PV SYSTEM TESTING AND COMMISSIONING REPORT

Part A: PV System Inspection Report Initial verification


Periodic verification

Installation Address : Reference

Circuits Inspected: Date:

Inspected By: Witnessed By:

Yes No NA Remarks
1.0 DC System - General
1.1 The DC System has been designed,
specified and installed to the
requirements of SS638 and IEC
62548:2016

1.2 The maximum PV array is suitable for


the array location

1.3 All system components and mounting


structures have been selected and
erected to withstand the expected
external influences such as wind,
temperature and corrosion

1.4 Roof fixing and cable entries are


weatherproof (where applicable).

2.0 DC System – Protection against electric shock


2.1 Protective measure provided by extra
low voltage (SELV/PELV)

2.2 Protection by use of class II or


equivalent insulation adopted on the DC
side
2.3 PV String and array cables have been
selected and erected so as to minimise
the risk of earth faults and short circuits.
Typically achieved by the use of cables
with protective and reinforced insulation
(often termed "double insulated")

3.0 DC System - Protection against the effects of insulation faults


3.1 Galvanic separation in place inside the
inverter or

3.2 Functional earthinq of any DC


conductor

3.3 PV Array Earth Insulation Resistance


detection and alarm system is installed
– to the requirements of IEC
62548:2016
8 Boon Lay Way
#05-06 Tradehub 21
Singapore- 609964
GST Reg.No:202213083W

PV SYSTEM TESTING AND COMMISSIONING REPORT

Yes No NA Remarks
3.4 PV Array Earth Residual Monitoring
detection and alarm is installed - to the
requirements of IEC 62548:2016

4.0 DC System - Protection against overcurrent


4.1 For system without string overcurrent
protective device:

• IMOD_MAX_OCPR (the module


maximum series fuse rating) is greater
than the possible reverse current
4.2 For system without string overcurrent
protective device:

• String cables are sized to


accommodate the maximum combined
fault current from parallel string

4.3 For systems with string overcurrent


protective device:

• String overcurrent protective devices


are fitted and correctly specified to
therequirements of IEC 62548:2016

4.4 For system with array/ sub-array


overcurrent protective devices:

• Overcurrent protective devices are


fitted and correctly specified to the
requirements

4.5 For systems where the inverter(s) can


produce DC back-feed into the PV array
circuits:

• Any back-feed current is lower than


both the module maximum fuse
rating andthe string cable ampere
rating

5.0 DC System – Earthing and bonding arrangements


5.1 Where the PV system includes
functional earthing of one of
the DC conductors:

• The functional earth connection has


been specified and installed to the
requirements of IEC 62548:2016

5.2 Where a PV system has a direct


connection to earth on the DC side:

• A functional earth fault interrupter is


provided to the requirements of IEC
62548:2016

5.3 Array frame bonding arrangements


have been specified and installed
to therequirements of IEC
62548:2016

5.4 Where protective earthing and/or


equipotential bonding conductors are
installed:

• They are parallel to, and bundled with


the DC cables
8 Boon Lay Way
#05-06 Tradehub 21
Singapore- 609964
GST Reg.No:202213083W

PV SYSTEM TESTING AND COMMISSIONING REPORT

Yes No NA Remarks

6.0 DC System – Protection against the effect of lightning and overvoltage


6.1 To minimize voltages induced by
lightning, the area of all wiring loops
has been kept as small as possible

6.2 Measures are in place to protect long


cables (e.g. Screening or the use of
SPDs)

6.3 Where SPDs are fitted, they have been


installed to the requirements of IEC
62548:2016

7.0 DC System – Protection against the effect of lightning and overvoltage


7.1 The PV modules are rated for the
maximum possible DC system voltage

7.2 All DC components are rated for


continuous operation at DC and at the
maximum possible DC system voltage
and current as defined in IEC
62548:2016

7.3 Wiring systems have been selected and


erected to withstand the expected
external influences such as wind,
temperature, UV and solar radiation

7.4 Means of isolation and disconnection


have been provided for the PV array
strings and PV sub-arrays - to the
requirements of IEC 62548:2016

7.5 A DC switch disconnector is fitted to the


DC side of the inverter to the
requirement of IEC 62548:2016

7.6 If blocking diodes are fitted, their


reverse voltage rating is at least 2 x Voc
(STC) of the PV string in which they are
fitted (see IEC 62548:2016)

7.7 Plug and socket connectors mated


together are of the same type and from
the same manufacturer and comply with
the requirements of IEC 62548:2016

8.0 AC System
8.1 A means of isolating the inverter has
been provided on the AC side

8.2 All isolation and switching devices have


been connected such that PV
installation is wired to the "load" side
and the public supply to the "source"
side

8.3 The inverter operational parameters


have been programmed to local
regulations
8 Boon Lay Way
#05-06 Tradehub 21
Singapore- 609964
GST Reg.No:202213083W

PV SYSTEM TESTING AND COMMISSIONING REPORT

Yes No NA Remarks
8.4 Where a RCD is installed to the AC
circuit feeder an inverter, the RCD type
has been verified to ensure it has been
selected accordingly to the
requirements of IEC 62548:2016

9.0 Labeling and Identification


9.1 All circuits, protective devices, switches
and terminals suitably labelled to the
requirements of SS 638 and IEC
62548:2016

9.2 A ll DC junction boxes (PV generator


and PV array boxes) carry a warning
label indicating that active parts inside
the boxes are fed from a PV array and
may still be live after isolation from the
PV inverter and public supply

9.3 Means of isolation on the AC side is


clearly labelled
9.4 Dual supply warning labels are fitted at
point of interconnection

9.5 A single line wiring diagram is displayed


on site
9.6 Installer details are displayed on site

9.7 Shutdown procedures are displayed on


site
9.8 Emergency procedures are displayed
on site (where relevant)

9.9 All signs and labels are suitably affixed


and durable
8 Boon Lay Way
#05-06 Tradehub 21
Singapore- 609964
GST Reg.No:202213083W

PV SYSTEM TESTING AND COMMISSIONING REPORT

Part B: PV Array Test Report Initial verification


Periodic verification

Installation Address : Reference

Circuits Inspected: Date:

Inspected By: Witnessed By:

Test Instruments Brand Model Serial No. Remarks

Inverter No. / Model


Inverter Serial Number
Inverter Functions Correctly Yes / No
Total Connected DC Capacity
(Wp)
MPPT No. MPPT 1 MPPT 2 MPPT 3 MPPT 4 MPPT 5 MPPT 6
String No. S1 S2 S3 S4 S5 S6 S7 S8 S9 S10 S11 S12
Make/Model
Watt-Peak
(Wp)
Module
Voc (STC)
Isc (STC)
Quantity
Type
String over-
Rating (A)
current
protective DC rating (V)
device Capacity (KA)
Type
Wiring
Line (mm²)
Voc (V)
String test
Isc (A)
(Pass /Fail) Irradiance
(W/m2)
Polarity check
Test voltage
Array insulation (V)
resistance Positive - Earth
(MΩ)
(Pass / Fail) Negative -
Earth (MΩ)
Earth continuity (where fitted)

Comments
8 Boon Lay Way
#05-06 Tradehub 21
Singapore- 609964
GST Reg.No:202213083W

PV SYSTEM TESTING AND COMMISSIONING REPORT

Part B: PV Array Test Report Initial verification


Periodic verification

Installation Address : Reference

Circuits Inspected: Date:

Inspected By: Witnessed By:

Test Instruments Brand Model Serial No. Remarks

Inverter No. / Model


Inverter Serial Number
Inverter Functions Correctly Yes / No
Total Connected DC Capacity
(Wp)
MPPT No. MPPT 1 MPPT 2 MPPT 3 MPPT 4 MPPT 5 MPPT 6
String No. S1 S2 S3 S4 S5 S6 S7 S8 S9 S10 S11 S12
Make/Model
Watt-Peak
(Wp)
Module
Voc (STC)
Isc (STC)
Quantity
Type
String over-
Rating (A)
current
protective DC rating (V)
device Capacity (KA)
Type
Wiring
Line (mm²)
Voc (V)
String test
Isc (A)
(Pass /Fail) Irradiance
(W/m2)
Polarity check
Test voltage
Array insulation (V)
resistance Positive - Earth
(MΩ)
(Pass / Fail) Negative -
Earth (MΩ)
Earth continuity (where fitted)

Comments
8 Boon Lay Way
#05-06 Tradehub 21
Singapore- 609964
GST Reg.No:202213083W
PV SYSTEM TESTING AND COMMISSIONING REPORT
Part C: AC test Report Initial verification
Periodic verification

Installation address: Reference


Description of work under test: Date:
Tested By: Witnessed by:

Test Instruments Brand Model Serial No. Remarks


Insulation continuity tester
Digital Multimeter

Type & Size of Rating Line to Neutral (MΩ) Line to Earth (MΩ) Line to Line (MΩ)
& Remarks
Cable/Busbar Phase L1-N L2-N L3-N N-E L1-E L2-E L3-E L1-L2 L1-L3 L2-L3

Rating Line to Neutral (V) Line to Earth (V) Line to Line (V) Remarks
Description &
Phase L1-N L2-N L3-N N-E L1-E L2-E L3-E L1-L2 L1-L3 L2-L3

AC Voltage

Continuity Test

Phase Rotation