PIT
MACHINE OVER
LOAD SPEED CAR INSIDE LIFT - WELL ENTRANCE DEPT
ROOM HEAD
(m.p.s) H
PERSONS Kg. A B C D E K L
MANUAL DOOR
10 680 1.00 & 1.50 1350 1300 1800 2000 800 3300 4500 4400
1.00 & 1.50 2000 1100 2500 1800 900 4000 4300
13 884
2.50 2000 1100 2500 1900 900 4000 4400 2500 5400
1.50 2000 1300 2500 2100 1000 4000 4600 1600 4400
16 1088
2.50 2000 1300 2500 2100 1000 4000 4600 2500 5400
1.50 2000 1550 2500 2400 1000 4000 4900 1600 4400
20 1360
2.50 2000 1550 2500 2400 1000 4000 4900 2500 5400
SPECIFICATIONS AND STANDARDS
Passenger Loads (Kg.) Area Sq. metre
4 272 0.77
Area of
5 340 0.95
CAR/CAGE
6 408 1.12
inside
7 476 1.28
8 544 1.45
Leveling
Accuracy Single speed upto 0.65 M/Sec upto ± 75mm
Permissible VF upto 1.00 M/Sec upto ± 7-10mm
as per BIS
Running
Sill to Sill ± 20-25mm
Clearance
Door Opening
700mm width X 2000mm Height
(MINIMUM)
Lift Shaft 250 mm thick Brick wall OR 125 mm thick RCC wall (without plaster)
Enclosure OR 5 mm thick toughened glass OR Expanded metal sheet (2sq. Inch)
1) Floor must be atleast 150 mm thick.
2) Wall should not be common with either water tank or Bath room or toilet or any other similar construction.
3)Door must open towards outside.
Machine Room
4) Must be provided with cross ventilation arrangement.
5)Door size is 915 mm width X 2000 mm Height
6) Approch stair must be Regular Stair or step system stair and must be able to take a load off 300 Kg.
Lift (Electric) IS No. 14665 / 1988
Ropes IS No. 2365 / 1977
Bureau of Indian
Outline dimension IS No. 3534 / 1979
Standards
Safety Gear & Governor IS No. 9878 / 1981
References
Guid Rails IS No. 10448 / 1982
Car & Counter Guide Shoe IS No. 11615 / 1986
1) 3 Phase copper wiring with P.V.C Insulation to be provided &
terminated on main switch in machine room.( With 32 Amp. Tpn)
2) Adequate permanent lighting to be provided in the machine room & lift pit.
Electrical
3)Convenient outlet 15 AMPS / 5 AMPS in the machine room.
4) 1 phase lighting wiring for lighting to be provided & terminated on SPN (Single phase with neutral) in machine room.Wiring
from SPN to be provided & terminated on out-let 5 AMPS at half of hoist way.
Auto Door Collapsible door Telescopic SS Finish
Control Panel with Goods Elevator Door Operator COP & LOP
VVVF drive Mechanism
Guide Shoe
Counter Guide Shoe Governor Safety Block