LAND DETAILS
W MOUZA:- BRAJRAJNAGAR UNIT NO-1
5011
2754 2762
P.S:- BRAJRAJNAGAR 5010
VACANT LAND
2754
WITHIN 100M
2755
2758 2761
N PLOT NO.- 2628
2757 5012
PUMP KHATA NO.- 618 2756
W ATTEND ROOM W 3.0M 3.0M TOTAL AREA -AC 0.296 DEC.OR 1200 SQM 2631
2621
4.0X3.0M 2620
NEAREST RLY. STATION:- BRAJRAJNAGAR
DIST:- JHARSUGUDA
D STATE:- ODISHA
W WITHIN 100M 40.0M 2628
FRONT ELEVATION OF WITHIN 100M PIN NO.- 768225 SITE FOR
SECTIONAL ELEVATION (X-X) VACANT LAND HSD PUMPS 2624
PLAN OF ATTENDANT ROOM SITE FOR VACANT LAND
PUMP ATTENDANT ROOM PORTA CABIN 30.0M PUMP 2627
2625
98
50MM.SUCTION PIPE 1000MM
30.0M 2566
39.5M
BELOW GL AS PER IS:1239
ELECTRIC PUMP WITH FLP. MOTOR TO KU 2597
CONTROL VALVE AND PLACED ON CEMENTED ALTAR DOPA
LI 9M 2626
EMERGENCY SHUT OFF
BAST
I WID
E R
SWITCH FOR MOTOR PUMP 10.0M 40.0M OA D
F1
VACANT LAND
WITHIN 100M
2596
PUMP SHED TO LA
KHAN
3.0M 1.8M HIGH BARBED WIRE FENCING PU R VI LL
AGE
1.5M 3.0M 1.5M 4M=R 6.0M 2592
PART VILLAGE MAP 2579 4983259
PARKING & FILLING AREA
1.75M 1.5M V
DIESEL BOUSER FILLING 4M=R4M=R SITE PLAN SITE PLAN FOR WORK 78
FOR DIESEL BOUSER
4M=R 2590
T4 2575 2581
SB 9.0M SHOP FOR CONSUMER 2574
6.0M SCALE:-1:1500
OVERHEAD FILLING POINT V V V
FACILITY 2573 49 78 INDEX MAP
T3 D T2 T1
D D SCALE:-NOT TO SCALE
R=4.5M W
S 20KL 22 KL
F1 20KL HSD TANK HSD TANK F1
3 SIDES OF THE LICENCES PRIMISES
W PUMP
ATTEND ROOM
S S F F F 250 MM THK. BRICK GUARD WALL IN LIFTING HOOK T. 22KL CAPACITY UNDER GROUND TANK SIZE 2500 MM Ø X 5250 MM
D
GATE 4.0X3.0M
FE
S S S C.M.1:4 WITH 12 MM C. MT. PLASTER EARTHING BOSS LONG LAID IN ORDINARY EARTH PIT.
4.0M
D
F FF
F 3.0M FILL PIPE(75MMØ) IN 1:4 WITH 2 COATS OF WHITE WASHING T. 20KL CAPACITY UNDER GROUND TANK SIZE 2500 MM Ø X 5250 MM
FB 4M=R
SUCTION PIPE(50MMØ) LONG LAID IN ORDINARY EARTH PIT.
VENT PIPE(50MMØ) DRIVEWAY LEVEL T. 45KL CAPACITY UNDER GROUND TANK SIZE 2750 MM Ø X 8250 MM
0.30 DIP(50MMØ)
30.0M 150 MM THICK0.15 LONG LAID IN ORDINARY EARTH PIT.
7.00M PCC 1:2:4 SWEET SAND S. 50 MM SUCTION LINE LAID IN 61 CM UNDER GROUND TUNNEL UPTO E.O.P.
0.90
8.0M D R I V E W A Y FILLING F. FILL POINT FITTED WITH AIR TIGHT THREADED BRASS CAP DECANTING FOR T/L.
D. DIP PIPE WITH CAP ASSEMBLY.
FB
0.15 V. VENT PIPE 6.0 M HIGH OPEN ENDS COVERED WITH TWO LAYERS OF
1.50M H.S.D EO PUMP
NON CORRDIBLE METAL WIRE GAUGE NOT LESS THAN 11 MESH
ATTEND ROOM
4.0X3.0M
0.90M
25MM Ø HOLDING 2. ALL ELECTRICAL FITTINGS ARE FLAME PROOF CONFORMING TO IS 2148.
2.75
FE
14.0M 4.0M 2.0M 2.0M 2.0M 11.0M
H.S.D DUO PUMP DOWN BOLT 3. THERE IS NO BUILDING DRAIN OR SEWER WITHIN 1.5 M OF UNDER GROUND TANK.
H.S.D EO PUMP
D.P. SWITCH 4. THE TANKS PAINTED WITH 2 COATS OF HOT BITUMEN TANK MASTIC
D R I V E W A Y OVER 2 COATS RED LEAD GRAPHITS TO. PROTECT AGAINST CORROSION
8.0M AS PER C C E S APPROVAL NO P-3 (9) 242 DT 28.12.84.
6.25M 450 TKH
R.C.C. BEAM 5. THE TANKS FEBRICATED WITH 6 MM THK FOR SHELL PLATE AND
IN 0.300.25 0.25
0.30 8 MM THK FOR END PLATE AS PER IS 10987.
G G G 10 2L STIRRUP
OUT @ 150MM C/C. 6. 1.8 M. HIGH BARBED WIRE FENCING ALL SIDES OF THE LICENCES PREMISES.
4.0M 9.15M 13.7M 9.15M 4.0M LONGITUDINAL SECTION OF EARTH PIT 20/22/45 KL TANK 7. FIRE BUCKET 2 NOS FOR EACH DISPENSING PUMP (F B).
8. 10 KG CAPACITY D. C .P TYPE FIRE EXTINGUSHER (F E). 2 NOS.
9. NO STRUCTURE WILL BE PROVIDED WITHIN 6.0M RADIOUS OF DISPENSING PUMP.
250 10. PROPOSED CONSUMER OUTFIT WITHIN MINES PREMISES NOT ON
300