Technical overview 06/002
Accessories 06/011,
06/016
Dimensions 06/024
06/002 Moeller HPL0211-2001/2002 Moeller HPL0211-2001/2002 06/003
Overload Relays, Motor-Protective Relays Overload Relays, Motor-Protective Relays
Overview Overview
Overload / Motor-Protective Relays
Z00 0.1 – 24
Z1 6 – 75
Z5-.../...K3 25 – 100
Z5-.../...K4 35 – 150
Z5-.../FF250 50 – 250
Notes 1) Up to DILM580
06/004 Moeller HPL0211-2001/2002 Moeller HPL0211-2001/2002 06/005
Overload Relays Overload Relays
ZE, Z00 Overload Relays ZE, Z00 Overload Relays
Overload / Motor-Protective Relays
Z5 overload relays
For direct mounting
Phase-failure sensitivity to IEC/EN 60 947
25 – 35 1 3 5 97 95 1M 1B DIL3M80, 125 100 Z5-35/SK3 1 off
DIL3AM85, 071573 Separate mounting
35 – 50 DIUL3M80/11, 160 125 Z5-50/SK3
2 4 6 98 96
DIUL3AM85/11, 071572
SDAINL3M125,
50 – 70 SDAINL3AM150 250 160 Z5-70/SK3
071571 2
Accessories Page
1 Contactors 05/014
Accessories 05/016
06/008 Moeller HPL0211-2001/2002 Moeller HPL0211-2001/2002 06/009
Overload Relays, Motor-Protective Relays Overload Relays, Motor-Protective Relays
Z5 Overload Relays, ZW7 Current-Transformer Operated Overload Relays Z5 Overload Relays, ZW7 Current-Transformer Operated Overload Relays
Overload / Motor-Protective Relays
Ir Max. Max.
A Circuit diagram Make contacts Break contacts A gG/gL A gG/gL
Z5 overload relays
Phase-failure sensitivity to IEC/EN 60 947
For separate mounting
25 – 35 1 3 5 97 95 1M 1B 125 100 Z5-35/KK3 1 off Overload release:
071569 Tripping class 10 A, except for ZW7
35 – 50 2 4 6 98 96
160 125 Z5-50/KK3
071568
Short-circuit protection:
50 – 70 250 160 Z5-70/KK3 The maximum admissible fuse for the contactor must be observed.
071567
70 – 100 315 200 Z5-100/KK3
071566 Suitable for the protection of EEx e motors.
PTB certificate no.
35 – 50 1 3 5 97 95 1M 1B 160 125 Z5-50/KK4 1 off Z5-.../KK..: 3.53-23022/94
071560
50 – 70 2 4 6 98 96
250 160 Z5-70/KK4
071559
70 – 100 315 200 Z5-100/KK4
071558
95 – 125 315 250 Z5-125/KK4
071557
150–120 315 250 Z5-150/KK4
046555
50 – 70 1 3 5 97 95 1M 1B 250 160 Z5-70/FF250 1 off
210070
70 – 100 2 4 6 98 96
315 200 Z5-100/FF250
210071
95 – 125 315 250 Z5-125/FF250
210072
120 – 160 355 250 Z5-160/FF250
210073
160 – 220 500 400 Z5-220/FF250
210074
200 – 250 500 400 Z5-250/FF250
210075
ZW7 current transformer-operated overload relay
For separate mounting
42 – 63 1M 1B ZW7-63 1 off
97 95 000245
60 – 90 ZW7-90
98 96
002618
85 – 125 ZW7-125
004991
110 – 160 ZW7-160
007364
160 – 240 ZW7-240
009737
190 – 290 ZW7-290
052448
270 – 400 ZW7-400
045329
360 – 540 ZW7-540
047702
420 – 630 ZW7-630
050075
06/010 Moeller HPL0211-2001/2002
ZEV – The revolutionary motor-protective relay for motor currents from 1–820 A
Technological advances require completely new approaches: the application of Simple engineering:
newly developed sensor systems and tripping units has made motor protection The multi-voltage module automatically adapts to different voltages from
considerably simpler and more economical. All Z overload relays provide the 24 – 240 V 50/60 Hz and 24 – 240 V DC, thus enabling flexible application with all
standard functions: protection in the event of phase failure, overload, or current conventional control voltages.
imbalance. The innovative ZEV motor-protective system from Moeller can now do
all these things and much more: Simple and space-saving mounting:
Ring-type sensors enable the innovative ZEV overload relays to be used even for
Severe starting conditions: small motors. With high motor currents and large cable sizes, the sensor cables are
Even the most severe starting situations can be dealt with by the ZEV motor- simply laid around the supply cables. There is no need for main circuit wiring with
protective system. The enhanced tripping classes (up to Class 40) provide reliable complex cable matching to another unit, nor for drilling a mounting plate. Instead,
protection for motors with starting times of up to 40 seconds. the sensor is simply affixed using a Velcro fastening, saving installation time and
Protection for any motor starting situation can be optimally set by preselecting expense. The volume of the transformer is reduced by up to 58 times in comparison
one of the eight tripping classes between 5 and 40. An earth fault is quickly with conventional transformers, saving valuable space in the control panel.
detected by the external core-balance transformers. The integrated thermistor
connection allows the relay to be upgraded to provide a full motor-protective
system.
Ir
A A
Current sensors
1 – 25 DILE(E)M, ZEV-XSW-25 1 off
DIL00(A)M, 209635
DIL0(A)M
2–65 DIL1(A)M, ZEV-XSW-65
DIL2(A)M 209636
10 – 145 DIL3M80, ZEV-XSW-145
DIL3AM85, 209637
DIL4M115,
DIL4AM145
40 – 820 DILM185 ZEV-XSW-820
to 209641
DILM820
Connecting cables
Length 200 mm ZEV-XSW-25, ZEV-XVK-20 1 off
ZEV-XSW-65, 209643
Length 400 mm ZEV-XSW-145, ZEV-XVK-40
ZEV-XSW-820 209644
Length 800 mm ZEV-XVK-80
209645
SSW core-balance transformers
For earth-leakage monitoring
o 40 mm 0.3 SSW40-0,3 1 off
028286
0.5 SSW40-0,5
028305
1 SSW40-1
028306
o 65 mm 0.5 SSW65-0,5
028307
1 SSW65-1
028316
o 120 mm 0.5 SSW120-0,5
028319
1 SSW120-1
028321
06/012 Moeller HPL0211-2001/2002
L1 Menu
L2
L3
N Class
5 10 15 20
ON OFF
25 30 35 40
C1 C2 Y1 Y2 A1 A2 95 97 05 07 Free
Reset ~ = e parameter
1
0 – 820 A
Fault !
> 105%
L1 L2 L3
Free IF 1)
l µP Reset
% parameter 1
Class Free Free
Hand Auto
parameter 2 parameter
1
T1 Mode Up !
M > 105%
Test Down
3~ T2 Reset
ON OFF IF 1)
96 98 06 08
Inputs Outputs
A1/A2 Rated control voltage 95/96 Break contact for overload/thermistor
T1/T2 Thermistor sensor 97/98 Make contact for overload/thermistor
C1/C2 SSW core-balance transformers 05/06 Break contacts freely assignable
Y1/Y2 Remote reset 07/08 Make contacts freely assignable
Operational readiness delay after tripping: 5 – 12 min (depending on the tripping class set) with thermistor
tripping at 5 K below response temperature
Contactors for normal and overload operation are designed to CLASS 10. The maximum rated operational current of the contactor must be reduced depending on the
CLASS setting on the ZEV so that the contactors are not thermally overloaded if the tripping times are relatively long. The rated operational current Ie of the contactors
can be calculated using the following derating factors:
ICLASS = ICLASS 10 = Ie ICLASS 15 = Ie 0.82 ICLASS 20 = Ie 0.71 ICLASS 25 = Ie 0.63 ICLASS 30 = Ie 0.58 ICLASS 35 = Ie 0.53 ICLASS 40 = Ie 0.5
With ZEV-XSW-25 to ZEV-XSW-145 ring-type sensors, the motor supply leads are passed through the apertures, one phase at a time. For motor currents of less than 1 A,
the motor supply leads have to be looped back through ZEV-XSW-25. The number of loops is governed by the rated motor current.
Number of loops 4 3 2
Rated motor current IN [A] 0.31 – 0.4 0.41 – 0.62 0.63 – 1.24
Setting current on the relay IE [A] 1.24 – 1.6 1.23 – 1.86 1.26 – 2.48
between the minimum and maximum value
Multi-function device
• Selector switch with/without automatic reset
• Short-circuit tripping in the sensor cable
• Zero-voltage safe
• For manual or remote resetting
• Test button
• Short-circuit recognition and zero-voltage safety
can be de-activated
• Mains and fault LED display
3 3 6 24 – 240 V 50/60 Hz, EMT6-DBK 1 off
24 – 240 V DC 066168
Accessories
Screw adapter CS-TE 1 off
095853
Moeller HPL0211-2001/2002 06/015
Overload Relays, Motor-Protective Relays
Thermistor Overload Relays for Machine Protection
N
Characteristic values of sensor circuit at Us and +20 °C
EMT6-DB, EMT6-DBK
L+ Hand EMT6...
UT1-T2 IT1-T2
RT1-T2 V DC max. mA max.
A1/A2
A1 Y1 Y2 21 13
T1, T2 short-circuited – 1.9
3,6 K
Power Tripped T1/T2 4 k 3 0.8
1,6 k
0
T1-T2 open 5.1 –
US
Y1/Y2, RESET
A2 T1 T2 22 14
Functions that can be disconnected on EMT6-DBK:
13–14, 21–22
Function Disconnection via link
Tripped LED Short-circuit recognition Y1 – Y3
PTC
Zero-voltage safety Y1 – Y4
EMT6-DBK
L+ Zero-voltage safe operation 12000
Resistance [ ]
Tripped LED
PTC NAT
Short circuit NAT NAT NAT NAT
–20° –5° +5° +15°
N
06/016 Moeller HPL0211-2001/2002
Bases
For separate mounting Z00 EZ00 5 off For snap-fitting on an EN 50 022
022630 top-hat rail or screw fixing
Z1 EZ1 5 off
025003
Push-buttons
For enclosed overload relays
Mounting diameter 22.5 mm
External reset button, IP65
Front ring Matt chromed MDE-06 10 off Blue button plate
095773
Black MDE-06-S 10 off
003092
Matt chromed MDE-287 5 off Blue button plate: RESET
012110
Black MDE-287-S 5 off
080098
Off button, IP65
Front ring Matt chromed MDA-04 5 off Red button plate
022625
Black MDA-04-S
003093
Matt chromed MDA-10 Red button plate with
029744 white circle
Black MDA-10-S
003094
Matt chromed MDA-110 Red button plate: STOP
036863
Black MDA-110-S
080118
Moeller HPL0211-2001/2002 06/017
Overload Relays, Motor-Protective Relays
Accessories
Shrouds
Z5-.../FF250 Z5/FF250-XHB 1 off Overload relay
215217 for separate mounting
Z5/FF250
-XHB
Z5-.../FF250
DIL M400
-XHB
DIL M185/
225/250
Z5/FF250
-XHB-Z
Z5-.../FF250
Z5/FF250
-XHB
06/018 Moeller HPL0211-2001/2002
Tripping characteristics
These tripping characteristics show mean values of drops to approximately 25% of that shown. Specific for the correct selection of overload relays for EEx e
the tolerance range at 20 °C ambient temperature characteristics for each individual setting range are motors and for documentation at the point of
starting from cold. They show the tripping times in available on request. These characteristics for ZE, Z00, installation.
relation to the response current. At operational Z1 and Z5, format 55 75, self-adhesive, correspond
temperature, the tripping time of the overload relay to the data in the PTB test report and are used both
2h 2h 2h 2h 2h
100 ZE 100 Z5 100 ZW7 ZEV 3-pole 100
60 Z00 60 60 100
40 40 40 50
Z1
20 20 20
Minutes
Minutes
20
Minutes
Minutes
10 10 10 15
6 6 10 10
6 CLASS 40
4 4 4 5 5 35
CLASS 40
2 2 2 35 30
2 2
1 1 1 Maximum 30 25
40 40 40 1 25 1
3-phase 3-phase
20 20 20
20 20
Seconds
10
Seconds
10 10 Minimum
Seconds
20
10
Seconds
6 6 6 15 10 CLASS 20
4 4 7 10
4 2-phase 2-phase 5 5 15
2 2 2 3 CLASS 5 10
2 2 5
1 1 1
0.6 0.6 0.6 1 1
1 1.5 2 3 4 6 8 10 15 20 1 1.5 2 3 4 6 8 1015 20 1 1.5 2 3 4 6 8 10 15 20 1 2 3 4 5 6 7 8 910 0.7 1 2 5 8
x Setting current x Setting current x Setting current x Setting current
ZE Z00 Z1 ZW7
Setting Tripping Setting Tripping Setting Tripping Setting Tripping
range characteristics range characteristics range characteristics range characteristics
to to to to
A AWA no. A AWA no. A AWA no. A AWA no.
0.1 – 0.16 23-1036-1 0.1 – 0.16 23-657-10 6 – 10 23-657-40 42 – 63 23-657-60
0.16 – 0.24 23-1036-2 0.16 – 0.24 23-657-12 10 – 16 23-657-42 60 – 90 23-657-62
0.24 – 0.4 23-1036-3 0.24 – 0.4 23-657-14 16 – 24 23-657-44 85 – 125 23-657-64
0.4 – 0.6 23-1036-4 0.4 – 0.6 23-657-16 24 – 40 23-657-46 100 – 160 23-657-66
0.6 – 1.0 23-1036-5 0.6 – 1.0 23-657-18 40 – 57 23-657-48 160 – 240 23-657-68
1.0 – 1.6 23-1036-6 1.0 – 1.6 23-657-20 50 – 63 23-657-49 190 – 290 23-657-70
1.6 – 2.4 23-1036-7 1.6 – 2.4 23-657-22 63 – 75 23-657-51.2 270 – 400 23-657-72
2.4 – 4 23-1036-8 2.4 – 4 23-657-24 360 – 540 23-657-74
4–6 23-1036-9 4–6 23-657-26 420 – 630 23-657-76
6–9 23-1036-10 6 – 10 23-657-28
10 – 16 23-657-30
16 – 24 23-657-32
Between the main contacts and the auxiliary contacts V AC 300 440 440 440 440 440 440 5003) – – – –
as well as between the main contacts
Current setting A 0.1 – 9 0.1 – 24 6 – 75 25 – 100 35 – 142 50 – 250 40 – 630 1 – 8204) 1 – 25 2–65 10 – 145 40 – 820
Short-circuit protection
Max. fuse Page 05/004 05/004 05/006 05/006 05/006 05/006 For overload relay in conjunction with transformers
As required for contactor
Current heat loss (3 current paths)
Lower value of the setting range W 2.5 2.5 3 (7) < 16 < 16 < 16 3 – – – – –
Maximum setting W 6 6 7.5 (10) < 28 < 28 < 28 10 – – – – –
Terminal capacity 27 mm
Solid mm2 2 (0.75– 2.5) 2 (1 – 6) 2 (1 – 16)2) 16 16 – – – – – – –
Flexible without ferrule mm2 – – – 50 70 – – – – – – –
Flexible with ferrule mm2 2 (0.5 – 1.5) 2 (1 – 6) 1 25 50 70 – – – – – – –
2 (1 – 10)2)
Stranded mm2 – – – 50 70 – – – – – – –
Flexible with cable lug mm2 – – – – – 95 – – – – – –
Stranded with cable lug mm2 – – – – – 120 – – – – – –
Solid or stranded AWG 18 – 14 8–14 14 – 2 2 2/0 250 MCM – – – – – –
Flat conductor3) mm – – – 6 9 0.8 6 16 0.8 6 16 0.8 – – – – – –
Busbar mm – – – – – 20 3 – – – – – –
Terminal screws M3.5 M4 M6 M8 M10 M8 25 – – – – – –
Pozidriv screwdriver Size 2 2 2 – – – – – – – – –
Standard screwdriver mm 0.8 5.5 16 16 – – – – – – – – –
Hexagon socket head spanner SW mm – – – 4 5 – – – – – – –
Hexagon head spanner SW mm – – – – – 13 – – – – – –
Tightening torque Nm 1.2 1.8 3.5 6 10 10 – 14 – – – – – –
Notes 1) Operating range to IEC/EN 60 947, 2) When using two conductors, use equal cross-sections 3) Z5-.../FF250: Secure using 1) Operating range to IEC/EN 60 947,
PTB: 5 °C to +50 °C box terminal PTB: −5 °C to +50 °C
2) Limited legibility of the LCD display at < −15 °C
3) With ZEV ... between busbar and sensor
4) Setting range dependent on current sensor
06/022 Moeller HPL0211-2001/2002
Z Overload Relays
Technical Data
Overload / Motor-Protective Relays
Z Overload Relays
Dimensions
Overload / Motor-Protective Relays
Overload relays
ZE
5.5
106
49
32 58
45
>5
=
Z00 + EZ00
Z1 + EZ1
EZ00 EZ1
4.7 a1 a 45 60
a1 35 50
a
c1 EZ00: 2 M4 x 12
c EZ1: 2 M5 x15 a2 34 41.5
MDA
MDE a3
a3 22.5 30
MDA... b 85 86
b1
b1 42.5 42.5
b2
b3
a2
MDE... b2 60 –
b4
b
b3 75 75
b4 41 36
b5 b5 7.5 –
12 c 73 112
c1 90 102
Z5-.../SK
a1 햲 c
Z5-.../SK3 Z5-.../SK4
a3 c1
a 100 118
a1 80 80
a2 80 100
a3 28 28
b 117 117
b1 74 74
b2 135 135
b2
b1
b
Z5
b3 22 23
c 133 133
c1 82.5 84
d 94 94
∅6 ∅7
b3
a2
a e
Z5-.../KK
c
Z5-.../KK3 Z5-.../KK4
e
a 100 118
a1 80 100
b 120 120
b1 74 74
c 133 133
d 94 94
7
b1
e ∅6 ∅7
MDA
MDE
MDA 16.5
a1 MDE
a
Moeller HPL0211-2001/2002 06/025
Z Overload Relays, Current-Transformer Operated Overload Relays, Thermistor Overload Relays
Dimensions
Z5-.../FF250
110
121
96
144
48
111
MDA
MDE
7
169
144
94
74
25 5 7
MDA
16.5
11
MDE
128
ZW7-...
185
44
21
MDE M4
26
26
44
71
55
85
33
55
MDE
159
172 – 250
200
65 65
27
3.2
2.5
+0.4
o 29.5
0
24.1
22.5 102
8
22.3+0.4
0
2–5
06/026 Moeller HPL0211-2001/2002
Motor-protective relays
ZEV
29
59.2
103
78
93
37
7.2 4.5 75
45
Current sensors
ZEV-XSW-...
4.5
103
78
35
37
93
a1 c
a
8
ZEV-XSW-... 25 65 145
a 45 70 90
d2
a1 24 49 68
c 50 58 65
35
d1 6 13 21
d2
d2 11.2 19 26
d1
Moeller HPL0211-2001/2002 06/027
ZEV Motor-Protective Relays
Dimensions
ZEV ZEV-XSW-...
c1
Current sensors
ZEV-XSW-820
~150
35
125 3
37
26