You are on page 1of 32

REVERSE CYCLE AIR TO

WATER HEAT PUMP - CHILLERS


INSTALLATION, COMMISSIONING,
OPERATION & MAINTENANCE
Provisional Release 035-16870-100 Rev.0 (01/12)

STY L E: A
REFRIG ERANT: R410 A
COOL ING CAPACITIES: 183 K W TO 426 K W
H EATING CAPACITIES: 187 K W TO 469 K W
035-16870-100 Rev. 0 I-i

TABLE OF CONTENTS

1 SUPPLIER INF ORMATION 4 INSTALLATION

1.1 Introduction 1.1 4.1 L ocation Req uirements 4.1

1.2 W arranty 1.1 4.2 L ocation Clearances 4.1

1.3 Safety 1.1 4.3 Compressor Shipping Bolts 4.2

1.4 Responsib ility for Safety 1.2 4.4 Installation of Vib ration Isolators 4.2

1.5 Ab out this Manual 1.2 4.5 Pipework Connection 4.2

1.6 Misuse of Eq uipment 1.2 4.6 W ater Treatment 4.3

1.7 Emergency Shutdown 1.3 4.7 Pipework Arrangement 4.3

1.8 Safety L ab els 1.3 4.8 Connection Types & Siz es 4.4

1.9 Material Safety Data 1.4 4.9 Refrigerant Relief Valve Piping 4.4

4.10 Ductwork Connection 4.4


2 PRODUCT DESCRIPTION
4.11 Electrical Connection 4.5
2.1 Introduction 2.1
4.12 Power W iring 4.5
2.2 Compressors 2.1
4.13 Volts Free Contacts 4.6
2.3 Refrigerant Circuits 2.1
4.14 Control Panel W iring 4.7
2.4 Refrigerant to W ater H eat Ex changer 2.2
4.15 System Inputs 4.7
2.5 Amb ient Coils 2.2
4.16 Connection Diagram 4.8
2.6 Power and Control Panels 2.2

2.7 ACCESSORIES AND OPTIONS 2.4 5 COMMISSIONING

2.8 Nomenclature 2.5 5.1 Preparation 5.1

2.9 Functional Description 2.6 5.2 First Time Start-up 5.3

3 TRANSPORTATION, HANDLING AND 6 UNIT OPERATION


STORAGE
6.1 G eneral Description 6.1
3.1 Delivery and Storage 3.1
6.2 Start-up 6.1
3.2 Inspection 3.1
6.3 Normal Running and Cycling 6.1
3.3 Moving the U nit 3.1
6.4 Shutdown 6.1
3.4 L ifting W eights 3.1

(01/12)
I-ii 035-16870-100 Rev. 0

7 MAINTENANCE 10 SPARE PARTS

7.1 G eneral Req uirements 7.1 10.1 Recommended Spares 10.1

7.2 Daily Maintenance 7.1 10.2 Recommended Compressor Oil 10.1

7.3 Scheduled Maintenance 7.2 10.3 Associated Drawings 10.1

7.4 Plate H eat Ex changer In-Service Inspection 7.2


11 DECOMMISSIONING. DISMANTLING AND
DISPOSAL
8 Tr o u b le Sh o o ting
11.1 G eneral 11.1
8.1 Competent Persons Troub le Shooting G uide 8.1

8.2 Sensor Calib ration Charts 8.3

9 TECHNICAL DATA

9.1 Flow Rate and Pressure Drop G raph 9.1

9.2 Operating L imitations 9.2

9.3 Physical Data 9.3

9.4 U nit Electrical Data 9.5

9.5 Compressor Data 9.6

9.6 Fan Electrical Data 9.6

9.7 Connection Data 9.6

9.8 Dimensions 9.7

9.9 W eight Distrib ution and Anti-Vib ration Data 9.14

9.10 Isolator Installation 9.16

9.11 Clearances 9.16

9.12 P & I Diagram 9.18

(01/12)
035-16870-100 Rev. 0 1- 1

1 SUPPLIER INF ORMATION For warranty purposes, the following conditions must b e
satisfied:
1.1 Intr o d u c tio n
The initial start of the unit must b e carried out b y trained
Y ORK Y L AE Tempo ™ heat pump-chillers are personnel from an Authorised Y ORK Service Centre.
manufactured to the highest design and construction
standards to ensure high performance, reliab ility and Only genuine Y ORK approved spare parts, oils and
adaptab ility to all types of air conditioning installations. refrigerants must b e used.

The units provide chilled and warm liq uid for all air All the scheduled maintenance operations detailed in
conditioning applications and are not suitab le for this manual must b e performed at the specified times b y
purposes other than those specified in this manual. suitab ly trained and q ualified personnel.

This manual contains all the information req uired for Failure to satisfy any of these conditions will
correct installation and commissioning of the unit, automatically void the warranty.
together with operating and maintenance instructions.
The manual should b e read thoroughly b efore 1.3 Sa fety
attempting to operate or service the unit.
Sta nd a r d s fo r Sa fety
All procedures detailed in the manual, including
installation, commissioning and maintenance task s Y L AE Tempo™ heat pump-chillers are designed and
must only b e performed b y suitab ly trained and q ualified b uilt within an EN ISO 9001 accredited design and
personnel. manufacturing organisation and, within the limits
specified in this manual, are in conformity with the
The manufacturer will not b e liab le for any injury or essential health and safety req uirements of the
d a m a g e c a u s e d b y i n c o r r e c t i n s t a l l a ti o n , following European U nion Directives:
commissioning, operation or maintenance resulting
from a failure to follow the procedures and instructions Machinery Directive (89/392/EEC)
detailed in the manual.
L ow Voltage Directive (73/23/EEC, EN 60204)
1.2 Wa r r a nty
EMC Directive (89/336/EEC)
J ohnson Controls warrants all eq uipment and materials
against defects in work manship and materials for Refrigeration eq uipment b uilt at Y ORK Sab adell
eighteen months from availab ility unless ex tended conforms to the applicab le and essential safety
warranty has b een agreed as part of the contract. req uirements of Pressure Eq uipment Directive
97/23/EC (PED) and b ear CE mark ing.
The warranty is limited to free replacement and shipping
of any faulty part, or sub -assemb ly that has failed due to F lu o r ina ted Gr eenh o u se Ga ses
poor q uality or manufacturing errors. All claims must b e
supported b y evidence that the failure has occurred n This eq uipment contains fluorinated greenhouse
within the warranty period, and that the unit has b een gases covered b y the K yoto Protocol.
operated within the designed parameters specified.
n The glob al warming potential of the refrigerant
All warranty claims must specify the unit model and (R410A) used in this unit is 1720 .
serial numb er. These details are printed on the unit
identification plate, fitted on the control panel. n The refrigerant q uantity is stated in the Physical
Data tab le in Section 9 of this document.
The unit warranty will b e void if any modification to the
unit is carried out without prior written approval from n The fluorinated greenhouse gases in this
J ohnson Controls. eq uipment may not b e vented to the atmosphere.

n This eq uipment should only b e serviced b y


q ualified technicians.

(01/12)
1- 2 035-16870-100 Rev. 0

1.4 Respo nsib ility fo r Sa fety 1.6 Misu se o f Eq u ipm ent

Every care has b een tak en in the design and Su ita b ility fo r Applic a tio n
manufacture of the units to ensure that they meet the
safety req uirements listed in the previous paragraph. The units provide chilled liq uid for all air conditioning
H owever, the individual operating or work ing on any applications and are not suitab le for purposes other than
machinery is primarily responsib le for: those specified in these instructions. Any use of the
eq uipment other than its intended use, or operation of
Personal safety, safety of other personnel, and the the eq uipment contrary to the relevant procedures may
machinery. result in injury to the operator, or damage to the
eq uipment.
Correct utilisation of the machinery in accordance with
the procedures detailed in the manuals. The unit must not b e operated outside the design limits
specified in this manual.
1.5 Ab o u t th is Ma nu a l
Str u c tu r a l Su ppo r t
The following symb ols are used in this document to alert
the reader to areas of potential haz ard. Structural support of the unit must b e provided as
indicated in these instructions. Failure to provide proper
A Wa r ning is g iv en in th is d o c u m ent to support may result in injury to the operator, or damage to
id entify a h a z a r d w h ic h c o u ld lea d to the eq uipment.
per so na l inju r y . Usu a lly a n instr u c tio n w ill
b e g iv en, to g eth er w ith a b r ief ex pla na tio n Mec h a nic a l Str eng th
a nd th e po ssib le r esu lt o f ig no r ing th e
instr u c tio n. The unit is not designed to withstand loads or stresses
from adjacent eq uipment, pipework or structures.
A Ca u tio n identifies a haz ard which could Additional components must not b e mounted on the
lead to damage to the machine, damage to unit. Any such ex traneous loads may cause structural
other eq uipment and/or environmental failure and may result in injury to the operator, or
pollution. U sually an instruction will b e given, damage to the eq uipment.
together with a b rief ex planation and the
possib le result of ignoring the instruction. Gener a l Ac c ess

A No t e is used to highlight additional There are a numb er of areas and features that may b e a
information which may b e helpful to you b ut haz ard and potentially cause injury when work ing with
where there are no special safety the unit unless suitab le safety precautions are tak en. It
implications. is important to ensure access to the unit is restricted to
suitab ly q ualified persons who are familiar with the
potential haz ards and precautions necessary for safe
The contents of this manual include suggested b est operation and maintenance of eq uipment containing
work ing practices and procedures. These are issued for high temperatures, pressures and voltages.
guidance only, they do not tak e precedence over the
ab ove stated individual responsib ility and/or local safety Pr essu r e Sy stem s
regulations.
The unit contains refrigerant vapour and liq uid under
This manual and any other document supplied with the pressure, release of which can b e a danger and cause
unit, are the property of Y ORK which reserves all rights. injury. The user should ensure that care is tak en during
They may not b e reproduced, in whole or in part, without installation, operation and maintenance to avoid
prior written authorisation from an Authorised J ohnson damage to the pressure system. No attempt should b e
Controls representative. made to gain access to the component parts of the
pressure system other than b y suitab ly trained and
q ualified personnel.

(01/12)
035-16870-100 Rev. 0 1- 3

Elec tr ic a l 1.7 Em er g enc y Sh u td o w n

The unit must b e earthed. No installation or In case of emergency the power panel is fitted with a
maintenance work should b e attempted on electrical non-fused disconnect switch. W hen operated, it
eq uipment without first switching off, isolating and disconnects the unit power supply which removes the
lock ing-off the power supply. W ork on live eq uipment electrical supply from the control system.
must only b e carried-out b y suitab ly trained and
q ualified personnel. No attempt should b e made to gain 1.8 Sa fety La b els
access to inside of the control panel, wiring or other
electrical enclosures during normal operation of the unit. The following lab els are fix ed to each unit to give
instruction, or to indicate potential haz ards which may
Ro ta ting Pa r ts ex ist.

Fan guards must b e fitted at all times and not removed W hite symb ol on b lue b ack ground
unless the main power supply has b een isolated. If F o r s a f e o p e r a t i o n , r e a d th e
ductwork is to b e fitted, req uiring the wire fan guards to Instructions first
b e removed, alternative safety measures must b e tak en
to protect against the risk of injury from rotating fans.

Sh a r p Ed g es Black symb ol on yellow b ack ground


W arning: This machine may start
The finning on the amb ient coils has sharp metal edges. automatically without prior warning
Reasonab le care should b e tak en when work ing in
contact with the coils to avoid the risk of minor ab rasions
and lacerations. The use of gloves is recommended. Black symb ol on yellow b ack ground
W arning: H ot surface
Refr ig er a nts a nd Oils

Refrigerants and oils used in the unit are generally


non-tox ic, non-flammab le and non-corrosive, and pose
no special safety haz ards. U se of gloves and safety Black symb ol on yellow b ack ground
glasses are, however, recommended when work ing on W arning: Safety relief valve may
the unit. Build up of refrigerant vapour, from a leak for discharge gas or liq uid without prior
ex ample, does pose a risk of asphyx iation in confined or warning
enclosed spaces and attention should b e given to good
ventilation. For more comprehensive information on Black symb ol on yellow b ack ground
safety precautions for use of refrigerants and oils, refer W arning: Isolate all electrical sources
to the Materials Safety Data tab les provided. of supply b efore opening or removing
the cover, as lethal voltages may ex ist
Hig h Tem per a tu r e a nd Pr essu r e Clea ning

H igh temperature and pressure cleaning methods (e.g. Black symb ol on yellow b ack ground
steam cleaning) should not b e used on any part of the G eneral attention symb ol
pressure system as this may cause operation of the
pressure relief device(s). Detergents and solvents that
may cause corrosion should also b e avoided.
Black symb ol on yellow b ack ground
Power factor correction fitted
W arning: On isolating the supply it
may tak e up to 60 seconds for the
capacitor voltage to fall b elow 60 volts

(01/12)
1- 4 035-16870-100 Rev. 0

1.9 Ma ter ia l Sa fety Da ta

The R410A refrigerant safety data and thermal and acoustic materials data given in the following section is
applicab le to all models.

Refr ig er a nt Sa fety Da ta R410 A:


COMPOSITION/INFORMATION ON ING REDIENTS
Components Material PENTAFL U OROETH ANE (H FC-125) DIFL U OROMETH ANE (H FC-32)
CAS Numb er 354-33-6 75-10-5
% 50 50
H AZ ARDS IDENTIFICATION
Potential H ealth Effects Inhalation of high concentrations of vapour is harmful and may cause heart irregularities,
unconsciousness, or death. Intentional misuse or delib erate inhalation may cause death
without warning. Vapour reduces ox ygen availab le for b reathing and is heavier than air. L iq uid
contact can cause frostb ite.
At flame temperatures, this material can decompose to hydrogen fluoride which can b e lethal
at much lower concentrations.
H uman H ealth Effects Overex posure to the vapours b y inhalation may include temporary nervous system depression
with anaesthetic effects such as diz z iness, headache, confusion, incoordination, and loss of
consciousness. H igher ex posures to the vapours may cause temporary alteration of the
heart's electrical activity with irregular pulse, palpitations, or inadeq uate circulation. G ross
overex posure may b e fatal. Sk in contact with the liq uid may cause frostb ite.
Individuals with preex isting diseases of the central nervous or cardiovascular system may
have increased susceptib ility to the tox icity of increased ex posures.
Carcinogenicity None of the components present in this material at concentrations eq ual to or greater than
Information 0.1% are listed b y IARC, NTP, OSH A or ACG IH as a carcinogen.
FIRST AID MEASU RES
Inhalation If inhaled, immediately remove to fresh air. K eep person calm.
If not b reathing, give artificial respiration. If b reathing is difficult, give ox ygen. Call a physician.
Sk in Contact Flush area with luk ewarm water. Do not use hot water. If frostb ite has occurred, call a
physician.
Eye Contact In case of contact, immediately flush eyes with plenty of water for at least 15 minutes. Call a
physician.
Ingestion Do not induce vomiting. G ive plenty of water in sips
Notes to Physicians TH IS MATERIAL MAY MAK E TH E H EART MORE SU SCEPTIBL E TO ARRH Y TH MIAS.
Catecholamines such as adrenaline, and other compounds having similar effects, should b e
reserved for emergencies and then used only with special caution.
FIRE FIG H TING MEASU RES
Flammab le Properties Flash Point : No flash point
Flammab le L imits in Air, % b y Volume:
L EL : None per ASTM E681
U EL : None per ASTM E681
Autoignition: Not determined

(01/12)
035-16870-100 Rev. 0 1- 5

Refr ig er a nt Sa fety Da ta R410 A:


Fire and Ex plosion Cylinders may rupture under fire conditions. Decomposition may occur.
H az ards Contact of welding or soldering torch flame with high concentrations of refrigerant can result in
visib le changes in the siz e and colour of torch flames. This flame effect will only occur in
concentrations of product well ab ove the recommended ex posure limit, therefore stop all work
and ventilate to disperse refrigerant vapours from the work area b efore using any open flames.
R-410A is not flammab le in air at temperatures up to 100 deg C (212 deg F) at atmospheric
pressure. H owever, mix tures of R-410A with high concentrations of air at elevated pressure
and/or temperature can b ecome comb ustib le in the presence of an ignition source. R-410A
can also b ecome comb ustib le in an ox ygen enriched environment (ox ygen concentrations
greater than that in air). W hether a mix ture containing R-410A and air, or R-410A in an ox ygen
enriched atmosphere b ecomes comb ustib le depends on the inter-relationship of 1) the
temperature 2) the pressure, and 3) the proportion of ox ygen in the mix ture. In general,
R-410A should not b e allowed to ex ist with air ab ove atmospheric pressure or at high
temperatures; or in an ox ygen enriched environment. For ex ample: R-410A should NOT b e
mix ed with air under pressure for leak testing or other purposes.
Ex tinguishing Media As appropriate for comb ustib les in area.
Fire Fighting Cool cylinder with water spray or fog. Self-contained b reathing apparatus (SCBA) is req uired if
Instructions cylinders rupture and contents are released under fire conditions. W ater runoff should b e
contained and neutraliz ed prior to release.
ACCIDENTAL REL EASE MEASU RES
Safeguards (Personnel) NOTE: Review FIRE FIG H TING MEASU RES and H ANDL ING (PERSONNEL )
sections b efore proceeding with clean-up. U se appropriate PERSONAL PROTECTIVE
EQ U IPMENT during clean-up.
Accidental Release Ventilate area, especially low or enclosed places where heavy vapours might collect.
Measures Ex tinguish open flames. U se self-contained b reathing apparatus (SCBA) for large spills or
releases. Eliminate electrical sources.
H ANDL ING AND STORAG E
H andling (Personnel) Avoid b reathing vapour. Avoid liq uid contact with eyes and sk in. U se with sufficient ventilation
to k eep employee ex posure b elow recommended limits. See Fire and Ex plosion Data section.
Storage Clean, dry area. Do not heat ab ove 52 deg C (125 deg F).
EX POSU RE CONTROL S/PERSONAL PROTECTION
Engineering Controls Avoid b reathing vapours. Avoid contact with sk in or eyes. U se with sufficient ventilation to
k eep employee ex posure b elow the recommended ex posure limit. L ocal ex haust should b e
used if large amounts are released. Mechanical ventilation should b e used in low or enclosed
places.
Personal Protective Impervious gloves should b e used to avoid prolonged or repeated ex posure. Chemical splash
Eq uipment goggles should b e availab le for use as needed to prevent eye contact. U nder normal
manufacturing conditions, no respiratory protection is req uired when using this product
provided ex posure is maintained at or b elow occupational limits. Self-contained b reathing
apparatus (SCBA) is req uired if a large release occurs.
Ex posure G uidelines Applicab le Ex posure L imits
PENTAFL U OROETH ANE (H FC-125)
PEL (OSH A) : None Estab lished
TL V (ACG IH ) : None Estab lished
AEL * (DuPont) : 1000 ppm, 8 & 12 H r. TW A
W EEL (AIH A) : 1000 ppm, 4900 mg/m3, 8 H r. TW A
DIFL U OROMETH ANE (H FC-32)
AEL * (DuPont) : 1000 ppm, 8 & 12 H r. TW A
W EEL (AIH A) : 1000 ppm, 8 H r. TW A
* AEL is DuPont's Acceptab le Ex posure L imit. W here governmentally imposed occupational
ex posure limits which are lower than the AEL are in effect, such limits shall tak e precedence.

(01/12)
1- 6 035-16870-100 Rev. 0

Refr ig er a nt Sa fety Da ta R410 A:


PH Y SICAL AND CH EMICAL PROPERTIES
Physical Data Boiling Point : - 60.8 F (-51.6 C) @ 1 atm
Vapour Pressure : 239.7 psia 25 C (77 F)
% Volatiles : 100 W T%
Evaporation Rate : (Cl4 = 1) G reater than 1
Solub ility in W ater : Not determined
Odour : Slight ethereal
Form : L iq uefied gas
Colour : Clear, colourless
Specific G ravity : 1.066 @ 25 C (77 F)
STABIL ITY AND REACTIVITY
Chemical Stab ility Material is stab le. H owever, avoid open flames and high temperatures.
Incompatib ility with Incompatib le with active metals, alk ali or alk aline earth metals--powdered Al, Z n, Be, etc.
Other Materials
Decomposition Decomposition products are haz ardous. This material can b e decomposed b y high
temperatures (open flames, glowing metal surfaces, etc.) forming hydrofluoric acid and
possib ly carb onyl fluoride. These materials are tox ic and irritating. Contact should b e avoided.
Polymeriz ation Polymeriz ation will not occur.
Other H az ards Decomposition : Decomposition products are haz ardous. This material can b e decomposed b y
high temperatures (open flames, glowing metal surfaces, etc.) forming hydrofluoric acid, and
possib ly carb onyl halides.
TOX ICOL OG ICAL INFORMATION
Animal Data The b lend is untested.
H FC-125
Inhalation 4-hour AL C: > 709,000 ppm in rats
Single ex posure to high doses caused: L ethargy. L ab oured b reathing. W eak cardiac
sensitiz ation, a potentially fatal disturb ance of heart rhythm caused b y a heightened
sensitivity to the action of epinephrine. L owest-Ob served-Adverse-Effect-L evel for cardiac
sensitiz ation: 100,000 ppm.
Repeated ex posure caused: No significant tox icological effects.
No-Ob served-Adverse-Effect-L evel(NOAEL ): 50,000 ppm
ADDITIONAL TOX ICOL OG ICAL EFFECTS:
No animal data are availab le to define the following effects of this material: carcinogenicity,
reproductive tox icity. In animal testing this material has not caused developmental tox icity.
Tests have shown that this material does not cause genetic damage in b acterial or
mammalian cell cultures, or in animals. This material has not b een tested for its ab ility to
cause permanent genetic damage in reproductive cells of mammals (not tested for heritab le
genetic damage).
H FC-32
Inhalation 4 hour-AL C: > 520,000 ppm in rats
Single ex posure caused: L ethargy. Spasms. L oss of mob ility in the hind limb s. Other effects
include weak cardiac sensitiz ation, a potentially fatal disturb ance of heart rhythm caused b y a
heightened sensitivity to the action of epinephrine. 250,000 ppm.
Repeated ex posure caused pathological changes of the lungs, liver, spleen, k idneys. In more
recent studies repeated ex posure caused: No significant tox icological effects.
No-Ob served-Effect-L evel (NOEL ): 49,100 ppm.
No animal data are availab le to define the following effects of this material: carcinogenicity,
reproductive tox icity. Animal data show slight fetotox icity b ut only at ex posure levels producing
other tox ic effects in the adult animal. Tests have shown that this material does not cause
genetic damage in b acterial or mammalian cell cultures, or in animals. This material has not
b een tested for its ab ility to cause permanent genetic damage in reproductive cells of
mammals (not tested for heritab le genetic damage).

(01/12)
035-16870-100 Rev. 0 1- 7

Refr ig er a nt Sa fety Da ta R410 A:


DISPOSAL CONSIDERATIONS
W aste Disposal Comply with Federal, State, and local regulations. Reclaim b y distillation or remove to a
permitted waste disposal facility.
TRANSPORTATION INFORMATION
Shipping Information DOT/IMO/IATA
Proper Shipping Name : L iq uefied G as, N.O.S. (Pentafluoroethane and Difluoromethane)
H az ard Class : 2.2
U N No. : 3163
L ab el(s) : Nonflammab le G as
Shipping Containers : Tank Cars. Cylinders. Ton Tank s

Oil Sa fety Da ta YORK 'V' Oil:

Sec tio n 1 Su b sta nc e Pr o d u c t Info r m a tio n

Product Trade Name: Y ORK "V" Oil.


Chemical Name: Carb ox ylic Ester.

Sec tio n 2 Co m po nents a nd Ha z a r d Sta tem ent

This product is non-haz ardous. This material has no k nown haz ards under applicab le laws.

Sec tio n 3 Sa fe Ha nd ling a nd Sto r a g e

H andling: K eep containers closed when not in use. W ash thoroughly after handling. Empty container contains product
residue which may ex hib it haz ards of product.
Storage: No special storage precautions req uired.

Sec tio n 4 Ph y sic a l Da ta

Appearance: Clear liq uid.


Boiling Point: Not Determined.
Vapour Pressure: Not Determined.
Specific G ravity (water= 1): 0.97 @ 15.6° C.
Volatiles, Percent b y Volume: U nk nown.
Odour: Mild.
Solub ility in W ater: Insolub le.
Evaporation Rate: Not Determined.

Sec tio n 5 F ir e a nd Ex plo sio n Ha z a r d s

Flash Point: > 232° C, 450° F COC (Minimum).


Flammab le L imits: not estab lished.
Autoignition Temperature: no data.
Ex tinguishing Media: CO2, dry chemical or foam. W ater can b e used to cool and protect ex posed material.
U nusual Fire and Ex plosion H az ards: Tox ic fumes, gases or vapours may evolve on b urning.
Special Fire Fighting Techniq ues: Firefighters should use approved self-contained b reathing apparatus. W ater may cause
splattering. Material will float on water.

(01/12)
1- 8 035-16870-100 Rev. 0

Oil Sa fety Da ta YORK 'V' Oil:

Sec tio n 6 Rea c tiv ity Da ta

Stab ility: Material is normally stab le at moderately elevated temperatures and pressures.
H az ardous Polymeriz ation: W ill not occur.
Incompatib le Materials: Strong acids. Strong b ases. Strong ox idiz ing agents.
Decomposition Temperature: Not Determined.
Thermal Decomposition: Smok e, carb on monox ide, carb on diox ide, aldehydes and other products of incomplete
comb ustion.

Sec tio n 7 Hea lth Ha z a r d Da ta

F ir st Aid Pr o c ed u res
Ingestion: DO NOT INDU CE VOMITING . If conscious, give 2 glasses of water. G et immediate medical attention.
Eyes: Flush with water at least 15 minutes. G et medical attention if eye irritation develops or persists.
Sk in: W ash with soap and water. G et medical attention if irritation develops. L aunder contaminated clothing b efore reuse.
Inhalation: Remove ex posed person to fresh air if adverse effects are ob served.
Additional Information: Note to physician: Treat symptomatically.

Sec tio n 8 Per so na l Pr o tec tio n Info r m a tio n

Respiratory Protection: U se respirator with an organic vapour cartridge if ex posure limit is ex ceeded.
Ventilation: U se with adeq uate ventilation.
Protective G loves: Neoprene.
Eye/Face Protection: Safety glasses.
Clothing: L ong sleeve shirt is recommended.

Sec tio n 9 Spill o r Lea k Pr o c ed u r es

Spill Procedures: Personal Protective Eq uipment must b e worn, see Personal Protection Information (Section 8). Ventilate
area if spilled in confined space or other poorly ventilated areas. Prevent entry into sewers and waterways. Residual liq uid
can b e ab sorb ed on inert material. Properly dispose of all materials.

Sec tio n 10 Wa ste Dispo sa l Meth o d s

This material, if discarded, should b e disposed of in a licensed facility in accordance with local regulations.

Th er m a l & Ac o u stic Ma ter ia ls Da ta


H ealth H az ard & First Aid Tox icity Index < 10 to NES713 Issue 3 (1991): Non-haz ardous, non-tox ic. No first aid necessary.
Stab ility / Reactivity Stab le.
H andling / U se / Disposal No special handling precautions req uired. Dispose of according to local laws and regulations
governing non-b iodegradab le non-haz ardous solid wastes.
Fire & Ex plosion Flammab ility rating Class 1 to BS 476 pt 7: Non-flammab le. If forced to b urn, comb ustion
products are typically over 95% carb on diox ide and carb on monox ide.

(01/12)
035-16870-100 Rev. 0 2- 1

1
8

1 Control Panel 2
2 Power Panel
3 Non-Fused Disconnect Switch
4 Accumulator
3
5 Compressor
6 Refrigerant to W ater
Plate H eat Ex changer 4
7 L iq uid Receiver
5
8 Amb ient Coil 6
9 Fans 7

2.2 Co m pr esso r s
2 PRODUCT DESCRIPTION
The unit has hermetic scroll compressors. H igh
2.1 Intr o d u c tio n efficiency is achieved through a controlled orb it and the
use of advanced scroll geometry. All rotating parts are
Y ORK Y L AE Tempo™ heat pump-chillers provide statically and dynamically b alanced. The compressor
chilled and warm liq uid for all air conditioning motors have integral protection against overloads. The
applications . All units are designed to b e located overload protection will automatically reset. Starting is
outside on the roof of a b uilding or at ground level. direct on line. The motor terminal b ox es have IP-54
weather protection.
The unit consists of two separate refrigerant circuits with
two or three hermetic scroll compressors in each circuit, The compressors are switched On and Off b y the unit
a single stainless steel plate type heat ex changer, microprocessor to provide capacity control. Each
amb ient coils and ex pansion valves. compressor is fitted with a crank case strap heater.

The units are completely assemb led with all 2.3 Refr ig er a nt Cir c u its
interconnecting refrigerant piping and internal wiring,
ready for field installation. Two independent refrigerant circuits are provided. Each
circuit uses copper refrigerant pipe formed on computer
Before delivery, the unit is pressure tested, evacuated, controlled b ending machines to reduce the numb er of
and fully charged with refrigerant and oil in each of the b raz ed joints resulting in a reliab le and leak resistant
independent refrigerant circuits. After assemb ly, an system.
operational test is performed with water flowing through
the plate heat ex changer to ensure that each refrigerant Each circuit shall incorporate all components necessary
circuit operates correctly. for the designed operation including: a liq uid refrigerant
accumulator, a liq uid receiver, a four way reversing
The unit structure is manufactured from heavy gauge, valve, a service valve, isolation (b all) valves, pressure
galvanised steel and coated with 'Champagne' relief valves, a high ab sorption removab le core
b ak ed-on powder paint. filter-drier, a sight glass with moisture indicator, a
cooling mode thermal ex pansion valve and two heat
pump mode thermal ex pansion valves. Suction lines
shall b e covered with closed-cell insulation.

(01/12)
2- 2 035-16870-100 Rev. 0

2.4 Refr ig er a nt to Wa ter Hea t Ex c h a ng er Th e c o ntr o l pa nel inc lu d es:

The refrigerant to water heat ex changer is a stainless n A L iq uid Crystal Display (two display lines of twenty
steel plate type heat ex changer with a design work ing characters per line) with L ight Emitting Diode b ack
pressure of 10 b arg on the water side. The plate heat lighting for outdoor viewing.
ex changer is eq uipped with a heater for frost protection
to – 20° C and insulated with flex ib le closed-cell foam. n A Colour coded 12-b utton k eypad.
W ater connection to the plate heat ex changer is via 3
inch Victaulic groove connections. n Customer terminal b lock for control inputs and
liq uid flow switch.
2.5 Am b ient Co ils
Th e m ic r o pr o c esso r c o ntr o l inc lu d es:
The amb ient coils are seamless copper tub es, arranged
in staggered rows, mechanically ex panded into epox y Status K ey for display of:
coated aluminium fins. Integral sub -cooling is included.
n Status of the unit and each refrigerant circuit
Fans have metal ‘sick le’ b lades integrated into the rotor
of an ex ternal rotor motor. They are designed for n System and unit safety fault messages
max imum efficiency and statically and dynamically
b alanced for vib ration free operation. They are directly Display/Print K eys for display of:
driven b y independent motors, and positioned for
vertical air discharge. The fan guards are constructed n Chilled and warm liq uid and amb ient air
from heavy-gauge, corrosion resistant, coated steel. temperatures

The IP54 fan motors are the totally enclosed air-over n System pressures (each circuit)
type. They will feature b all b earings that are
doub le-sealed and permanently lub ricated. n Operating hours and starts (each compressor)

2.6 Po w er a nd Co ntr o l Pa nels n L oad and unload timers and cooling demand

All power components and controls are contained in a n L iq uid pump, plate heat ex changer heater,
IP55 cab inet with hinged and lock ab le outer doors. solenoid valve and condenser fan status
Power and control sections are housed in separate
enclosures. n Operating data for the systems

Th e po w er pa nel inc lu d es: n H istory including time, date and reason for last fault
shutdown
n A factory mounted non-fused disconnect switch
with ex ternal, lock ab le handle to enab le An RS-232 port, in conjunction with this press-to-print
connection of the unit power supply. The b utton, is provided to permit the capab ility of hard copy
disconnect switch can b e used to isolate the power print-outs via a separate printer (b y others).
for servicing.
Entry K eys
n Factory mounted compressor contactors,
compressor fuses and overloads to provide n To program and modify system values
overload and short circuit protection.

n Factory mounted fan contactors and manual motor


starters for overload and short circuit protection.

n Factory mounted control transformer to convert the


unit supply voltage to 110 V - 1 Ø - 50 H z for the
control system.

n Control supply fuses and connections for a remote


emergency stop device.

(01/12)
035-16870-100 Rev. 0 2- 3

Setpoints K eys for programming: n Compressor run status

n Chilled and warm liq uid temperature setpoint and n No load condition
range
n Day, date and time
n Remote reset temperature range
n Daily start/stop times
n Set daily schedule/holiday for start/stop
n H oliday status
n Manual override for servicing
n Automatic or manual system lead/lag control
n L ow and high amb ient cutouts
n L ead system definition
n L ow liq uid temperature cutout
n Compressor starts & operating hours (each
n L ow suction pressure cutout compressor)

n H igh discharge pressure cutout n Status of plate heat ex changer heater and fan
operation
n Anti-recycle timer (compressor start cycle time)
n Run permissive status
U nit K eys
n Numb er of compressors running
n To set time and unit options
n Mode valve status
U nit ON/OFF switch
n L oad & unload timer status
n To activate or deactivate the unit
n W ater pump status
The microprocessor control system is capab le of
displaying the following: L iq uid Temperature Reset via a Y ORK ISN DDC or
Building Automation System (b y others)
n L eaving liq uid temperature
Provisions is included for optional remote chilled or
n L ow leaving liq uid temperature cutout setting warm water temperature reset or up to two steps of
demand load limiting (depending on model) from an
n L ow amb ient temperature cutout setting ex ternal b uilding automation system.

n Amb ient air temperature The operating program is stored in a non-volatile


memory (EPROM) to eliminate unit failure due to AC
n Metric or Imperial data power failure/b attery discharge. Programmed setpoints
are retained in a lithium b attery b ack ed RTC memory.
n Discharge and suction pressure cutout settings

n System discharge and suction pressures

n Anti-recycle timer status

n Anti-coincident system start timer condition

(01/12)
2- 4 035-16870-100 Rev. 0

2.7 ACCESSORIES AND OPTIONS Pla te Hea t Ex c h a ng er Ex tensio n K it

Po w er F a c to r Co r r ec tio n Ex tension k it simplifies connections to customer


pipework . K it includes a flow switch and water strainer
Factory mounted passive (static) power factor and terminates with a 3” Victualic groove connection.
correction capacitors to correct unit compressor power This option can b e handed left or right when facing the
factors to a target of 0.9 (depending on operating control panel. It is not insulated or trace heated
conditions). therefore, if glycol is not used, in regions where freez e
conditions occur the contractor must apply some form of
So ft Sta r ter s adeq uate frost protection.

Factory mounted soft starters reduce the inrush current Vic ta u lic Co u pling
to the last compressor on each refrigerant circuit. They
are preset so that no field adjustment is req uired. Victaulic coupling supplied loose for field installation.
U sed to connect the plate heat ex changer, plate heat
Bu ild ing Au to m a tio n Sy stem (BAS) / EMS ex changer ex tension k it or H ydro K it option to an
Inter fa c e associated grooved pipe / fitting.

Provides a means of resetting the leaving liq uid Vic ta u lic F la ng e K it


temperature from the BAS / EMS (Factory Mounted):
Victaulic PN10 flange joint k it (10 b ar) supplied loose for
Printed circuit b oard to accept 4 to 20 mA, 0 to 10 Vdc, or field installation. Includes flange and companion flange
dry contact closure input from the BAS / EMS. and all necessary nuts, b olts and gask ets. U sed to
connect the plate heat ex changer, plate heat ex changer
Note: A Y ORK ISN Building Automation System can ex tension k it or H ydro K it option to an associated
provide a Setpoint Temperature Reset signal direct to grooved pipe / fitting
the standard control panel via the standard on-b oard
RS485 port. Cannot b e fitted when a Micro G ateway is Pr e-Co a ted Hy d r o ph ilic Am b ient Co il F ins
fitted.
The amb ient coils are constructed of b lue hydrophilic
Mic r o Ga tew a y coated aluminium fins. The H ydrophilic coating
increases the rate that water runs off the fins and
Interface to enab le communication with b uilding control therefore improves the defrost action. It is also protects
systems using BACnet or MODBU S protocols. See the fin against salt corrosion and is therefore
separate Y ork documentation. (Cannot b e fitted when a recommended for units installed at the seashore.
(BAS) Interface is fitted).
Du a l Releif Va lv es
La ng u a g e LCD a nd K ey pa d
Dual relief valve option to aid maintenance.
English, Spanish, French, G erman and Italian language
unit L CD read-out and k eypads are availab le. Standard Lo w So u nd (LS) Unit Co m pr esso r So u nd
language is English. Enc lo su r es

38 m m Pla te Hea t Ex c h a ng er Insu la tio n Includes compressor acoustically lined enclosures


(factory fit).
Doub le thick ness insulation provided for enhanced
efficiency, and low temperature applications.

(01/12)
035-16870-100 Rev. 0 2- 5

Hig h Pr essu r e F a ns Co nta iner isa tio n

Fans and motors suitab le for high ex ternal static U nits shipped complete with refrigerant charge in
conditions up to 120 Pa. standard containers.

Am b ient Co il Wir e Gu a r d s Hy d r o K it

W elded wire mesh guards mounted over the amb ient Factory fitted H ydro K it suitab le for water glycol systems
coils (factory mounted). with up to 35% glycol at leaving liq uid temperatures
down to -6° C. The k it is availab le in single or dual pump
Unit Wir e Enc lo su r e variants, with open drive air cooled motor running at
2900 rpm.
W elded wire mesh guards over amb ient coils and
around the b ottom of the unit (field or factory mounted Components are mounted on a painted galvanised steel
options availab le). b ase plate and include: one or two pumps, two isolation
valves per pump, a flow switch, a water filter (20
Neo pr ene Pa d Iso la to r s microns), relief, b leed and drain valves, a pressure
gauge, and an ex pansion vessel.
Recommended for normal installations (field mounted).
The pumps and flow switch are factory wired to the unit
25 m m Spr ing Iso la to r s control system to provide auto pump starting and
running.
L evel adjustab le, spring and cage type isolators for
mounting under the unit b ase rails (field mounted). All pipework and fittings are galvanised and outlets are
Victaulic groove type. 19 mm, thermal insulation is
Lifting Lu g K it included. Pressure tapping points are included for
differential pressure measurement (gauges to b e
One set of ISO Mk 5 camlocs to enab le safe and easy supplied b y others). Dual pump models have non-return
unit handling. valves and isolating valves.

This option can b e handed left or right when facing the


control panel. It is not trace heated therefore, if glycol is
not used, in regions where freez e conditions occur the
contractor must apply some form of adeq uate frost
2.8 No m enc la tu r e protection/trace heating.

YLAE0260H P50X AA
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
BASE PRODU CT TY PE NOMINAL CAPACITY U NIT DESIG NATION REFRIG ERANT VOL TAG E / STARTER DESIG N / DEVEL OPMENT L EVEL

Y : Y ork # # # # kW H : H eat P : Pump 5 0 : 400 / 3 / 50 A : Design Series


L : Scroll :0200 :0240 :0260 :0300 X : Direct on L ine A : Engineering Change
A : Air Cooled :0330 :0370 :0440 :0480 S :Soft Start or PIN L evel
E : European

(01/12)
2- 6 035-16870-100 Rev. 0

2.9 F u nc tio na l Desc r iptio n HEAT PUMP MODE

L iq uid refrigerant enters the amb ient coil and is fully


C O O L IN G & D EF R O S T M O D E evaporated and superheated b y the energy ab sorb ed
L ow T empera tu re L iq u id

H ig h P ressu re S u b-Cooled L iq u id Ambient Coils


from the amb ient air. L ow-pressure superheated
L ow P ressu re S u perh ea ted V a pou r refrigerant vapour passes through the four-way
H ig h P ressu re S u perh ea ted V a pou r reversing valve and the accumulator and enters the
O il compressor, where pressure and superheat are
increased. H igh-pressure superheated refrigerant
vapour enters the refrigerant to water plate heat
4 W ay
ex changer where heat is rejected to the water. The
Compressors V a lv e high-pressure liq uid refrigerant, leaving the heat
L iq u id
R e c e iv e r
ex changer passes through the liq uid receiver and
W a te r
enters thermostatic ex pansion valves TEV2 and TEV3
In where the refrigerant pressure is reduced and
Ac c u m u la to r
P la te H e a t
Ex c h a n g e r T EV 1
sub seq uently cooled b efore returning to the amb ient
W a te r
O ut
coil.

DEF ROST
COOLING AND DEF ROST MODES
W hen ice b uilds up on the amb ient coils defrost is
initiated b y operating the machine in a cooling mode.
L ow pressure liq uid refrigerant enters the plate heat
Each of the two refrigerant circuits will b e defrosted one
ex changer and is evaporated and superheated b y the
at a time. W hen defrost is operative the circuit operating
heat energy ab sorb ed from the chilled liq uid. L ow
in heat pump mode is in b alance with the circuit
pressure vapour enters the compressor, via the
operating in defrost (cooling). Therefore, heat energy is
four-way reversing valve, where pressure and
not removed from the hot water system.
superheat are increased. The high pressure vapour is
fed to the amb ient coils and fans, via the four way
reversing valve, where heat is removed. The fully
condensed and sub cooled liq uid passes through the
ex pansion valve (TEV1) where pressure is reduced and
further cooling tak es place b efore returning to the plate
heat ex changer.

H EAT P U M P M O D E
L ow T empera tu re L iq u id

H ig h P ressu re S u b-Cooled L iq u id Ambient Coils


L ow P ressu re S u perh ea ted V a pou r

H ig h P ressu re S u perh ea ted V a pou r

O il T EV 3
T EV 2

4 W ay
Compressors V a lv e

L iq u id
R ec eiv er

W a te r
In

P la te H e a t
Ac c u m u la to r Ex c h a n g e r
W a te r
O ut

(01/12)
035-16870-100 Rev. 0 3- 1

3 TRANSPORTATION, HANDLING AND Care should b e tak en to avoid damaging the


STORAGE amb ient coil fins when moving the unit.

3.1 Deliv er y a nd Sto r a g e

To ensure consistent q uality and max imum reliab ility, all U nits are provided with four lifting holes in the b ase
units are tested and inspected b efore leaving the frame which accept the accessory lifting lug set (part
factory. U nits are shipped completely assemb led and numb er 026L 00261-000).
containing refrigerant under pressure.
The four lugs (2 x RH and 2 x L H ) should b e inserted into
If the unit is to b e put into storage, b efore installation, the the respective holes in the b ase frame and turned so
following precautions should b e ob served: that the spring loaded pin engages into the hole and the
flanges on the lug lock b ehind the hole. The lugs should
Ensure that all openings, such as water connections, b e attached to the cab les/chains using shack les or
are securely sealed. safety hook s.
CORRECT INCORRECT
The amb ient coils should b e covered to protect the fins
from potential damage and corrosion, particularly where LU G
LU G L IFTING H OL E
b uilding work is in progress. IN BASE FRAME FL ANG E
FL ANG E
The unit should b e stored in a location where there is
minimal activity to limit the risk of accidental physical L OCK ING PIN
damage.
L IFTING H OL E
L OCK ING PIN IN BASE FRAME
To prevent inadvertent operation of the pressure relief
devices the unit must not b e steam cleaned.
LU G

It is recommended that the unit is periodically inspected


during storage.

3.2 Inspec tio n L OCK ING


PIN

Remove any transit pack ing and inspect the unit to FL ANG E
ensure that all components have b een delivered and
that no damage has occurred during transit. If any
damage is evident, it should b e noted on the shipment
documentation and a claim entered according to the 3.4 Lifting Weig h ts
instructions given.
For details of weights and weight distrib ution refer to
Major damage must b e reported immediately to your Section 9.
local J ohnson Controls representative.

3.3 Mo v ing th e Unit

Before moving the unit, ensure that the installation site is


suitab le and is capab le of supporting the weight of the
unit and all associated services.

The unit should b e lifted using lifting lugs and a spreader


b ar or frame of sufficient width to prevent damage to the
unit from the lifting chains.

The unit must only b e lifted b y the b ase frame


at the points provided. Never move the unit on
rollers, or lift the unit using a fork -lift truck .

(01/12)
3- 2 035-16870-100 Rev. 0

Ty pic a l Lifting Ar r a ng em ent

(01/12)
035-16870-100 Rev. 0 4- 1

4 INSTALLATION The channels should b e spaced at the same centres as


the vib ration mounting holes in the unit b ase frame and
4.1 Lo c a tio n Req u ir em ents must b e at least 120 mm wide at the contact points. This
will allow vib ration isolators to b e fitted if req uired.
To achieve optimum performance and troub le-free
service, it is essential that the proposed installation site Any ductwork or attenuators fitted ab ove the unit must
meets with the location and space req uirements for the not have a total static pressure resistance, at full unit
model b eing installed. For dimensions, weight and airflow, ex ceeding the capab ility of the fans installed in
space req uirements, including service access details, the unit.
refer to Section 9.
Ind o o r Insta lla tio ns
It is important to ensure that the minimum service
access space is maintained for cleaning and The unit may b e installed in an enclosed plant room
maintenance purposes. providing the floor is level and of suitab le strength to
support the full operating weight of the unit. It is essential
Th e u nit sh o u ld no t b e insta lled d ir ec tly o n that there is adeq uate clearance for airflow to the unit.
fla m m a b le m a ter ia ls su c h a s w o o d en The discharge air from the top of the unit must b e ducted
str u c tu r es o r r o o fs. away to prevent recirculation of air within the plant room.
If common ducts are used for fans, non-return dampers
must b e fitted to the outlet from each fan.

Ou td o o r Insta lla tio ns The discharge ducting must b e siz ed with a total static
pressure loss, together with any intak e static pressure
The units may b e installed at ground level, or on a loss, less than the availab le static pressure capab ility for
suitab le rooftop location. In b oth cases an adeq uate the type of fan fitted.
supply of air is req uired. Avoid locations where the air
discharge from the unit may b e ob jectionab le. The discharge air duct usually rejects outside the
b uilding through a louvre. The outlet must b e positioned
The location should b e selected for minimum sun to prevent the air b eing drawn directly b ack into the air
ex posure and away from b oiler flues and other sources intak e for the condenser coils as such recirculation will
of airb orne chemicals that could attack the condenser affect unit performance.
coils and any other materials in the unit.
4.2 Lo c a tio n Clea r a nc es
If located in an area accessib le to unauthorised
persons, steps must b e tak en to prevent access to the Adeq uate clearances around the unit(s) are req uired for
unit b y means of a protective fence. This will help to the unrestricted airflow for the air-cooled condenser
prevent the possib ility of vandalism, accidental damage, coils and to prevent recirculation of warm discharge air
or possib le harm caused b y unauthorised removal of b ack onto the coils. If clearances given are not
protective guards or opening panels to ex pose rotating maintained, airflow restriction or recirculation will cause
or high voltage components. a loss of unit performance, an increase in power
consumption and may cause the unit to malfunction.
For ground level locations, the unit must b e installed on Consideration should also b e given to the possib ility of
a suitab le flat and level concrete b ase that ex tends to down draughts, caused b y adjacent b uildings, which
fully support the two side channels of the unit b ase may cause recirculation or uneven unit airflow.
frame. A one-piece concrete slab , with footings
ex tending b elow the frost line is recommended. To For locations where significant cross winds are
avoid noise and vib ration transmission the unit should ex pected, such as ex posed roof tops, a solid enclosure
not b e secured to the concrete b ase. or louvre type is recommended to prevent wind
turb ulence interfering with the unit airflow.
On rooftop installations, choose a location with
adeq uate structural strength to safely support the entire W hen units are installed in an enclosure, the enclosure
operating weight of the unit and service personnel. If the height should not ex ceed the height of the unit on more
unit is elevated b eyond the normal reach of service than one side. If the enclosure is of louvered
personnel, a suitab le catwalk capab le of supporting construction the same req uirement of static pressure
service personnel, their eq uipment, and the loss applies as for ducts and attenuators stated ab ove.
compressors must b e installed. The unit may b e
mounted on a concrete slab , similar to ground floor W here accumulation of snow is lik ely, additional height
locations, or on steel channels of suitab le strength. must b e provided under the unit to ensure normal airflow
to the unit is unimpeded.

(01/12)
4- 2 035-16870-100 Rev. 0

The clearance dimensions given are 4.5 Pipew o r k Co nnec tio n


necessary to maintain good airflow and
ensure correct unit operation. It is also Gener a l Req u ir em ents
necessary to consider access req uirements
for safe operation and maintenance of the unit The following piping recommendations are intended to
and power and control panels. L ocal H ealth ensure satisfactory operation of the unit(s). Failure to
and Safety Regulations, or practical follow these recommendations could cause damage to
considerations for service replacement of the unit, or loss of performance, and may invalidate the
large components, may req uire larger warranty.
clearances than those given in Section 9.
The max imum flow rate and pressure drop for
4.3 Co m pr esso r Sh ipping Bo lts the cooler must not b e ex ceeded at any time.
Refer to Section 9 for details.
Remove the 4 b olts securing the underside of each
compressor to the unit b ase.

The compressor shipping b olts must b e n The liq uid must enter the plate heat ex changer b y
refitted prior to any sub seq uent movement of the INLET connection (refer to Section 9 ).
the unit.
n A flow switch must b e installed in the customer
pipework at the outlet of the plate heat ex changer
Compressor shipping b olts
and wired b ack to the control panel using screened
(remove b efore operation) cab le. For details refer to 'Electrical Connection.'
This is to prevent damage to the plate heat
ex changer caused b y the unit operating without
adeq uate liq uid flow. To prevent turb ulent flow
there must b e straight pipework either side of the
flow switch eq ual in length to at least 5 times the
diameter of the pipe.

n The flow switch used must have gold plated


contacts for low voltage/current operation. Paddle
type flow switches suitab le for 10 b arg work ing
pressure and having a 1" B.S.P. connection may
b e ob tained from J ohnson Controls as an
accessory for the unit.

n The liq uid pump installed in the pipework system


4.4 Insta lla tio n o f Vib r a tio n Iso la to r s should discharge directly into the unit plate heat
ex changer section of the system. The pump may
Optional sets of vib ration isolators may b e supplied b e controlled ex ternal to the unit — b ut an override
loose with each unit. must b e wired to the control panel so that the unit
can start the pump in the event that the liq uid
n Identify each mount and its correct location on the temperature falls b elow the minimum setting. For
unit. details refer to 'Electrical Connection.'

Mo u nts - Insta lla tio n n Pipework and fittings must b e separately


supported to prevent any loading on the plate heat
n Place each mount in its correct position and lower ex changer. Flex ib le connections are
the unit carefully onto the mounts. recommended which will also minimise
transmission of vib rations to the b uilding. Flex ib le
n Transfer the unit weight evenly to the springs and fit connections must b e used if the unit is mounted on
and adjust the mounts in accordance with anti-vib ration mounts as some movement of the
Section 9. unit can b e ex pected in normal operation.

n Pipework and fittings immediately adjacent to the


plate heat ex changer should b e readily
de-mountab le to enab le cleaning b efore operation,
and to facilitate visual inspection of the plate heat
ex changer noz z les.

(01/12)
035-16870-100 Rev. 0 4- 3

n The plate heat ex changer must b e protected b y a 4.6 Wa ter Tr ea tm ent


strainer, preferab ly of 20 microns, fitted as close as
possib le to the liq uid inlet connection, and provided The unit performance given in the Design G uide is
with a means of local isolation. b ased on a fouling factor of 0.044 m² ° C/k W
(0.00025 ft²hr° F/Btu). Dirt, scale, grease and certain
n The plate heat ex changer must not b e ex posed to types of water treatment will adversely affect the heat
flushing velocities or deb ris released during ex changer surfaces and therefore unit performance.
flushing. It is recommended that a suitab ly siz ed Foreign matter in the water system will increase the heat
b y-pass and valve arrangement is installed to allow ex changer pressure drop, reducing the flow rate and
flushing of the pipework system. The b y-pass may causing potential damage to the heat ex changer tub es.
b e used during maintenance to isolate the heat
ex changer without disrupting flow to other units. Aerated, b rack ish or salt water is not recommended for
use in the water system. J ohnson Controls recommend
n Thermometer and pressure gauge connections that a water treatment specialist is consulted to
should b e provided on the inlet and outlet determine that the proposed water composition will not
connections of the plate heat ex changer. affect the plate heat ex changer materials of carb on steel
and copper. The pH value of the water flowing through
n Drain and air vent connections should b e provided the plate heat ex changer must b e k ept b etween 7 and
at all low and high points in the pipework to permit 8.5.
drainage of the system and to vent any air in the
pipes. 4.7 Pipew o r k Ar r a ng em ent

n L iq uid systems at risk of freez ing, due to low The following are suggested pipework arrangements for
amb ient temperatures, should b e protected using single unit installations. For multiple unit installations,
insulation and heater tape and/or a suitab le glycol each unit should b e piped as shown.
solution. The liq uid pump must also b e used to
ensure liq uid is circulated when the amb ient Rec o m m end a tio ns o f th e Bu ild ing Ser v ic es
temperature approaches freez ing point. Insulation Resea r c h Asso c ia tio n
should also b e installed around the plate heat
ex changer noz z les. H eater tape of 21 watts per
metre under the insulation is recommended,
supplied independently and controlled b y an
amb ient temperature thermostat set to switch on at
3° C ab ove the freez ing temperature of the liq uid.

n The liq uid circulation pump must b e controlled b y


the unit. This will ensure that when the liq uid
temperature falls within 2 or 3° C of freez ing the
pump will start.

n The plate heat ex changer is protected b y heater


mats under the insulation which are supplied from
the unit control system power supply. During risk of Isolating Valve - Normally Open

freez ing the control system should b e left switched


Isolating Valve - Normally Closed
'ON' to provide the freez e protection function
unless the liq uid systems have b een drained.
Flow Regulating Valve

Any deb ris left in the water pipework b etween Flow Measurement Device
the strainer and plate heat ex changer could
cause serious damage to the tub es in the Strainer
plate heat ex changer and must b e avoided.
Pressure Tapping
The installer/user must also ensure that the
q uality of the water in circulation is adeq uate,
Flow Switch
without any dissolved gasses which may
cause ox idation of steel parts within the plate Flanged Connection
heat ex changer.

(01/12)
4- 4 035-16870-100 Rev. 0

4.8 Co nnec tio n Ty pes & Siz es 4.10 Du c tw o r k Co nnec tio n

For connection siz es relevant to individual models refer Gener a l Req u ir em ents
to Section 9.
There will b e a loss of capacity if the unit air
Pla te Hea t Ex c h a ng er Co nnec tio ns volume is reduced. Therefore ensure that fans
have sufficient ex ternal static pressure b efore
L iq uid connections on all plate heat ex changer are applying ductwork or other attached
victaulic grooves. components.

4.9 Refr ig er a nt Relief Va lv e Piping The following ductwork recommendations are intended
to ensure satisfactory operation of the unit. Failure to
The plate heat ex changer is protected against internal follow these recommendations could cause damage to
refrigerant over pressure and fire b y refrigerant relief the unit, or loss of performance, and may invalidate the
valves. Pressure relief valves are mounted on the warranty.
suction, discharge and accumulator lines.
n W hen ducting is to b e fitted to the fan discharge it is
It is recommended that a vent pipe is fitted to each valve recommended that the duct should b e the same
and directed so that when the valve is activated the cross sectional area as the fan outlet and straight
release of high pressure gas and liq uid cannot b e a for at least one metre to ob tain static regain from
danger or cause injury. For indoor installations pressure the fan.
relief valves should b e piped to the ex terior of the
b uilding. n Ductwork should b e suspended with flex ib le
hangers to prevent noise and vib ration b eing
The siz e of any pipework attached to a relief valve must transmitted to the structure. A flex ib le joint is also
b e of sufficient diameter so as not to cause resistance to recommended b etween the duct attached to the
the operation of the valve. U nless otherwise specified b y fan and the nex t section for the same reason.
local regulations, the internal diameter depends on the Flex ib le connectors should not b e allowed to
length of pipe req uired and is given b y the following concertina.
formula:
n The unit is not designed to tak e structural loading.
5
D = 1.447 x L No significant amount of weight should b e allowed
to rest on the fan outlet flange, deck assemb lies or
W here: condenser coil module. No more than one metre of
light construction ductwork should b e supported b y
D = minimum pipe internal diameter in centimetres the unit. W here cross winds may occur, any
L = length of pipe in metres ductwork must b e supported to prevent side
loading on the unit.
If relief pipework is common to more than one valve its
cross sectional area must b e at least the total req uired n If the ducts from two or more fans are to b e
b y each valve. Valve types should not b e mix ed on a comb ined into a common duct, b ack -flow dampers
common pipe. Precautions should b e tak en to ensure should b e fitted in the individual fan ducts. This will
that the ex it of relief valves/vent pipe remain clear of prevent recirculation of air when only one of the
ob structions at all times. fans is running.

W hen the optional isolation valves are fitted in n U nits are supplied with outlet guards for safety and
the discharge pipework of each system, the to prevent damage to the fan b lades. If these
related pressure relief valve should b e piped guards are removed to fit ductwork , adeq uate
in the same manner as the other relief valves. alternative precautions must b e tak en to ensure
persons cannot b e harmed or put at risk from
rotating fan b lades.

(01/12)
035-16870-100 Rev. 0 4- 5

Co nnec tio n Deta ils a nd Dim ensio ns 4.11 Elec tr ic a l Co nnec tio n
(Hig h Pr essu r e F a ns Only )
The following connection recommendations are
intended to ensure safe and satisfactory operation of the
1 2 unit. Failure to follow these recommendations could
cause harm to persons, or damage to the unit, and may
invalidate the warranty.

No a d d itio na l c o ntr o ls (r ela y s, etc .) sh o u ld


B
b e m o u nted in th e c o ntr o l pa nel. Po w er
a nd c o ntr o l w ir ing no t c o nnec ted to th e
c o ntr o l pa nel sh o u ld no t b e r u n th r o u g h
th e c o ntr o l pa nel. If th ese pr ec a u tio ns a r e
3 no t fo llo w ed it c o u ld lea d to a r isk o f
elec tr o c u tio n. In a d d itio n, elec tr ic a l no ise
c o u ld c a u se m a lfu nc tio ns o r d a m a g e th e
u nit a nd its c o ntr o ls.

22.
After c o nnec tio n d o no t sw itc h o n po w er to
5° th e u nit. So m e inter na l c o m po nents a r e
22.5° liv e w h en po w er is sw itc h ed o n a nd th is
m u st o nly b e c a r r ied o u t b y Au th o r ised
A

per so ns.

The unit ON/OFF switch on the front of the control panel


has b een set in the 'OFF' position at the factory.

This switch MU ST remain in the 'OFF' position until the


unit is commissioned b y J ohnson Controls Authorised
personnel. If the switch is set to the 'ON' position b efore
commissioning then it must b e reported to J ohnson
1 Top Flange Controls, otherwise the warranty may b e invalidated.
2 G uard
4.12 Po w er Wir ing
3 16 H oles, 12 mm Ø for b olts on Ø C
These units are suitab le for 380 or 400 V,
3 phase, 50 H z nominal supplies only.
Dim ensio n (m m ) Minimum allowab le 360 V.
A 880 Max imum allowab le 440 V.
B 225

All electrical wiring should b e carried out in accordance


with local regulations. Route properly siz ed cab les to the
cab le entries in the b ottom of the power panel.

In accordance with EN 60204 it is the responsib ility of


the user to install over current protection devices
b etween the supply conductors and the power supply
terminals on the unit.

To ensure that no eddy currents are set up in the power


panel, the cab les forming each 3 phase power supply
must enter via the same cab le entry.

All so u r c es o f su pply to th e u nit m u st b e


ta k en v ia a c o m m o n po int o f iso la tio n (no t
su pplied b y YORK ).

(01/12)
4- 6 035-16870-100 Rev. 0

Sing le Po int Po w er Su pply Wir ing In accordance with EN 60204 it is recommended that
the customer wiring to these terminals uses orange
All models req uire one field provided 400 V, 3Ø , 50 H z wires. This will ensure that circuits not switched off b y
+ PE (Protected Earth) supply to the unit with circuit the units supply disconnecting device are distinguished
protection. b y colour, so that they can easily b e identified as live
even when the unit disconnecting devices are off. The
Connect the 3 phase supply to the non-fused unit voltage free contacts are rated at 125 VA.
disconnect switch located in the power panel using M10
lugs All inductive devices (relays) switched b y the unit
voltage free contacts must have their coil suppressed
Connect the earth wire to the main protective earth using standard RC suppressors. If these precautions
terminal located in the power panel. are not followed, electrical noise could cause
malfunctions or damage to the unit and its controls.
Co ntr o l Cir c u it Tr a nsfo r m er - Pr im a r y Vo lta g e
Ta pping s Ch illed Liq u id Pu m p Sta r ter

The control circuit transformer (400 V, 2Ø , 50 H z ) Terminals 23 and 24 close to start the liq uid pump. This
providing the 115 V, 1Ø , 50 H z supply to the unit control contact is closed if there is a 'L eaving L iq uid
system is fitted in a separate IP55 enclosure mounted Temperature Cutout' or any of the compressors are
b elow the control panel. running or the daily schedule is not calling for a
shutdown with the unit switch on.
Th e c o ntr o l c ir c u it tr a nsfo r m er is fa c to r y w ir ed fo r
a 40 0 V su pply . The contact must b e used to ensure that the
pump is running in the event of a 'L eaving
Additional primary tappings are availab le for 380 V and L iq uid Temperature Cutout'.
416 V supplies. W hen req uired the tappings should b e
changed:

W ith the supply to the unit isolated remove the lid of the The pump contact will not close to run the pump if the
transformer enclosure and rewire the transformer unit has b een powered up for less than 30 seconds, or if
primary tappings as shown on the wiring diagram or the pump has run in the last 30 seconds, to prevent
transformer lab el. pump motor overheating.

Rem o te Em er g enc y Sto p Dev ic e Ru n Co nta c ts

If req uired, a remote emergency stop device may b e Terminals 25 and 26 close to indicate that refrigerant
wired into the unit. This device should b e rated at 16 system 1 is running and terminals 27 and 28 close to
amps, 110 V, AC-15. The device should b e wired into indicate that refrigerant system 2 is running.
terminals 3 and 4 in the power panel after removing the
factory fitted link . Ala r m Co nta c ts

4.13 Vo lts F r ee Co nta c ts Each refrigerant system has a voltage-free normally


open contact that will close when control power is
All wiring to the voltage free contact terminal b lock on applied to the panel, if no fault conditions are present.
the Interface PCB req uires a supply provided b y the W hen a fault occurs which lock s a system out, or there is
customer max imum voltage 254 Vac, 28 Vdc. a power failure the contact opens. To ob tain a system
alarm signal, connect the alarm circuit to terminals 29
The customer must tak e particular care deriving the and 30 for No. 1 system and terminals 31 and 32 for
supplies for the voltage free terminals with regard to a No. 2 system.
common point of isolation. Thus, these circuits when
used must b e fed via the common point of isolation so
the voltage to these circuits is removed when the
common point of isolation to the unit is opened. This
common point of isolation is not supplied b y J ohnson
Controls.

(01/12)
035-16870-100 Rev. 0 4- 7

4.14 Co ntr o l Pa nel Wir ing

All wiring to the control terminal b lock on the Interface


PCB (nominal 30 Vdc) must b e run in screened cab le,
with the screen earthed at the panel end only. Run
screened cab le separately from mains cab le to avoid
electrical noise pick -up.

The voltage free contacts must b e suitab le for 30 Vdc


(gold contacts recommended). If the voltage free
contacts form part of a relay or contactor, the coil of the
device must b e suppressed using a standard R©
suppressor. The ab ove precautions must b e tak en to
avoid electrical noise that could cause a malfunction or
damage to the unit and its controls.

4.15 Sy stem Inpu ts

Mo d e Selec tio n

Connect a remote switch to terminals 13 and 16 to


provide remote mode selection if req uired. The switch
should b e open for cooling or closed for heating.

F lo w Sw itc h

A liq uid flow switch of suitab le type must b e connected


to terminals 13 and 18 to provide adeq uate protection
against loss of liq uid flow.

Rem o te Sta r t/Sto p

Connect a remote switch to terminals 13 and 14 to


provide remote start/stop control if req uired.

Rem o te Reset o f Liq u id Setpo int

The PW M input (terminals 13 and 20) allows reset of the


liq uid setpoint b y supplying a 'timed' contact closure.
Refer to Section 6 for details.

Rem o te Lo a d Lim iting

L oad limiting prevents the unit from loading b eyond a


desired value. The unit % load limit depends on the
numb er of compressors on the unit. The load limit inputs
to terminals 13 and 21 work in conjunction with the PW M
input to terminals 13 and 20.

(01/12)
4- 8 035-16870-100 Rev. 0

4.16 Co nnec tio n Dia g r a m

(01/12)
035-16870-100 Rev. 0 5- 1

5 COMMISSIONING F a ns: Check that all fans are free to rotate and are not
damaged. Ensure b lades are at the same height when
5.1 Pr epa r a tio n rotated. Ensure fan guard is securely fix ed.

Commissioning of this unit should only b e Co m pr esso r o il: The oil level in multiple scroll
carried out b y J ohnson Controls Authorised compressors (piped in parallel) must b e check ed
personnel. directly after all compressors are shut down and have
b een allowed time to stab ilise.

The oil level must b e b etween ½ and ¾ in the oil sight


The unit On/Off switch on the front of the control panel glass mounted on each compressor.
has b een set to the Off position at the factory. This
switch must remain in the Off position, preventing Despite the oil b alancing line there is a small
running of the unit until commissioned b y Authorised pressure difference within the compressors
personnel. If the switch has b een set to the On position which may lead to confusing oil levels in each
b efore commissioning then it must b e reported to of their respective sight glasses.
J ohnson Controls otherwise the warranty may b e
invalidated.
Iso la tio n/pr o tec tio n: Verify that all sources of electrical
Pr epa r a tio n - Po w er Off supply to the unit are tak en from a point of isolation.

The following check s should b e made with the customer Co ntr o l pa nel: Check the panel to see that it is free of
supply/supplies to the unit switched OF F . foreign materials (wire, metal chips, etc.) and clean out if
req uired.
Inspec tio n: Inspect unit for installation damage. If
found tak e action and/or repair as appropriate. Po w er c o nnec tio ns: Check the customer power
cab les are connected correc tly. Ensure that
Refr ig er a nt c h a r g e: U nits are normally shipped as connections of power cab les within the power panel to
standard with a full refrigerant operating charge. Check the non-fused switch disconnects are tight.
that refrigerant pressure is present in b oth systems and
that no leak s are apparent. If no pressure is present a Ea r th ing : Verify that the unit earth terminal is properly
leak test must b e undertak en, the leak (s) located and connected to a suitab le earthing point. Ensure that all
repaired. Repaired systems must b e evacuated with a unit internal earth connections are tight.
suitab le vacuum pump/recovery unit as appropriate to
b elow 100 microns b efore charging. Co m pr esso r Ov er lo a d Setting s: Check the factory
setting of the Compressor Overload Settings as follows:
Do not charge liq uid refrigerant with static SY S 1 SY S 2
water in the plate heat ex changer. Care must YLAE0 20 0 HP 36 36
also b e tak en to charge liq uid refrigerant YLAE0 240 HP 28 28
slowly to avoid ex cessive thermal stress at the YLAE0 260 HP 44 44
charging point. YLAE0 30 0 HP 57 44
YLAE0 330 HP 57 57
Once the vacuum is b rok en, charge into the condenser YLAE0 370 HP 44 44
coils with the full operating charge as given in Section 9. YLAE0 440 HP 57 44
YLAE0 480 HP 57 57
L iq uid sub -cooling measured at the liq uid line
should b e b etween 8.5 and 11.0 ° C at circuit
full load. Sub -cooling is determined b y the Co ntr o l Cir c u it Tr a nsfo r m er : Verify that the control
level of refrigerant charge in each system. circuit transformer primary tapping is correct for the site
voltage, refer to Section 4 for details.

Va lv es: Ensure that the compressor discharge b all Su pply v o lta g e: Verify that the site voltage supply
valves and the liq uid line service valves are set correctly corresponds to the unit req uirement and is within the
(OPEN). limits given in Section 9. The phase imb alance should
less than 2% of the average voltage.

(01/12)
5- 2 035-16870-100 Rev. 0

Sw itc h Setting s: Ensure that the unit On/Off toggle Pr o g r a m m ed o ptio ns: Verify that the options factory
switch on the control panel is set to OFF. Set the programmed into the Microprocessor Control Centre
non-fused disconnect switch to ON. The customers are in accordance with the customers order
disconnection devices can now b e set to ON. req uirements b y pressing the ‘OPTIONS’ k ey on the
k eypad and reading the settings from the display. Refer
Th e m a c h ine is no w liv e! also to the MBCS Manual for notes and ex planation of
messages.

Pr o g r a m m ed setting s: Ensure the system cut-out and


operational settings are in accordance with operational
req uirements b y pressing the ‘PROG RAM’ k ey (refer to
Cr a nk c a se Hea ter s: Verify the heaters are energised. MBCS Manual).
Depending upon the amb ient temperature the Da te & tim e: Programme the date and time b y first
crank case heaters must b e on for 12 to 24 ensuring that the CL K jumper on the microprocessor
hours b efore start-up. b oard is in the ON position. Then press the ‘CL OCK ’ k ey
and set the date and time (refer to MBCS Manual).

Wa ter Sy stem : Verify that the liq uid system has b een Sta r t/Sto p sc h ed u le: Programme the daily and holiday
installed correctly, and has b een commissioned with the start/stop b y pressing the ‘SCH EDU L E/ADVANCE
correct direction of water flow through the plate heat DAY ’ k ey (refer to MBCS Manual).
ex changer. Inlet should b e at the refrigerant pipework
connection end of the plate heat ex changer. Purge air Setpo ints: Set the req uired leaving chilled liq uid
from the plate heat ex changer using the air vent temperature set-point and control range using the
mounted in the pipework . ‘COOL ING SETPOINTS’ k ey (refer to MBCS Manual).

Flow rates and pressure drops must b e within the limits Co m pr esso r Oper a tio n: U se the ‘OPTIONS’ k ey to
given in Section 9. Operation outside of these limits is switch off each refrigerant system in turn (refer to MBCS
undesirab le and could cause damage. Manual) and then check the compressors on the active
system:
F lo w sw itc h : Verify a liq uid flow switch is correctly fitted
in the customer’s pipework on the plate heat ex changer Connect a manifold gauge to each refrigerant circuit
outlet, and wired into the control panel correctly. suction and discharge service valves and temporarily
start each compressor and check that the discharge
Tem per a tu r e senso r (s): Ensure the leaving (-BL CT) pressure rises and the suction pressure decreases to
liq uid temperature sensor is coated with heat ensure that the compressors are operating in the correct
conductive compound (Part No. 013-00890-000) and direction. Any faults found must b e corrected b efore
are inserted in the water inlet and outlet sensor pock ets starting the unit.
of the cooler.
After completing the check s on b oth circuits, set b oth
Co ntr o l su pply : Verify the control panel display is systems to on using the ‘OPTIONS’ k ey.
illuminated.

HP c u t -o u t r eset : Check that the hand reset


mechanical high pressure cut-outs mounted on the
discharge lines are at the correct setting and are reset.

(01/12)
035-16870-100 Rev. 0 5- 3

5.2 F ir st Tim e Sta r t-u p Th er m a l Ex pa nsio n v a lv e a d ju st m ent : The


ex pansion valves are factory set and should not need
During the commissioning period there should adjustment. If any superheat values are out of range,
b e sufficient heat load to run the unit under however, the ex pansion valve adjusting screw should
stab le full load operation to enab le the unit b e adjusted no more than 1 turn at a time (‘in’ to increase
controls, and system operation to b e set up superheat, ‘out’ to decrease superheat), allowing at
correctly and a commissioning log tak en. least 10 minutes for the valve to stab ilise b efore
Read the following section in conjunction with recheck ing the value of superheat.
the MBCS Manual, then proceed step b y step
as follows: Su b c o o ling : Check liq uid sub cooling at steady full
compressor load only. It is important that all fans are
Inter lo c k s: Verify that liq uid is flowing through the plate running for the system. Measure liq uid line temperature
heat ex changer and that a load is present. Ensure that on the copper line b eside the main liq uid line service
any remote run interlock s are in the run position and that valve. Measure liq uid pressure at the liq uid line service
the run schedule req uires the unit to run or is overridden. valve. Sub cooling should b e 5° C to 7° C relative to the
’b ub b le’ temperature. If sub cooling is out of range add or
Sta r t-u p: Set the unit switch to the ON position to start remove refrigerant as req uired. Do not overcharge the
the unit (there may b e a few seconds delay b efore the unit.
first compressor starts b ecause of the anti-recycle
timer). Be ready when each compressor starts, to switch Gener a l o per a tio n: After completion of the ab ove
the unit off immediately if any unusual noises or other check s for System 1 repeat the process for system 2. In
adverse conditions develop. Refer to the Section 6 for addition, check that loading occurs as specified in the
the normal operating seq uence from start-up. Section 6 and that general operation is correct.

Refr ig er a nt flo w : W hen a compressor starts a flow of


liq uid refrigerant will b e seen in the liq uid line sight glass.
After several minutes operation and providing a full
charge of refrigerant is in the system, the b ub b les will
disappear and b e replaced b y a solid column of liq uid.
Check that the moisture indicator is satisfactory
(G reen).

Sy stem Oper a tio n: U se the ‘OPER DATA’ k ey to check


the system pressures and temperatures.

F a n r o t a t io n: As discharge pressure rises, the


condenser fans operate in stages to control the
pressure. Verify that the fan operation is correct for the
type of unit.

Su c tio n Su per h ea t: Check suction superheat at steady


full system load only. It is important that no b ub b les
show in the liq uid line sight glass. Measure suction
temperature on the copper line ab out 150 mm b efore the
compressor suction service valve. Measure suction
pressure at the compressor service valve. Superheat
should b e 5.5° C to 7.0° C relative to the ‘dew’
temperature.

(01/12)
5- 4 035-16870-100 Rev. 0

This Page L eft Intentionally Blank

(01/12)

You might also like