You are on page 1of 96

Edition 10/2022

MANUAL

SIMATIC
ET 200SP
BusAdapter

support.industry.siemens.com
Introduction
1

Safety instructions
2

SIMATIC Product overview


3
ET 200SP
BusAdapter BusAdapter BA 2xRJ45
4

Equipment Manual
BusAdapter BA 2xFC
5

BusAdapter BA 2xM12
6

BusAdapter BA 2xSCRJ
7

BusAdapter BA 2xLC
8

BusAdapter BA 2xLC-LD
9

BusAdapter BA SCRJ/RJ45
10

BusAdapter BA SCRJ/FC
11

BusAdapter BA LC/RJ45
12

BusAdapter BA LC/FC
13

BusAdapter BA LC-LD/RJ45
14

BusAdapter BA LC-LD/M12
15
10/2022
A5E41449003-AC

Continued on next page


Continued

BusAdapter BA-Send 1xFC


16

Strain relief
17

Dimension drawings
A
ET 200SP
BusAdapter
Accessories
B
Equipment Manual
Compatibility
C
Legal information
Warning notice system
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent
damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert
symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are
graded according to the degree of danger.

DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.

WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.

CAUTION
indicates that minor personal injury can result if proper precautions are not taken.

NOTICE
indicates that property damage can result if proper precautions are not taken.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will
be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to
property damage.
Qualified Personnel
The product/system described in this documentation may be operated only by personnel qualified for the specific
task in accordance with the relevant documentation, in particular its warning notices and safety instructions.
Qualified personnel are those who, based on their training and experience, are capable of identifying risks and
avoiding potential hazards when working with these products/systems.
Proper use of Siemens products
Note the following:

WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical
documentation. If products and components from other manufacturers are used, these must be recommended or
approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and
maintenance are required to ensure that the products operate safely and without any problems. The permissible
ambient conditions must be complied with. The information in the relevant documentation must be observed.

Trademarks
All names identified by ® are registered trademarks of Siemens AG. The remaining trademarks in this publication
may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software
described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the
information in this publication is reviewed regularly and any necessary corrections are included in subsequent
editions.

Siemens AG A5E41449003-AC Copyright © Siemens AG 2018 - 2022.


Digital Industries Ⓟ 11/2022 Subject to change All rights reserved
Postfach 48 48
90026 NÜRNBERG
GERMANY
Table of contents

1 Introduction........................................................................................................................................ 8
1.1 Industry Mall..................................................................................................................... 11
1.2 Siemens Industry Online Support...................................................................................... 11

2 Safety instructions.............................................................................................................................. 12
2.1 Security information......................................................................................................... 12

3 Product overview................................................................................................................................ 13

4 BusAdapter BA 2xRJ45........................................................................................................................ 15
4.1 Product overview.............................................................................................................. 15
4.2 Connecting....................................................................................................................... 15
4.3 Diagnostics....................................................................................................................... 18
4.4 Technical specifications.................................................................................................... 19

5 BusAdapter BA 2xFC........................................................................................................................... 20
5.1 Product overview.............................................................................................................. 20
5.2 Connecting....................................................................................................................... 20
5.3 Diagnostics....................................................................................................................... 25
5.4 Technical specifications.................................................................................................... 26

6 BusAdapter BA 2xM12........................................................................................................................ 27
6.1 Product overview.............................................................................................................. 27
6.2 Connecting....................................................................................................................... 28
6.3 Diagnostics....................................................................................................................... 32
6.4 Technical specifications.................................................................................................... 33

7 BusAdapter BA 2xSCRJ........................................................................................................................ 34
7.1 Product overview.............................................................................................................. 34
7.2 Connecting....................................................................................................................... 34
7.3 Diagnostics....................................................................................................................... 38
7.4 Technical specifications.................................................................................................... 39

BusAdapter
Equipment Manual, 10/2022, A5E41449003-AC 5
Table of contents

8 BusAdapter BA 2xLC........................................................................................................................... 41
8.1 Product overview.............................................................................................................. 41
8.2 Connecting....................................................................................................................... 41
8.3 Diagnostics....................................................................................................................... 45
8.4 Technical specifications.................................................................................................... 46

9 BusAdapter BA 2xLC-LD...................................................................................................................... 48
9.1 Product overview.............................................................................................................. 48
9.2 Connecting....................................................................................................................... 48
9.3 Diagnostics....................................................................................................................... 52
9.4 Technical specifications.................................................................................................... 53

10 BusAdapter BA SCRJ/RJ45................................................................................................................... 54
10.1 Product overview.............................................................................................................. 54
10.2 Connecting....................................................................................................................... 55
10.3 Diagnostics....................................................................................................................... 57
10.4 Technical specifications.................................................................................................... 58

11 BusAdapter BA SCRJ/FC....................................................................................................................... 60
11.1 Product overview.............................................................................................................. 60
11.2 Connecting....................................................................................................................... 61
11.3 Diagnostics....................................................................................................................... 63
11.4 Technical specifications.................................................................................................... 64

12 BusAdapter BA LC/RJ45....................................................................................................................... 66
12.1 Product overview.............................................................................................................. 66
12.2 Connecting....................................................................................................................... 67
12.3 Diagnostics....................................................................................................................... 69
12.4 Technical specifications.................................................................................................... 70

13 BusAdapter BA LC/FC.......................................................................................................................... 71
13.1 Product overview.............................................................................................................. 71
13.2 Connecting....................................................................................................................... 72
13.3 Diagnostics....................................................................................................................... 74
13.4 Technical specifications.................................................................................................... 75

14 BusAdapter BA LC-LD/RJ45.................................................................................................................. 76
14.1 Product overview.............................................................................................................. 76
14.2 Connecting....................................................................................................................... 77
14.3 Diagnostics....................................................................................................................... 79
14.4 Technical specifications.................................................................................................... 80

BusAdapter
6 Equipment Manual, 10/2022, A5E41449003-AC
Table of contents

15 BusAdapter BA LC-LD/M12.................................................................................................................. 81
15.1 Product overview.............................................................................................................. 81
15.2 Connecting....................................................................................................................... 82
15.3 Diagnostics....................................................................................................................... 84
15.4 Technical specifications.................................................................................................... 85

16 BusAdapter BA-Send 1xFC.................................................................................................................. 86


16.1 Product overview.............................................................................................................. 86
16.2 Connecting....................................................................................................................... 88
16.3 Diagnostics....................................................................................................................... 89
16.4 Technical specifications.................................................................................................... 90

17 Strain relief......................................................................................................................................... 91
17.1 Product overview.............................................................................................................. 91
17.2 Installing.......................................................................................................................... 92

A Dimension drawings........................................................................................................................... 94
A.1 BusAdapter dimension drawings....................................................................................... 94
A.2 Strain relief dimension drawings....................................................................................... 94

B Accessories......................................................................................................................................... 95
B.1 Accessories....................................................................................................................... 95

C Compatibility...................................................................................................................................... 96

BusAdapter
Equipment Manual, 10/2022, A5E41449003-AC 7
Introduction 1
Purpose of the documentation
This manual supplements the system manual ET 200SP distributed I/O system
(https://support.automation.siemens.com/WW/view/en/58649293).
Functions that generally relate to the system are described in this manual.
The information provided in this manual and in the system/function manuals supports you in
commissioning the system.

Conventions
CPU: When the term "CPU" is used in this manual, it applies to the CPUs of the S7-1500
automation system as well as to the CPUs/interface modules of the distributed I/O system
ET 200SP.
STEP 7: In this documentation, "STEP 7" is used as a synonym for all versions of the
configuration and programming software "STEP 7 (TIA Portal)".
Please also observe notes marked as follows:

NOTE
A note contains important information on the product described in the documentation, on
the handling of the product or on the section of the documentation to which particular
attention should be paid.

ID link for the digital nameplate

The ID link is a globally unique identifier according to IEC 61406, which you will find in the
future as a QR code on your product and the product packaging.
The figure shows an example of an ID link for the BusAdapter RJ45.
You can recognize the ID link by the frame with a black frame corner at the bottom right. The
ID link takes you to the digital nameplate of your product.
Scan the QR code on the product or on the packaging label with a smartphone camera,
barcode scanner, or reader app. Call the ID link.

BusAdapter
8 Equipment Manual, 10/2022, A5E41449003-AC
Introduction

In the digital nameplate, you will find product data, manuals, declarations of conformity,
certificates and other helpful information about your product.

Recycling and disposal


For environmentally friendly recycling and disposal of your old equipment, contact a certified
electronic waste disposal company and dispose of the equipment according to the applicable
regulations in your country.

*HQHUDO )XQFWLRQPDQXDOVRQJHQHUDOWRSLFV
LQIRUPDWLRQ
ವ&RPPXQLFDWLRQ ವ352),1(7
ವ'HVLJQLQJLQWHUIHUHQFHIUHHFRQWUROOHUV

'HYLFHLQIRUPDWLRQ
0DQXDOZLWKGHWDLOHGLQIRUPDWLRQRQWKH

ವ%XV$GDSWHU

%DVLFLQIRUPDWLRQ ,QIRUPDWLRQRQWKH%XV$GDSWHU
ವ7,$3RUWDORQOLQHKHOS

Device information
The BusAdapter manual contains information, for example, on properties, assembling,
connecting, configuring and parameter assignment, alarms and diagnostics and technical
specifications of the BusAdapter.
General information
The function manuals contain detailed descriptions on general topics such as PROFINET and
communication.
You can download the documentation free of charge from the Internet
(https://support.industry.siemens.com/cs/ww/de/view/109742709).

"mySupport"
With "mySupport", your personal work area, you make the most of your Industry Online
Support.
In "mySupport" you can store filters, favorites and tags, request CAx data and put together
your personal library in the Documentation area. Furthermore, your data is automatically
filled into support requests and you always have an overview of your current requests.
You must register once to use the full functionality of "mySupport".
You can find "mySupport" on the Internet (https://support.industry.siemens.com/My/ww/de/).

"mySupport" - Documentation
In the Documentation area of "mySupport", you have the possibility to combine complete
manuals or parts of them to make your own manual.
You can export the manual in PDF format or in an editable format.
Your documentation is available in My Documentation Manager
(http://support.industry.siemens.com/My/ww/de/documentation).

BusAdapter
Equipment Manual, 10/2022, A5E41449003-AC 9
Introduction

"mySupport" - CAx data


In the CAx data area in "mySupport", you can access the current product data for your CAx or
CAe system.
You configure your own download package with a few clicks.
In doing so you can select:
• Product images, 2D dimension drawings, 3D models, internal circuit diagrams, EPLAN
macro files
• Manuals, characteristics, operating manuals, certificates
• Product master data
You can find "mySupport" - CAx data on the Internet
(http://support.industry.siemens.com/my/ww/de/CAxOnline).

Application examples
The application examples support you with various tools and examples for solving your
automation tasks. Solutions are shown in interplay with multiple components in the system -
separated from the focus on individual products.
Additional information can be found on the Internet under Application examples
(https://support.industry.siemens.com/sc/ww/de/sc/2054).

SIMATIC Automation Tool


You can use the SIMATIC Automation Tool to perform commissioning and maintenance
activities simultaneously on various SIMATIC S7 stations as a bulk operation independent of
the TIA Portal.
The SIMATIC Automation Tool provides a multitude of functions:
• Scanning of a PROFINET/Ethernet system network and identification of all connected CPUs
• Address assignment (IP, subnet, gateway) and station name (PROFINET device) to a CPU
• Transfer of the date and the programming device/PC time converted to UTC time to the
module
• Program download to CPU
• RUN/STOP mode switchover
• CPU localization by means of LED flashing
• Reading out of CPU error information
• Reading of the CPU diagnostic buffer
• Reset to factory settings
• Firmware update of the CPU and connected modules
You can find the SIMATIC Automation Tool on the Internet
(https://support.industry.siemens.com/cs/ww/de/view/98161300).

BusAdapter
10 Equipment Manual, 10/2022, A5E41449003-AC
Introduction
1.2 Siemens Industry Online Support

PRONETA
With SIEMENS PRONETA (PROFINET network analysis), you analyze the plant network during
commissioning. PRONETA features two core functions:
• The topology overview independently scans PROFINET and all connected components.
• PRONETA also scans: configuration of the station name, IP subnet mask and identification
and maintenance data (I&M1..3)
For more information, refer to SIEMENS PRONETA
(https://support.industry.siemens.com/cs/ww/de/view/67460624).

1.1 Industry Mall


The Industry Mall is the catalog and order system of Siemens AG for automation and drive
solutions on the basis of Totally Integrated Automation (TIA) and Totally Integrated Power
(TIP).
You can find catalogs for all automation and drive products on the Internet
(https://mall.industry.siemens.com).

1.2 Siemens Industry Online Support


You can find current information on the following topics quickly and easily here:
• Product support
All the information and extensive know-how on your product, technical specifications,
FAQs, certificates, downloads, and manuals.
• Application examples
Tools and examples to solve your automation tasks – as well as function blocks,
performance information and videos.
• Services
Information about Industry Services, Field Services, Technical Support, spare parts and
training offers.
• Forums
For answers and solutions concerning automation technology.
• mySupport
Your personal working area in Industry Online Support for messages, support queries, and
configurable documents.
This information is provided by the Siemens Industry Online Support in the Internet
(https://support.industry.siemens.com).

BusAdapter
Equipment Manual, 10/2022, A5E41449003-AC 11
Safety instructions 2
2.1 Security information
Siemens provides products and solutions with industrial security functions that support the
secure operation of plants, systems, machines and networks.
In order to protect plants, systems, machines and networks against cyber threats, it is
necessary to implement – and continuously maintain – a holistic, state-of-the-art industrial
security concept. Siemens’ products and solutions constitute one element of such a concept.
Customers are responsible for preventing unauthorized access to their plants, systems,
machines and networks. Such systems, machines and components should only be connected
to an enterprise network or the internet if and to the extent such a connection is necessary
and only when appropriate security measures (e.g. firewalls and/or network segmentation)
are in place.
For additional information on industrial security measures that may be implemented, please
visit (https://www.siemens.com/industrialsecurity).
Siemens' products and solutions undergo continuous development to make them more
secure. Siemens strongly recommends that product updates are applied as soon as they are
available and that the latest product versions are used. Use of product versions that are no
longer supported, and failure to apply the latest updates may increase customers' exposure to
cyber threats.
To stay informed about product updates, subscribe to the Siemens Industrial Security RSS
Feed visit (https://www.siemens.com/cert).

BusAdapter
12 Equipment Manual, 10/2022, A5E41449003-AC
Product overview 3
Introduction
The SIMATIC BusAdapters connect Industrial Ethernet to your system ET 200SP. Select the
necessary connection technology and connection method for your process from the different
versions of the SIMATIC BusAdapter.

Supported PROFINET devices


The SIMATIC BusAdapter can be used, for example, for:
• ET 200SP interface module and central processing unit (CPU and Open Controller)
• PN/PN Couplers
• PN/MF Coupler
• Switches
• Network transitions (IE/PB Link)
• Communication for SIMATIC ET200SP (CP1542, CP1543)

Overview
The SIMATIC BusAdapters can be ordered in the following versions:
Interface Variant Article number Properties of the BusAdapter
RJ45 BA 2xRJ45 6ES7193-6AR00-0AA0 PROFINET BusAdapter with standard Ethernet socket for
standard RJ45 connector
BA LC/RJ45 6ES7193-6AG20-0AA0
BA SCRJ/RJ45 6ES7193-6AP20-0AA0
BA LC-LD/RJ45 6ES7193-6AG60-0AA0
FC BA 2xFC 6ES7193-6AF00-0AA0 PROFINET BusAdapter with FastConnect Ethernet con­
nection for direct connection of the bus cable for applic­
BA SCRJ/FC 6ES7193-6AP40-0AA0
ations with increased EMC and vibration/shock load
BA LC/FC 6ES7193-6AG40-0AA0
BA-Send 1xFC 6ES7193-6AS00-0AA0
M12 BA 2xM12 6ES7193-6AM00-0AA0 PROFINET BusAdapter with standard M12 plug (D-
coded) or as a pluggable push-pull version with
BA LC-LD/M12 6ES7193-6AG70-0AA0
increased mechanical load rating
SCRJ BA 2xSCRJ 6ES7193-6AP00-0AA0 PROFINET BusAdapter with fiber-optic cable connection
POF/PCF for SCRJ connector for applications with
BA SCRJ/RJ45 6ES7193-6AP20-0AA0
increased EMC and vibration/shock load as well as elec­
BA SCRJ/FC 6ES7193-6AP40-0AA0 trical potential differences between two stations

BusAdapter
Equipment Manual, 10/2022, A5E41449003-AC 13
Product overview

Interface Variant Article number Properties of the BusAdapter


LC BA 2xLC 6ES7193-6AG00-0AA0 PROFINET BusAdapter with glass fiber-optic cable con­
nection for LC connector for applications with increased
BA LC/RJ45 6ES7193-6AG20-0AA0
EMC and vibration/shock load as well as electric poten­
BA LC/FC 6ES7193-6AG40-0AA0 tial differences between two stations. Media type mul­
timode. Multimode phaser only
LC-LD BA 2xLC-LD 6ES7193-6AG50-0AA0 PROFINET BusAdapter with glass fiber-optic cable con­
nection for LC connector for applications with increased
BA LC-LD/RJ45 6ES7193-6AG60-0AA0
EMC and vibration/shock load as well as electric poten­
BA LC-LD/M12 6ES7193-6AG70-0AA0 tial differences between two stations. Media type single
mode

See also
Strain relief (Page 91)

BusAdapter
14 Equipment Manual, 10/2022, A5E41449003-AC
BusAdapter BA 2xRJ45 4
4.1 Product overview

Article number
6ES7193-6AR00-0AA0

View

Figure 4-1 BusAdapter BA 2×RJ45

Properties
• Direct connection of the Industrial Ethernet/ PROFINET cable
• Two standard Ethernet sockets for standard RJ45 connector

4.2 Connecting

Tools required
3 to 3.5 mm screwdriver, alternatively TX10 (torx).

BusAdapter
Equipment Manual, 10/2022, A5E41449003-AC 15
BusAdapter BA 2xRJ45
4.2 Connecting

Accessories required
• Connector:
– IE FC RJ45 plug 180 2X2 (6GK1901-1BB10-2A)
– IE FC RJ45 plug 180 4X2 (6GK1901-1BB12-2A)
• Cables:
– IE FC TP standard cable (6XV1840-2A)
– IE FC TP trailing cable (6XV1840-3AH10)
– IE FC TP Marine Cable (6XV1840-4AH10)
– IE FC TP robust cable (6XV1841-2)
– IE TP torsion cable (6XV1870-2F)
• Read the information in the system manual Industrial Ethernet/PROFINET
(https://support.industry.siemens.com/cs/ww/en/view/84922825), section "Installing
network components in cabinets".

Pin assignment
The following table shows the signal name and description of the pin assignment of the
BusAdapter BA 2×RJ45.

Table 4-1 Industrial Ethernet/PROFINET pin assignment with BusAdapter BA 2×RJ45


View Signal name Description
3RUW 6KLHOGLQJ 1 TD Transmit Data +
2 TD_N Transmit Data –
3 RD Receive Data +
4 TERM1 Termination Network 1
6KLHOGLQJ
5 TERM1 Termination Network 1
6 RD_N Receive Data –
7 TERM2 Termination Network 2

3RUW 8 TERM2 Termination Network 1

Procedure
Watch video sequence of "Connecting BusAdapter BA 2xRJ45 to the ET 200SP interface mod­
ule" (https://support.industry.siemens.com/cs/ww/de/view/95886218)
To connect Industrial Ethernet/PROFINET to the PROFINET device via the BusAdapter
BA 2xRJ45, follow these steps:
1. Plug the BusAdapter BA 2×RJ45 into the PROFINET device.
2. Screw the BusAdapter BA 2×RJ45 to the PROFINET device (1 screw with 0.25 Nm
tightening torque).
3. Insert the RJ45 bus connector into the Industrial Ethernet/PROFINET port on the
BusAdapter BA 2×RJ45.
You can also swap steps 2 and 3.

BusAdapter
16 Equipment Manual, 10/2022, A5E41449003-AC
BusAdapter BA 2xRJ45
4.2 Connecting

BusAdapter BA 2×RJ45 installed




 

 

① CPU
② BusAdapter BA 2×RJ45
③ Industrial Ethernet/PROFINET connecting cable
④ Interface module
Figure 4-2 BusAdapter BA 2×RJ45 installed (using an ET 200SP CPU/interface module as an example)

NOTE
Installation guidelines for modules with Industrial Ethernet/ PROFINET interfaces
Ensure that all devices are connected to the SELV/PELV power supply (or equivalent). Only
then are you permitted to operate the modules with Industrial Ethernet/ PROFINET interfaces
in LAN networks (Local Area Networks).
A data transfer point that guarantees this degree of safety is prescribed for connection to the
WAN (Wide Area Network).

BusAdapter
Equipment Manual, 10/2022, A5E41449003-AC 17
BusAdapter BA 2xRJ45
4.3 Diagnostics

4.3 Diagnostics

LEDs
The figure below shows the LEDs on the BusAdapter BA 2xRJ45:




① LK1 (green)
② LK2 (green)
Figure 4-3 LEDs on the BusAdapter BA 2xRJ45

LK1/LK2 LEDs on the BusAdapter


Table 4-2 Status and error displays
LED Meaning Remedy
LK1/LK2
There is no Ethernet connection between the Check whether the bus cable to the switch or IO control­
off Industrial Ethernet/PROFINET interface of your ler is disconnected.
PROFINET device and a communication part­
ner, e.g. IO controller.
There is an Ethernet connection between the -
on Industrial Ethernet/PROFINET interface of your
PROFINET device and a communication part­
ner, e.g. IO controller.
The "Node flash test" is running. The RN/ER/MT -
flashes LEDs are also flashing.

BusAdapter
18 Equipment Manual, 10/2022, A5E41449003-AC
BusAdapter BA 2xRJ45
4.4 Technical specifications

4.4 Technical specifications

Technical specifications of BusAdapter BA 2×RJ45


The following table shows the technical specifications as of the issue date. You can find a
data sheet including daily updated technical specifications on the Internet
(https://support.industry.siemens.com/cs/de/en/pv/6ES7193-6AR00-0AA0/td?dl=de).

Article number 6ES7193-6AR00-0AA0


General information
Product type designation BA 2x RJ45
Interfaces
Number of PROFINET interfaces 1
Supports protocol for PROFINET IO
• Number of RJ45 ports 2
• Number of SCRJ ports 0
• Number of LC ports 0
Cable length
– Cu conductors 100 m
Ambient conditions
Ambient temperature during operation
• horizontal installation, min. -30 °C
• horizontal installation, max. 60 °C
• vertical installation, min. -30 °C
• vertical installation, max. 50 °C
Altitude during operation relating to sea level
• Installation altitude above sea level, max. 5 000 m; restrictions for installation altitudes >
2 000 m, see ET 200SP system manual
Dimensions
Width 20 mm
Height 69.5 mm
Depth 59 mm
Weights
Weight, approx. 46 g

BusAdapter
Equipment Manual, 10/2022, A5E41449003-AC 19
BusAdapter BA 2xFC 5
5.1 Product overview

Article number
6ES7193-6AF00-0AA0

View

Figure 5-1 BusAdapter BA 2xFC

Properties
• Direct connection of the Industrial Ethernet/ PROFINET cable
• High mechanical load capacity
• High immunity against electromagnetic interference
• Two PROFINET IO ports

5.2 Connecting

Tools required
3 to 3.5 mm screwdriver, alternatively TX10 (torx).

BusAdapter
20 Equipment Manual, 10/2022, A5E41449003-AC
BusAdapter BA 2xFC
5.2 Connecting

Accessories required
• If you use Fast Connect Cable, we recommend the Industrial Ethernet Fast Connect
Stripping Tool (6GK1901-1GA00) with green knife cassette (6GK1901-1B). This
guarantees fast and safe stripping.
• Fast Connect Cable (recommended types):
• Fast Connect Cable (recommended types):
– IE FC TP Standard Cable GP 2x2 (6XV1840-2AH10)
– IE FC TP Trailing Cable 2x2 (6XV1840-3AH10)
– IE FC TP Flexible Cable GP 2x2 (6XV1870-2B)
– IE FC TP Trailing Cable 2x2 (6XV1870-2D)
– IE TP Torsion Cable 2x2 (6XV1870-2F)
– IE FC TP Food Cable GP 2x2 (6XV1871-2L)
– IE FC TP Festoon Cable 2x2 (6XV1871-2S)
• Read the information in the system manual Industrial Ethernet/PROFINET
(https://support.industry.siemens.com/cs/ww/en/view/84922825), section "Installing
network components in cabinets".

Pin assignment
The following table shows the signal name and description of the pin assignment of the
BusAdapter BA 2×FC:

Table 5-1 Industrial Ethernet/PROFINET pin assignment with BusAdapter BA 2×FC


View Signal name Description
4 RD_N Receive Data -
1PSU 3 TD_N Transmit Data -
2 RD Receive Data +

1 TD Transmit Data +

 Shielding
 ①
1






1PSU
Figure BusAdapter BA 2xFC

Procedure
Watch video sequence of "Connecting the BusAdapter BA 2xFC to the interface module"
(https://support.industry.siemens.com/cs/ww/de/view/95886218)

BusAdapter
Equipment Manual, 10/2022, A5E41449003-AC 21
BusAdapter BA 2xFC
5.2 Connecting

To connect PROFINET IO to the PROFINET device via the BusAdapter BA 2xFC, follow these
steps:
1. Strip insulation from the sheath of the PROFINET connecting cable as follows:
s 

Figure 5-2 PROFINET connecting cable

2. Pull back the locking slide and fold up the cover of the connection element.

① Locking slide
3. Pull up the wire guide as far as it will go.

② Wire guide

BusAdapter
22 Equipment Manual, 10/2022, A5E41449003-AC
BusAdapter BA 2xFC
5.2 Connecting

4. Insert the unstripped single cores of the PROFINET connecting cable (4b) into the cable
routing as far as it will go (4a). Firmly press down the wire guide as far as it will go (4c).
Please refer to the color coding.

D

B


C

③ Shield contact
④ Connecting cable
5. Close the cover of the connection element (5a). Then push the locking slide forwards as
far as it will go (5b).

B

C

6. Screw the BusAdapter BA 2×FC to the PROFINET device (1 screw with 0.25 Nm tightening
torque). To do this, use a screwdriver with a 3 to 3.5 mm blade, alternatively TX10.

BusAdapter
Equipment Manual, 10/2022, A5E41449003-AC 23
BusAdapter BA 2xFC
5.2 Connecting

BusAdapter BA 2xFC installed


 

 

 

 

① CPU
② BusAdapter BA 2xFC
③ Industrial Ethernet/PROFINET connecting cable
④ Connection element
Figure 5-3 BusAdapter BA 2xFC installed (using an ET 200SP CPU/interface module as an example)

NOTE
Installation guidelines for modules with Industrial Ethernet/ PROFINET interfaces
Ensure that all devices are connected to the SELV/PELV power supply (or equivalent). Only
then are you permitted to operate the modules with Industrial Ethernet/ PROFINET interfaces
in LAN networks (Local Area Networks).
A data transfer point that guarantees this degree of safety (SELV/PELV) is prescribed for
connection to the WAN (Wide Area Network).

BusAdapter
24 Equipment Manual, 10/2022, A5E41449003-AC
BusAdapter BA 2xFC
5.3 Diagnostics

5.3 Diagnostics

LEDs
The figure below shows the LEDs on the BusAdapter BA 2xFC:




① LK1 (green)
② LK2 (green)
Figure 5-4 LEDs on the BusAdapter BA 2xFC

LK1/LK2 LEDs on the BusAdapter


Table 5-2 Status and error displays
LED Meaning Remedy
LK1/LK2
There is no Ethernet connection between the Industrial Check whether the bus cable to the switch
off Ethernet/PROFINET interface of your PROFINET device or IO controller is disconnected.
and a communication partner, e.g. IO controller.
There is an Ethernet connection between the Industrial -
on Ethernet/PROFINET interface of your PROFINET device
and a communication partner, e.g. IO controller.
The "Node flash test" is running. The RN/ER/MT LEDs are -
flashes also flashing.

BusAdapter
Equipment Manual, 10/2022, A5E41449003-AC 25
BusAdapter BA 2xFC
5.4 Technical specifications

5.4 Technical specifications

Technical specifications of the BusAdapters BA 2×FC


The following table shows the technical specifications as of the issue date. You can find a
data sheet including daily updated technical specifications on the Internet
(https://support.industry.siemens.com/cs/de/en/pv/6ES7193-6AF00-0AA0/td?dl=de).

Article number 6ES7193-6AF00-0AA0


General information
Product type designation BA 2xFC
Interfaces
Number of PROFINET interfaces 1
Supports protocol for PROFINET IO
• Number of FC (FastConnect) connections 2
Cable length
– Cu conductors 100 m
Ambient conditions
Ambient temperature during operation
• horizontal installation, min. -30 °C
• horizontal installation, max. 60 °C
• vertical installation, min. -30 °C
• vertical installation, max. 50 °C
Altitude during operation relating to sea level
• Installation altitude above sea level, max. 5 000 m; restrictions for installation altitudes >
2 000 m, see ET 200SP system manual
Dimensions
Width 20 mm
Height 69.5 mm
Depth 59 mm
Weights
Weight, approx. 53 g

BusAdapter
26 Equipment Manual, 10/2022, A5E41449003-AC
BusAdapter BA 2xM12 6
6.1 Product overview

Article number
6ES7193-6AM00-0AA0

View

Figure 6-1 View BA 2xM12

Properties
• Two M12 push-pull sockets according to IEC 61076-2-012
• Connection option of the Industrial Ethernet/PROFINET cable using two connector
versions:
– Pluggable push-pull version (see the section "Accessories required")
– Standard M12 connector (D-coded) with screw-type terminal
• Increased mechanical load capacity
• High immunity against electromagnetic interference

BusAdapter
Equipment Manual, 10/2022, A5E41449003-AC 27
BusAdapter BA 2xM12
6.2 Connecting

6.2 Connecting

Installing the bus connector

NOTE
Push-pull connector
For simplifying installation (only plugging in instead of screwing with a defined torque), we
recommend using the push-pull plug for the PROFINET connection.

Tools required
3 to 3.5 mm screwdriver, alternatively TX10 (torx).

Accessories required
• Push-pull version:
– Unlatching straps (6ES7193-6DL00-2AA0)
• M12 connecting cables with push-pull connection system:
– M12 connecting cable 0.5 m (6XV1 871-8AE50)
– M12 connecting cable 1.0 m (6XV1 871-8AH10)
– M12 connecting cable 1.5 m (6XV1 871-8AH15)
– M12 connecting cable 2.0 m (6XV1 871-8AH20)
– M12 connecting cable 3.0 m (6XV1 871-8AH30)
– M12 connecting cable 5.0 m (6XV1 871-8AH50)
– M12 connecting cable 10.0 m (6XV1 871-8AN10)
– M12 connecting cable 15.0 m (6XV1 871-8AN15)
• Siemens pre-assembled connector/cable M12 D-coded without push/pull up to a
maximum length of 15 m:
– IE Connecting Cable M12-180/M12-180 0.3M (6XV1870-8A E30)
– IE Connecting Cable M12-180/M12-180 0.5M (6XV1870-8A E50)
– IE Connecting Cable M12-180/M12-180 1M (6XV1870-8A H10)
– IE Connecting Cable M12-180/M12-180 1.5M (6XV1870-8A H20)
– IE Connecting Cable M12-180/M12-180 2M (6XV1870-8A H30)
– IE Connecting Cable M12-180/M12-180 3M (6XV1870-8A H30)
– IE Connecting Cable M12-180/M12-180 5M (6XV1870-8A H50)
– IE Connecting Cable M12-180/M12-180 10M (6XV1870-8A N10)
– IE Connecting Cable M12-180/M12-180 15M (6XV1870-8A N15)

BusAdapter
28 Equipment Manual, 10/2022, A5E41449003-AC
BusAdapter BA 2xM12
6.2 Connecting

• Siemens pre-assembled connector/cable M12 D-coded without push/pull up to a


maximum length of 100 m:
– Currently only available as a custom made solution. Mr. Hertlein (Tel.: +49 (172)
3172810, juergen.hertlein@siemens.com) is the main contact person for passive
components that are not available as standard equipment in the catalog. He
implements all custom-made solutions.
Read the information in the system manual Industrial Ethernet/PROFINET
(https://support.industry.siemens.com/cs/ww/en/view/84922825), section "Installing network
components in cabinets".

Pin assignment
The following table shows the signal name and description of the pin assignment of the
BusAdapter BA 2×M12.

Table 6-1 Industrial Ethernet/PROFINET pin assignment with BusAdapter BA 2×M12


View Signal name Description
1 TD+ Transmit Data +
 
2 RD+ Receive Data +
3 TD- Transmit Data -
 
4 RD- Receive Data –

 

 

Procedure for standard M12 connector


To connect PROFINET IO to the PROFINET device via the BusAdapter BA 2xM12, follow these
steps:
1. Plug the BusAdapter BA 2×M12 into the PROFINET device.
2. Screw the BusAdapter BA 2×M12 to the PROFINET device (1 screw with 0.25 Nm
tightening torque).
3. Plug the M12 bus connector into the PROFINET port on the BusAdapter BA 2×M12.
Tightening torque for the M12 screw connector is 0.4 - 0.5 Nm.

Procedure for push-pull connectors


Insert the connector axially into the socket till the connection clicks into place.

BusAdapter
Equipment Manual, 10/2022, A5E41449003-AC 29
BusAdapter BA 2xM12
6.2 Connecting

You can detach the connector with an axial pull on the outer unlocking sleeve. To do so, you
need to first disassemble the BusAdapter.

NOTE
Simple unlocking of the push-pull connector without previous disassembly of the
BusAdapter
With push-pull connectors, if necessary, pull the unlatching strap over the connector.
The unlatching strap allows detaching of the connector without previous disassembly of the
BusAdapter

BusAdapter BA 2xM12 installed




① Interface module
② BusAdapter BA 2xM12
③ Industrial Ethernet/PROFINET connecting cable with M12 plug
Figure 6-2 Connecting the BusAdapter BA 2xM12 to the interface module

BusAdapter
30 Equipment Manual, 10/2022, A5E41449003-AC
BusAdapter BA 2xM12
6.2 Connecting

NOTE
Installation guidelines for modules with Industrial Ethernet/ PROFINET interfaces
Ensure that all devices are connected to the SELV/PELV power supply (or equivalent). Only
then are you permitted to operate the modules with Industrial Ethernet/ PROFINET interfaces
in LAN networks (Local Area Networks).
A data transfer point that guarantees this degree of safety is prescribed for connection to the
WAN (Wide Area Network).

Using accessories
• Use the strain relief (Page 91) for vibration and shock loads exceeding 1g.
• For easier removal of push-pull connectors, fit the unlatching straps,
6ES7193-6DL00-2AA0 (under development).

① Unlatching straps
② Strain relief
Figure 6-3 Using accessories

Compatibility of the M12 sockets used


The M12 sockets used conform to IEC 61076-2-012 and can thus be used with the M12 push-
pull connectors as well as with conventional D-coded M12 connectors with screwed
connections.

BusAdapter
Equipment Manual, 10/2022, A5E41449003-AC 31
BusAdapter BA 2xM12
6.3 Diagnostics

6.3 Diagnostics

LEDs
The figure below shows the LEDs on the BusAdapter BA 2xM12:




① LK1 (green)
② LK2 (green)
Figure 6-4 LEDs on the BusAdapter BA 2xM12

LK1/LK2 LEDs on the BusAdapter


Table 6-2 Status and error displays
LED Meaning Remedy
LK1/LK2
There is no Ethernet connection between the Check whether the bus cable to the switch or IO control­
off Industrial Ethernet/PROFINET interface of your ler is disconnected.
PROFINET device and a communication part­
ner, e.g. IO controller.
There is an Ethernet connection between the -
on Industrial Ethernet/PROFINET interface of your
PROFINET device and a communication part­
ner, e.g. IO controller.
The "Node flash test" is running. The RN/ER/MT -
flashes LEDs are also flashing.

BusAdapter
32 Equipment Manual, 10/2022, A5E41449003-AC
BusAdapter BA 2xM12
6.4 Technical specifications

6.4 Technical specifications

Technical specifications of BusAdapter BA 2xM12


The following table shows the technical specifications as of the issue date. You can find a
data sheet including daily updated technical specifications on the Internet
(https://support.industry.siemens.com/cs/de/en/pv/6ES7193-6AM00-0AA0/td?dl=de).

Article number 6ES7193-6AM00-0AA0


General information
Product type designation BA 2x M12 BusAdapter
Interfaces
Number of PROFINET interfaces 1
Supports protocol for PROFINET IO
• Number of M12 ports 2
Cable length
– Cu conductors 100 m
Ambient conditions
Ambient temperature during operation
• horizontal installation, min. -30 °C; No condensation
• horizontal installation, max. 60 °C
• vertical installation, min. -30 °C; No condensation
• vertical installation, max. 50 °C
Altitude during operation relating to sea level
• Installation altitude above sea level, max. 5 000 m; restrictions for installation altitudes >
2 000 m, see ET 200SP system manual
Dimensions
Width 20 mm
Height 73.5 mm
Depth 59 mm
Weights
Weight, approx. 59 g

BusAdapter
Equipment Manual, 10/2022, A5E41449003-AC 33
BusAdapter BA 2xSCRJ 7
7.1 Product overview

Article number
6ES7193-6AP00-0AA0

View

Figure 7-1 BusAdapter BA 2xSCRJ

Properties
• Two FOC connections POF/PCF for SCRJ plug connector
• Applications with increased EMC and vibration/shock load
• Applications with potential differences between two stations

7.2 Connecting

Tools required
3 to 3.5 mm screwdriver, alternatively TX10 (torx).

BusAdapter
34 Equipment Manual, 10/2022, A5E41449003-AC
BusAdapter BA 2xSCRJ
7.2 Connecting

Accessories required
• Connector for PROFINET connection: IE SCRJ POF Plug
• Fiber-optic cable:
– IE POF standard cable (6XV1874-2A)
– IE POF trailing cable (6XV1874-2B)
– IE PCF standard cable (6XV1861-2A)
– IE PCF trailing cable (6XV1861-2C)

Requirements

• Prepare the IE POF cables with the connectors IE SCRJ POF Plug or IE SC RJ PCF Plug.
You will find more Instructions in the installation instructions:
– POF fiber-optic cables with IE SCRJ POF plugs (A5E00351141).
– PCF fiber-optic cables with IE SCRJ PCF plugs (A5E00835119).
• When installing the fiber-optic cable, make sure the bending radius is not less than
permitted:
– IE POF/PCF standard cable: 150 mm
– IE POF/PCF trailing cable: 60 mm
• The maximum lengths of the fiber-optic cables are as follows:
– IE POF standard cable: 50 m
– IE POF trailing cable: 50 m
– IE PCF standard cable: 100 m
– IE PCF trailing cable: 100 m
• When the PROFINET device is the last device of the fiber-optic cable network, the
unoccupied fiber-optic cable interface must be closed with a blanking plug. When the
modules ship, the blanking plugs are inserted in the PROFINET sockets of the BusAdapter.

BusAdapter
Equipment Manual, 10/2022, A5E41449003-AC 35
BusAdapter BA 2xSCRJ
7.2 Connecting

Pin assignment
The following table shows the signal name and description of the pin assignment of the
BusAdapter BA 2×SCRJ.

Table 7-1 Industrial Ethernet/PROFINET pin assignment with BusAdapter BA 2×SCRJ


View Signal name Description
3RUW Receive Data


② Transmit Data

3RUW

Procedure

1. Plug the BusAdapter BA 2×SCRJ into the PROFINET device.


2. Screw the BusAdapter BA 2×SCRJ to the PROFINET device (1 screw with 0.25 Nm
tightening torque). To do this, use a screwdriver with a 3 to 3.5 mm blade, alternatively
TX10.
3. Remove the blanking plugs from the PROFINET sockets.
4. Hold the prepared connector by the housing. Insert it into the PROFINET socket on the
BusAdapter BA 2xSCRJ until you hear it click into place. The coding of the connectors
ensures a safe connection.

CAUTION
The BusAdapter/synchronization module contains a laser system and is classified as
a "CLASS 1 LASER PRODUCT" in accordance with IEC 60825-1.
Can cause personal injury.
Avoid direct eye contact with the laser beam. Do not open the housing. Read the
information in the system manual
(https://support.industry.siemens.com/cs/ww/en/view/84133942) carefully.

You can swap steps 3 and 4.

BusAdapter
36 Equipment Manual, 10/2022, A5E41449003-AC
BusAdapter BA 2xSCRJ
7.2 Connecting

BusAdapter BA 2×SCRJ installed




① Interface module
② BusAdapter BA 2xSCRJ
③ Industrial Ethernet/PROFINET connecting cable (FOC)
Figure 7-2 BusAdapter BA 2×SCRJ connected to interface module (using ET 200SP interface module as
an example)

Reusing used fiber-optic cables

NOTE
Shorten both fiber-optic cores by the damaged lengths and reassemble the connectors. This
will prevent any attenuation losses due to the heavily stressed portions of the fiber-optic
cores.

Reference
For more information on the installation guidelines for fiber-optic cables, refer to the SIMATIC
NET PROFIBUS Network Manual
(https://support.industry.siemens.com/cs/de/de/view/1172302).

BusAdapter
Equipment Manual, 10/2022, A5E41449003-AC 37
BusAdapter BA 2xSCRJ
7.3 Diagnostics

7.3 Diagnostics

LEDs
The figure below shows the LED display on the BusAdapter BA 2xSCRJ:




① LK1 (green)
② MT1 (yellow)
③ LK2 (green)
④ MT2 (yellow)
Figure 7-3 LEDs on the BusAdapter BA 2xSCRJ

LK1/LK2 and MT1/MT2 LEDs on the BusAdapter


Table 7-2 Status and error displays
LED Meaning Remedy
LK1/LK2 MT1/MT2
Not relevant There is no Ethernet connection Check whether the bus cable to the switch or
off between the Industrial Ether­ IO controller is disconnected.
net/PROFINET interface of your
PROFINET device and a communication
partner, e.g. IO controller.
Not relevant There is an Ethernet connection -
on between the Industrial Ether­
net/PROFINET interface of your
PROFINET device and a communication
partner, e.g. IO controller.
Not relevant The "Node flash test" is running. The -
flashes RN/ER/MT LEDs are also flashing.
Not relevant No error -
off

BusAdapter
38 Equipment Manual, 10/2022, A5E41449003-AC
BusAdapter BA 2xSCRJ
7.4 Technical specifications

LED Meaning Remedy


LK1/LK2 MT1/MT2
Not relevant • Fiber-optic error Causes and measures for the transmission
on • Maintenance demanded: attenu­ route:
ation through the fiber-optic cable • Replace the fiber-optic cable if damaged or
is already so high that operation aged.
will soon no longer be possible. • Ensure correct installation of the PROFINET
plugs or PROFINET connectors.
• Adhere to maximum length of 50 m for
POF cable or 100 m for PCF cable.
• Ensure that the FOC connectors fit
securely.

7.4 Technical specifications

Technical specifications of BusAdapter BA 2×SCRJ


The following table shows the technical specifications as of the issue date. You can find a
data sheet including daily updated technical specifications on the Internet
(https://support.industry.siemens.com/cs/de/en/pv/6ES7193-6AP00-0AA0/td?dl=de).

Article number 6ES7193-6AP00-0AA0


General information
Product type designation BA 2xSCRJ
HW functional status from FS04
Interfaces
Number of PROFINET interfaces 1; 2 ports (switch) SCRJ FO
Supports protocol for PROFINET IO
• Number of SCRJ ports 2
• Number of LC ports 0
Cable length
– PCF 100 m
– Plastic FOC (POF) 50 m
– PCF-GI 250 m
Ambient conditions
Ambient temperature during operation
• horizontal installation, min. -25 °C
• horizontal installation, max. 60 °C
• vertical installation, min. -25 °C
• vertical installation, max. 50 °C
Altitude during operation relating to sea level
• Installation altitude above sea level, max. 5 000 m; restrictions for installation altitudes >
2 000 m, see ET 200SP system manual

BusAdapter
Equipment Manual, 10/2022, A5E41449003-AC 39
BusAdapter BA 2xSCRJ
7.4 Technical specifications

Article number 6ES7193-6AP00-0AA0


Dimensions
Width 20 mm
Height 69.5 mm
Depth 59 mm
Weights
Weight, approx. 50 g

BusAdapter
40 Equipment Manual, 10/2022, A5E41449003-AC
BusAdapter BA 2xLC 8
8.1 Product overview

Article number
6ES7193-6AG00-0AA0

View

Figure 8-1 BusAdapter BA 2xLC

Properties
• BusAdapter BA 2×LC is designed for multimode fiber-optic cables with a maximum length
of 3 km.
• Applications with increased EMC and vibration/shock load
• Applications with potential differences between two stations

8.2 Connecting

Tools required
3 to 3.5 mm screwdriver, alternatively TX10 (torx).

BusAdapter
Equipment Manual, 10/2022, A5E41449003-AC 41
BusAdapter BA 2xLC
8.2 Connecting

Accessories required
• If you prepare the FC FO cables with the IE FC FO LC plug, we recommend the FC FO
Termination Kit (LC) (6GK1900-0RL00-0AA0). You can cleave the glass fiber precisely
using the FC FO Termination Kit (LC).

CAUTION
Cleaving the fiber-optic cable
– Wear protective glasses during the cleaving process.
– Dispose of the remaining fibers in a suitable waste container.

• Connector for PROFINET fiber-optic cable connection: IE FC FO LC Plug (10 duplex plugs:
6GK1900-1RB00-2AB0)
• Fiber-optic cable:
– IE FC FO Standard Cable GP (62.5/200/230) (6XV1847-2A)
– IE FC FO Trailing Cable (62.5/200/230) (6XV1847-2C)
• Pre-assembled FO cables with LC connection plug in various lengths:
– IE FO Robust Cable (6XV1873-5Rxx)
– IE FO Standard Cable (6XV1873-5Axx)
– IE FO Trailing Cable (6XV1873-5Cxx)
• FO patch cables/adapter cables with LC connection plug
– MM Cord SC/LC (6XV1843-5EH10-0CA0)
– MM Cord BFOC/LC (6XV1843-5EH10-0AB0)
– MM Cord LC/LC (6XV1843-5EH10-0AA0)
See also Cabling technology in SIOS
(https://support.industry.siemens.com/cs/attachments/109766358/IE_cabling-
technology_EN_Web.pdf).

BusAdapter
42 Equipment Manual, 10/2022, A5E41449003-AC
BusAdapter BA 2xLC
8.2 Connecting

Pin assignment
The following table shows the signal name and description of the pin assignment of the
BusAdapter BA 2×LC:

Table 8-1 Industrial Ethernet/PROFINET pin assignment with BusAdapter BA 2xLC


View Signal name Description
3RUW Receive Data



② Transmit Data

3RUW

Requirements
• Prepare the IE FC FO cable with the IE FC FO LC plug connectors. For detailed instructions,
refer to the assembly instructions Preparing IE FC FO Cable with the plug-in connector IE
FC FO LC Plug (A5E36312721).
• When installing the fiber-optic cable, make sure the bending radius is not less than
permitted:
– IE FC FO Standard Cable GP (62.5/200/230): 70 mm
– IE FC FO Trailing Cable (62.5/200/230) (6XV1847-2C): 88 mm
• The maximum lengths of the fiber-optic cables are as follows:
– IE FC FO Standard Cable GP (62.5/200/230): 2 km
– IE FC FO Trailing Cable (62.5/200/230): 2 km
• When the interface module is the last device of the fiber-optic cable network, the
unoccupied fiber-optic cable interface must be closed with a blanking plug. When the
modules ship, the blanking plugs are inserted in the PROFINET sockets of the BusAdapter.

Procedure
To connect PROFINET IO to the PROFINET device via the BusAdapter BA 2xLC, follow these
steps:
1. Plug the BusAdapter BA 2xLC into the PROFINET device.
2. Screw the BusAdapter BA 2xLC to the PROFINET device (1 screw with 0.25 Nm tightening
torque). To do this, use a screwdriver with a 3 to 3.5 mm blade, alternatively TX10.
3. Remove the blanking plugs from the PROFINET sockets.

BusAdapter
Equipment Manual, 10/2022, A5E41449003-AC 43
BusAdapter BA 2xLC
8.2 Connecting

4. Hold the prepared connector by the housing. Insert it into the PROFINET socket on the
BusAdapter BA 2xLC until you hear it click into place. The coding of the connectors
ensures a safe connection.

CAUTION
The BusAdapter/synchronization module contains a laser system and is classified as
a "CLASS 1 LASER PRODUCT" in accordance with IEC 60825-1.
Can cause personal injury.
Avoid direct eye contact with the laser beam. Do not open the housing. Read the
information in the system manual
(https://support.industry.siemens.com/cs/ww/en/view/84133942) carefully.

BusAdapter BA 2xLC installed




① Interface module
② BusAdapter BA 2xLC
③ Industrial Ethernet/PROFINET fiber-optic connection cable
Figure 8-2 Connecting the BusAdapter BA 2xLC to the interface module

BusAdapter
44 Equipment Manual, 10/2022, A5E41449003-AC
BusAdapter BA 2xLC
8.3 Diagnostics

Reusing used fiber-optic cables

NOTE
Shorten both fiber-optic cores by the damaged lengths and reassemble the connectors. This
will prevent any attenuation losses due to the heavily stressed portions of the fiber-optic
cores.

Fiber type and shape of the fiber end

NOTE
When setting up an optical connection, note the following:
• Use the multimode fiber type
• Use appropriate shape of the fiber end:
– PC (Physical Contact): Flat, rounded, polished fiber end
– UPC (Ultra Physical Contact): Flat, rounded, highly polished fiber end

Reference
For more information on the installation guidelines for fiber-optic cables, refer to the SIMATIC
NET PROFIBUS Network Manual
(https://support.industry.siemens.com/cs/de/de/view/1172302).

8.3 Diagnostics

LEDs
The figure below shows the LEDs on the BusAdapter BA 2xLC:

BusAdapter
Equipment Manual, 10/2022, A5E41449003-AC 45
BusAdapter BA 2xLC
8.4 Technical specifications




① LK1 (green)
② LK2 (green)
Figure 8-3 BA front LED_LK1_LK2

LK1/LK2 LEDs on the BusAdapter


Table 8-2 Status and error displays
LED Meaning Remedy
LK1/LK2
There is no Ethernet connection between the Industrial Check whether the bus cable to the switch
off Ethernet/PROFINET interface of your PROFINET device or IO controller is disconnected.
and a communication partner, e.g. IO controller.
There is an Ethernet connection between the Industrial -
on Ethernet/PROFINET interface of your PROFINET device
and a communication partner, e.g. IO controller.
The "Node flash test" is running. The RN/ER/MT LEDs are -
flashes also flashing.

8.4 Technical specifications

Technical specifications of BusAdapter BA 2xLC


The following table shows the technical specifications as of the issue date. You can find a
data sheet including daily updated technical specifications on the Internet
(https://support.industry.siemens.com/cs/de/en/pv/6ES7193-6AG00-0AA0/td?dl=de).

Article number 6ES7193-6AG00-0AA0


General information
Product type designation BA 2xLC
HW functional status from FS04
Interfaces

BusAdapter
46 Equipment Manual, 10/2022, A5E41449003-AC
BusAdapter BA 2xLC
8.4 Technical specifications

Article number 6ES7193-6AG00-0AA0


Number of PROFINET interfaces 1; 2 ports (switch) LC Multimode Glass Fibre
Supports protocol for PROFINET IO
• Number of SCRJ ports 0
• Number of LC ports 2; Wavelength of 1 270 ... 1 380 nm, corresponds
to 100BASE-FX
Cable length
– Multimode graded-index fiber 50/125 3 km
µm
– Multimode graded-index fiber 3 km
62.5/125 μm
Ambient conditions
Ambient temperature during operation
• horizontal installation, min. -30 °C
• horizontal installation, max. 60 °C
• vertical installation, min. -30 °C
• vertical installation, max. 50 °C
Altitude during operation relating to sea level
• Installation altitude above sea level, max. 5 000 m; restrictions for installation altitudes >
2 000 m, see ET 200SP system manual
Dimensions
Width 20 mm
Height 69.5 mm
Depth 59 mm
Weights
Weight, approx. 40 g

BusAdapter
Equipment Manual, 10/2022, A5E41449003-AC 47
BusAdapter BA 2xLC-LD 9
9.1 Product overview

Article number
6ES7193-6AG50-0AA0

View

Figure 9-1 BA 2xLC-LD

Properties
• BusAdapter BA 2×LC-LD (Long Distance) is designed for single-mode fiber-optic cables
with a maximum length of 20 km
• Applications with increased EMC and vibration/shock load
• Applications with potential differences between two stations

9.2 Connecting

Tools required
3 to 3.5 mm screwdriver, alternatively TX10 (torx).

BusAdapter
48 Equipment Manual, 10/2022, A5E41449003-AC
BusAdapter BA 2xLC-LD
9.2 Connecting

Accessories required

CAUTION
Cleaving the fiber-optic cable
• Wear protective glasses during the cleaving process.
• Dispose of the remaining fibers in a suitable waste container.

• Connector for PROFINET fiber-optic cable connection: IE FC FO LC Plug


• Fiber-optic cable:
– Single-mode fiber 9/125/300 OS1 and OS2
• Tested cables:
– IE FC FO Robust cable GP (6XV1843-2R)
– SM Cord LC/LC (6XV1843-5FH10-0AA0)
Additional information on cables and connection technology can be found on our FastCon­
nect (http://www.siemens.com/fastconnect) homepage and in SIOS
(https://support.industry.siemens.com/cs/attachments/109766358/IE_cabling-
technology_EN_Web.pdf).

Pin assignment
The following table shows the signal name and description of the pin assignment of the
BusAdapter BA 2×LC-LD:

Table 9-1 Industrial Ethernet/PROFINET pin assignment with BusAdapter BA 2xLC-LD


View Signal name Description
3RUW Receive Data



② Transmit Data

3RUW

NOTE
The metal part of the LC-LD transceiver is non-grounded and must not be grounded.

BusAdapter
Equipment Manual, 10/2022, A5E41449003-AC 49
BusAdapter BA 2xLC-LD
9.2 Connecting

Requirements
• When installing the fiber-optic cable, make sure the bending radius is not less than
permitted:
– IE FC FO Robust cable GP (6XV1843-2R): 90 mm (single), 135 mm (multi)
– SM Cord LC/LC (6XV1843-5FH10-0AA0): 42 mm
• The maximum lengths of the fiber-optic cables are as follows:
– IE FC FO Robust cable GP (6XV1843-2R): 20 km
– SM Cord LC/LC (6XV1843-5FH10-0AA0): 20 km
• When the interface module is the last device of the fiber-optic cable network, the
unoccupied fiber-optic cable interface must be closed with a blanking plug. When the
modules ship, the blanking plugs are inserted in the PROFINET sockets of the BusAdapter.

Procedure
To connect PROFINET IO to the PROFINET device via the BusAdapter BA 2xLC-LD, follow these
steps:
1. Plug the BusAdapter BA 2xLC-LD into the PROFINET device.
2. Screw the BusAdapter BA 2xLC-LD to the PROFINET device (1 screw with 0.25 Nm
tightening torque). To do this, use a screwdriver with a 3 to 3.5 mm blade, alternatively
TX10.
3. Remove the blanking plugs from the PROFINET sockets.
4. Hold the prepared connector by the housing. Insert it into the PROFINET socket on the
BusAdapter BA 2xLC-LD until you hear it click into place. The coding of the connectors
ensures a safe connection.

CAUTION
The BusAdapter/synchronization module contains a laser system and is classified as
a "CLASS 1 LASER PRODUCT" in accordance with IEC 60825-1.
Can cause personal injury.
Avoid direct eye contact with the laser beam. Do not open the housing. Read the
information in the system manual
(https://support.industry.siemens.com/cs/ww/en/view/84133942) carefully.

BusAdapter
50 Equipment Manual, 10/2022, A5E41449003-AC
BusAdapter BA 2xLC-LD
9.2 Connecting

BusAdapter BA 2xLC-LD installed




① Interface module
② BusAdapter BA 2xLC-LD
③ Industrial Ethernet/PROFINET fiber-optic connection cable
Figure 9-2 Connecting the BusAdapter BA 2xLC-LD to the interface module

Reusing used fiber-optic cables

NOTE
Shorten both fiber-optic cores by the damaged lengths and reassemble the connectors. This
will prevent any attenuation losses due to the heavily stressed portions of the fiber-optic
cores.

Fiber type and shape of the fiber end

NOTE
When setting up an optical connection, note the following:
• Use the single-mode fiber type
• Use appropriate shape of the fiber end:
– PC (Physical Contact): Flat, rounded, polished fiber end
– UPC (Ultra Physical Contact): Flat, rounded, highly polished fiber end

BusAdapter
Equipment Manual, 10/2022, A5E41449003-AC 51
BusAdapter BA 2xLC-LD
9.3 Diagnostics

Reference
For more information on the installation guidelines for fiber-optic cables, refer to the SIMATIC
NET PROFIBUS Network Manual
(https://support.industry.siemens.com/cs/de/de/view/1172302).

9.3 Diagnostics

LEDs
The figure below shows the LEDs on the BusAdapter BA 2xLC-LD:




① LK1 (green)
② LK2 (green)
Figure 9-3 LED displays on the BusAdapter BA 2xLC-LD

LK1/LK2 LEDs on the BusAdapter


Table 9-2 Status and error displays
LED Meaning Remedy
LK1/LK2
There is no Ethernet connection between the Industrial Check whether the bus cable to the switch
off Ethernet/PROFINET interface of your PROFINET device or IO controller is disconnected.
and a communication partner, e.g. IO controller.
There is an Ethernet connection between the Industrial -
on Ethernet/PROFINET interface of your PROFINET device
and a communication partner, e.g. IO controller.
The "Node flash test" is running. The RN/ER/MT LEDs are -
flashes also flashing.

BusAdapter
52 Equipment Manual, 10/2022, A5E41449003-AC
BusAdapter BA 2xLC-LD
9.4 Technical specifications

9.4 Technical specifications

Technical specifications of BusAdapter 2x LC-LD


The following table shows the technical specifications as of the issue date. You can find a
data sheet including daily updated technical specifications on the Internet
(https://support.industry.siemens.com/cs/de/en/pv/6ES7193-6AG50-0AA0/td?dl=de).

Article number 6ES7193-6AG50-0AA0


General information
Product type designation BA 2 x LC-LD
Interfaces
Number of PROFINET interfaces 1; 2 ports (switch) LC-LD single-mode fiber-optic
cable
Supports protocol for PROFINET IO
• Number of LC ports 2; wavelength of 1 270 ... 1 380 nm, corresponds
to 100BASE-LX
Cable length
– single-mode fiber-optic cable 9/125 µm 20 km; 10 km for topology or IRT configuration;
max. attenuation 13 dB
Ambient conditions
Ambient temperature during operation
• horizontal installation, min. -30 °C
• horizontal installation, max. 60 °C
• vertical installation, min. -30 °C
• vertical installation, max. 50 °C
Altitude during operation relating to sea level
• Installation altitude above sea level, max. 5 000 m; restrictions for installation altitudes >
2 000 m, see ET 200SP system manual
Dimensions
Width 20 mm
Height 69.5 mm
Depth 59 mm
Weights
Weight, approx. 40 g

BusAdapter
Equipment Manual, 10/2022, A5E41449003-AC 53
BusAdapter BA SCRJ/RJ45 10
10.1 Product overview

Article number
6ES7193-6AP20-0AA0

View

① Fiber-optic cable SCRJ


② RJ45
Figure 10-1 BusAdapter BA SCRJ/RJ45

Properties
You connect Industrial Ethernet/PROFINET connection cables to the PROFINET device via the
BusAdapter BA SCRJ/RJ45:
• Optically with fiber-optic cables (FOC) with an SCRJ connector to port 1
• Electrically with a standard RJ45 connector to port 2
To do this, screw the BusAdapter BA SCRJ/RJ45 to the PROFINET device and plug in the SCRJ
connector or the RJ45 connector.
You loop through the Industrial Ethernet/PROFINET via the integrated 2-port switch. You can
use any port of the BusAdapter for feeding or for looping through. The integrated media
converter converts the signals automatically.

BusAdapter
54 Equipment Manual, 10/2022, A5E41449003-AC
BusAdapter BA SCRJ/RJ45
10.2 Connecting

10.2 Connecting

Connecting the SCRJ connector


You can find more information about the required tools, accessories, requirements and
procedures in the section Connecting BusAdapter BA 2×SCRJ (Page 34).

Connecting the RJ45 connector


You can find more information about the required tools, accessories and procedures in the
section Connecting BusAdapter BA 2×RJ45 (Page 15).

Pin assignment
The following table shows the signal names and description of the pin assignment for the
BusAdapter BA SCRJ/RJ45:

Table 10-1 Industrial Ethernet/PROFINET pin assignment with BusAdapter BA SCRJ/RJ45


View Signal name Description
3RUW Receive Data


② Transmit Data

 1 TD Transmit Data +
2 TD_N Transmit Data -
6KLHOGLQJ 3 RD Receive Data +

4 TERM1 Termination Network 1
5 TERM1 Termination Network 1

6 RD_N Receive Data -
3RUW 7 TERM2 Termination Network 2
8 TERM2 Termination Network 2

BusAdapter
Equipment Manual, 10/2022, A5E41449003-AC 55
BusAdapter BA SCRJ/RJ45
10.2 Connecting

BusAdapter BA SCRJ/RJ45 installed

① Interface module
② BusAdapter BA SCRJ/RJ45
③ Industrial Ethernet/PROFINET connecting cable
Figure 10-2 Connecting the BusAdapter BA SCRJ/RJ45 to the interface module

NOTE
Installation guidelines for modules with Industrial Ethernet/ PROFINET interfaces
Ensure that all devices are connected to the SELV/PELV power supply (or equivalent). Only
then are you permitted to operate the modules with Industrial Ethernet/ PROFINET interfaces
in LAN networks (Local Area Networks).
A data transfer point that guarantees this degree of safety is prescribed for connection to the
WAN (Wide Area Network).

BusAdapter
56 Equipment Manual, 10/2022, A5E41449003-AC
BusAdapter BA SCRJ/RJ45
10.3 Diagnostics

10.3 Diagnostics

LEDs
The figure below shows the LEDs on the BusAdapter BA SCRJ/RJ45:





① LK1 (green)
② MT (yellow)
③ LK2 (green)
Figure 10-3 LED displays on the BusAdapter BA SCRJ/RJ45

LK1/LK2 and MT LEDs on the BusAdapter


Table 10-2 Status and error displays
LED Meaning Remedy
LK1/LK2 MT
Not relevant There is no Ethernet connection Check whether the bus cable to the switch or
off between the Industrial Ether­ IO controller is disconnected.
net/PROFINET interface of your
PROFINET device and a communication
partner, e.g. IO controller.
Not relevant There is an Ethernet connection -
on between the Industrial Ether­
net/PROFINET interface of your
PROFINET device and a communication
partner, e.g. IO controller.
Not relevant The "Node flash test" is running. The -
flashes RN/ER/MT LEDs are also flashing.
Not relevant No error -
off

BusAdapter
Equipment Manual, 10/2022, A5E41449003-AC 57
BusAdapter BA SCRJ/RJ45
10.4 Technical specifications

LED Meaning Remedy


LK1/LK2 MT
Not relevant • Fiber-optic error Causes and measures for the transmission
on • Maintenance demanded: attenu­ route:
ation through the fiber-optic cable • Replace the fiber-optic cable if damaged or
is already so high that operation aged.
will soon no longer be possible. • Ensure correct installation of the PROFINET
plugs or PROFINET connectors.
• Adhere to maximum length of 50 m for
POF cable or 100 m for PCF cable.
• Ensure that the FOC connectors fit
securely.

10.4 Technical specifications

Technical specifications of BusAdapter BA SCRJ/RJ45


The following table shows the technical specifications as of the issue date. You can find a
data sheet including daily updated technical specifications on the Internet
(https://support.industry.siemens.com/cs/de/en/pv/6ES7193-6AP20-0AA0/td?dl=de).

Article number 6ES7193-6AP20-0AA0


General information
Product type designation BA SCRJ/RJ45
HW functional status from FS04
Interfaces
Number of PROFINET interfaces 1; 2 ports (SCRJ + RJ45)
Supports protocol for PROFINET IO
• Number of RJ45 ports 1
• Number of SCRJ ports 1
• Number of LC ports 0
Cable length
– PCF 100 m
– Plastic FOC (POF) 50 m
– PCF-GI 250 m
– Cu conductors 100 m
Ambient conditions
Ambient temperature during operation
• horizontal installation, min. -25 °C
• horizontal installation, max. 60 °C
• vertical installation, min. -25 °C
• vertical installation, max. 50 °C
Altitude during operation relating to sea level

BusAdapter
58 Equipment Manual, 10/2022, A5E41449003-AC
BusAdapter BA SCRJ/RJ45
10.4 Technical specifications

Article number 6ES7193-6AP20-0AA0


• Installation altitude above sea level, max. 5 000 m; restrictions for installation altitudes >
2 000 m, see ET 200SP system manual
Dimensions
Width 20 mm
Weights
Weight, approx. 50 g

BusAdapter
Equipment Manual, 10/2022, A5E41449003-AC 59
BusAdapter BA SCRJ/FC 11
11.1 Product overview

Article number
6ES7193-6AP40-0AA0

View

① SCRJ fiber-optic cable


② FastConnect FC
Figure 11-1 BusAdapter BA SCRJ/FC

Properties
• You connect Industrial Ethernet/PROFINET to the PROFINET device via the BusAdapter BA
SCRJ/FC .
• The BusAdapter BA SCRJ/FC has one port for connection of a copper cable and one port for
connection of a fiber-optic cable.
Screw the BusAdapter BA SCRJ/FC with the attached Fast Connect bus cable onto the interface
module and plug in the SCRJ connector.
You loop through the Industrial Ethernet/PROFINET via the integrated 2-port switch. You can
use any port of the BusAdapter for feeding or for looping through. The integrated media
converter converts the signals automatically.

BusAdapter
60 Equipment Manual, 10/2022, A5E41449003-AC
BusAdapter BA SCRJ/FC
11.2 Connecting

11.2 Connecting

Connecting the SCRJ connector


You can find more information about the required tools, accessories, requirements and
procedures in the section Connecting BusAdapter BA 2×SCRJ (Page 34).

Connecting FC plug-in connectors


You can find more information about the required tools, accessories and procedures in the
section Connecting BusAdapter BA 2×FC (Page 20).

Pin assignment
The following table shows the signal name and description of the pin assignment of the
BusAdapter BA SCRJ/FC.

Table 11-1 Industrial Ethernet/PROFINET pin assignment with BusAdapter BA SCRJ/FC


View Signal name Description
3RUW Receive Data



② Transmit Data


1 RD_N Receive Data –


 6KLHOGLQJ
 2 TD_N Transmit Data -

 3 RD Receive Data +
4 TD Transmit Data +
3RUW

Procedure
To connect PROFINET IO to the PROFINET device via the BusAdapter BA SCRJ/FC, follow these
steps:
1. Plug the BusAdapter BA SCRJ/FC into the PROFINET device.
2. Screw the BusAdapter BA SCRJ/FC to the PROFINET device (1 screw with 0.25 Nm
tightening torque). To do this, use a screwdriver with a 3 to 3.5 mm blade, alternatively
TX10.
3. Plug the RJ45 bus connector into the PROFINET port on the BusAdapter BA SCRJ/FC.

BusAdapter
Equipment Manual, 10/2022, A5E41449003-AC 61
BusAdapter BA SCRJ/FC
11.2 Connecting

BusAdapter BA SCRJ/FC installed

① Interface module
② BusAdapter BA SCRJ/FC
③ Industrial Ethernet/PROFINET connecting cable
Figure 11-2 BusAdapter BA SCRJ/FC installed (using an ET 200SP interface module as an example)

NOTE
Installation guidelines for modules with Industrial Ethernet/ PROFINET interfaces
Ensure that all devices are connected to the SELV/PELV power supply (or equivalent). Only
then are you permitted to operate the modules with Industrial Ethernet/ PROFINET interfaces
in LAN networks (Local Area Networks).
A data transfer point that guarantees this degree of safety is prescribed for connection to the
WAN (Wide Area Network).

BusAdapter
62 Equipment Manual, 10/2022, A5E41449003-AC
BusAdapter BA SCRJ/FC
11.3 Diagnostics

11.3 Diagnostics

LEDs
The figure below shows the LEDs on the BusAdapter BA SCRJ/FC:





① LK1 (green)
② MT (yellow)
③ LK2 (green)
Figure 11-3 LEDs on the BusAdapter BA SCRJ/FC

LK1/LK2 and MT LEDs on the BusAdapter


Table 11-2 Status and error displays
LED Meaning Remedy
LK1/LK2 MT
Not relevant There is no Ethernet connection Check whether the bus cable to the switch or
off between the Industrial Ether­ IO controller is disconnected.
net/PROFINET interface of your
PROFINET device and a communication
partner, e.g. IO controller.
Not relevant There is an Ethernet connection -
on between the Industrial Ether­
net/PROFINET interface of your
PROFINET device and a communication
partner, e.g. IO controller.
Not relevant The "Node flash test" is running. The -
flashes RN/ER/MT LEDs are also flashing.
Not relevant No error -
off

BusAdapter
Equipment Manual, 10/2022, A5E41449003-AC 63
BusAdapter BA SCRJ/FC
11.4 Technical specifications

LED Meaning Remedy


LK1/LK2 MT
Not relevant • Fiber-optic error Causes and measures for the transmission
on • Maintenance demanded: attenu­ route:
ation through the fiber-optic cable • Replace the fiber-optic cable if damaged or
is already so high that operation aged.
will soon no longer be possible. • Ensure correct installation of the PROFINET
plugs or PROFINET connectors.
• Adhere to maximum length of 50 m for
POF cable or 100 m for PCF cable.
• Ensure that the FOC connectors fit
securely.

11.4 Technical specifications

Technical specifications of BusAdapter BA SCRJ/FC


The following table shows the technical specifications as of the issue date. You can find a
data sheet including daily updated technical specifications on the Internet
(https://support.industry.siemens.com/cs/de/en/pv/6ES7193-6AP40-0AA0/td?dl=de).

Article number 6ES7193-6AP40-0AA0


General information
Product type designation BA SCRJ/FC
HW functional status from FS04
Interfaces
Number of PROFINET interfaces 1; 2 ports (SCRJ + FC)
Supports protocol for PROFINET IO
• Number of FC (FastConnect) connections 1
• Number of SCRJ ports 1
• Number of LC ports 0
Cable length
– PCF 100 m
– Plastic FOC (POF) 50 m
– PCF-GI 250 m
– Cu conductors 100 m
Ambient conditions
Ambient temperature during operation
• horizontal installation, min. -25 °C
• horizontal installation, max. 60 °C
• vertical installation, min. -25 °C
• vertical installation, max. 50 °C
Altitude during operation relating to sea level

BusAdapter
64 Equipment Manual, 10/2022, A5E41449003-AC
BusAdapter BA SCRJ/FC
11.4 Technical specifications

Article number 6ES7193-6AP40-0AA0


• Installation altitude above sea level, max. 5 000 m; restrictions for installation altitudes >
2 000 m, see ET 200SP system manual
Dimensions
Width 20 mm
Height 69.5 mm
Depth 59 mm
Weights
Weight, approx. 50 g

BusAdapter
Equipment Manual, 10/2022, A5E41449003-AC 65
BusAdapter BA LC/RJ45 12
12.1 Product overview

Article number
6ES7193-6AG20-0AA0

View

① Glass fiber-optic cable LC


② RJ45
Figure 12-1 BusAdapter BA LC/RJ45

Properties
You connect Industrial Ethernet/PROFINET connection cables to the PROFINET device via the
BusAdapter BA LC/RJ45:
• Optically with glass fiber-optic cables with an LC connector to port 1
• Electrically with a standard RJ45 connector to port 2
To do this, screw the BusAdapter BA LC/RJ45 to the PROFINET device and plug in the LC
connector or the RJ45 connector.
You loop through the Industrial Ethernet/PROFINET via the integrated 2-port switch. You can
use any port of the BusAdapter for feeding or for looping through. The integrated media
converter converts the signals automatically.

BusAdapter
66 Equipment Manual, 10/2022, A5E41449003-AC
BusAdapter BA LC/RJ45
12.2 Connecting

12.2 Connecting

Attaching LC connectors
You can find more information about the required tools, accessories, requirements and
procedures in the section Connecting BusAdapter BA 2×LC (Page 41).

Connecting the RJ45 connector


You can find more information about the required tools, accessories and procedures in the
section Connecting BusAdapter BA 2×RJ45 (Page 15).

Pin assignment
The following table shows the signal name and description of the pin assignment of the
BusAdapter BA LC/RJ45:

Table 12-1 Industrial Ethernet/PROFINET pin assignment with BusAdapter BA LC/RJ45


View Signal name Description
3RUW Receive Data


② Transmit Data

1 TD Transmit Data +
2 TD_N Transmit Data -
6KLHOGLQJ 3 RD Receive Data +

4 TERM1 Termination Network 1
5 TERM1 Termination Network 1

6 RD_N Receive Data -
3RUW
7 TERM2 Termination Network 2
8 TERM2 Termination Network 2

BusAdapter
Equipment Manual, 10/2022, A5E41449003-AC 67
BusAdapter BA LC/RJ45
12.2 Connecting

BusAdapter BA LC/RJ45 installed




① Interface module
② BusAdapter BA LC/RJ45
③ Industrial Ethernet/PROFINET connecting cable
Figure 12-2 BusAdapter BA LC/RJ45 installed (using an ET 200SP interface module as an example)

NOTE
Installation guidelines for modules with Industrial Ethernet/ PROFINET interfaces
Ensure that all devices are connected to the SELV/PELV power supply (or equivalent). Only
then are you permitted to operate the modules with Industrial Ethernet/ PROFINET interfaces
in LAN networks (Local Area Networks).
A data transfer point that guarantees this degree of safety is prescribed for connection to the
WAN (Wide Area Network).

BusAdapter
68 Equipment Manual, 10/2022, A5E41449003-AC
BusAdapter BA LC/RJ45
12.3 Diagnostics

12.3 Diagnostics

LEDs
The figure below shows the LEDs on the BusAdapter BA LC/RJ45:




① LK1 (green)
② LK2 (green)
Figure 12-3 BA front LED_LK1_LK2

LEDs LK1/LK2 on the BusAdapter


Table 12-2 Status and error displays
LED Meaning Remedy
LK1/LK2
There is no Ethernet connection between the Industrial Check whether the bus cable to the switch
off Ethernet/PROFINET interface of your PROFINET device or IO controller is disconnected.
and a communication partner, e.g. IO controller.
There is an Ethernet connection between the Industrial -
on Ethernet/PROFINET interface of your PROFINET device
and a communication partner, e.g. IO controller.
The "Node flash test" is running. The RN/ER/MT LEDs are -
flashes also flashing.

BusAdapter
Equipment Manual, 10/2022, A5E41449003-AC 69
BusAdapter BA LC/RJ45
12.4 Technical specifications

12.4 Technical specifications

Technical specifications of the BusAdapters BA LC/RJ45


The following table shows the technical specifications as of the issue date. You can find a
data sheet including daily updated technical specifications on the Internet
(https://support.industry.siemens.com/cs/de/en/pv/6ES7193-6AG20-0AA0/td?dl=de).

Article number 6ES7193-6AG20-0AA0


General information
Product type designation BA LC/RJ45
HW functional status from FS04
Interfaces
Number of PROFINET interfaces 1; 2 ports (switch) LC / RJ45
Supports protocol for PROFINET IO
• Number of RJ45 ports 1
• Number of SCRJ ports 0
• Number of LC ports 1; Wavelength of 1 270 ... 1 380 nm, corresponds
to 100BASE-FX
Cable length
– Cu conductors 100 m
– Multimode graded-index fiber 50/125 3 km
µm
– Multimode graded-index fiber 3 km
62.5/125 μm
Ambient conditions
Ambient temperature during operation
• horizontal installation, min. -30 °C
• horizontal installation, max. 60 °C
• vertical installation, min. -30 °C
• vertical installation, max. 50 °C
Altitude during operation relating to sea level
• Installation altitude above sea level, max. 5 000 m; restrictions for installation altitudes >
2 000 m, see ET 200SP system manual
Dimensions
Width 20 mm
Height 69.5 mm
Depth 59 mm
Weights
Weight, approx. 32 g

BusAdapter
70 Equipment Manual, 10/2022, A5E41449003-AC
BusAdapter BA LC/FC 13
13.1 Product overview

Article number
6ES7193-6AG40-0AA0

View

① Glass fiber-optic cable LC


② FastConnect FC
Figure 13-1 BusAdapter BA LC/FC

Properties
You connect Industrial Ethernet/PROFINET connection cables to the PROFINET device via the
BusAdapter BA LC/FC:
• Optically with glass fiber-optic cables with an LC connector to port 1
• Electrically with direct connection of the Fast Connect bus cable to port 2
Screw the BusAdapter BA LC/FC with the attached Fast Connect bus cable onto the PROFINET
device and plug in the LC connector.
You loop through the Industrial Ethernet/PROFINET via the integrated 2-port switch. You can
use any port of the BusAdapter for feeding or for looping through. The integrated media
converter converts the signals automatically.

BusAdapter
Equipment Manual, 10/2022, A5E41449003-AC 71
BusAdapter BA LC/FC
13.2 Connecting

13.2 Connecting

Attaching LC connectors
You can find more information about the required tools, accessories, requirements and
procedures in the section Connecting BusAdapter BA 2×LC (Page 41).

Connecting FastConnect bus cable


You can find more information about the required tools, accessories and procedures in the
section Connecting BusAdapter BA 2×FC (Page 20).

Pin assignment
The following table shows the signal name and description of the pin assignment of the
BusAdapter BA LC/FC:

Table 13-1 Industrial Ethernet/PROFINET pin assignment with BusAdapter BA LC/FC


View Signal name Description
3RUW Receive Data



② Transmit Data


1 RD_N Receive Data –


 6KLHOGLQJ
 2 TD_N Transmit Data -

 3 RD Receive Data +
4 TD Transmit Data +
3RUW

BusAdapter
72 Equipment Manual, 10/2022, A5E41449003-AC
BusAdapter BA LC/FC
13.2 Connecting

BusAdapter BA LC/FC installed




① Interface module
② BusAdapter BA LC/FC
③ Industrial Ethernet/PROFINET connecting cable
Figure 13-2 Connecting the BusAdapter BA LC/FC to the interface module

NOTE
Installation guidelines for modules with Industrial Ethernet/ PROFINET interfaces
Ensure that all devices are connected to the SELV/PELV power supply (or equivalent). Only
then are you permitted to operate the modules with Industrial Ethernet/ PROFINET interfaces
in LAN networks (Local Area Networks).
A data transfer point that guarantees this degree of safety is prescribed for connection to the
WAN (Wide Area Network).

BusAdapter
Equipment Manual, 10/2022, A5E41449003-AC 73
BusAdapter BA LC/FC
13.3 Diagnostics

13.3 Diagnostics

LEDs
The figure below shows the LEDs on the BusAdapter BA LC/FC:




① LK1 (green)
② LK2 (green)
Figure 13-3 BA front LED_LK1_LK2

LK1/LK2 LEDs on the BusAdapter


Table 13-2 Status and error displays
LED Meaning Remedy
LK1/LK2
There is no Ethernet connection between the Industrial Check whether the bus cable to the switch
off Ethernet/PROFINET interface of your PROFINET device or IO controller is disconnected.
and a communication partner, e.g. IO controller.
There is an Ethernet connection between the Industrial -
on Ethernet/PROFINET interface of your PROFINET device
and a communication partner, e.g. IO controller.
The "Node flash test" is running. The RN/ER/MT LEDs are -
flashes also flashing.

BusAdapter
74 Equipment Manual, 10/2022, A5E41449003-AC
BusAdapter BA LC/FC
13.4 Technical specifications

13.4 Technical specifications

Technical specifications of the BusAdapters BA LC/FC


The following table shows the technical specifications as of the issue date. You can find a
data sheet including daily updated technical specifications on the Internet
(https://support.industry.siemens.com/cs/de/en/pv/6ES7193-6AG40-0AA0/td?dl=de).

Article number 6ES7193-6AG40-0AA0


General information
Product type designation BA LC/FC
HW functional status from FS04
Interfaces
Number of PROFINET interfaces 1
Supports protocol for PROFINET IO
• Number of FC (FastConnect) connections 1
• Number of SCRJ ports 0
• Number of LC ports 1; Wavelength of 1 270 ... 1 380 nm, corresponds
to 100BASE-FX
Cable length
– Cu conductors 100 m
– Multimode graded-index fiber 50/125 3 km
µm
– Multimode graded-index fiber 3 km
62.5/125 μm
Ambient conditions
Ambient temperature during operation
• horizontal installation, min. -30 °C
• horizontal installation, max. 60 °C
• vertical installation, min. -30 °C
• vertical installation, max. 50 °C
Altitude during operation relating to sea level
• Installation altitude above sea level, max. 5 000 m; restrictions for installation altitudes >
2 000 m, see ET 200SP system manual
Dimensions
Width 20 mm
Height 69.5 mm
Depth 59 mm
Weights
Weight, approx. 50 g

BusAdapter
Equipment Manual, 10/2022, A5E41449003-AC 75
BusAdapter BA LC-LD/RJ45 14
14.1 Product overview

Article number
6ES7193-6AG60-0AA0

View
BA LC - LD/RJ45

6ES7193-6AG60- 0AA0 


① Glass fiber-optic cable LC


② RJ45
Figure 14-1 BusAdapter BA LC-LD/RJ45

Properties
You connect Industrial Ethernet/PROFINET connection cables to the PROFINET device via the
BusAdapter BA LC-LD/RJ45:
• Optically with glass fiber-optic cables with an LC connector to port 1
• Electrically with a standard RJ45 connector to port 2.
To do this, screw the BusAdapter BA LC-LD/RJ45 to the PROFINET device and plug in the LC
connector or the RJ45 connector.
You loop through the Industrial Ethernet/PROFINET via the integrated 2-port switch. You can
use any port of the BusAdapter for feeding or for looping through. The integrated media
converter converts the signals automatically.

BusAdapter
76 Equipment Manual, 10/2022, A5E41449003-AC
BusAdapter BA LC-LD/RJ45
14.2 Connecting

14.2 Connecting

Attaching LC connectors
You can find more information about the required tools, accessories, requirements and
procedures in the section Connecting BusAdapter BA 2xLC-LD (Page 48).

Connecting the RJ45 connector


You can find more information about the required tools, accessories and procedures in the
section Connecting BusAdapter BA 2×RJ45 (Page 15).

Pin assignment
The following table shows the signal name and description of the pin assignment of the
BusAdapter BA LC-LD/RJ45:

Table 14-1 Industrial Ethernet/PROFINET pin assignment with BusAdapter BA LC-LD/RJ45


View Signal name Description
3RUW Receive Data


② Transmit Data

1 TD Transmit Data +
2 TD_N Transmit Data -
6KLHOGLQJ 3 RD Receive Data +

4 TERM1 Termination Network 1
5 TERM1 Termination Network 1

6 RD_N Receive Data -
3RUW
7 TERM2 Termination Network 2
8 TERM2 Termination Network 2

NOTE
The metal part of the LC-LD transceiver is non-grounded and must not be grounded.

BusAdapter
Equipment Manual, 10/2022, A5E41449003-AC 77
BusAdapter BA LC-LD/RJ45
14.2 Connecting

BusAdapter BA LC-LD/RJ45 installed




① Interface module
② BusAdapter BA LC-LD/RJ45
③ Industrial Ethernet/PROFINET connecting cable
Figure 14-2 BusAdapter BA LC-LD/RJ45 installed (using an ET 200SP interface module as an example)

NOTE
Installation guidelines for modules with Industrial Ethernet/ PROFINET interfaces
Ensure that all devices are connected to the SELV/PELV power supply (or equivalent). Only
then are you permitted to operate the modules with Industrial Ethernet/ PROFINET interfaces
in LAN networks (Local Area Networks).
A data transfer point that guarantees this degree of safety is prescribed for connection to the
WAN (Wide Area Network).

BusAdapter
78 Equipment Manual, 10/2022, A5E41449003-AC
BusAdapter BA LC-LD/RJ45
14.3 Diagnostics

14.3 Diagnostics

LEDs
The figure below shows the LEDs on the BusAdapter BA LC-LD/RJ45:




① LK1 (green)
② LK2 (green)
Figure 14-3 LED displays on the BusAdapter BA LC-LD/RJ45

LEDs LK1/LK2 on the BusAdapter


Table 14-2 Status and error displays
LED Meaning Remedy
LK1/LK2
There is no Ethernet connection between the Industrial Check whether the bus cable to the switch
off Ethernet/PROFINET interface of your PROFINET device or IO controller is disconnected.
and a communication partner, e.g. IO controller.
There is an Ethernet connection between the Industrial -
on Ethernet/PROFINET interface of your PROFINET device
and a communication partner, e.g. IO controller.
The "Node flash test" is running. The RN/ER/MT LEDs are -
flashes also flashing.

BusAdapter
Equipment Manual, 10/2022, A5E41449003-AC 79
BusAdapter BA LC-LD/RJ45
14.4 Technical specifications

14.4 Technical specifications

Technical specifications of the BusAdapters BA LC-LD/RJ45


The following table shows the technical specifications as of the issue date. You can find a
data sheet including daily updated technical specifications on the Internet
(https://support.industry.siemens.com/cs/de/en/pv/6ES7193-6AG60-0AA0/td?dl=de).

Article number 6ES7193-6AG60-0AA0


General information
Product type designation BA LC-LD / RJ45
Interfaces
Number of PROFINET interfaces 1; 2 ports (switch) 1x LC-LD single-mode + 1x
RJ45
Supports protocol for PROFINET IO
• Number of RJ45 ports 1
• Number of LC ports 1; wavelength of 1 270 ... 1 380 nm, corresponds
to 100BASE-LX
Cable length
– Cu conductors 100 m
– single-mode fiber-optic cable 9/125 µm 20 km; 10 km for topology or IRT configuration;
max. attenuation 13 dB
Ambient conditions
Ambient temperature during operation
• horizontal installation, min. -30 °C
• horizontal installation, max. 60 °C
• vertical installation, min. -30 °C
• vertical installation, max. 50 °C
Altitude during operation relating to sea level
• Installation altitude above sea level, max. 5 000 m; restrictions for installation altitudes >
2 000 m, see ET 200SP system manual
Dimensions
Width 20 mm
Height 69.5 mm
Depth 59 mm
Weights
Weight, approx. 32 g

BusAdapter
80 Equipment Manual, 10/2022, A5E41449003-AC
BusAdapter BA LC-LD/M12 15
15.1 Product overview

Article number
6ES7193-6AG70-0AA0

View
M12
BA LC - LD/

70-0AA0


6ES7193-6AG

① Glass fiber-optic cable LC


② M12
Figure 15-1 BusAdapter BA LC-LD/M12

Properties
You connect Industrial Ethernet/PROFINET connection cables to the PROFINET device via the
BusAdapter BA LC-LD/M12:
• Optically with glass fiber-optic cables with an LC connector to port 1
• Electrically with a standard 12-pin connector to port 2.
To do this, screw the BusAdapter BA LC-LD/M12 to the PROFINET device and plug in the LC
connector or the M12 plug.
You loop through the Industrial Ethernet/PROFINET via the integrated 2-port switch. You can
use any port of the BusAdapter for feeding or for looping through. The integrated media
converter converts the signals automatically.

BusAdapter
Equipment Manual, 10/2022, A5E41449003-AC 81
BusAdapter BA LC-LD/M12
15.2 Connecting

15.2 Connecting

Attaching LC connectors
You can find more information about the required tools, accessories, requirements and
procedures in the section Connecting BusAdapter BA 2xLC-LD (Page 48).

Connecting M12 plugs


You can find more information about the required tools, accessories and procedures in the
section Connecting BusAdapter BA 2×M12 (Page 27).

Pin assignment
The following table shows the signal name and description of the pin assignment of the
BusAdapter BA LC-LD/M12:
Table 15-1 Industrial Ethernet/PROFINET pin assignment with BusAdapter BA LC-LD/M12
View Signal name Description

① Receive Data
1PSU
② Transmit Data

 1 TD+ Transmit Data +

 2 RD+ Receive Data +


3 TD- Transmit Data -
4 RD- Receive Data -
 

 

1PSU

NOTE
The metal part of the LC-LD transceiver is non-grounded and must not be grounded.

BusAdapter
82 Equipment Manual, 10/2022, A5E41449003-AC
BusAdapter BA LC-LD/M12
15.2 Connecting

BusAdapter BA LC-LD/M12 installed

① Interface module
② BusAdapter BA LC-LD/M12
③ Industrial Ethernet/PROFINET connecting cable
Figure 15-2 BusAdapter BA LC-LD/M12 installed (using an ET 200SP interface module as an example)

NOTE
Installation guidelines for modules with Industrial Ethernet/ PROFINET interfaces
Ensure that all devices are connected to the SELV/PELV power supply (or equivalent). Only
then are you permitted to operate the modules with Industrial Ethernet/ PROFINET interfaces
in LAN networks (Local Area Networks).
A data transfer point that guarantees this degree of safety is prescribed for connection to the
WAN (Wide Area Network).

BusAdapter
Equipment Manual, 10/2022, A5E41449003-AC 83
BusAdapter BA LC-LD/M12
15.3 Diagnostics

15.3 Diagnostics

LEDs
The figure below shows the LEDs on the BusAdapter BA LC-LD/M12:




① LK1 (green)
② LK2 (green)
Figure 15-3 LED displays on the BusAdapter BA LC-LD/M12

LEDs LK1/LK2 on the BusAdapter


Table 15-2 Status and error displays
LED Meaning Remedy
LK1/LK2
There is no Ethernet connection between the Industrial Check whether the bus cable to the switch
off Ethernet/PROFINET interface of your PROFINET device or IO controller is disconnected.
and a communication partner, e.g. IO controller.
There is an Ethernet connection between the Industrial -
on Ethernet/PROFINET interface of your PROFINET device
and a communication partner, e.g. IO controller.
The "Node flash test" is running. The RN/ER/MT LEDs are -
flashes also flashing.

BusAdapter
84 Equipment Manual, 10/2022, A5E41449003-AC
BusAdapter BA LC-LD/M12
15.4 Technical specifications

15.4 Technical specifications

Technical specifications of the BusAdapters BA LC-LD/M12


The following table shows the technical specifications as of the issue date. You can find a
data sheet including daily updated technical specifications on the Internet
(https://support.industry.siemens.com/cs/de/en/pv/6ES7193-6AG70-0AA0/td?dl=de).

Article number 6ES7193-6AG70-0AA0


General information
Product type designation BA LC-LD / M12
Interfaces
Number of PROFINET interfaces 1; 2 ports (switch) 1x LC-LD single-mode + 1x
M12
Supports protocol for PROFINET IO
• Number of LC ports 1; wavelength of 1 270 ... 1 380 nm, corresponds
to 100BASE-LX
• Number of M12 ports 1
Cable length
– Cu conductors 100 m
– single-mode fiber-optic cable 9/125 µm 20 km; 10 km for topology or IRT configuration;
max. attenuation 13 dB
Ambient conditions
Ambient temperature during operation
• horizontal installation, min. -30 °C
• horizontal installation, max. 60 °C
• vertical installation, min. -30 °C
• vertical installation, max. 50 °C
Altitude during operation relating to sea level
• Installation altitude above sea level, max. 5 000 m; restrictions for installation altitudes >
2 000 m, see ET 200SP system manual
Dimensions
Width 20 mm
Height 69.5 mm
Depth 59 mm
Weights
Weight, approx. 45 g

BusAdapter
Equipment Manual, 10/2022, A5E41449003-AC 85
BusAdapter BA-Send 1xFC 16
16.1 Product overview

Article number
6ES7193-6AS00-0AA0

View
BA-Send FC

DIAG

;
X1
ON 
ET-CONNECTI
-0AA0
6ES7193-6AS00

Figure 16-1 View of the BusAdapter BA-Send 1xFC

Properties
The module has the following technical properties:
• BusAdapter for the direct connection of ET-Connection
• Connects the interface module via ET-Connection with the ET 200AL I/O modules
• Supports all ET 200AL I/O modules
The module supports the following functions:
• Identification data I&M 0 to 3. See system manual ET 200SP Distributed I/O System
(http://support.automation.siemens.com/WW/view/en/58649293).

Maximum configuration
• 16 ET 200AL I/O modules
• 15 m bus cable between BusAdapter BA Send and the first ET 200AL I/O module and
between two ET 200AL I/O modules.

BusAdapter
86 Equipment Manual, 10/2022, A5E41449003-AC
BusAdapter BA-Send 1xFC
16.1 Product overview

• Supported functions:

Function Mixed configuration


ET 200SP ET 200AL I/O modules on
IM CPU ET-Connection

Isochronous mode ● -- --
Configuration control ● ● ●
Shared device ● ● ●
PROFIenergy ● -- ●
System redundancy S2 ●1 -- ●1
1) With IM 155-6 PN/3 HF and IM 155-6 PN/2 HF V4.2 or higher

Accessories
The following components must be ordered separately:
• Labeling strips
• Reference identification label
• Stripping tool for ET-Connection
• Bus cables for ET-Connection

See also
You will find additional information on accessories and the other components in the system
manuals ET 200AL Distributed I/O System
(http://support.automation.siemens.com/WW/view/en/89254965) and the Accessories/Spare
parts section of the ET 200SP Distributed I/O System
(http://support.automation.siemens.com/WW/view/en/58649293) system manual.

BusAdapter
Equipment Manual, 10/2022, A5E41449003-AC 87
BusAdapter BA-Send 1xFC
16.2 Connecting

16.2 Connecting

ET-Connection with BusAdapter BA-Send 1xFC


The following table shows the signal names and the designations for the pin assignment of
the BusAdapter BA-Send 1xFC.

Table 16-1 ET connection pin assignment with BusAdapter BA-Send 1xFC


View Signal name Description
3RUW 1 TD Transmit Data +
2 RD Receive Data +
 3 TD_N Transmit Data –

6KLHOGLQJ
 4 RD_N Receive Data -


Block diagram
7/&

(7&RQQHFWLRQ
FRQQHFWLRQ

Figure 16-2 Schematic circuit diagram for BusAdapter BA-Send 1xFC

BusAdapter
88 Equipment Manual, 10/2022, A5E41449003-AC
BusAdapter BA-Send 1xFC
16.3 Diagnostics

16.3 Diagnostics

LED display
The figure below shows the LED display (status and fault display) of the BusAdapter BA-Send
1xFC.

① DIAG (green/red)
Figure 16-3 LED display

Meaning of the LED display


The table below explains the meaning of the status and fault display.

DIAG LED
Table 16-2 Status and fault display DIAG
DIAG LED Meaning Remedy
There is no connection between the ET-Connection Check whether the bus cable is interrupted.
Off interface of the BusAdapter BA-Send 1xFC and the
ET 200AL.
The CPU/interface module does not support the BA- Run a firmware update.
Send 1xFC.
There is a connection between the ET-Connection ---
On interface of the BusAdapter BA-Send 1xFC and the
ET 200AL.
There is (at least) one diagnostics alarm of an ET- Check the ET-Connection device.
Flashes Connection device. Group error for all ET-Connection
bus nodes.
Set configuration does not match the actual config­ Check the configuration of the ET-Connection to see
uration on the ET-Connection. whether a module is missing or defective, or wheth­
er a non-configured module is wired.

BusAdapter
Equipment Manual, 10/2022, A5E41449003-AC 89
BusAdapter BA-Send 1xFC
16.4 Technical specifications

16.4 Technical specifications

Technical specifications of the BusAdapter BA-Send 1xFC


The following table shows the technical specifications as of the issue date. You can find a
data sheet including daily updated technical specifications on the Internet
(https://support.industry.siemens.com/cs/de/en/pv/6ES7193-6AS00-0AA0/td?dl=en).

Article number 6ES7193-6AS00-0AA0


General information
Product type designation BA-Send 1xFC
HW functional status From FS05
Interfaces
Supports protocol for PROFINET IO
Cable length
– Cu conductors 15 m; from IM firmware V3.3: between BA-send
and the first ET-CONNECTION bus node and
between all other bus nodes
ET-Connection
• Number of interfaces ET connection 1
• FC (FastConnect) Yes
Ambient conditions
Ambient temperature during operation
• horizontal installation, min. -30 °C
• horizontal installation, max. 60 °C
• vertical installation, min. -30 °C
• vertical installation, max. 50 °C
Altitude during operation relating to sea level
• Installation altitude above sea level, max. 5 000 m; restrictions for installation altitudes >
2 000 m, see ET 200SP system manual
Dimensions
Width 20 mm
Weights
Weight, approx. 44 g

BusAdapter
90 Equipment Manual, 10/2022, A5E41449003-AC
Strain relief 17
17.1 Product overview

Article number
6ES7193-6RA00-1AN0 (VPE: 5 strain relief units incl. screws)

View

Figure 17-1 Strain relief

Properties
• The strain relief is a mechanical protective device for the electrical Industrial
Ethernet/PROFINET cables on the BusAdapter
• The strain relief is suitable for all electrical Industrial Ethernet/PROFINET cables of the
BusAdapter
• The strain relief is an optional accessories.
• The cable ties are not included in the delivery. We recommend cable ties with a width of
4.8 mm. The maximum width is 7.0 mm. The length of the cable tie is min. 60 mm.

BusAdapter
Equipment Manual, 10/2022, A5E41449003-AC 91
Strain relief
17.2 Installing

17.2 Installing

Requirement
• The Industrial Ethernet/PROFINET cables are not inserted on the BusAdapter. The inserted
Industrial Ethernet/PROFINET cables hamper the mounting of the strain relief.
• BusAdapter and strain relief can be mounted separately.

Tools required
Screwdriver TX10 (torx).

Procedure
To install the strain relief, follow these steps:
1. Press the strain relief below the BusAdapter seat of the PROFINET device.

Figure 17-2 Strain relief before mounting

2. Fasten the strain relief (1 screw with 0.7 to 0.8 Nm tightening torque).
3. Plug the BusAdapter into the PROFINET device.
4. Screw the BusAdapter to the PROFINET device (1 screw with 0.25 Nm tightening torque).

BusAdapter
92 Equipment Manual, 10/2022, A5E41449003-AC
Strain relief
17.2 Installing

5. Fasten each Industrial Ethernet/PROFINET cable individually to the strain relief with the
cable ties.

Figure 17-3 Strain relief installed

BusAdapter
Equipment Manual, 10/2022, A5E41449003-AC 93
Dimension drawings A
A.1 BusAdapter dimension drawings
The figure below shows the dimension drawing of the BusAdapter BA 2xRJ45 as an example.





 

Figure A-1 Dimensional drawing of BusAdapter BA 2xRJ45

A.2 Strain relief dimension drawings


The figure below shows the dimension drawing of the strain relief.


 

Figure A-2 Strain relief dimension drawing

BusAdapter
94 Equipment Manual, 10/2022, A5E41449003-AC
Accessories B
B.1 Accessories
Additional accessories are available for the SIMATIC BusAdapters:

Accessories Article number Property Figure


Strain relief 6ES7193-6RA00-1AN0 The strain relief is a mechanical pro­
tective device for the electrical
Industrial Ethernet/PROFINET cables
on the BusAdapter. The strain relief
can be ordered as optional accessor­
ies.
You install the strain relief on the
PROFINET device (e.g.: interface
module) before you install the
BusAdapter.
You can find additional information
in section Strain relief (Page 91).
Reference 6ES7193-6LF30-0AW0 The labels enable the reference iden­
identification tification labeling of the BusAdapter.
label (10 mats The labels can be ordered on a mat
with 16 labels for thermal transfer and inkjet print­
each) ers as optional accessories.
You insert the reference identifica­
tion label into the opening on the
top of the BusAdapter.

Cables and connectors


You can find the recommended cables and connectors with the respective BusAdapters.

Assembly tools

Tool MLFB Description


Industrial Ethernet Fast­ 6GK1901-1GA00 Stripping tool for the fast stripping of IE FastCon­
Connect Stripping Tool nect cables with green blade cassette
Termination Kit FC LC 6GK1900-0RL00-0AA0 Assembly case for on-site assembly of FC LC con­
Plug nectors to FC FOC cables
Termination Kit SC RJ 6GK1900-0ML00-0AA0 Assembly case for on-site assembly of SC RJ con­
POF Plug nectors consisting of stripping tool, Kevlar scissors,
polishing set

BusAdapter
Equipment Manual, 10/2022, A5E41449003-AC 95
Compatibility C
Overview of the introduction of the BusAdapter in the engineering tools
The table shows with which STEP 7 version or HSP version you can use the BusAdapters.

STEP 7 Classic
In STEP 7 Release HSP version STEP 7 TIA Portal
available from installable from
BA 2xRJ45 V5.5.4.0 HSP0250, V1.0 V13
V5.5.3.0
BA 2xFC V5.5.4.0 HSP0250, V1.0 V13
V5.5.3.0
BA 2xSCRJ V5.5.4.0 HSP0250, V1.0 V13 SP1
V5.5.3.0
BA SCRJ/R45 V5.6.0.0 HSP0250, V3.0 V13 SP1
V5.5.4.0 (HSP0129)
BA SCRJ/FC V5.6.0.0 HSP0250, V3.0 V13 SP1
V5.5.4.0 (HSP0129)
BA 2xLC V5.6.0.0 HSP0250, V4.0 V13 SP1 Upd6
V5.5.4.0 (HSP0158)
BA LC/RJ45 V5.6.0.0 HSP0250, V4.0 V13 SP1 Upd6
V5.5.4.0 (HSP0158)
BA LC/FC V5.6.0.0 HSP0250, V4.0 V13 SP1 Upd6
V5.5.4.0 (HSP0158)
BA 2xM12 - HSP0250, V5.0 V16
V5.5.4.0 (HSP0302)
BA 2xLC-LD - - V18
BA LC-LD/RJ45 - - V18
BA LC-LD/M12 - - V18

BusAdapter
96 Equipment Manual, 10/2022, A5E41449003-AC