T EC H N I C A L C ATA LO G U E

SACE Emax 2
Low voltage air circuit-breakers

SACE Emax 2
Consultation guide

Chapter 1 Chapter 6

Main characteristics Accessories


Overview of the SACE Emax 2 fam- Accessories for SACE Emax 2 circuit
ily, distinctive features of the se- breakers (signaling, control, inter-
ries, product conformity and ser- locks, etc..) and for Ekip protection
vice. trip units (connectivity, measure-
ments, protection, etc).

Chapter 2 Chapter 7

The ranges Installation


Electrical characteristics of auto- Installation and circuit breaker per-
matic circuit breakers, switch dis- formance in switchgear, installa-
connectors and derived versions. tion environment, degree of pro-
tection and limiting curves.

Chapter 3 Chapter 8

Protection trip units Overall dimensions


Latest generation Ekip protec- Overall dimensions for fixed circuit
tion trip units for power distri- breakers, withdrawable circuit
bution and generation. breakers and accessories.

Chapter 4 Chapter 9

Software functions Wiring diagrams


New generation of functionalities Circuit-breaker and accessories
ready for every type of system wiring diagrams.
and simple to use.

Chapter 5 Chapter 10

Supervision and connectivity Ordering codes


Supervision, Energy Management Ordering codes with configuration
and complete integration in the examples.
systems with the possibility of
communicating with several proto-
cols and energy management via
cloud.
2/2 S A C E E M A X 2 LO W V O LTA G E A I R C I R C U I T- B R E A K E R S


SACE Emax 2 automatic circuit breakers
Common data
Rated service voltage Ue [V] 690
Rated insulation voltage Ui [V] 1000
Rated impulse withstand voltage Uimp [kV] 12
Frequency [Hz] 50 - 60
Number of poles 3- 4
Version Fixed - Withdrawable
Suitable for isolation according to IEC 60947-2

SACE Emax 2 E1.2


Performance levels B C N
Rated uninterrupted current Iu @ 40°C [A] 630 630 250
[A] 800 800 630
[A] 1000 1000 800
[A] 1250 1250 1000
[A] 1600 1600 1250
[A] 1600
[A]
Neutral pole current-carrying capacity for 4-pole CBs [%Iu] 100 100 100
Rated ultimate short-circuit 400-415 V [kA] 42 50 66
breaking capacity Icu
440 V [kA] 42 50 66
500-525 V [kA] 42 42 50
690 V [kA] 42 42 50
Rated service short-circuit breaking capacity Ics [%Icu] 100 100 100 1)
Rated short-time withstand (1s) [kA] 42 42 50
current Icw
(3s) [kA] 24 24 30
Rated short-circuit making 400-415 V [kA] 88 105 145
capacity (peak value) Icm
440 V [kA] 88 105 145
500-525 V [kA] 88 88 105
690 V [kA] 88 88 105
Utilization category (according to IEC 60947-2) B B B
Breaking 4) Maximum breaking time for I<Icw [ms] 40 40 40
Maximum breaking time for I>Icw [ms] 25 25 25
Dimensions H - Fixed/Withdrawable [mm] 296/363.5 296/363.5 296/363.5
D - Fixed/Withdrawable [mm] 183/271 183/271 183/271
W - Fixed 3p/4p/4p FS [mm] 210/280
W - Withdrawable 3p/4p/4p FS [mm] 278/348
Weights (CB with trip unit and Fixed 3p/4p/4p FS kg 14/16
current sensor) Withdrawable 3p/4p/4p FS kg 38/43
including fixed part
1) Ics : 50kA for 400V…440V voltage; 2) Ics: 125kA for 400V...440V voltage; 3) E4.2H 3200A: 66 Icw (3s); 4) Total clearing time is the sum of breaking time and trip time

SACE Emax 2 E1.2


Mechanical life with regular ordinary [Iu] ≤ 1000 1250 1600
maintenance prescribed by the manufacturer
[No. cycles x 1000] 20 20 20
Frequency [Oper./Hour] 60 60 60
Electrical life with regular 440 V [No. cycles x 1000] 8 8 8
ordinary maintenance prescribed
690 V [No. cycles x 1000] 8 6,5 6,5
by the manufacturer
Frequency [Oper./Hour] 30 30 30
THE R ANGES 2/3

02
E2.2 E4.2 E6.2
B N S H N S H V H V X
1600 800 250 800 3200 3200 3200 2000 4000 4000 4000
2000 1000 800 1000 4000 4000 4000 2500 5000 5000 5000
1250 1000 1250 3200 6300 6300 6300
1600 1250 1600 4000
2000 1600 2000
2500 2000 2500
2500
100 100 100 100 100 100 100 100 50-100 50-100 50-100
42 66 85 100 66 85 100 150 100 150 150
42 66 85 100 66 85 100 150 100 150 150
42 66 66 85 66 66 85 100 100 130 130
42 66 66 85 66 66 85 100 100 100 100
100 100 100 100 100 100 100 100 2) 100 100 100
42 66 66 85 66 66 85 100 100 100 120
42 50 50 66 50 66 75 3) 75 100 100 100
88 145 187 220 145 187 220 330 220 330 440
88 145 187 220 145 187 220 330 220 330 440
88 145 145 187 145 145 187 220 220 286 286
88 145 145 187 145 145 187 220 220 220 264
B B B B B B B B B B B
40 40 40 40 40 40 40 40 40 40 40
25 25 25 25 25 25 25 25 25 25 25
371/425 371/425 371/425 371/425 371/425 371/425 371/425 371/425 371/425 371/425 371/425
270/383 270/383 270/383 270/383 270/383 270/383 270/383 270/383 270/383 270/383 270/383
276/366 384/510 762/888/1014
317/407 425/551 803/929/1069
41/53 56/70 109/125/140
84/99 110/136 207/234/260

E2.2 E4.2 E6.2


< 1600 1600 2000 2500 < 2500 2500 3200 4000 4000 5000 6300
25 25 25 20 20 20 20 15 12 12 12
60 60 60 60 60 60 60 60 60 60 60
15 12 10 8 10 8 7 5 4 3 2
15 10 8 7 10 8 7 4 4 2 2
30 30 30 30 20 20 20 20 10 10 10
3/14 S A C E E M A X 2 LO W V O LTA G E A I R C I R C U I T- B R E A K E R S


Overview
SACE Emax 2 trip units offer a complete range of solutions for any
installation requirements, for both distribution and generator protection.
New features are now available with a renewed black look and feel.

Ekip Dip: The standard trip unit

Ekip Dip LI
Ekip Dip LSI
Ekip Dip LSIG

• Overcurrent protection for distribution systems


• Phase and neutral current measurements
• LED Permanent trip cause signalization
• Ekip Multimeter to display data and measure-
ments

Ekip Touch: The smart trip unit

Ekip Touch LI
Ekip Touch LSI
Ekip Touch LSIG

• Advanced set of protections and measure-


ments, always upgradable and customizable
• Intuitive touchscreen interface
• High measurement accuracy of electrical pa-
rameters

Ekip Hi-Touch: The ultimate trip unit

Ekip Hi-Touch LSI


Ekip Hi-Touch LSIG

• Complete set of protections and measurements


• Dual settings of protection
• Network Analyzer function
P R OT E C T I O N T R I P U N I T S 3/15

03
Ekip G: The generator trip unit

Ekip G Touch LSIG


Ekip G Hi-Touch LSIG

• Designed for installations with generators such


as Genset, cogeneration and marine applica-
tions
• Dedicated set of generator protections

Ekip LCD: The hardened trip unit

Ekip LCD LI
Ekip LCD LSI
Ekip LCD LSIG
Ekip Hi-LCD LSI
Ekip Hi-LCD LSIG
Ekip G LCD LSIG
Ekip G Hi-LCD LSIG

• Suitable for installation in aggressive environ-


ments and secure applications
• Available for both distribution and generator
protection functions

Protection Watchdog
SACE Emax 2 trip units offer a great variety of The Ekip trip units ensure high reliability thanks
overcurrent protection functions, with thresholds to an electronic circuit that periodically checks
and timing that can be easily set through dip the continuity of internal connections, such as
switches or few simple steps directly from the trip coil, rating plug and each current sensor
touchscreen display. These units are available in (ANSI 74).
different versions: LI, LSI, LSIG. In case of an alarm, a message is shown on the
All the Ekip trip units also include a thermal mem- display (Ekip Touch) or through LEDs signaliza-
ory function. The protection unit is able to record tion (Ekip Dip). If a protection function inter-
the trips which have occurred in the last few min- venes, the unit always checks that the circuit
utes. Since the trip causes overheating, in order breaker has been opened through auxiliary con-
to protect the cables and let them cool down, the tacts that indicate the position of the main con-
trip unit imposes a shorter delay tripping time in tacts. Otherwise, the unit creates an alarm (ANSI
case of a fault. In this way, the system is pro- BF code - Breaker Failure) that can be used to
tected against damages due to cumulative over- command the opening of the upstream circuit
heating. breaker. Ekip trip units are also provided with
self-protection against abnormal temperature
(OT) to ensure correct operations.
3/18 S A C E E M A X 2 LO W V O LTA G E A I R C I R C U I T- B R E A K E R S


Technical characteristics for protection
trip units
Protection functions

ABB Code ANSI/IEEE Function Threshold


C37.2 Code
L 49 Overload protection I1 = 0.4 - 0.42 - 0.45 - 0.47 - 0.5 - 0.52 - 0.55 - 0.57 - 0.6 - 0.62 - 0.65 - 0.67 - 0.7 -
0.72 - 0.75 - 0.77 - 0.8 - 0.82 - 0.85 - 0.87 - 0.9 - 0.92 - 0.95 - 0.97 - 1 x In
Thermal memory
Tolerance trip between 1.05 and 1.2 x I1

S 50TD Time-delayed overcurrent protection I2 = 0.6 - 0.8 - 1 - 1.5 - 2 - 2.5 - 3 - 3.5 - 4 - 5 - 6 - 7 - 8 - 9 - 10 x In


Tolerance ± 7% If ≤ 6 x In
± 10% If > 6 x In
51 Time-delayed overcurrent protection I2 = 0.6 - 0.8 - 1 - 1.5 - 2 - 2.5 - 3 - 3.5 - 4 - 5 - 6 - 7 - 8 - 9 - 10 x In
Thermal memory
Tolerance ± 7% If ≤ 6 x In
± 10% If > 6 x In
I 50 Instantaneous overcurrent protection I3= 1.5 - 2 - 3 - 4 - 5 - 6 - 7 - 8 - 9 - 10 - 11 - 12 - 13 - 14 - 15 x In
Tolerance ± 10%
G 50N TD Earth fault protection I4 (1) = 0.1 - 0.2 - 0.3 - 0.4 - 0.6 - 0.8 - 1 x In

Tolerance ± 7%

51N Earth fault protection I4 (1) = 0.1 - 0.2 - 0.3 - 0.4 - 0.6 - 0.8 - 1 x In

Tolerance ± 7%
(1) With Vaux all thresholds are available. Without Vaux minimum threshold is limited to: 0.3In (with In = 100A), 0.25In (with In = 400A) or 0.2In (for all other ratings)
(2) The minimum trip time is 1s, regardless of the type of curve set (self-protection)
(3) Total clearing time is the sum of breaking time and trip time

The tollerances above apply to trip units already powered by the main
circuit with current flowing in at least two phases or an auxiliary power
supply. In all other cases the following tollerance values apply

ABB Code Trip threshold Trip time


L Trip between 1.05 and 1.2 x I1 ± 20%
S ± 10% ± 20%
I ± 15% ≤ 60ms
G ± 15% ± 20%
P R OT E C T I O N T R I P U N I T S 3/19

03
Trip time (3) Excludibility Pre Alarm Trip curve Ekip Dip

with If = 3 I1, t1 = 3 - 12 - 24 - 36 - 48 - 72 - 108 - 144s (2) no 50 ... 90% I1 t = k / I2


Step 1%
no
± 10% If ≤ 6 x In
± 20% If > 6 x In
with If > I2, t2 = 0.1 - 0.2 - 0.3 - 0.4 - 0.5 - 0.6 - 0.7 - 0.8s yes - t=k
The better of the two data:
± 10% t2 or ± 40 ms
with If = 10 In, t2 = 0.1 - 0.2 - 0.3 - 0.4 - 0.5 - 0.6 - 0.7 - 0.8s yes - t = k / I2
yes -
± 15% If ≤ 6 x In
± 20% If > 6 x In
Instantaneous yes - t=k
≤ 30 ms
with If > I4, t4 = 0.1 - 0.2 - 0.4 - 0.8s yes 50 ... 90% I4 t=k
Step 1%
The better of the two data:
± 10% t4 or ± 40 ms
with If = 3In, t4 = 0.1 - 0.2 - 0.4 - 0.8s yes 50 ... 90% I4 t = k / I2
Step 1%
± 15%
6/4 SACE EMAX 2 LOW VOLTAGE AIR CIRCUIT-BREAKERS


Accessories for circuit-breakers
SACE Emax 2 circuit-breakers offer a wide range tion and installation requirements of every cus-
of accessories developed to satisfy the applica- tomer.

Automatic Switch- Derived versions


circuit-breaker disconnector
E1.2 E2.2 - E1.2 E2.2 - CS MT MTP
E4.2 - E4.2 - E2.2 - E4.2 - E6.2
E6.2 E6.2
Signalling
Standard open/closed auxiliary contacts - AUX 4Q / / / / - -
Open/closed auxiliary contacts - AUX 6Q - / - / - -
Open/closed auxiliary contacts- AUX 15Q / / / / - -
Auxiliary position contacts - AUP
Ready to close signalling contact - RTC / / / / - - -
TU Reset mechanical signalling of the tripping of protection trip unit - TU Reset / / - - - - -
Contact signalling tripping of Ekip protection trip unit - S51 / / - - - - -
Second contact signalling tripping of Ekip protection trip unit - S51/2 - / - - - - -
Contact signalling loaded springs – S33 M/2 (supplied with Motor) / / / / - -
Control
Opening and closing release - YO/YC / / / / - - *
Second opening and closing release - YO2/YC2 / / / / - - -
Undervoltage release - YU / / / / - - -
Electronic time-delay device for undervoltage release - UVD / / / / - - -
Motor - M / / / / - -
Remote reset - YR / / - - - - -
Opening and closing release test unit - YO/YC Test Unit / / / / - - *
Safety
Key lock and padlock in open position - KLC and PLC / / / / - -
Key lock and padlock in racked-in / test / racked-out position - KLP and PLP
Shutter lock - SL
Lock for racking-out mechanism with circuit-breaker in closed position
Lock for racking in / racking out the mobile part when the door is open - DLR - - - -
Lock to prevent door opening when circuit-breaker is in racked-in /
- -
test position - DLP
Lock to prevent door opening when circuit-breaker is in closed position - DLC / / / / - -
Anti-insertion lock / / / /
Mechanical operation counter - MOC / / / / - -
Protection devices
Protection device for opening and closing pushbuttons - PBC / / / / - -
IP30 Protection / / / / - -
IP54 Protection / / / / - -
Terminal covers - HTC / LTC / - - - - - -
Separators - PB / / / / - - -
Connections
Orientable rear terminal - HR/VR / / / / - -
Front terminal - F / / - -
Other configurations / / / / - -
Interlocks and switching devices
/ / / / / / / /
Mechanical interlock - MI - - -

Automatic transfer switches - ATS / / / / - - -


Standard accessory for fixed circuit-breaker Standard accessory for fixed part
Accessory on request for fixed circuit-breaker Accessory on request for fixed part
Standard accessory for mobile part * Only closing release YC
Accessory on request for mobile part
ACCESSORIES 6/5

Signalling
Open / closed auxiliary contacts - AUX (Fig. 01A/B/C)
SACE Emax 2 circuit-breakers can be equipped with auxiliary contacts that signal the open or closed
status of the circuit-breaker. The first block of four standard contacts is always provided with the auto-
matic circuit-breakers. The switching contacts are available in the following configurations:
Open / closed auxiliary contacts (AUX 4Q) E1.2 E2.2 … E6.2
4 auxiliary standard
contacts digital signals
— mixed
Fig. 01-A
Open / closed supplementary auxiliary contacts (AUX 6Q)
6 auxiliary standard -
contacts digital signals -
mixed -
Open / closed external supplementary auxiliary contacts (AUX 15Q)
15 auxiliary standard
contacts digital signals

Fig. 01-B Maximum number of open / closed 19 25
auxiliary contacts that can be installed

Standard contact Contact for digital signals


Type changeover contacts changeover contacts
Minimum load 100mA @ 24V 1mA @ 5V
Breaking capacity
DC 24V - 0.1A

06
125V 0.3A @ 10ms -
250V 0.15A @ 10ms -
AC 250V 5A @ cosϕ 1 -

Fig. 01-C 5A @ cosϕ 0.7 -
5A @ cosϕ 0.3 -
400V 3A @ cosϕ 1 -
2A @ cosϕ 0.7 -
1A @ cosϕ 0.3 -


Electrical diagram reference: figures 1, 81, 91

Aux 6Q is an alternative to the Ekip Signalling 4K module. AUX 15Q is an alternative to the mechanical
interlock (MI), the DLC for E1.2 lock or the DLP lock if mounted on the right side.
6/6 SACE EMAX 2 LOW VOLTAGE AIR CIRCUIT-BREAKERS


Accessories for circuit-breakers
Auxiliary position contacts - AUP (Fig. 02A/B)
When the circuit-breaker is a withdrawable version, the position of the mobile part can be signalled
electrically by accessorizing the fixed part with one of the following signalling contact units:
Auxiliary position contacts (AUP) E1.2 E2.2 … E6.2
6 auxiliary standard -
contacts digital signals -
5 auxiliary standard -
contacts digital signals -
5 standard -
supplementary

auxiliary digital signals -
Fig. 02-A
contacts
Maximum number of auxiliary position
6 10
contacts that can be installed

Standard contact Contact for digital signals


Type changeover contacts changeover contacts
Minimum load 100mA @ 24V 1mA @ 5V
Breaking capacity

Fig. 02-B DC 24V - 0.1A
125V 0.3A @ 0ms -
250V 0.15A @ 0ms -
AC 250V 5A @ cosϕ 1 -
5A @ cosϕ 0.7 -
5A @ cosϕ 0.3 -
400V 3A @ cosϕ 1 -
2A @ cosϕ 0.7 -
1A @ cosϕ 0.3 -

Electrical diagram reference: figures 95, 96, 97

Ready to close signalling contact - RTC (Fig. 03)


The ready to close signalling contact – RTC – indicates that the circuit-breaker is ready to receive the closing
command. The circuit-breaker is ready to close when the following conditions have been met:
• circuit-breaker open
• springs loaded
• no opening command or locks on the opening command
• circuit-breaker reset following tripping of Ekip protection trip unit
• YU energized.
Standard contact Contact for digital signals
Type Switching
Minimum load 100mA @ 24V 1mA @ 5V
Breaking capacity
— 24V - 0.1
DC
Fig. 03 250V 0.5A @ 0ms / 0.2A 10ms -
AC 250V 3A @ cosϕ 0.7 -

Electrical diagram reference: figure 71
ACCESSORIES 6/7

Mechanical signalling of the tripping of protection trip unit - TU Reset (Fig. 04)
The automatic circuit-breakers are always equipped with a mechanical device that signals
the tripping status of the protection trip units. After the Ekip trip unit has tripped due to an electrical
fault, the signalling device clearly indicates the tripping status on the front of the circuit- breaker. The
— circuit-breaker can be reset only after the signalling pushbutton has been restored to its normal oper-
Fig. 04 ating position. The device conforms to the Ansi 86T standard.
Emax 2 is fitted with the anti-pumping function. With the anti-pumping function the opening order al-
ways takes priority over a closing order. Moreover, when the Circuit Breaker is in open position due to a
trip, the anti-pumping function allows the reclosing of the operating mechanism only after a reset of
the trip, avoiding improper or accidental closing.

Contact signalling tripping of protection trip unit Ekip – S51 (Fig. 05)
The contact signals the opening of the circuit- breaker after the Ekip protection trip unit has tripped.
The circuit-breaker can only be closed after the “TU Reset” tripped trip unit mechanical signalling push-
button has been restored to its normal operating position.
The switching contact, which is always supplied with the standard version of the automatic cir-
cuit-breakers, is also available on request in a version for digital signals (for electrical characteristics,
please refer to the RTC contact). It can also be associated with an optional accessory for resetting by

remote control - YR. For electromechanical characteristics, please refer to the RTC contact.
Fig. 05 For E2.2, E4.2 and E6.2 it is possible to double the signal for the tripping of the Ekip Trip Unit specifying
the dedicated code for the S51/2. The S51/2 is an alternative of the YR contact.

Electrical diagram reference: figure 11

06
Contact signalling loaded springs – S33 M/2
This contact is always supplied with a geared motor; it remotely signals the spring status of the circuit-
breaker operating mechanism. It is available in both standard version and version for digital signals.

Standard contact Contact for digital signals


Type changeover contacts changeover contacts
Minimum load 100mA @ 24V 1mA @ 5V
Breaking capacity
DC 24V - 0.1A
125V 0.3A @ 0ms -
250V 0.15A @ 0ms -
AC 250V 5A @ cosϕ 1 -
5A @ cosϕ 0.7 -
5A @ cosϕ 0.3 -
400V 3A @ cosϕ 1 -
2A @ cosϕ 0.7 -
1A @ cosϕ 0.3 -


Electrical diagram reference: figure 12
6/8 SACE EMAX 2 LOW VOLTAGE AIR CIRCUIT-BREAKERS


Accessories for circuit-breakers
Control
Opening and closing release- YO/YC (Fig. 06)
The opening and closing releases enable the circuit-breaker to be controlled remotely. Opening
is always possible, while closing is available only when the closing springs of the operating mechanism
are loaded and the circuit-breakers is ready to close. The releases operate by means of minimum im-
pulse current duration time of 100 ms.
Furthermore, they can operate in permanent service. In this case, if opening command is given by
means of the opening release, the circuit-breaker can be closed by de-energizing the opening release
and, after a time of at least 30 ms, by controlling the closing.
The circuit breaker operating mechanism has an anti-pumping function that ensures safety and reli-
ability.

Electrical diagram reference: figures 75, 77


Fig. 06

Second opening and closing release - YO2/YC2


For certain installations the redundancy of mechanisms and circuit-breaker operating circuits is
often requested. To answer these needs, the SACE Emax 2 circuit-breakers can be equipped
with double opening release and double closing release. The technical characteristics of the second
opening release remain the same as those of the first opening and closing release. A double closing re-
lease can be used for E2.2, E4.2 and E6.2 circuit-breakers; a second open release in an alternative to un-
dervoltage release.

Electrical diagram reference: figures 72, 79

General characteristics
Power supply (Un) AC DC
24V
30V
48V
60V
110V…120V
120V…127V
220V…240V
240V…250V
380V…400V -
415V…440V -
480V…500V -
YO/YO2: 70%...110% Un
Operating limits (IEC60947-2 standards)
YC/YC2: 85%...110% Un
Inrush power (Ps) 300VA 300W
Continuous power (Pc) 3.5VA 3.5W
Opening time (YO/YO2)
E1.2 35 ms
E2.2 … E6.2 55 ms
Closing time (YC/YC2)
E1.2 50 ms
E2.2 … E6.2 70 ms
ACCESSORIES 6/9

Opening and closing release test unit - YO/YC Test Unit


The opening and closing releases test unit helps ensure that the various version of releases are running
smoothly, to guarantee a high level of reliability in controlling circuit-breaker opening.
The test unit ensures the continuity of the opening and closing releases with a rated operating
voltage between 24V and 250V (AC and DC), as well as verifies the functions of the opening and closing
coil electronic circuit. Continuity is checked cyclically with an interval of 30s between tests. The unit
has optic signals via LEDs on the front, which provide the following information:
POWER ON: correct power supply of the YO/YC Test Unit
OPEN ON: coil switch absent, power supply absent or insufficient, interrupted cables
SHORT ON: coil switch failure, short-circuited cables
OPEN and SHORT FLASHING: faulty coil switch or incorrect supply
OPEN and SHORT OFF: correct operation of the coil switch.
Two relays with one change-over area also available on board the unit, to allow remote signalling of the
following events:
Failure of a test - resetting takes place automatically when the alarm stops
Failure of three tests - resetting occurs only by pressing the manual RESET on the unit.
Characteristics of device
Auxiliary power supply 24V...250V AC/DC
Specification of the signalling relays
Maximum interruped current 6A
Maximum interrupted voltage 250V AC

06
Undervoltage release – YU (Fig. 07)
The undervoltage release opens the circuit- breaker when there is a significant voltage drop or power
failure. It can be used for safe remote tripping, for blocking closing or to control the voltage in the pri-
mary and secondary circuits. The power supply for the release is therefore obtained on the supply side of
the circuit-breaker or from an independent source. Circuit-breaker closing is permitted only when the re-
lease is powered. The undervoltage release is an alternative to as second shunt trip or the anti-racking
out device. The circuit-breaker is opened with trip unit power supply voltages of 35-70% Un. The cir-
cuit-breaker can be closed with a trip unit power supply voltage of 85-110% Un.

General characteristics
Power supply (Un) AC DC
24V
30V
— 48V
Fig. 07 60V
110V…120V
120V…127V
220V…240V
240V…250V -
380V…400V -
415V…440V -
480V…500V -
Inrush power (Ps) 300VA 300W
Continuous power (Pc) 3.5VA 3.5W
Opening time (YU)
E1.2 30 ms
E2.2 … E6.2 50 ms


Electrical diagram reference: figure 73
6/10 SACE EMAX 2 LOW VOLTAGE AIR CIRCUIT-BREAKERS


Accessories for circuit-breakers
Time-delay device for undervoltage release (UVD) (Fig. 08)
The undervoltage release can be combined with an electronic time-delay device for the circuitbreaker,
allowing for delayed external tripping with adjustable preset times. Use of the delayed undervoltage
trip unit is recommended to prevent tripping when the power supply network for the trip unit is subject
to brief voltage drops or power supply failures. Circuit-breaker closing is inhibited when it is not pow-
ered. The time-delay device must be used with an undervoltage release with the same voltage.
General characteristics
Power supply (UVD) AC DC
24-30V -
— 48V
Fig. 08
60V
110-127V
220-250V
Adjustable opening time (YU + D): 0.5-1-1.5-2-3 s

Resetting remotely- YR
The reset coil YR permits remote resetting of the circuit-breaker after a release has tripped due to an
overcurrent condition. It is available for all automatic circuit-breakers, in different voltage supply:
General characteristics
Power supply (Un) AC DC
24V
110V
220V
Operating limits 90%...110% Un


Electrical diagram reference: figure 4

Motor – M (Fig. 09A/B)


The motor automatically loads the closing springs of the circuit-breaker. The device, which can be in-
stalled from the front, automatically reloads the springs of the operating device when they are un-
loaded and power is present. In the event no power is present, the springs can be manually loaded by a
dedicated lever on the operating device. The motor is always supplied with the limit switch contact S33
M/2 which signals the status of the springs.
General characteristics
Power supply (Un) AC DC
24V-30V
48V-60V
100V…130V
220V…250V

Fig. 09A Operating limits (IEC60947-2 standards) 85%...110% Un
Inrush power (Ps) 300VA E1.2 300W E1.2
500VA E2.2 ... E6.2 500W E2.2 ... E6.2
Inrush time 200ms
Continuous power (Pc) 100VA E1.2 100W E1.2
150VA E2.2 ... E6.2 150W E2.2 ... E6.2
Charging time
E1.2 8 sec
E2.2 … E6.2 7 sec
Note: charging time is refering to standard condition (Vn; Tamb)

— —
Fig. 09B Electrical diagram reference: figure 13
ACCESSORIES 6/11

Safety
Key lock in open position - KLC (Fig. 10)
Due to these safety devices, the SACE Emax 2 circuit-breaker can be locked in the open position. The
lock can also be used during maintenance activities when the shield of the accessories area is removed.
The device is available with lock with different keys – KLC-D (for only one circuit- breaker) or with the
same keys – KLC-S (for several circuit-breakers). Four different key numbers are available for the KLC-S.
SACE Emax 2 also allows alternative key lock to be installed. The following key lock set-ups are also
available:
• Ronis
• STI
• Kirk
• Castell
— In this case, the key locks must be supplied by the customer.
Fig. 10

Padlocks - PLC (Fig. 11)


These padlock options allow the circuit-breaker to be kept open by acting directly on the mechanical
operating device (opening pushbutton). Three different padlock versions are available:
• Locking device with plastic structure for up to a maximum of three padlocks of 4 mm
• Locking device with metal structure for up to a maximum of two padlocks of 8 mm
• Locking device with metal structure for one padlock of 7 mm or for padlock holders
The padlocks must be supplied by the customer. This device is an alternative to the PBC.

Key lock in racked-in / test / racked-out position - KLP (Fig. 12)

06
This device enables the mobile part to be locked in one of the three positions: racked-in, test
and racked-out. This device can be supplied with locks with different keys – KLP-D or with the same
keys – KLP-S.
A second key lock option can be added for a maximum of two key locks per breaker. Locking in the
racked-in, test and racked-out positions can be achieved by using other key locks – KLP-A.
Adapters are offered for acceptance of Ronis, STI, Kirk and Castell locks, which are to be provided by
the customer. With the exception of the Castell version, every circuit-breaker can accept up to two key

locks. Moreover, it is possible to allow locking only when in the racked-out position with a supplemen-
Fig. 11
tary accessory.

Padlock in racked-in / test / racked-out position - PLP (Fig. 13)


This device can hold up to three padlocks of 8 mm in diameter. The structure housing the padlocks can
also be used in combination with the 2 lock KLP keylock option. Furthermore, it enables the lock of the
moving part in the racked-out position only by means of the supplementary lock in racked-out position.

Shutter lock – SL
When the mobile part is in the test position, the shutters of the fixed part close, maintaining the insula-
tion distance and physically segregating the live parts of the of the cradle from the internal breaker
compartment of the cradle. Using two dedicated mechanisms, the upper and lower shutters can be
locked independently of one another. The shutter lock is always supplied with the fixed part of the
— SACE Emax 2 circuit-breakers and locks the shutters, using a maximum of three padlocks of 4 mm, 6
Fig. 12 mm or 8 mm.


Fig. 13
6/12 SACE EMAX 2 LOW VOLTAGE AIR CIRCUIT-BREAKERS


Accessories for circuit-breakers
Protection devices
Lock for racking-out mechanism with circuit- breaker in closed position (Fig. 14)
All SACE Emax 2 withdrawable circuit-breakers are always supplied with a lock that prevents the mobile
part from being racked in and racked out when the circuit- breaker is in the closed position. To rack in
the mobile part, the circuit-breaker must be in the open position.

Fig. 14 Lock for racking in / racking out the mobile part when the door is open - DLR
This accessory, which is mounted on the fixed part, prevents the mobile part from being racked in or
out when the switchgear door is open.

Lock to prevent door opening when the circuit- breaker is in racked-in / test position - DLP (Fig. 15)
This safety device prevents the switchgear door from being opened when the mobile part of the with-
drawable version of the circuit-breaker is in the racked-in or test position. This accessory can be in-
stalled on either the right-hand or left-hand side of the fixed part. It is available for circuit- breakers
E2.2, E4.2 and E6.2. If mounted on the right side, it is an alternative to the mechanical interlock, the

Fig. 15
AUX 15Q or the DLC.

Lock to prevent door opening when the circuit- breaker is in the closed position - DLC (Fig. 16)
This prevents the compartment door from being opened when the circuit-breaker is in the closed posi-
tion (and with the circuit-breaker racked in for withdrawable circuit-breakers).
It also blocks the circuit breaker from closing when the compartment door is open. DLC for E1.2 is an al-
ternative to the mechanical interlock and the AUX 15Q. DLC direct door for E2.2...E6.2 is compatible

with mechanical interlocks type A-B-D and the AUX 15Q. DLC cable door for E2.2...E6.2 is not compati-
Fig. 16 ble with mechanical interlock. DLC cable door for E2.2... E6.2 is compatible with the AUX 15Q.

Anti-insertion lock
The withdrawable circuit-breakers are equipped with special locks that allow the mobile part to
be inserted only into the corresponding fixed part.

Mechanical operation counter - MOC (Fig. 17)


The number of mechanical operations is often one of the elements that determines the frequency of or-
dinary maintenance operations on circuit-breakers. With this mechanical operation counter, which is al-
ways visible on the front of the circuit-breaker, the user knows how many mechanical operations the
device has performed.


Fig. 17
ACCESSORIES 6/13

Protection device for opening and closing pushbuttons - PBC (Fig. 18)
This accessory is applied to the safety cover of the circuit-breaker and is available in two
versions:
• Pushbutton protection device, which blocks operations on both the opening and closing pushbuttons
unless the special key is used.
• Padlockable pushbutton protection device, which makes it possible to block either or both pushbut-
tons and lock the covers in place. It does not trip the breaker as a standard "Padlock device" would.
• PBC is an alternative to PLC padlocks.

IP30 Protection (Fig. 19)


Supplied with every circuit-breaker, the cover frame is installed on the door of the switchgear
to achieve IP30 degree of protection on the front part of the circuit-breaker.

IP54 Protection (Fig. 20)


— This transparent cover completely protects the front of the circuit-breaker, enabling an IP54 degree of
Fig. 18
protection to be achieved. This accessory is provided with double key lock (same or different keys).

Terminal covers – HTC / LTC (Fig. 21)


These accessories are installed over in the terminal area, thereby reducing the risk of direct contact
with the live parts of the circuit-breaker. Two versions are available for E1.2: HTC high terminal covers
and LTC low terminal covers.

Separators - PB (Fig. 22)

06
These protection devices increase the insulation distance between adjacent phases. They are available
for all the frames.

— 0-ARC Distance top cover


Fig. 19
This accessory allows the circuit-breakers to reach the 0-arc distance performance. Installable on the
fixed part of E2.2, E4.2 and E6.2 gives the possibility to dimension the cubicle at the same height of the
fixed part. The 0-arc distance top cover is not compatible with the AUP auxiliary contacts IEC version,
but alternatively it is possible to install the AUP auxiliary contacts UL version.

Remote Racking Device - RRD


The Remote Racking Device (RRD) operates Emax 2 circuit breakers without being in front of the gear.
— The remote control is connected to the main device through 10mt cable that allows the Racking-in/out
Fig. 20 command from a remote location. The cable length guarantees enough distance from the arc flash
boundary of traditional low voltage switchgears. The RRD can only operate with the circuit breaker in
open position and discharged springs. The RRD for switchgear and controlgear has been investigated
by UL in accordance with the Standards UL 2876 and CSA-C22.2 (n.14).

General charateristics
— Rated service voltage 100...127V AC
Fig. 21
200...240V AC/DC
Frequency 50-60Hz
Rated power 150 W, 120VA
Working and storage temperature range -5°C...+70°C
Minimum time interval between operation 3 minutes
Maximum operating distance 100m

Weight 11Kg
Fig. 22
6/16 SACE EMAX 2 LOW VOLTAGE AIR CIRCUIT-BREAKERS


Accessories for circuit-breakers
Interlocks and switching devices
Mechanical interlocks
These interlock systems enable various opening
and closing configurations to be obtained be-
tween two or three circuit-breakers. Four types of
interlock configuration are available:

Types of interlock Possible application Logic Circuit-breakers


Type A

Excludes the possibility of having two Main line power supply and emergency Available between
1 2
circuit-breakers in the closed position power supply. circuit-breakers of
at the same time. O O different sizes and
with any fixed /
 I O withdrawable version
O I

 

Type B

Permits a pair of circuit-breakers to be Two power supplies from transformers 1 2 3 Available between
closed if the third is open. The latter can and one emergency power supply. E2.2, E4.2 and E6.2
only be closed when the pair is open. O O O circuit-breakers
and with any fixed /
 I O O withdrawable version
O O I

   I O I

O I O

Type C

Permits two out of three circuit-breakers Two half-busbars can be powered by a 1 2 3 Available between
to be closed at the same time. single transformer (bus-tie closed) or by E2.2, E4.2 and E6.2
both at the same time (bus-tie open). O O O circuit-breakers
and with any fixed /
I O O withdrawable version
O I O

O O I

O I I
  
I I O

I O I

Type D

Permits one out of three interlocked Three power supplies on the same busbar 1 2 3 Available between
circuit-breakers to be closed. that must not operate in parallel. E2.2, E4.2 and E6.2
O O O circuit-breakers
and with any fixed /
I O O withdrawable version

O I O

O O I
  
ACCESSORIES 6/17

The mechanical interlocks offer multiple solu- ATS022 is also designed for the connection of an
tions for installation that simplify their integra- auxiliary supply, which enables the use of further
tion into the switchgear. The interlocks can be functions.
mounted: The ATS021 and ATS022 devices carry out control
• vertically VR of both power supply lines and also analyze:
• horizontally HR • phase imbalance;
• mixed L • frequency imbalance;
• phase loss.
Different types of interlocks can be supplied ac- In addition to the standard control functions, the
cording to the maximum distance between two ATS022 unit also permits:
interlocked breakers: • the priority line to be selected;
Configuration Type A Type B, C, D
• a third circuit-breaker to be controlled;
• the device to be integrated into a supervision
Horizontal 2750mm 1600mm
system with Modbus communication (auxiliary
Vertical 1000mm 1000mm
supply needed);
Breakers E1.2 -
• parameters to be read and set, and measure-
E2.2
ments and alarms to be displayed by means of a
E4.2
graphical display.
E6.2

Typical applications are: supply of UPS (Uninter-


For B, C and D types, the maximum distance be-
rupted Power Supply) units, operating rooms and
tween the two furthest breakers is 3200mm for
primary hospital services, emergency power for
horizontal configurations and 2000mm for verti-
civil buildings, airports, hotels, databases and
cal configurations. It is possible to make the me-

06
telecommunication systems and power supply of
chanical interlock among three circuit-breakers
industrial lines in continuous processes.
disposed in 'L position' by using the cables of
For correct configuration, each circuit-breaker
three horizontal circuit-breakers interlock. Make
connected to the ATS021 or ATS022 device must
sure the distance between the horizontal and ver-
be fitted with the following accessories:
tical circuit-breakers respects the minimum and
• mechanical interlock;
maximum distance. All cables can be cut to guar-
• motorized control of opening and closing;
antee easy installation in switchboards.
• contact for signalling status (open / closed) and
Mechanical interlocks are not compatible with AUX
contact for signalling tripping;
15Q, the lock for preventing door opening when
• contact for signalling circuit-breaker racked in
the circuit breaker is in the closed position (DLC)
(for withdrawable circuit-breaker).
or when the circuit breaker is in the racked in or
test position (DLP). if mounted on the right side.

External Automatic Transfer Switches ATS


The ATS (Automatic Transfer Switch) is a net-
work-unit transfer device used in installations
where switching from the main power line to an
emergency line is required in order to ensure that
power is supplied to the loads in the case of
power loss or abnormalities from the main line.
These devices are able to control the entire trans-
fer procedure automatically, but also offer com-
mands for performing the procedure manually.
The new generation of ATSs (ATS021 and ATS022)
offers the most advanced and complete solution
for ensuring service continuity. The ATS021 and
ATS022 devices can also be used with all auto-
matic circuit-breakers and switch-disconnectors
of the Tmax XT family. The ATS021 and ATS022 de-
vices have been designed to be self-powered.
ORDERING CODES 10/21


Automatic circuit-breakers
Withdrawable version for power distribution

SACE Emax E1.2B • Mobile part of withdrawable circuit-breaker (MP)


Size Iu Icu Icw Type 3 Poles 4 Poles
(440 V) (1s) Code Code
E1.2B 630 42 42 E1.2B 630 Ekip Dip LI 1SDA072051R1 1SDA072681R1
E1.2B 630 Ekip Dip LSI 1SDA072052R1 1SDA072682R1
E1.2B 630 Ekip Dip LSIG 1SDA072053R1 1SDA072683R1
E1.2B 630 Ekip Touch LI 1SDA072054R1 1SDA072684R1
E1.2B 630 Ekip Touch LSI 1SDA072055R1 1SDA072685R1
E1.2B 630 Ekip Touch LSIG 1SDA072056R1 1SDA072686R1
E1.2B 630 Ekip Hi-Touch LSI 1SDA072058R1 1SDA072688R1
E1.2B 630 Ekip Hi-Touch LSIG 1SDA072059R1 1SDA072689R1
800 42 42 E1.2B 800 Ekip Dip LI 1SDA072091R1 1SDA072721R1
E1.2B 800 Ekip Dip LSI 1SDA072092R1 1SDA072722R1
E1.2B 800 Ekip Dip LSIG 1SDA072093R1 1SDA072723R1
E1.2B 800 Ekip Touch LI 1SDA072094R1 1SDA072724R1
E1.2B 800 Ekip Touch LSI 1SDA072095R1 1SDA072725R1
E1.2B 800 Ekip Touch LSIG 1SDA072096R1 1SDA072726R1
E1.2B 800 Ekip Hi-Touch LSI 1SDA072098R1 1SDA072728R1
E1.2B 800 Ekip Hi-Touch LSIG 1SDA072099R1 1SDA072729R1
1000 42 42 E1.2B 1000 Ekip Dip LI 1SDA072131R1 1SDA072761R1
E1.2B 1000 Ekip Dip LSI 1SDA072132R1 1SDA072762R1
E1.2B 1000 Ekip Dip LSIG 1SDA072133R1 1SDA072763R1
E1.2B 1000 Ekip Touch LI 1SDA072134R1 1SDA072764R1
E1.2B 1000 Ekip Touch LSI 1SDA072135R1 1SDA072765R1
E1.2B 1000 Ekip Touch LSIG 1SDA072136R1 1SDA072766R1
E1.2B 1000 Ekip Hi-Touch LSI 1SDA072138R1 1SDA072768R1
E1.2B 1000 Ekip Hi-Touch LSIG 1SDA072139R1 1SDA072769R1
1250 42 42 E1.2B 1250 Ekip Dip LI 1SDA072171R1 1SDA072801R1
E1.2B 1250 Ekip Dip LSI 1SDA072172R1 1SDA072802R1
E1.2B 1250 Ekip Dip LSIG 1SDA072173R1 1SDA072803R1
E1.2B 1250 Ekip Touch LI 1SDA072174R1 1SDA072804R1
E1.2B 1250 Ekip Touch LSI 1SDA072175R1 1SDA072805R1
E1.2B 1250 Ekip Touch LSIG 1SDA072176R1 1SDA072806R1
E1.2B 1250 Ekip Hi-Touch LSI 1SDA072178R1 1SDA072808R1
E1.2B 1250 Ekip Hi-Touch LSIG 1SDA072179R1 1SDA072809R1
1600 42 42 E1.2B 1600 Ekip Dip LI 1SDA072211R1 1SDA072841R1
E1.2B 1600 Ekip Dip LSI 1SDA072212R1 1SDA072842R1
E1.2B 1600 Ekip Dip LSIG 1SDA072213R1 1SDA072843R1
E1.2B 1600 Ekip Touch LI 1SDA072214R1 1SDA072844R1
E1.2B 1600 Ekip Touch LSI 1SDA072215R1 1SDA072845R1
E1.2B 1600 Ekip Touch LSIG 1SDA072216R1 1SDA072846R1
E1.2B 1600 Ekip Hi-Touch LSI 1SDA072218R1 1SDA072848R1
10

E1.2B 1600 Ekip Hi-Touch LSIG 1SDA072219R1 1SDA072849R1


10/22 S A C E E M A X 2 LO W V O LTA G E A I R C I R C U I T- B R E A K E R S


Automatic circuit-breakers
Withdrawable version for power distribution

SACE Emax E1.2C • Mobile part of withdrawable circuit-breaker (MP)


Size Iu Icu Icw Type 3 Poles 4 Poles
(440 V) (1s) Code Code
E1.2C 630 50 42 E1.2C 630 Ekip Dip LI 1SDA072061R1 1SDA072691R1
E1.2C 630 Ekip Dip LSI 1SDA072062R1 1SDA072692R1
E1.2C 630 Ekip Dip LSIG 1SDA072063R1 1SDA072693R1
E1.2C 630 Ekip Touch LI 1SDA072064R1 1SDA072694R1
E1.2C 630 Ekip Touch LSI 1SDA072065R1 1SDA072695R1
E1.2C 630 Ekip Touch LSIG 1SDA072066R1 1SDA072696R1
E1.2C 630 Ekip Hi-Touch LSI 1SDA072068R1 1SDA072698R1
E1.2C 630 Ekip Hi-Touch LSIG 1SDA072069R1 1SDA072699R1
800 50 42 E1.2C 800 Ekip Dip LI 1SDA072101R1 1SDA072731R1
E1.2C 800 Ekip Dip LSI 1SDA072102R1 1SDA072732R1
E1.2C 800 Ekip Dip LSIG 1SDA072103R1 1SDA072733R1
E1.2C 800 Ekip Touch LI 1SDA072104R1 1SDA072734R1
E1.2C 800 Ekip Touch LSI 1SDA072105R1 1SDA072735R1
E1.2C 800 Ekip Touch LSIG 1SDA072106R1 1SDA072736R1
E1.2C 800 Ekip Hi-Touch LSI 1SDA072108R1 1SDA072738R1
E1.2C 800 Ekip Hi-Touch LSIG 1SDA072109R1 1SDA072739R1
1000 50 42 E1.2C 1000 Ekip Dip LI 1SDA072141R1 1SDA072771R1
E1.2C 1000 Ekip Dip LSI 1SDA072142R1 1SDA072772R1
E1.2C 1000 Ekip Dip LSIG 1SDA072143R1 1SDA072773R1
E1.2C 1000 Ekip Touch LI 1SDA072144R1 1SDA072774R1
E1.2C 1000 Ekip Touch LSI 1SDA072145R1 1SDA072775R1
E1.2C 1000 Ekip Touch LSIG 1SDA072146R1 1SDA072776R1
E1.2C 1000 Ekip Hi-Touch LSI 1SDA072148R1 1SDA072778R1
E1.2C 1000 Ekip Hi-Touch LSIG 1SDA072149R1 1SDA072779R1
1250 50 42 E1.2C 1250 Ekip Dip LI 1SDA072181R1 1SDA072811R1
E1.2C 1250 Ekip Dip LSI 1SDA072182R1 1SDA072812R1
E1.2C 1250 Ekip Dip LSIG 1SDA072183R1 1SDA072813R1
E1.2C 1250 Ekip Touch LI 1SDA072184R1 1SDA072814R1
E1.2C 1250 Ekip Touch LSI 1SDA072185R1 1SDA072815R1
E1.2C 1250 Ekip Touch LSIG 1SDA072186R1 1SDA072816R1
E1.2C 1250 Ekip Hi-Touch LSI 1SDA072188R1 1SDA072818R1
E1.2C 1250 Ekip Hi-Touch LSIG 1SDA072189R1 1SDA072819R1
1600 50 42 E1.2C 1600 Ekip Dip LI 1SDA072221R1 1SDA072851R1
E1.2C 1600 Ekip Dip LSI 1SDA072222R1 1SDA072852R1
E1.2C 1600 Ekip Dip LSIG 1SDA072223R1 1SDA072853R1
E1.2C 1600 Ekip Touch LI 1SDA072224R1 1SDA072854R1
E1.2C 1600 Ekip Touch LSI 1SDA072225R1 1SDA072855R1
E1.2C 1600 Ekip Touch LSIG 1SDA072226R1 1SDA072856R1
E1.2C 1600 Ekip Hi-Touch LSI 1SDA072228R1 1SDA072858R1
E1.2C 1600 Ekip Hi-Touch LSIG 1SDA072229R1 1SDA072859R1
ORDERING CODES 10/23

SACE Emax E1.2N • Mobile part of withdrawable circuit-breaker (MP)


Size Iu Icu Icw Type 3 Poles 4 Poles
(440 V) (1s) Code Code
E1.2N 250 66 50 E1.2N 250 Ekip Dip LI 1SDA072041R1 1SDA072671R1
E1.2N 250 Ekip Dip LSI 1SDA072042R1 1SDA072672R1
E1.2N 250 Ekip Dip LSIG 1SDA072043R1 1SDA072673R1
E1.2N 250 Ekip Touch LI 1SDA072044R1 1SDA072674R1
E1.2N 250 Ekip Touch LSI 1SDA072045R1 1SDA072675R1
E1.2N 250 Ekip Touch LSIG 1SDA072046R1 1SDA072676R1
E1.2N 250 Ekip Hi-Touch LSI 1SDA072048R1 1SDA072678R1
E1.2N 250 Ekip Hi-Touch LSIG 1SDA072049R1 1SDA072679R1
630 66 50 E1.2N 630 Ekip Dip LI 1SDA072071R1 1SDA072701R1
E1.2N 630 Ekip Dip LSI 1SDA072072R1 1SDA072702R1
E1.2N 630 Ekip Dip LSIG 1SDA072073R1 1SDA072703R1
E1.2N 630 Ekip Touch LI 1SDA072074R1 1SDA072704R1
E1.2N 630 Ekip Touch LSI 1SDA072075R1 1SDA072705R1
E1.2N 630 Ekip Touch LSIG 1SDA072076R1 1SDA072706R1
E1.2N 630 Ekip Hi-Touch LSI 1SDA072078R1 1SDA072708R1
E1.2N 630 Ekip Hi-Touch LSIG 1SDA072079R1 1SDA072709R1
800 66 50 E1.2N 800 Ekip Dip LI 1SDA072111R1 1SDA072741R1
E1.2N 800 Ekip Dip LSI 1SDA072112R1 1SDA072742R1
E1.2N 800 Ekip Dip LSIG 1SDA072113R1 1SDA072743R1
E1.2N 800 Ekip Touch LI 1SDA072114R1 1SDA072744R1
E1.2N 800 Ekip Touch LSI 1SDA072115R1 1SDA072745R1
E1.2N 800 Ekip Touch LSIG 1SDA072116R1 1SDA072746R1
E1.2N 800 Ekip Hi-Touch LSI 1SDA072118R1 1SDA072748R1
E1.2N 800 Ekip Hi-Touch LSIG 1SDA072119R1 1SDA072749R1
1000 66 50 E1.2N 1000 Ekip Dip LI 1SDA072151R1 1SDA072781R1
E1.2N 1000 Ekip Dip LSI 1SDA072152R1 1SDA072782R1
E1.2N 1000 Ekip Dip LSIG 1SDA072153R1 1SDA072783R1
E1.2N 1000 Ekip Touch LI 1SDA072154R1 1SDA072784R1
E1.2N 1000 Ekip Touch LSI 1SDA072155R1 1SDA072785R1
E1.2N 1000 Ekip Touch LSIG 1SDA072156R1 1SDA072786R1
E1.2N 1000 Ekip Hi-Touch LSI 1SDA072158R1 1SDA072788R1
E1.2N 1000 Ekip Hi-Touch LSIG 1SDA072159R1 1SDA072789R1
1250 66 50 E1.2N 1250 Ekip Dip LI 1SDA072191R1 1SDA072821R1
E1.2N 1250 Ekip Dip LSI 1SDA072192R1 1SDA072822R1
E1.2N 1250 Ekip Dip LSIG 1SDA072193R1 1SDA072823R1
E1.2N 1250 Ekip Touch LI 1SDA072194R1 1SDA072824R1
E1.2N 1250 Ekip Touch LSI 1SDA072195R1 1SDA072825R1
E1.2N 1250 Ekip Touch LSIG 1SDA072196R1 1SDA072826R1
E1.2N 1250 Ekip Hi-Touch LSI 1SDA072198R1 1SDA072828R1
E1.2N 1250 Ekip Hi-Touch LSIG 1SDA072199R1 1SDA072829R1
1600 66 50 E1.2N 1600 Ekip Dip LI 1SDA072231R1 1SDA072861R1
E1.2N 1600 Ekip Dip LSI 1SDA072232R1 1SDA072862R1
10

E1.2N 1600 Ekip Dip LSIG 1SDA072233R1 1SDA072863R1


E1.2N 1600 Ekip Touch LI 1SDA072234R1 1SDA072864R1
E1.2N 1600 Ekip Touch LSI 1SDA072235R1 1SDA072865R1
E1.2N 1600 Ekip Touch LSIG 1SDA072236R1 1SDA072866R1
E1.2N 1600 Ekip Hi-Touch LSI 1SDA072238R1 1SDA072868R1
E1.2N 1600 Ekip Hi-Touch LSIG 1SDA072239R1 1SDA072869R1
10/24 S A C E E M A X 2 LO W V O LTA G E A I R C I R C U I T- B R E A K E R S


Automatic circuit-breakers
Withdrawable version for power distribution

SACE Emax E2.2B • Mobile part of withdrawable circuit-breaker (MP)


Size Iu Icu Icw Type 3 Poles 4 Poles
(440 V) (1s) Code Code
E2.2B 1600 42 42 E2.2B 1600 Ekip Dip LI 1SDA072331R1 1SDA072961R1
E2.2B 1600 Ekip Dip LSI 1SDA072332R1 1SDA072962R1
E2.2B 1600 Ekip Dip LSIG 1SDA072333R1 1SDA072963R1
E2.2B 1600 Ekip Touch LI 1SDA072334R1 1SDA072964R1
E2.2B 1600 Ekip Touch LSI 1SDA072335R1 1SDA072965R1
E2.2B 1600 Ekip Touch LSIG 1SDA072336R1 1SDA072966R1
E2.2B 1600 Ekip Hi-Touch LSI 1SDA072338R1 1SDA072968R1
E2.2B 1600 Ekip Hi-Touch LSIG 1SDA072339R1 1SDA072969R1
2000 42 42 E2.2B 2000 Ekip Dip LI 1SDA072371R1 1SDA073001R1
E2.2B 2000 Ekip Dip LSI 1SDA072372R1 1SDA073002R1
E2.2B 2000 Ekip Dip LSIG 1SDA072373R1 1SDA073003R1
E2.2B 2000 Ekip Touch LI 1SDA072374R1 1SDA073004R1
E2.2B 2000 Ekip Touch LSI 1SDA072375R1 1SDA073005R1
E2.2B 2000 Ekip Touch LSIG 1SDA072376R1 1SDA073006R1
E2.2B 2000 Ekip Hi-Touch LSI 1SDA072378R1 1SDA073008R1
E2.2B 2000 Ekip Hi-Touch LSIG 1SDA072379R1 1SDA073009R1
ORDERING CODES 10/25

SACE Emax E2.2N • Mobile part of withdrawable circuit-breaker (MP)


Size Iu Icu Icw Type 3 Poles 4 Poles
(440 V) (1s) Code Code
E2.2N 800 66 66 E2.2N 800 Ekip Dip LI 1SDA072241R1 1SDA072871R1
E2.2N 800 Ekip Dip LSI 1SDA072242R1 1SDA072872R1
E2.2N 800 Ekip Dip LSIG 1SDA072243R1 1SDA072873R1
E2.2N 800 Ekip Touch LI 1SDA072244R1 1SDA072874R1
E2.2N 800 Ekip Touch LSI 1SDA072245R1 1SDA072875R1
E2.2N 800 Ekip Touch LSIG 1SDA072246R1 1SDA072876R1
E2.2N 800 Ekip Hi-Touch LSI 1SDA072248R1 1SDA072878R1
E2.2N 800 Ekip Hi-Touch LSIG 1SDA072249R1 1SDA072879R1
1000 66 66 E2.2N 1000 Ekip Dip LI 1SDA072271R1 1SDA072901R1
E2.2N 1000 Ekip Dip LSI 1SDA072272R1 1SDA072902R1
E2.2N 1000 Ekip Dip LSIG 1SDA072273R1 1SDA072903R1
E2.2N 1000 Ekip Touch LI 1SDA072274R1 1SDA072904R1
E2.2N 1000 Ekip Touch LSI 1SDA072275R1 1SDA072905R1
E2.2N 1000 Ekip Touch LSIG 1SDA072276R1 1SDA072906R1
E2.2N 1000 Ekip Hi-Touch LSI 1SDA072278R1 1SDA072908R1
E2.2N 1000 Ekip Hi-Touch LSIG 1SDA072279R1 1SDA072909R1
1250 66 66 E2.2N 1250 Ekip Dip LI 1SDA072301R1 1SDA072931R1
E2.2N 1250 Ekip Dip LSI 1SDA072302R1 1SDA072932R1
E2.2N 1250 Ekip Dip LSIG 1SDA072303R1 1SDA072933R1
E2.2N 1250 Ekip Touch LI 1SDA072304R1 1SDA072934R1
E2.2N 1250 Ekip Touch LSI 1SDA072305R1 1SDA072935R1
E2.2N 1250 Ekip Touch LSIG 1SDA072306R1 1SDA072936R1
E2.2N 1250 Ekip Hi-Touch LSI 1SDA072308R1 1SDA072938R1
E2.2N 1250 Ekip Hi-Touch LSIG 1SDA072309R1 1SDA072939R1
1600 66 66 E2.2N 1600 Ekip Dip LI 1SDA072341R1 1SDA072971R1
E2.2N 1600 Ekip Dip LSI 1SDA072342R1 1SDA072972R1
E2.2N 1600 Ekip Dip LSIG 1SDA072343R1 1SDA072973R1
E2.2N 1600 Ekip Touch LI 1SDA072344R1 1SDA072974R1
E2.2N 1600 Ekip Touch LSI 1SDA072345R1 1SDA072975R1
E2.2N 1600 Ekip Touch LSIG 1SDA072346R1 1SDA072976R1
E2.2N 1600 Ekip Hi-Touch LSI 1SDA072348R1 1SDA072978R1
E2.2N 1600 Ekip Hi-Touch LSIG 1SDA072349R1 1SDA072979R1
2000 66 66 E2.2N 2000 Ekip Dip LI 1SDA072381R1 1SDA073011R1
E2.2N 2000 Ekip Dip LSI 1SDA072382R1 1SDA073012R1
E2.2N 2000 Ekip Dip LSIG 1SDA072383R1 1SDA073013R1
E2.2N 2000 Ekip Touch LI 1SDA072384R1 1SDA073014R1
E2.2N 2000 Ekip Touch LSI 1SDA072385R1 1SDA073015R1
E2.2N 2000 Ekip Touch LSIG 1SDA072386R1 1SDA073016R1
E2.2N 2000 Ekip Hi-Touch LSI 1SDA072388R1 1SDA073018R1
E2.2N 2000 Ekip Hi-Touch LSIG 1SDA072389R1 1SDA073019R1
2500 66 66 E2.2N 2500 Ekip Dip LI 1SDA072411R1 1SDA073041R1
E2.2N 2500 Ekip Dip LSI 1SDA072412R1 1SDA073042R1
10

E2.2N 2500 Ekip Dip LSIG 1SDA072413R1 1SDA073043R1


E2.2N 2500 Ekip Touch LI 1SDA072414R1 1SDA073044R1
E2.2N 2500 Ekip Touch LSI 1SDA072415R1 1SDA073045R1
E2.2N 2500 Ekip Touch LSIG 1SDA072416R1 1SDA073046R1
E2.2N 2500 Ekip Hi-Touch LSI 1SDA072418R1 1SDA073048R1
E2.2N 2500 Ekip Hi-Touch LSIG 1SDA072419R1 1SDA073049R1
10/26 S A C E E M A X 2 LO W V O LTA G E A I R C I R C U I T- B R E A K E R S


Automatic circuit-breakers
Withdrawable version for power distribution

SACE Emax E2.2S • Mobile part of withdrawable circuit-breaker (MP)


Size Iu Icu Icw Type 3 Poles 4 Poles
(440 V) (1s) Code Code
E2.2S 250 85 66 E2.2S 250 Ekip Dip LI 1SDA073648R1 1SDA073658R1
E2.2S 250 Ekip Dip LSI 1SDA073649R1 1SDA073659R1
E2.2S 250 Ekip Dip LSIG 1SDA073650R1 1SDA073660R1
E2.2S 250 Ekip Touch LI 1SDA073651R1 1SDA073661R1
E2.2S 250 Ekip Touch LSI 1SDA073652R1 1SDA073662R1
E2.2S 250 Ekip Touch LSIG 1SDA073653R1 1SDA073663R1
E2.2S 250 Ekip Hi-Touch LSI 1SDA073655R1 1SDA073665R1
E2.2S 250 Ekip Hi-Touch LSIG 1SDA073656R1 1SDA073666R1
800 85 66 E2.2S 800 Ekip Dip LI 1SDA072251R1 1SDA072881R1
E2.2S 800 Ekip Dip LSI 1SDA072252R1 1SDA072882R1
E2.2S 800 Ekip Dip LSIG 1SDA072253R1 1SDA072883R1
E2.2S 800 Ekip Touch LI 1SDA072254R1 1SDA072884R1
E2.2S 800 Ekip Touch LSI 1SDA072255R1 1SDA072885R1
E2.2S 800 Ekip Touch LSIG 1SDA072256R1 1SDA072886R1
E2.2S 800 Ekip Hi-Touch LSI 1SDA072258R1 1SDA072888R1
E2.2S 800 Ekip Hi-Touch LSIG 1SDA072259R1 1SDA072889R1
1000 85 66 E2.2S 1000 Ekip Dip LI 1SDA072281R1 1SDA072911R1
E2.2S 1000 Ekip Dip LSI 1SDA072282R1 1SDA072912R1
E2.2S 1000 Ekip Dip LSIG 1SDA072283R1 1SDA072913R1
E2.2S 1000 Ekip Touch LI 1SDA072284R1 1SDA072914R1
E2.2S 1000 Ekip Touch LSI 1SDA072285R1 1SDA072915R1
E2.2S 1000 Ekip Touch LSIG 1SDA072286R1 1SDA072916R1
E2.2S 1000 Ekip Hi-Touch LSI 1SDA072288R1 1SDA072918R1
E2.2S 1000 Ekip Hi-Touch LSIG 1SDA072289R1 1SDA072919R1
1250 85 66 E2.2S 1250 Ekip Dip LI 1SDA072311R1 1SDA072941R1
E2.2S 1250 Ekip Dip LSI 1SDA072312R1 1SDA072942R1
E2.2S 1250 Ekip Dip LSIG 1SDA072313R1 1SDA072943R1
E2.2S 1250 Ekip Touch LI 1SDA072314R1 1SDA072944R1
E2.2S 1250 Ekip Touch LSI 1SDA072315R1 1SDA072945R1
E2.2S 1250 Ekip Touch LSIG 1SDA072316R1 1SDA072946R1
E2.2S 1250 Ekip Hi-Touch LSI 1SDA072318R1 1SDA072948R1
E2.2S 1250 Ekip Hi-Touch LSIG 1SDA072319R1 1SDA072949R1
ORDERING CODES 10/27

SACE Emax E2.2S • Mobile part of withdrawable circuit-breaker (MP)


Size Iu Icu Icw Type 3 Poles 4 Poles
(440 V) (1s) Code Code
E2.2S 1600 85 66 E2.2S 1600 Ekip Dip LI 1SDA072351R1 1SDA072981R1
E2.2S 1600 Ekip Dip LSI 1SDA072352R1 1SDA072982R1
E2.2S 1600 Ekip Dip LSIG 1SDA072353R1 1SDA072983R1
E2.2S 1600 Ekip Touch LI 1SDA072354R1 1SDA072984R1
E2.2S 1600 Ekip Touch LSI 1SDA072355R1 1SDA072985R1
E2.2S 1600 Ekip Touch LSIG 1SDA072356R1 1SDA072986R1
E2.2S 1600 Ekip Hi-Touch LSI 1SDA072358R1 1SDA072988R1
E2.2S 1600 Ekip Hi-Touch LSIG 1SDA072359R1 1SDA072989R1
2000 85 66 E2.2S 2000 Ekip Dip LI 1SDA072391R1 1SDA073021R1
E2.2S 2000 Ekip Dip LSI 1SDA072392R1 1SDA073022R1
E2.2S 2000 Ekip Dip LSIG 1SDA072393R1 1SDA073023R1
E2.2S 2000 Ekip Touch LI 1SDA072394R1 1SDA073024R1
E2.2S 2000 Ekip Touch LSI 1SDA072395R1 1SDA073025R1
E2.2S 2000 Ekip Touch LSIG 1SDA072396R1 1SDA073026R1
E2.2S 2000 Ekip Hi-Touch LSI 1SDA072398R1 1SDA073028R1
E2.2S 2000 Ekip Hi-Touch LSIG 1SDA072399R1 1SDA073029R1
2500 85 66 E2.2S 2500 Ekip Dip LI 1SDA072421R1 1SDA073051R1
E2.2S 2500 Ekip Dip LSI 1SDA072422R1 1SDA073052R1
E2.2S 2500 Ekip Dip LSIG 1SDA072423R1 1SDA073053R1
E2.2S 2500 Ekip Touch LI 1SDA072424R1 1SDA073054R1
E2.2S 2500 Ekip Touch LSI 1SDA072425R1 1SDA073055R1
E2.2S 2500 Ekip Touch LSIG 1SDA072426R1 1SDA073056R1
E2.2S 2500 Ekip Hi-Touch LSI 1SDA072428R1 1SDA073058R1
E2.2S 2500 Ekip Hi-Touch LSIG 1SDA072429R1 1SDA073059R1

10
10/28 S A C E E M A X 2 LO W V O LTA G E A I R C I R C U I T- B R E A K E R S


Automatic circuit-breakers
Withdrawable version for power distribution

SACE Emax E2.2H • Mobile part of withdrawable circuit-breaker (MP)


Size Iu Icu Icw Type 3 Poles 4 Poles
(440 V) (1s) Code Code
E2.2H 800 100 85 E2.2H 800 Ekip Dip LI 1SDA072261R1 1SDA072891R1
E2.2H 800 Ekip Dip LSI 1SDA072262R1 1SDA072892R1
E2.2H 800 Ekip Dip LSIG 1SDA072263R1 1SDA072893R1
E2.2H 800 Ekip Touch LI 1SDA072264R1 1SDA072894R1
E2.2H 800 Ekip Touch LSI 1SDA072265R1 1SDA072895R1
E2.2H 800 Ekip Touch LSIG 1SDA072266R1 1SDA072896R1
E2.2H 800 Ekip Hi-Touch LSI 1SDA072268R1 1SDA072898R1
E2.2H 800 Ekip Hi-Touch LSIG 1SDA072269R1 1SDA072899R1
1000 100 85 E2.2H 1000 Ekip Dip LI 1SDA072291R1 1SDA072921R1
E2.2H 1000 Ekip Dip LSI 1SDA072292R1 1SDA072922R1
E2.2H 1000 Ekip Dip LSIG 1SDA072293R1 1SDA072923R1
E2.2H 1000 Ekip Touch LI 1SDA072294R1 1SDA072924R1
E2.2H 1000 Ekip Touch LSI 1SDA072295R1 1SDA072925R1
E2.2H 1000 Ekip Touch LSIG 1SDA072296R1 1SDA072926R1
E2.2H 1000 Ekip Hi-Touch LSI 1SDA072298R1 1SDA072928R1
E2.2H 1000 Ekip Hi-Touch LSIG 1SDA072299R1 1SDA072929R1
1250 100 85 E2.2H 1250 Ekip Dip LI 1SDA072321R1 1SDA072951R1
E2.2H 1250 Ekip Dip LSI 1SDA072322R1 1SDA072952R1
E2.2H 1250 Ekip Dip LSIG 1SDA072323R1 1SDA072953R1
E2.2H 1250 Ekip Touch LI 1SDA072324R1 1SDA072954R1
E2.2H 1250 Ekip Touch LSI 1SDA072325R1 1SDA072955R1
E2.2H 1250 Ekip Touch LSIG 1SDA072326R1 1SDA072956R1
E2.2H 1250 Ekip Hi-Touch LSI 1SDA072328R1 1SDA072958R1
E2.2H 1250 Ekip Hi-Touch LSIG 1SDA072329R1 1SDA072959R1
1600 100 85 E2.2H 1600 Ekip Dip LI 1SDA072361R1 1SDA072991R1
E2.2H 1600 Ekip Dip LSI 1SDA072362R1 1SDA072992R1
E2.2H 1600 Ekip Dip LSIG 1SDA072363R1 1SDA072993R1
E2.2H 1600 Ekip Touch LI 1SDA072364R1 1SDA072994R1
E2.2H 1600 Ekip Touch LSI 1SDA072365R1 1SDA072995R1
E2.2H 1600 Ekip Touch LSIG 1SDA072366R1 1SDA072996R1
E2.2H 1600 Ekip Hi-Touch LSI 1SDA072368R1 1SDA072998R1
E2.2H 1600 Ekip Hi-Touch LSIG 1SDA072369R1 1SDA072999R1
2000 100 85 E2.2H 2000 Ekip Dip LI 1SDA072401R1 1SDA073031R1
E2.2H 2000 Ekip Dip LSI 1SDA072402R1 1SDA073032R1
E2.2H 2000 Ekip Dip LSIG 1SDA072403R1 1SDA073033R1
E2.2H 2000 Ekip Touch LI 1SDA072404R1 1SDA073034R1
E2.2H 2000 Ekip Touch LSI 1SDA072405R1 1SDA073035R1
E2.2H 2000 Ekip Touch LSIG 1SDA072406R1 1SDA073036R1
E2.2H 2000 Ekip Hi-Touch LSI 1SDA072408R1 1SDA073038R1
E2.2H 2000 Ekip Hi-Touch LSIG 1SDA072409R1 1SDA073039R1
2500 100 85 E2.2H 2500 Ekip Dip LI 1SDA072431R1 1SDA073061R1
E2.2H 2500 Ekip Dip LSI 1SDA072432R1 1SDA073062R1
E2.2H 2500 Ekip Dip LSIG 1SDA072433R1 1SDA073063R1
E2.2H 2500 Ekip Touch LI 1SDA072434R1 1SDA073064R1
E2.2H 2500 Ekip Touch LSI 1SDA072435R1 1SDA073065R1
E2.2H 2500 Ekip Touch LSIG 1SDA072436R1 1SDA073066R1
E2.2H 2500 Ekip Hi-Touch LSI 1SDA072438R1 1SDA073068R1
E2.2H 2500 Ekip Hi-Touch LSIG 1SDA072439R1 1SDA073069R1
ORDERING CODES 10/29

SACE Emax E4.2N-S-H • Mobile part of withdrawable circuit-breaker (MP)


Size Iu Icu Icw Type 3 Poles 4 Poles
(440 V) (1s) Code Code
E4.2N 3200 66 66 E4.2N 3200 Ekip Dip LI 1SDA072491R1 1SDA073121R1
E4.2N 3200 Ekip Dip LSI 1SDA072492R1 1SDA073122R1
E4.2N 3200 Ekip Dip LSIG 1SDA072493R1 1SDA073123R1
E4.2N 3200 Ekip Touch LI 1SDA072494R1 1SDA073124R1
E4.2N 3200 Ekip Touch LSI 1SDA072495R1 1SDA073125R1
E4.2N 3200 Ekip Touch LSIG 1SDA072496R1 1SDA073126R1
E4.2N 3200 Ekip Hi-Touch LSI 1SDA072498R1 1SDA073128R1
E4.2N 3200 Ekip Hi-Touch LSIG 1SDA072499R1 1SDA073129R1
4000 66 66 E4.2N 4000 Ekip Dip LI 1SDA072541R1 1SDA073171R1
E4.2N 4000 Ekip Dip LSI 1SDA072542R1 1SDA073172R1
E4.2N 4000 Ekip Dip LSIG 1SDA072543R1 1SDA073173R1
E4.2N 4000 Ekip Touch LI 1SDA072544R1 1SDA073174R1
E4.2N 4000 Ekip Touch LSI 1SDA072545R1 1SDA073175R1
E4.2N 4000 Ekip Touch LSIG 1SDA072546R1 1SDA073176R1
E4.2N 4000 Ekip Hi-Touch LSI 1SDA072548R1 1SDA073178R1
E4.2N 4000 Ekip Hi-Touch LSIG 1SDA072549R1 1SDA073179R1
E4.2S 3200 85 66 E4.2S 3200 Ekip Dip LI 1SDA072501R1 1SDA073131R1
E4.2S 3200 Ekip Dip LSI 1SDA072502R1 1SDA073132R1
E4.2S 3200 Ekip Dip LSIG 1SDA072503R1 1SDA073133R1
E4.2S 3200 Ekip Touch LI 1SDA072504R1 1SDA073134R1
E4.2S 3200 Ekip Touch LSI 1SDA072505R1 1SDA073135R1
E4.2S 3200 Ekip Touch LSIG 1SDA072506R1 1SDA073136R1
E4.2S 3200 Ekip Hi-Touch LSI 1SDA072508R1 1SDA073138R1
E4.2S 3200 Ekip Hi-Touch LSIG 1SDA072509R1 1SDA073139R1
4000 85 66 E4.2S 4000 Ekip Dip LI 1SDA072551R1 1SDA073181R1
E4.2S 4000 Ekip Dip LSI 1SDA072552R1 1SDA073182R1
E4.2S 4000 Ekip Dip LSIG 1SDA072553R1 1SDA073183R1
E4.2S 4000 Ekip Touch LI 1SDA072554R1 1SDA073184R1
E4.2S 4000 Ekip Touch LSI 1SDA072555R1 1SDA073185R1
E4.2S 4000 Ekip Touch LSIG 1SDA072556R1 1SDA073186R1
E4.2S 4000 Ekip Hi-Touch LSI 1SDA072558R1 1SDA073188R1
E4.2S 4000 Ekip Hi-Touch LSIG 1SDA072559R1 1SDA073189R1
E4.2H 3200 100 85 E4.2H 3200 Ekip Dip LI 1SDA072511R1 1SDA073141R1
E4.2H 3200 Ekip Dip LSI 1SDA072512R1 1SDA073142R1
E4.2H 3200 Ekip Dip LSIG 1SDA072513R1 1SDA073143R1
E4.2H 3200 Ekip Touch LI 1SDA072514R1 1SDA073144R1
E4.2H 3200 Ekip Touch LSI 1SDA072515R1 1SDA073145R1
E4.2H 3200 Ekip Touch LSIG 1SDA072516R1 1SDA073146R1
E4.2H 3200 Ekip Hi-Touch LSI 1SDA072518R1 1SDA073148R1
E4.2H 3200 Ekip Hi-Touch LSIG 1SDA072519R1 1SDA073149R1
4000 100 85 E4.2H 4000 Ekip Dip LI 1SDA072561R1 1SDA073191R1
E4.2H 4000 Ekip Dip LSI 1SDA072562R1 1SDA073192R1
10

E4.2H 4000 Ekip Dip LSIG 1SDA072563R1 1SDA073193R1


E4.2H 4000 Ekip Touch LI 1SDA072564R1 1SDA073194R1
E4.2H 4000 Ekip Touch LSI 1SDA072565R1 1SDA073195R1
E4.2H 4000 Ekip Touch LSIG 1SDA072566R1 1SDA073196R1
E4.2H 4000 Ekip Hi-Touch LSI 1SDA072568R1 1SDA073198R1
E4.2H 4000 Ekip Hi-Touch LSIG 1SDA072569R1 1SDA073199R1
ORDERING CODES 10/57


Fixed parts

Size Performance Iu Type of Type 3 Poles 4 Poles


range terminal Code Code
E1.2 B, C, N, L 250 - 1600 HR - HR E1.2 W FP Iu=1600 HR HR 1SDA073907R1 1SDA073908R1
E2.2 B, N, S, H 250 - 2000 HR - HR E2.2 W FP Iu=2000 HR HR 1SDA073909R1 1SDA073910R1
E2.2 N, S, H 2500 HR - HR E2.2 W FP Iu=2500 HR HR 1SDA073911R1 1SDA073912R1
E4.2 N, S, H 3200 HR - HR E4.2 W FP Iu=3200 HR HR 1SDA073913R1 1SDA073914R1
E4.2 N, S, H 4000 HR - HR E4.2 W FP Iu=4000 or
1SDA073915R1 1SDA073916R1
V version HR HR
E4.2 V 2000-4000 HR - HR E4.2 W FP Iu=4000 or
1SDA073915R1 1SDA073916R1
V version HR HR
E6.2 H, V 4000-5000 HR - HR E6.2 W FP Iu=5000 HR HR 1SDA073917R1 1SDA073918R1
E6.2/f H, V 4000-5000 HR - HR E6.2 W FP Iu=5000 HR HR 1SDA073919R1
E6.2 (1) H, V, X 4000-6300 HR - HR E6.2 W FP Iu=6300 or
1SDA073920R1 1SDA073921R1
X version HR HR
E6.2/f (1) H, V, X 4000-6300 HR - HR E6.2 W FP Iu=6300 or
1SDA073922R1
X version HR HR
1) These types of fixed parts are suitable for all types of E6.2 mobile parts from 4000A to 6300A (all Icu performance level)

Phase separators are mandatory with Emax 2/E9 circuit breakers. For withdrawable version, phase separators have to be ordered as loose part.
For fixed version, they are provided as standard.

0-Arc distance top cover for fixed parts


Size Type Code
E2.2…E6.2 (1) 0-arc distance top cover E2.2…6.2 W FP 1SDA085710R1
— 1) Factory fitted only. Not compatible with standard AUP, it is necessary to order the following codes:
NOTE: the standard AUP 5 contacts 400V E2.2...E6.2 - left set 1SDA080373R1
fixed parts can not AUP 5 contacts 24V E2.2...E6.2 - left set 1SDA080374R1
accept MT/MTP device. AUP 5 suppl. contacts 400V E2.2...E6.2 - right set 1SDA080375R1
In order to allow the AUP 5 suppl. contacts 24V E2.2...E6.2 - right set 1SDA080376R1
utilization of MT/
MTP mobile parts is
mandatory to install the
grounding clamps on
fixed parts. Accessoriz-
ing only in the factory
10
10/58 S A C E E M A X 2 LO W V O LTA G E A I R C I R C U I T- B R E A K E R S


Accessories
Electrical accessories
First and second opening release - YO
Size Type Code
E1.2..E6.2 YO E1.2..E6.2 24V AC/DC 1SDA073668R1
E1.2..E6.2 YO E1.2..E6.2 30V AC/DC 1SDA073669R1
E1.2..E6.2 YO E1.2..E6.2 48V AC/DC 1SDA073670R1
E1.2..E6.2 YO E1.2..E6.2 60V AC/DC 1SDA073671R1
E1.2..E6.2 YO E1.2..E6.2 110-120V AC/DC 1SDA073672R1
E1.2..E6.2 YO E1.2..E6.2 120-127V AC/DC 1SDA073673R1
E1.2..E6.2 YO E1.2..E6.2 220-240V AC/DC 1SDA073674R1
E1.2..E6.2 YO E1.2..E6.2 240-250V AC/DC 1SDA073675R1
E1.2..E6.2 YO E1.2..E6.2 277V AC 1SDA073676R1
E1.2..E6.2 YO E1.2..E6.2 380-400V AC 1SDA073677R1
E1.2..E6.2 YO E1.2..E6.2 415-440V AC 1SDA073678R1
E1.2..E6.2 YO E1.2..E6.2 480-500V AC 1SDA073679R1

First and second closing release - YC


Size Type Code
E1.2..E6.2 YC E1.2..E6.2 24V AC/DC 1SDA073681R1
E1.2..E6.2 YC E1.2..E6.2 30V AC/DC 1SDA073682R1
E1.2..E6.2 YC E1.2..E6.2 48V AC/DC 1SDA073683R1
E1.2..E6.2 YC E1.2..E6.2 60V AC/DC 1SDA073684R1
E1.2..E6.2 YC E1.2..E6.2 110-120V AC/DC 1SDA073685R1
E1.2..E6.2 YC E1.2..E6.2 120-127V AC/DC 1SDA073686R1
E1.2..E6.2 YC E1.2..E6.2 220-240V AC/DC 1SDA073687R1
E1.2..E6.2 YC E1.2..E6.2 240-250V AC/DC 1SDA073688R1
E1.2..E6.2 YC E1.2..E6.2 277V AC 1SDA073689R1
E1.2..E6.2 YC E1.2..E6.2 380-400V AC 1SDA073690R1
E1.2..E6.2 YC E1.2..E6.2 415-440V AC 1SDA073691R1
E1.2..E6.2 YC E1.2..E6.2 480-500V AC 1SDA073692R1

YO/YC test unit


Size Type Code
E1.2...E6.2 (1) YO/YC test unit E1.2...E6.2 1SDA082751R1
1) Only as loose part

Undervoltage release - YU
Size Type Code
E1.2..E6.2 YU E1.2..E6.2 24V AC/DC 1SDA073694R1
E1.2..E6.2 YU E1.2..E6.2 30V AC/DC 1SDA073695R1
E1.2..E6.2 YU E1.2..E6.2 48V AC/DC 1SDA073696R1
E1.2..E6.2 YU E1.2..E6.2 60V AC/DC 1SDA073697R1
E1.2..E6.2 YU E1.2..E6.2 110-120V AC/DC 1SDA073698R1
E1.2..E6.2 YU E1.2..E6.2 120-127V AC/DC 1SDA073699R1
E1.2..E6.2 YU E1.2..E6.2 220-240V AC/DC 1SDA073700R1
E1.2..E6.2 YU E1.2..E6.2 240-250V AC/DC 1SDA073701R1
E1.2..E6.2 YU E1.2..E6.2 277V AC 1SDA073702R1
E1.2..E6.2 YU E1.2..E6.2 380-400V AC 1SDA073703R1
E1.2..E6.2 YU E1.2..E6.2 415-440V AC 1SDA073704R1
E1.2..E6.2 YU E1.2..E6.2 480-500V AC 1SDA073705R1

Electronic time-delay device for undervoltage release - UVD


Size Type Code
E1.2...E6.2 24...30V DC 1SDA038316R1
E1.2...E6.2 48V AC/DC 1SDA038317R1
E1.2...E6.2 60V AC/DC 1SDA038318R1
E1.2...E6.2 110...127V AC/DC 1SDA038319R1
E1.2...E6.2 220...250V AC/DC 1SDA038320R1
ORDERING CODES 10/59

Remote Reset - YR
Size Type Code
E1.2 YR 24V DC E1.2 1SDA073744R1
E1.2 (1) YR 110V AC/DC E1.2 1SDA073745R1
E1.2 (1) YR 220V AC/DC E1.2 1SDA073746R1
E2.2...E6.2 YR 24V DC E2.2...E6.2 1SDA073747R1
E2.2...E6.2 (1) YR 110V AC/DC E2.2...E6.2 1SDA073748R1
E2.2...E6.2 (1) YR 220V AC/DC E2.2...E6.2 1SDA073749R1
1) when YR is used in DC, the activation of YR must be done with a maximum impulse time of 50ms. The YR cannot be powered permanently.

Motor - M
Size Type Code
E1.2 M E1.2 24-30V AC/DC+S33 M/2 250V 1SDA073708R1
E1.2 M E1.2 48-60V AC/DC+S33 M/2 250V 1SDA073709R1
E1.2 M E1.2 100-130V AC/DC+S33 M/2 250V 1SDA073710R1
E1.2 M E1.2 220-250V AC/DC+S33 M/2 250V 1SDA073711R1
E1.2 M E1.2 380-415V AC+S33 M/2 250V 1SDA073713R1
E2.2...E6.2 M E2.2...E6.2 24-30V AC/DC+S33 M/2 400V 1SDA073722R1
E2.2...E6.2 M E2.2...E6.2 48-60V AC/DC+S33 M/2 400V 1SDA073723R1
E2.2...E6.2 M E2.2...E6.2 100-130V AC/DC+S33 M/2 400V 1SDA073724R1
E2.2...E6.2 M E2.2...E6.2 220-250V AC/DC+S33 M/2 400V 1SDA073725R1
E2.2...E6.2 M E2.2...E6.2 380-415V AC+S33 M/2 400V 1SDA073727R1
E1.2 M E1.2 24-30V AC/DC + S33 M/2 24V DC 1SDA073715R1
E1.2 M E1.2 48-60V AC/DC + S33 M/2 24V DC 1SDA073716R1
E1.2 M E1.2 100-130V AC/DC + S33 M/2 24V DC 1SDA073717R1
E1.2 M E1.2 220-250V AC/DC + S33 M/2 24V DC 1SDA073718R1
E1.2 M E1.2 380-415V AC + S33 M/2 24V DC 1SDA073720R1
E2.2...E6.2 M E2.2...E6.2 24-30V AC/DC + S33 M/2 24V DC 1SDA073729R1
E2.2...E6.2 M E2.2...E6.2 48-60V AC/DC + S33 M/2 24V DC 1SDA073730R1
E2.2...E6.2 M E2.2...E6.2 100-130V AC/DC + S33 M/2 24V DC 1SDA073731R1
E2.2...E6.2 M E2.2...E6.2 220-250V AC/DC + S33 M/2 24V DC 1SDA073732R1

Current sensor for neutral conductor outside the circuit-breaker (1)


Size Type Code
E1.2 - E2.2 Ext CS N E1.2 E2.2 2000A 1SDA073736R1
E2.2 Ext CS N E2.2 2500A 1SDA073737R1
E4.2 Ext CS N E4.2 3200A 1SDA073738R1
E4.2 - E6.2 Ext CS N E4.2 4000A E6.2 50% 1SDA073739R1
E6.2 Ext CS N E6.2 1SDA073740R1
E1.2 - E2.2 Ext CS N E1.2 - E2.2 2000A for 1% CB (2) 1SDA107553R1
E2.2 Ext CS N E2.2 2500A for 1% CB (2) 1SDA107554R1
E4.2 Ext CS N E4.2 3200A for 1% CB (2) 1SDA107555R1
E4.2 - E6.2 Ext CS N E4.2 4000A - E6.2 N 50% for 1% CB (2) 1SDA107556R1
E6.2 Ext CS N E6.2 for 1% CB (2) 1SDA107557R1
1) Only as loose part
2) To be used with circuit-breakers equipped with 1% accuracy feature only. The external neutral is not certified for 1% accuracy.

Homopolar toroid for the earthing conductor of main power supply (1)
Size Type Code
E1.2..E6.2 Homopolar toroid E1.2 … E6.2 100A 1SDA073743R1
E1.2..E6.2 Homopolar toroid E1.2 … E6.2 250A 1SDA076248R1
E1.2..E6.2 Homopolar toroid E1.2 … E6.2 400A 1SDA076249R1
E1.2..E6.2 Homopolar toroid E1.2 … E6.2 800A 1SDA076250R1
10

1) Only as loose part

Toroid for differential protection (1)


Size Type Code
E1.2 - E2.2 Toroid RC E1.2 3p/4p, E2.2 3p 1SDA073741R1
E2.2 - E4.2 Toroid RC E2.2 4p, E4.2 3p 1SDA073742R1
1) Only as loose part
ORDERING CODES 10/65


Accessories
Mechanical interlock
High or low terminal covers- HTC/LTC
Size Type 3 poles 4 poles
Code Code
E1.2 HTC high terminal covers E1.2 2pcs 1SDA073871R1 1SDA073872R1
E1.2 LTC low terminal covers E1.2 F 2pcs 1SDA073873R1 1SDA073874R1

Separators - PB (1)
Size Type Code
E1.2 PB Separators H=100mm 4pz E1.2 F 3P 1SDA073877R1
E1.2 PB Separators H=100mm 6pz E1.2 F 4P 1SDA073878R1
E1.2 PB Separators H=200mm 4pz E1.2 F 3P 1SDA073879R1
E1.2 PB Separators H=200mm 6pz E1.2 F 4P 1SDA073880R1
E1.2 PB Separators 2 pz E1.2 W FP 3P 1SDA076164R1
E1.2 PB Separators 3 pz E1.2 W FP 4P 1SDA076165R1
E2.2...E6.2 PB Separators 2 pz E2.2..E6.2 F 3P 1SDA076166R1
E2.2...E6.2 PB Separators 3 pz E2.2..E6.2 F 4P 1SDA076167R1
E2.2...E6.2 PB Separators 2 pz E2.2..E6.2 W FP 3P 1SDA076168R1
E2.2...E6.2 PB Separators 3 pz E2.2..E6.2 W FP 4P 1SDA076169R1
1) Only as loose part

Cables for mechanical interlock [Group 1]


Size Type Code
E1.2..E6.2 Type A horizontal 1SDA073881R1
E2.2..E6.2 Type B,C,D horizontal 1SDA073882R1
E1.2..E6.2 Type A vertical 1SDA073885R1
E2.2..E6.2 Type B,C,D vertical 1SDA073886R1
Order one type of cable for each interlock. The cable must be ordered on the fixed circuit-breaker or on the fixed part of withdrawable circuit-breaker.

Lever for mechanical interlock of fixed circuit-breaker or mobile part [Group 2]


Size Type 3 Poles 4 Poles
Code Code
E2.2 Lever for mechanical interlock 1SDA073889R1 1SDA073889R1
E4.2 Lever for mechanical interlock 1SDA073890R1 1SDA073890R1
E6.2 Lever for mechanical interlock 1SDA073891R1 1SDA073892R1
The lever for mechanical interlock is not required for E1.2

Support for mechanical interlock of fixed circuit-breaker [Group 3]


Size Type Code
E1.2 Type A - floor mounted 1SDA073893R1
E1.2 Type A - wall mounted 1SDA073894R1
E2.2 … E6.2 Type A / B / D 1SDA073895R1
E2.2 … E6.2 Type C 1SDA073897R1

Support for mechanical interlock of fixed part [Group 4]


Size Type Code
E1.2 Type A 1SDA073896R1
E2.2 … E6.2 Type A / B / D 1SDA073895R1
E2.2 … E6.2 Type C 1SDA073897R1
10

Automatic transfer switch


Size Type Code
E1.2..E6.2 ATS021 1SDA065523R1
E1.2..E6.2 ATS022 1SDA065524R1

ABB S.p.A.
5, Via Pescaria
I-24123, Bergamo
Phone: +39 035 395 111

www.abb.com

Stay tuned. Discover more by visiting the webpages reserved


to Emax 2 and be always up-to-date with the latest edition of
the catalogue.