 855 925 1500 1180 180 1 5/8 OD ² 6" N.B.¹ 1 5/8 OD ² 1430 155 155 675 3 1/8" OD ² 3 1/8" OD ²
140 2940 1195 855 925 1430 1255 1255 1 3/8 OD ² 6" N.B.¹ 1 3/8 OD ² 1410 190 120 675 2 5/8" OD ² 2 5/8" OD ²
150 2890 1275 825 815 1500 1100 1100 1 5/8 OD ² 8" N.B.¹ 1 5/8 OD ² 1430 155 155 675 3 1/8" OD ² 3 1/8" OD ²
170 2680 1240 825 815 1525 1155 1155 1 3/8 OD ² 8" N.B.¹ 1 3/8 OD ² 1410 155 165 675 2 5/8" OD ² 2 5/8" OD ²
200 3135 1240 825 1170 1670 1495 1495 1 5/8 OD ² 8" N.B.¹ 1 3/8 OD ² 1430/1410 150 160 675 3 1/8" OD ² 3 1/8" OD ²
230 3240 1240 825 1270 1670 1600 1600 1 5/8 OD ² 8" N.B.¹ 1 5/8 OD ² 1430 150 150 675 3 1/8" OD ² 3 1/8" OD ²
Connections: ¹ Victaulic, ² Female for Brazing
When Door Interlocked Isolator Option fitted, Add 30 mm to dimension B
9-22 035L02374-GB2 (05/02)
1-DSV 1-YLLSV
1-DSV 2-DSV
RV 1/2” FL.
(130,150,200 & 23)
1-ZCMTB 2-ZCMTB
COMP1 CP
Ps1 Ps2 2
RV 1/2” FL.
(130,150,200
RV 1/2” FL. & 23) 2-SSV
IS
1-SSV 2-LSV
1-LSV 2-RCF
1-RCF
LR 2-YLLSV
CLR 1-LSV
2-PV
1-PV
3/8” FL.
TEV/
YEEV
Pump Down
AL-R A B C D E F J M N P K U V1 V2 X Y
Capacity
140 2955 1120 855 925 1430 1255 95 1/2" 2 5/8" OD ² 6" N.B.¹ 275 1410 195 120 2 5/8" OD ² 2 5/8" OD ² 2 x 124 kg
170 2955 1120 825 814 1525 1155 120 1/2" 2 5/8" OD ² 8" N.B.¹ 275 1410 155 165 2 5/8" OD ² 2 5/8" OD ² 2 x 124 kg
200 3135 1120 825 1170 1670 1495 120 5/8" 3 1/8" OD ² 8" N.B.¹ 300 1430/1410 150 160 3 1/8" OD ² 2 5/8" OD ² 2 x 158 kg
230 3240 1120 825 1270 1670 1600 120 5/8" 3 1/8" OD ² 8" N.B.¹ 300 1430 150 150 3 1/8" OD ² 3 1/8" OD ² 2 x 158 kg
Connections: ¹ Victaulic, ² Female for Brazing
When Door Interlocked Isolator Option fitted, Add 30 mm to dimension B
Contact York for R134a Details
035L02374-GB2 (05/02) 9-23
WL Units
MICROPROCESSOR
CONTROL FUNCTIONS
DV DISPLAY VALVE
CHT CHILLED LIQUID
THEROMOSTAT
HPC HIGH PRESSUR CUTOUT
HPL HIGH PRESSURE LOAD
LIMITING
LPC LOW PRESSURE CUTOUT
DIF DIFFERENTIAL PRESSURE
CUTOUT
HTC HIGH TEMPERATURE CUTOUT
LTC LOW TEMPERATURE CUTOUT
LTI LOW DIFFERENTIAL
TEMPERATURE START INHIBIT
HCC HIGH CURRENT CUTOUT
LCC LOW CURRENT CUTOUT
-YLLSV LIQUID LINE SV
-YLISV LIQUID INJECTION SV
ECH
SYSTEM COMPONENTS
AL Units
MICROPROCESSOR
CONTROL FUNCTIONS
DV DISPLAY VALVE
CHT CHILLED LIQUID THEROMOSTAT
HPC HIGH PRESSUR CUTOUT
HPL HIGH PRESSURE LOAD LIMITING
LPC LOW PRESSURE CUTOUT
DIF DIFFERENTIAL PRESSURE CUTOUT
HTC HIGH TEMPERATURE CUTOUT
LTC LOW TEMPERATURE CUTOUT
LTI LOW DIFFERENTIAL
TEMPERATURE START INHIBIT
HCC HIGH CURRENT CUTOUT
LCC LOW CURRENT CUTOUT
-YLLSV LIQUID LINE SV
-YLISV LIQUID INJECTION SV
ECH
10 SPARE PARTS
All Models
Compressor Kit Part Number
4 Cylinder 398L00654-001
6 Cylinder 398L00654-002
8 Cylinder 398L00654-003
10-2 035L02374-GB2 (05/02)
Isolate the unit heat exchanger(s) from all external Only use lifting equipment of adequate
water systems and drain the heat exchanger capacity.
section(s) of the system. If no isolation valves are
installed it may be necessary to drain the complete
system(s).
After removal from position the unit parts may be
disposed of according to local laws and
regulations.
11-2 035L02374-GB2 (05/02)
YORK INTERNATIONAL
Subject to change without notice
Gardiners Lane South, Basildon, Essex SS14 3HE, England
ALL RIGHTS RESERVED