Professional Documents
Culture Documents
“GREEN STAR.”
Introduction Page 3
RINA GREEN STAR 3 Page 3
Marpol 73/78 Page 3
Chapter 1
Refrigerant Page 3
Chapter 2
Procedure for leak detector Page 4
Chapter 3
Procedure for refrigerant recovering Page 5
Pump Down Page 5
Caution Page 6
Chapter 4
Record list
Air conditioning unit Page 6
Provision Refrigerant plant Page 7
Chapter 5
Use of different types of refrigerant Page 7
Appendix
1. Diagrammatic details of permanent refrigeration system, HVAC plant.
2. Diagrammatic details of permanent refrigeration system, Provision plant.
3. Manual for R-407C leak detector system.
4. Manual refrigerant recovery system model 1686.05.
RINA Rules Green Star Design Pt. F, Ch.7. Sec.3 contains requirements to prevent the sea and
air pollutions.
Generally, the rules refer to applicable parts of Annex I, II, IV, V and VI of Marpol 73/78
consolidated edition 1997.
Annex I: Regulations for the Prevention of Pollution by Oil
Annex II: Regulations for the Control of Pollution by Noxious Liquid Substances in Bulk.
Annex IV: Regulations for the Prevention of Pollution by Sewage from ships.
Annex V Regulations for the Prevention of Pollution by Garbage from ships.
Annex VI Regulations for the Prevention of Air Pollution from ships.
Chapter 1
Refrigerant
Green Star Design Pt.F, Ch.7 Sec.3 chapter 2.3 Prevention of air pollution.
This plan is prepared according to above-mentioned rules and the effect on the ozone layer and
global warming potential have been considered according to The Montreal protocol on Substances
that deplete the ozone Layer.
The Refrigerant Management Procedure applies to the centralized air conditioning plant and the
provision refrigerator plan.
Domestic type stand-alone air conditioning units and refrigerators are not covered by these
requirements.
The emission criteria for refrigerants are limited to the requirements related to the properties of the
refrigerant used with respect to its ozone depleting potential (zero ozone depleting) and to its global
warming potential (ODP / GWP) as defined by the 1987 Montreal Protocol on Substances that
For these systems R – 407C will be used. R – 407C has a GWP of 1650 and an ODP of 0.
Chapter 2
Procedure for leak detector.
A leak detection system appropriate to the applicable refrigerant shall be provided to continuously
monitor the spaces of which refrigerants may leak. Alarms shall be given in the case of leakage
detected when concentrations exceed a predetermined limit.
For the HVAC system there will be installed two sets of detectors, one in air-conditioning plant room
(enclosed area), and one near the compressor in the engine room.
For the provision room will be installed four sets of detectors, one in the engine room near the
compressor and one in each of the cold chambers.
Please see the enclosed manual for R 407C leak detector system for the way of operation and the
location of the sensors.
Pump Down
Pump down means that the refrigerant in the refrigeration system is collected temporary in the
condenser. Pump down is accomplished when the refrigerant circuit is repaired, the unit cooler is
stopped for a prolonged period or it is moved to minimize the risk due to refrigerant leakage.
Caution:
1. If pump down continues for a long time, oil pressure may be lowered more or less,
but does not short circuit the oil pressure protection switch circuit.
2. After finishing pump down, do not forget to restore the short circuit of the terminal
on the low pressure side of the dual pressure switch.
Chapter 4
Record list
Item 1
Item 2
Content Page
1- Installation Instructions 2
2- Location Instructions 3
3- Typical Settings 3
4- Operating Instructions 3
5- Test/Function Instructions 4
7- Annual test 4
8- Troubleshooting 4
2010( ASH)
Murco Ltd.
114a Georges Street Lower, Dun Laoghaire Co Dublin. Ireland,
e-mail: info@murco.ie web: www.murcogasdetection.com
1
1- MGD Installation Instructions relay, and the device to be switched to either the N/O or N/C Terminals of the
volt free relay, depending on whether a 12 Volt output is required during an
The main alarm unit and its sensor(s) should be positioned carefully to avoid alarm condition or while the system is on standby. The return from the device
mechanical damage (from moving machinery, doors, etc.) thermal extremes is connected to OV on CN9/CN11
(close to heaters) and should not be placed unprotected in direct strong
drafts/airflows and areas where water or moisture is present unless an 1.4. Voltage Free Relays.
appropriate enclosure is used.
10A @ 120/230 VAC
Avoid routing sensor cabling outside of premises, or between buildings via
overhead cables. Also, sensor wiring should be kept a minimum of 500mm Two Level Unit: One Level Unit:
from mains and telephone cables. (See section on sensor location) 1 & 2 Channel Systems: CN5: Low Level Alarm CN4
CN4: High Level Alarm
When connecting the mains and / or sensor cables ensure a second
mechanical fixing is used. Use a cable tie inside the enclosure within 25mm 4 - 6 Channel Systems: CN10: Low Level Alarm CN10
of the cable gland. CN9: High Level Alarm
CN12: Fault Reporting Relays
When power to the unit is switched on, there is a 3-minute delay before the
system activates. This allows the sensors to warm up to the correct Notes: N/O and N/C refer to contact status in standby mode.
temperature for gas detection. On a two level unit, the green light on the On a two level system, A high level alarm condition on any sensor
alarm panel comes on after the delay, indicating that the system is ready. will override a low level alarm condition on another sensor.
On a one level system the green light comes on immediately. When a unit
has been off or stored for a long time the normalising period may be longer On 4 - 6 Channel two level units, the high level relay may be set for
than 3 minutes. After the 3 minutes has expired alarms may activate. You normal or Fail-Safe operation by setting jumper JP1 on the control
may deactivate the siren until normalisation is complete. (Key switch on 2 unit printed circuit board (Refer to Installation diagram)
level units, remove link on jumper JP1 in the case of a 1 level unit)
Connect leads to terminal block for Common (COM) and N/O and/or N/C
1.1 Remove the front cover. Mount the control unit using the mounting connections as required.
holes in the base such that the sensor cable terminal blocks are at the
1.5. Mains Connection.
bottom of the unit in a convenient position (observing the above note).
Connect mains supply (using 3-core 0.75 mm, Mains Flex for 230V systems
1.2 Wiring to Remote Sensors:
or 3 wire, 18 gauge 0.823mm sq mains flex for 120V Systems) to terminal
block CN3 (on 1 & 2 channel systems), or fused terminal block mounted on
Connect sensor cable (standard 4 wire alarm cable as specified below) to
base of control unit (4 - 6 channel systems), Connections L, N and E. Ensure
sensor terminal block CN1 on control unit positions 1,2,3 & 4. Route
that earth connections to the lid and base of the enclosure are maintained.
cable through the gland to remote sensor No.1.
NOTE: Connection to mains supply must be via an approved readily
Standard Sensors:
accessible, switched and fused (2 or 5 Amp Fuse) plug and socket or
Remove lid of sensor. (To open the sensor enclosure : turn the cable gland ½
as per local wiring regulations which should be within 3 meters (10
turn anticlockwise to loosen the internal nut, depress the clip on top of the
feet) of the control unit.
enclosure and open). Connect the other end of the sensor cable to terminal
• The mains cable used should be of an approved type HAR or
block CN1 positions 1,2,3 & 4. Mount sensor box. Replace lid. Repeat above
Cenelec approved or locally approved equivalent.
sequence for remaining sensors (depending on supplied system
• If replacement of the mains fuse is required use only the
configuration.) Feed the cable through the bottom of the sensor enclosure.
appropriate type from the table below
Please ensure that connections 1 to 4 on the sensor connect to their
Control Unit Type: Fuse Rating Sensor Connection Siren /
corresponding numbers on the terminal block in the main alarm unit,
230V Systems Main Supply Fuse: Auxiallry
otherwise the system will not function correctly.
1 - 2 Channel Unit: 20mm T50mA Not Applicable Not Applicable
230V Fuse
4 - 6 Channel Unit: 20mm T160mA 20mm T250 mA 20mm T315 mA
Maximum Sensor Wiring Length: 230V Systems 230V Fuse 230V Fuse 230V Fuse
1 - 2 Channel Standard Units: 40 Metres 7/0.2mm Alarm Cable
(Max. 3.52 Ohms / Core) Control Unit Type: Fuse Rating Sensor Connection Siren /
4 - 6 Channel Standard Units: 100 Metres 7/0.2mm Alarm Cable
120V Systems Main Supply Fuse: Auxiallry
(Max. 8.8 Ohms / Core) 1 - 2 Channel Unit: 20mm T100mA Not Applicable Not Applicable
120V Fuse
Maximum Sensor Wiring Length: 120V Systems 4 - 6 Channel Unit: 20mm T315mA 20mm T250 mA 20mm T315 mA
1 - 2 Channel Units: 60.9M (200 feet) 22 gauge, stranded 4 wire 230V Fuse 120V Fuse 230V Fuse
Alarm Cable (Max 3.52 Ohms/Wire)
4 - 6 Channel Units: 152.25 Metres (500 feet) 22 gauge, stranded • The blanking plugs for cable entries should only be removed if being
4 wire Alarm Cable (Max 8.8 Ohms/Wire) replaced by cable glands
• Ensure that the live and neutral conductors take the strain before the
You may use different cables and longer distances once the ohmic resistance earth conductor.
shown is not exceeded.
2. MGD - Location Instructions
For uncommitted 12 V DC @100mA output is obtained via CN9/CN11 Terminals However, in certain circumstances false alarms may be caused by the
‘+12V’ and ‘0V’ This output may be wired via the volt free relays to obtain a occasional presence of sufficiently high concentrations of other gaseous
switching 12 volt DC output to drive an external relay or solenoid as follows: impurities. If such a situation is likely to arise installers should check with our
Technical Department so that sensor (s) of suitable cross sensitivity can be
If both the buzzer and 12V DC output are corrected correctly they should not supplied. Examples of situations where such abnormalities may arise include.
exceed, 250MA in total.
• Plant room maintenance activity involving solvent or paint fumes or
Connect Terminal ‘+12V’ on CN9/CN11 to the ‘COM’ terminal of the volt free refrigerant leaks.
2
• Plant rooms in fruit ripening/storage facilities because of accidental gas • With air-cooled chillers or air-cooled condensers with non-enclosed
migration (bananas - ethylene, apples - carbon dioxide) condenser sections it is difficult to effectively monitor leaks in the coil
• Heavy localised exhaust fumes (carbon monoxide, dioxide, propane) sections. With some designs it will be possible using an airflow sensor
from engine driven forklifts in confined spaces or close to sensors. to monitor airflow to the start –up fans in the front or rear sections.
• If there is a possibility of refrigerant leaks into a duct or air-handling unit
A response delay is built in to the system to minimise the possibilities of false install a sensor to monitor the airflow.
alarms. (Two level units) or may be selected (one level units).
Weatherproof sensors should be used for unprotected outdoor applications.
Machinery rooms
There is NO ABSOLUTE RULE in determining the number of sensors and their Air Conditioning – Direct systems VRV/VRF
location. However a number of simple guidelines will help to make a decision. EN378 states that at least one detector shall be installed in each occupied
Sensors monitor a point as opposed to an area. If the gas leak does not reach the space being considered and the location of detectors shall be chosen in
sensor then no alarm will be raised. Therefore, it is extremely important to relation to the refrigerant and they shall be located where the refrigerant from
carefully select the sensor location. Also consider ease of access for maintenance. the leak will collect. In this case refrigerants are heavier than air and detectors
should have their sensors mounted low .e.g. at less than bed height in the
The size and nature of the site will help to decide which method is the most case of an hotel or other similar Category Class A spaces. Ceiling or other
appropriate to use. Locations requiring the most protection in a machinery or voids if not sealed are part of the occupied space.
plant room would be around compressors, pressurised storage vessels,
refrigerant cylinders or storage rooms or pipelines. Most vulnerable are valves, In a hotel room monitoring in ceiling voids would not
gauges, flanges, joints (brazed or mechanical), filling or draining connections etc strictly comply with EN378
Refrigerated Spaces Each of the sensors has a green light to indicate that power is present.
In refrigerated spaces sensors should be located in the return airflow to the
evaporators on a sidewall, below head high preferred, or on the ceiling, not To minimise false alarms, the system has a built in delay, between the arrival
directly in front of an evaporator. In large rooms with multiple evaporators, of gas at the sensor unit, and an alarm occurring. For one level units this
sensors should be mounted on the central line between 2 adjacent delay is approximately 3 minutes. For two level units, this delay is 20-25
evaporators, as turbulence will result in airflows mixing. seconds before a low level alarm, and 25-30 seconds on a high level alarm.
This delay can be deactivated in a one level unit by moving the link at position
Chillers JP1 to the off position. (See technical installation drawing)
In the case or small water or air-cooled enclosed chiller units mount the
sensor so as to monitor airflow to the extract fans. With larger models also Unit Operation
place a sensor inside the enclosure under or adjacent to the compressors Idle: Only the green light on the panel is on. No gas is present.
In the case of outdoor units: If the green light is off, power to the unit has been interrupted. Refer to the
troubleshooting guide.
• such as enclosed air-cooled chillers or the outdoor unit for VRV/VRF
systems mount the sensor so as to monitor airflow to the extract fan. Alarm Condition
With large units also place a sensor inside the enclosure under or
adjacent to the compressors One Level System:
One or more red lights on the panel turn on. The siren and the volt free relays
In the case of non-enclosed outdoor units operate. This indicates that gas at one or more sensors is at a level higher
than the preset alarm point.
• If there is an enclosed machinery section then locate a sensor there.
• In the case of units with enclosed compressors, mount sensors in the Two Level Systems:
enclosures Low Alarm: One of more yellow lights on the panel turn on. The sounder
• Where you have protective or acoustic panels mount the sensor low operates intermittently, and the low alarm volt free relay
down under the compressors where it is protected by the panels. operates: this indicates presence of a low level of gas on one or
more sensors.
3
High Alarm: One or more Red Lights on the panel turn on. The sounder Cause: 1. Power failure (check supply)
operates continuously, and the High alarm volt free relay 2. Tripped circuit breaker or blown fuse on electrical supply
operates: this indicates presence of a High level of gas on one 2. Blown fuse at the electrical supply on the controller PCB board.
or more of the sensors. 3. Two Level unit only: Has unit warmed up? (This takes 3-4
minutes after power is switched on.)
For the purpose of system maintenance, the siren may be disabled
temporarily, on two level units, by using the key-switch. On one level units Symptom: Red Light is on, but no alarm condition is active. i.e No siren and
this is achieved by setting a jumper JP1 on the control unit printed circuit no relay operation after 3 minutes.
board. The location of this is shown on the Installation Drawing (Separate
drawings for 1 - 2 and 4 - 6 channel units). Remove the link to disable the Cause: 1. Make sure the siren has not been deactivated (Key switch on 2
alarm level controllers or link on jumper JP1 on 1 level controllers
removed)
Resetting An Alarm Condition:
On one level units all of which have automatic reset no user intervention is 2. This indicates a wiring or sensor fault (call service provider).
required. The unit will reset shortly after the gas dissipates. (All one level If these are in order the calibration pot may have been adjusted
systems reset automatically) and may need to be reset. Check with us for instructions.
On two level units, low-level alarm conditions will reset automatically when Sensor:
the gas dissipates. High level alarm conditions require a manual reset (By Symptom: Green light on sensor is off.
pressing the reset button) Please note that a high alarm condition can only be
reset 30-60 seconds after the gas clears from around the sensors. Cause: This may indicate a wiring fault between the controller and sensor
or a sensor fault. Check power supply to the controller. Check
connections between the controller and the sensor to ensure that
5- MGD – Test / Function Instructions the wires from positions 1 to 4 on the sensor are connected to the
corresponding 1-4 on the controller. (See “Wiring Remote Sensors).
The MGD is calibrated in the factory and does not require to be calibrated on
installation. After installation the units should be bump tested. Expose the On a 4 to 6 channel unit check that the sensor fuse on the
sensors to test gas using a Murco ampoule (NH3 or CO2 etc) or test cylinder particular sensor connection position in the controller is not blown.
(appropriate to the installation) or if not available, crack open the valve of a
cigarette lighter (only for Semiconductor units) without igniting it and hold it If the fault is not cleared then the sensor has been damaged.
over the vent holes on the upper right side of the sensor. The gas is heavier than
air and should fall into the sensor. This will put the system into alarm. The red If you experience spurious alarms in the absence of a leak, contact
LED will light showing the system is in alarm. The delay will prevent the siren us for instructions and support.
sounding or relay switching for the preset delay, if delay is set.
9- Installation Diagrams
With a bump test you can see the functions of the sensor - the yellow/red led
will light, the relay and sounder will function.
1, 2 Sensor 1 Level Installation Diagram
To test the siren and or relay function, check the delay is set at zero using the
Alarm Panel
header as shown on the installation diagram and expose to gas as above.
JP1 Settings:
Mains Buzzer
Transformer 3 Minute Delay
OFF
After the gas has cleared, the red led, siren and relay will automatically reset
ON
OFF ON
on 1L Units with 2L press the reset button. JP1
Jumper
Link
CN3
Channel 1 Channel 2
Before testing the sensors on site the MGD must have been powered up and
NC
N0
4321 4321
C
Volt Free
6- MGD Sensor - Decorative remote sensor head installation Relays 4
If you do not wish to surface mount the MGD Sensor or need to match room 3
2
1
decor, we can supply a decorative faceplate (standard: brushed stainless steel (To operate external
equipment such as a fan etc...
Or initiate plant shutdown)
to fit a 44mm double gang back box in which you can mount the sensor PCB.
(UK and Ireland). 4
3
2
1
1. If construction / decoration is still going on, fit a standard plastic blanking Sensor Unit
plate immediately you install the sensor in the back box to avoid dust or USA - 60.9 metres (200 feet) MAX.
EUROPE - 40 metres MAX.
damage to the in-room sensor. You can fit the SS vented plate when
(Please ensure that connections 1 to 4
decoration is completed. on the sensor connect to their corresponding
numbers on the terminal block in the main alarm
unit, otherwise the system will not function correctly.)
2. Cleaning: the decorative face plate should be lightly dusted – it should
not be sprayed with cleaning/polishing aerosols.
1, 2 Sensor 2 Level Installation Diagram
Alarm Panel
7- MGD Sensor - Annual Test
Mains Buzzer
Transformer
To comply with the requirements of EN378 and the F GAS regulation sensors
must be tested annually. However local regulations may specify the nature and Sensor Unit
CN5
frequency of this test. If not the Murco recommended procedure should be
CN3
Channel 1 Channel 2
followed. Contact us for details.
NC
N0
4321 4321
C
4
4, 6 Sensor 1 Level Installation Diagram 4, 6 Sensor 2 Level Installation Diagram
Tansformer Base Earth Connection Lid Earth Connection Tansformer Base Earth Connection Lid Earth Connection
Fused Terminal Block
Fused Terminal Block
Mains
Mains
4321
As Required Repeat for Sensors 2-6
JP1 Settings: As Required
OFF ON Jumper
Max Wire Length 3 Minute Delay Max Wire Length
USA - 152.25 metres (500 feet) MAX. Link
EUROPE - 100 metres MAX. USA - 152.25 metres (500 feet) MAX.
OFF ON Jumper EUROPE - 100 metres MAX.
(Please ensure that connections 1 to 4 Link JP1 Settings:
on the sensor connect to their corresponding (Please ensure that connections 1 to 4
ON: Relay RL1 Normally Energised (De-energised
numbers on the terminal block in the main alarm on the sensor connect to their corresponding on High Alarm or Mains Failure Condition)
unit, otherwise the system will not function correctly.) numbers on the terminal block in the main alarm
unit, otherwise the system will not function correctly.) OFF: Relay RL1 Energised On Alarm
(Energised on High Alarm Condition)
4 4
3 3
2 2
1 1
10 - Mounting Instructions
mounting
measurements
86.0 53
122 mm
04.5
43.0
7.0
09.0
144 mm
123 mm
103.50
120
120
0.5
42 mm
O 4
8.0
mounting slots =
9mm long x 6mm wide
25.00 36.00 25.00
101 mm
59 mm
Exd
146mm
m
50 m
90 130 151
130
160
75 m
m
138
Mounting Holes
2 x Clearance for M6
Splashguard
M42 thread
146mm
1”BSP thread
112.0mm
1”BSP thread
81.50mm
Key Hole
thread varies withM42 thread
model Reset Button
13.00mm
16.00mm
Airflow Duct Mount 4,6 Sensor Controller Enclosure
Relay Expander Box
m
82.0m
Mounting locations as in IP66
Mounting
123.0mm
O5.10mm Holes
O10.00mm
m
.0m
193
240.50mm
224.70mm
146.0
0mm
1”BSP thread
O4.60mm
1,2 Sensor ControllerScrew
Enclosure
5.0
242.50mm
Screw 260.50mm
9.0 5.0
15.5
Cable
67.70mm
X X X X X X Cable Gland
81.50mm
Holes
Holes Diameter x = 12
9.0 x = 12.7mm, PG7
15.5
50.0 X X X X X X X y = 19
50.0
10.0
10.0
Screw
4.8
Screw
4.8
77.2
15.0
15.0
77.2
15.0
PG 7
12.7 74.5 12.7 12.5 5 plcs
PG 7
6
TECH. SPECIFICATION REFRIGERANT RECOVERY SYSTEM HI AIR KOREA
Item 1
Type : 1686.05
Item 2
Item 3
Item 4
Type : 1700.61
Item 5
Type : 100kg
Bedienungsanleitung
Instructions for use
Instruction d’utilisation
Instrucciones de uso
Istruzioni d'uso 1686.05
Gebruiksaanwijzing
Instruções de serviço
Οδηγίες Χρήσης
www.rothenberger.com
Intro
DEUTSCH Seite 3
Bedienungsanleitung bitte lesen und aufbewaren! Nicht wegwerfen! Bei Schäden durch
Bedienungsfehler erlischt die Garntie! Technische Äanderungen vorbehalten!
ENGLISH Page 12
Please read retain these directions for use. Do not throw them away! The warranty does not cover
damage caused by incorrect use of the equipment! Subject to technical modifications.
FRANÇAIS Page 21
Lire attentivement le mode d’emploi et le ranger à un endroit s{ur! Ne pas le jetter! La garantie est
annulée lors de dommages d{us à une manipulation erronée! Sous rèserve de modificaions techniques.
ESPAÑOL. Pais de origen Página 30
¡Por favor, lea y conserve el manual de instrucciones! ¡No lo tire! ¡En caso de daños por errores de
manejo, la garantía queda sin validez! Modificaciones técnicas reservadas.
ITALIANO Pagina 39
Per favore leggere e conservare le istruzioni per l’uso! Non gettarle via! In caso di danni dovuti ad
errori nell’ uso, la garanzia si estingue! Ci si riservano modifiche tecniche.
NEDERLANDS Bladzijde 48
Lees de handleiding zorgvulding door en bewaar haar goed! Niet weggoien! Bij schade door
bedieningsfouten komt de garantieverlening te vervallen! Technische wijzgingen voorbehouden.
PORTUGUES Pagina 57
Queiram ler e guardar o manual de instruções! Não deitar fora! Em caso de avarias por utilização
incorrecta, extingue-se garantia! Reservado o direito de alterações técnicas.
EΛΛΗΝΙΚΑ σελίδα 66
Παρακαλούμε διαβάστε και κρατήστε αυτές τις οδηγίες χρήσεως. Να μην τις πετάτε! Η εγγύηση δεν καλύπτει
τις ζημιές που προκαλούνται από λανθασμένη χρήση της συσκευής! Υπόκειται σε τεχνικές τροποποιήσεις.
2
SAFETY
! WARNING
GENERAL SAFETY GUIDELINES
a) Read all safety, operating guidelines and instructions before operating this unit.
b) This recovery unit should be operated by a qualified technician only.
c) Always wear safety goggles and protective gloves when working with refrigerants to protect your skin and
eyes from refrigerant gases and refrigerant liquid. Avoid getting in touch with causticity liquid or gas.
d) Do not expose the equipment in the sun or rain.
e) Please be sure that any room where you are working is thoroughly ventilated.
f) Use ONLY authorized refillable refrigerant tanks. It requires the use of recovering tanks with a
minimum of 27.6 bar working pressure.
g) Do not overfill the storage tank. Tank is full with 80% of volume. There should be enough space
for liquid expansion---overfilling of the tank may cause a violent explosion. Must use a 80% O.F.P
storage tank or a scale to avoid over filling.
h) Do not exceed the working pressure of Recovering Tank cylinder.
i) Do not mix different refrigerants together in one tank, or they could not be separated or used.
j) Before recovering the refrigerant, the tank should achieve the vacuum level: -0.1mpa, which is for
purging non-condensable gases. Each tank was full of nitrogen when it was manufactured in the
factory, thus the nitrogen should be evacuated before the first use.
k) When the unit is not used, all the valves should be closed. Because the air or the moisture of the air
may harm the recovery result and shorten the service life of the unit.
l) When using an extension cord it should be a 12AWG minimum and no longer than 30 meters, or it
may make the voltage drop and damage the compressor.
m) A dry filter must always be used and should be replaced frequently. And each type of refrigerant must
have its own filter. For the sake of assuring the normal operation of the unit, please use the filter
specified by our company. High quality dry filters will bring high quality services.
n) Special care should be taken when recovering from a "burned-out" system. Use two high acid capacity
filters, in series. When you have finished recovering from the system, flush the unit with a small amount
of clean refrigerant and refrigerant oil to purge off any foreign substances left in the unit.
o) This unit has an internal pressure protector. If the system’s internal pressure is higher than 38.5 bars,
the system will shut-off automatically. Turn off the power switch and release some pressure, then
reset it manually. (See Exploded Drawing 16).
If the unit automatically shuts-off, please restart it after troubleshooting.
Main reason and problem solving for automatic shut-off:
1. Check the output valve, please switch to open.
2. Check the valve on cylinder, please switch to open
3. Check the connecting hose blocked or not, if yes, please replace it (make sure all valves are off).
4. Check the temperature of cylinder, the pressure will rise if the temperature is raise.
(See Page 20 cooling method).
12
SAFETY
! WARNING
GENERAL SAFETY GUIDELINES
p) The power must be off when switching the recovery valve.
q) If the tank pressure exceeds 21 bars, use the storage tank cooling method to reduce the tank
pressure. (See Page 20 cooling method)
r) To maximize recovery rates, use the shortest possible length of 3/8" or larger hose. A hose no longer
than 0.9 meter is recommended.
s) When recovering large amounts of liquid, use the Liquid Push/Pull method. (See page 19 “System
Push/Pull method”)
t) After recovering, make sure there’s no refrigerant left in the unit. Read the Self-Purging Method
carefully. Liquid refrigerant remained may be expanded and destroy the components.
u) If the unit is to be stored or not used for any length of time, we recommend that it is completely
evacuated of any residual refrigerant and purged with dry nitrogen.
v) To avoid refrigerant losing, we suggest to use a hose with a stop valve.
13
CONTENTS
CONTENTS
1.Specifications . ..............................................................................................................................................................................................................15
2.Parts diagram and parts list ....................................................................................................................................................................................16
3.Wiring diagram ............................................................................................................................................................................................................17
4.Operation methods ...................................................................................................................................................................................................18
5.Troubleshooting .........................................................................................................................................................................................................20
EC Declaration .................................................................................................................................................................................................................75
14
INSTRUCTIONS FOR USE AND MAINTENANCE
1. Specifications
15
INSTRUCTIONS FOR USE AND MAINTENANCE
16
INSTRUCTIONS FOR USE AND MAINTENANCE
3. Wiring diagram
17
INSTRUCTIONS FOR USE AND MAINTENANCE
Purge
Close
Open Open
Liq
ui
d
Purge
8. Slowly open the input port on the unit. Close
18
INSTRUCTIONS FOR USE AND MAINTENANCE
HVAC-UNIT/APPLIANCE
CONTAINING REFRIGERANT Input
REFRIGERANT
RECOVERY
Filter MACHINE
Output
Vapor
Vapor Liquid
Recovery tank
Liquid
19
INSTRUCTIONS FOR USE AND MAINTENANCE
4.4. The storage cooling method 6. Throttle the Output valve of the unit so that the
Pre-work cooling procedure output pressure is 100psi greater than the input
1. To start you must have a minimum of 0.5kg of pressure, but never more than 300psi.
liquid refrigerant in the tank. 7. Run until tank is cold
2. Turn the Recover/Purge valve to the Recover
position. 4.5. Tank Cooling Procedure in the recovering process
3. Open the Vapor and Liquid valve of the storage 1. Open the vapor valve of the storage tank (it is
tank. closed while recovering).
4. Power on, and start the compressor. 2. Close the two valves of the manifold gauge set.
5. Open the Input valve and Output valve of the 3. Follow the sixth and seventh items of the
unit. Pre-work Cooling Procedure.
Manifold
gauge set
5. Troubleshooting
20
ROTHENBERGER Worldwide
Germany ROTHENBERGER Werkzeuge GmbH Mexico Bosques de Duraznos No. 69-1101
Industriestraße 7 • D-65779 Kelkheim/Germany Col. Bosques de las Lomas • México D.F. 11700
Tel. + 49 61 95 / 800 - 1 • Fax + 49 61 95 / 800 - 84 00 Tel. + 52 55 / 55 96 - 84 98
info@rothenberger.com • www.rothenberger.com Fax + 52 55 / 26 34 - 25 55
ROTHENBERGER Produktion GmbH Netherlands ROTHENBERGER Nederland bv
Lilienthalstraße 71 - 87 • D-37235 Hessisch-Lichtenau Postbus 45 • NL-5120 AA Rijen
Tel. + 49 56 02 / 93 94 - 0 • Fax + 49 56 02 / 93 94 36 Tel. + 31 1 61 / 29 35 79 • Fax + 31 1 61 / 29 39 08
info@rothenberger.nl • www.rothenberger.nl
Australia ROTHENBERGER Australia Pty. Ltd.
Unit 12 • 5 Hudson Avenue • Castle Hill • N.S.W. 2154 Poland ROTHENBERGER Polska Sp.z.o.o.
Tel. + 61 2 / 98 99 75 77 • Fax + 61 2 / 98 99 76 77 ul. Annopol 4A • PL-03-236 Warszawa
rothenberger@rothenberger.com.au Tel. + 48 22 / 213 59 00 • Fax + 48 22 / 213 59 01
www.rothenberger.com.au biuro@rothenberger.pl • www.rothenberger.pl
Austria ROTHENBERGER Werkzeuge- und Maschinen Portugal SUPER-EGO TOOLS FERRAMENTAS, S.A.
Handelsgesellschaft m.b.H. Apartado 62 - 2894-909 Alcochete - PORTUGAL
Gewerbeparkstraße 9 • A-5081 Anif near Salzburg Tel. + 351 91 / 930 64 00 • Fax + 351 21 / 234 03 94
Tel. + 43 62 46 / 7 20 91-45 • Fax + 43 62 46 / 7 20 91 -15 sul.pt@rothenberger.es
office@rothenberger.at • www.rothenberger.at
Singapore ROTHENBERGER Asia Pte. Ltd.
Belgium ROTHENBERGER Benelux bvba
147 Tyrwhitt Road
Antwerpsesteenweg 59 • B-2630 Aartselaar
Singapore 207561
Tel. + 32 3 / 8 77 22 77 • Fax + 32 3 / 8 77 03 94
Tel. + 65 / 6296 - 2031 • Fax + 65 / 6296 - 4031
info@rothenberger.be • www.rothenberger.be
sales@rothenberger.com.sg • www.rothenberger.com.sg
Brazil ROTHENBERGER do Brasil Ltda.
South Africa ROTHENBERGER-TOOLS SA (PTY) Ltd.
Rua marinho de Carvalho, No. 72 - Vila Marina
P.O. Box 4360 • Edenvale 1610
09921-005 Diadema - Sao Paulo - Brazil
165 Vanderbijl Street, Meadowdale Germiston
Tel. + 55 11 / 40 44 47-48 • Fax + 55 11 / 40 44 50-51
Gauteng (Johannesburg), South Africa
vendas@rothenberger.com.br • www.rothenberger.com.br
Tel. + 27 11 / 3 72 96 33 • Fax + 27 11 / 3 72 96 32
Bulgaria ROTHENBERGER Bulgaria GmbH info@rothenberger-tools.co.za
Boul. Sitniakovo 79 • BG-1111 Sofia
Spain ROTHENBERGER S.A.
Tel. + 35 9 / 2 9 46 14 59 • Fax + 35 9 / 2 9 46 12 05
Ctra. Durango-Elorrio, Km 2 • E-48220 Abadiano (Vizcaya)
info@rothenberger.bg • www.rothenberger.bg
(P.O. Box) 117 • E-48200 Durango (Vizcaya)
Chile ROTHENBERGER S.A., Oficinas en CHILE Tel. + 34 94 / 6 21 01 00 • Fax + 34 94 / 6 21 01 31
Merced# 32-Oficina 63-Santiago Centro export@rothenberger.es • www.rothenberger.es
Santiago – Chile Switzerland
ROTHENBERGER (Schweiz) AG
Tel. + 56 9 / 2 99 68 79 • + 56 2 / 4 17 91 30
Herostr. 9 • CH-8048 Zürich
Fax + 56 2 / 4 17 91 30 • ventas.chile@rothenberger.es
Tel. + 41 44 / 435 30 30 • Fax + 41 44 / 401 06 08
China ROTHENBERGER China info@rothenberger-werkzeuge.ch
D-4, No. 195 Qianpu Road, East New Area of Songjiang Turkey
ROTHENBERGER Tes. Alet ve Mak. San. Tic. Ltd. Sti
Industrial Zone, Shanghai 201611, China
Poyraz Sok. No: 20/3 - Detay Is Merkezi
Tel. + 86 21 / 67 60 20 77 • + 86 21 / 67 60 20 61
TR-34722 Kadiköy-Istanbul
Fax + 86 21 / 67 60 20 63 • office@rothenberger.cn
Tel. + 90 / 216 449 24 85 pbx • Fax + 90 / 216 449 24 87
Czech ROTHENBERGER CZ, nárˇadí a stroje, spol. s.r.o. rothenberger@rothenberger.com.tr
Republic Lnárˇská 907 / 12 • 104 00 Praha 10 – Uhrˇinˇeves
UAE ROTHENBERGER Middle East FZCO
Tel. + 42 02 / 71 73 01 83 • Fax + 42 02 / 67 31 01 87
PO Box 261190 • Jebel Ali Free Zone
info@rothenberger.cz • www.rothenberger.cz
Dubai, United Arab Emirates
Denmark ROTHENBERGER Scandinavia A/S Tel. + 971 / 48 83 97 77 • Fax + 971 / 48 83 97 57
Fåborgvej 8 • DK-9220 Aalborg Øst office@rothenberger.ae
Tel. + 45 98 / 15 75 66 • Fax + 45 98 / 15 68 23
UK ROTHENBERGER UK Limited
roscan@rothenberger.dk
2, Kingsthorne Park, Henson Way
France ROTHENBERGER France S.A. Kettering • GB-Northants NN16 8PX
24, rue des Drapiers, BP 45033 • F-57071 Metz Cedex 3 Tel. + 44 15 36 / 31 03 00 • Fax + 44 15 36 / 31 06 00
Tel. + 33 3 / 87 74 92 92 • Fax + 33 3 / 87 74 94 03 info@rothenberger.co.uk
info-fr@rothenberger.com
USA ROTHENBERGER USA LLC
Greece ROTHENBERGER Hellas S.A. 4455 Boeing Drive; USA-Rockford, IL 61109
Agias Kyriakis 45 • 17564 Paleo Faliro • Greece Tel. + 1 / 8 15 3 97 70 70 • Fax + 1 / 8 15 3 97 82 89
Tel. +30 210 94 02 049 • +30 210 94 07 302/3 www.rothenberger-usa.com
Fax +30 210 94 07 322
ROTHENBERGER USA Inc.
ro-he@otenet.gr • www.rothenberger.gr
Western Regional Office • USA-955 Monterey Pass Road
Hungary ROTHENBERGER Hungary Kft. Monterey Park, CA 91754
Gubacsi út 26 • H-1097 Budapest Tel. + 13 23 / 2 68 13 81 • Fax + 13 23 / 26 04 97
Tel. + 36 1 / 3 47 - 50 40 • Fax + 36 1 / 3 47 - 50 59
mail@rothenberger.hu
ROTHENBERGER Agency
India ROTHENBERGER India Private Limited
B-1/D-5,Ground Floor
Russia OLMAX
Mohan Cooperative Industrial Estate
Avtosavodskaya Uliza, Dom 25, Str. 13
Mathura Road, New Delhi 110044
115280 Moskau
Tel. + 91 11 / 41 69 90 40, 41 69 90 50 • Fax + 91 11 / 41 69 90 30
Tel. +7/09 57 92 59 44 • Fax +7/09 57 92 59 46
contactus@rothenbergerindia.com
olmax@olmax.ru • www.olmax.ru
Ireland ROTHENBERGER Ireland Ltd.
999217700.1.04
www.rothenberger.com
ROAIRVAC
ROTHENBERGER ROAIRVAC®
Bedienungsanleitung
Instructions for use
Instruction d’utilisation
Instrucciones de uso
Istruzioni d'uso R17006116
Instruções de serviço
R17006216
R17006316
R17006416
R17061J16
R17065J16
R17066J16
R17063J16
www.rothenberger.com
A Overview
mbar mbar
��� ����
mbar
mbar mbar
��� ����
mbar
B Overview mbar
VAC
mbar
REF
mbar mbar
VAC REF
mbar
mbar
2
C ROAIRVAC
6
3
3
INSTRUCTIONS FOR USE
Material included
1 Vacuum pump
1 Cable
1 Mineral Oil bottle
1 Connector 1/4”SAE –F – 5/16”SAE –M
1 Connector 1/4”SAE –F – 3/8”SAE –M
Instrucions for use
Instruction
10 ENGLISH
INSTRUCTIONS FOR USE
Technical Data
ROAIRVAC 1.5 ROAIRVAC 3.0 ROAIRVAC 6.0 ROAIRVAC 9.0*
230V,50-60Hz
R17006116 R17006216 R17006316 R17006416
CFM 60Hz/50Hz 1.5/1.2 3/2.5 6/5 9/8
l/min 60Hz/50Hz 42/34 85/71 170/142 255/227
HP 60Hz/50Hz 1/4 1/3 1/2 1
rpm 60Hz/50Hz 1720/1440 1720/1440 3440/2880 3440/2880
Poles 4 4 2 2
Stages 2 2 2 2
Ultimate Vacuum (micron) 25Mikron 25Mikron 25Mikron 25Mikron
Voltage 230V 230V 230V 230V
Frecuency 50/60Hz 50/60Hz 50/60Hz 50/60Hz
Connections 1/4”SAE 1/4”SAE 1/4”SAE 1/4”SAE
1/4”SAE F- 5/16”SAE M
Adaptors
1/4””SAE F-3/8””SAE M
Oil capacity (ml) 250 330 330 590
Dimensions (mmxmmxmm) 315x136x243 335x150x265 335x150x265 400x175x270
Weight (Kg) 9 10,7 11,5 17
Electrovalve (Y/N) Y Y Y Y
Gas Ballast (Y/N) Y Y Y Y
Mist filter (Y/N) Y Y Y Y
Vacuum Gauge (Y/N) Y Y Y Y
Vacuum Gauge OD (mm) 50 50 50 80
Vacuum Gauge Units mbar/Mpa mbar/Mpa mbar/Mpa mbar
ENGLISH 11
INSTRUCTIONS FOR USE
Set-up of pump before first operation The pumps’ motor must always be suitably grounded.
The pump temperature is not expected to rise to
Pump is supplied without oil charge; before initial a very high level during operation; however it is
operation, it is mandatory to fill the pump with the advisable to locate the unit in such a way that no
recommended oil charge (see “Filling of oil”). contact can be made, as it may cause burns. When
using the pump with other equipment, it must be
Filling of oil ensured that the pump is fixed properly and safe to
Pump must be turned off for filling the oil and level use for the operator. Vacuum pump is air cooled by
control. built-in fan; only use where the air can freely circulate
Pump is supplied with a mineral oil bottle but and keep it away from walls or obstacles no less than
without oil charge inside the vacuum pump; before 2” (5 cm). Do not cover the pump during operation.
initial operation, it is mandatory to fill the pump
with the oil up to the indicated oil level in the oil Operation
level sight glass. Only use ROTHENBERGER oil;
different lubricants reduce performance and may To guarantee reliability and high level of quality,
cause irreversible damage to the pump. Warranty is each pump is subjected to a rigorous testing and
void if other oil has been used. suitable preliminary running in before it leaves the
For fill-up proceed as follows: factory. Constant performance and long operating
life are assured by strictly observing the following
1. Unscrew charging plug (placed on upper part procedures:
of pump)
2. Slowly add the oil until middle of sight glass Pump start
has been reached (indicated by MAX MIN line) Before the first initial run, it is mandatory to:
3. Screw-on the plug again 1. fill the pump with the provided oil (see section
To avoid excessive filling, it is suggested to only add “filling of oil”).
the oil with a graduated recipient; in that way it is 2. Before subsequent start-ups, always check the
easy to check the added volume. In case of excessive oil level before starting the pump. If necessary,
filling, it is necessary to completely empty the pump top-up or replace the oil.
and repeat the oil filling procedure. 3. before connecting the pump to the system to
be evacuated, check that there is no pressure
WARNING: Do not pollute the environment by inside. In case of connecting the pump with
spilling oil; the lubricant oil is a special waste and a pressurized system, the vacuum gauge may
must be disposed off according to relevant local law break. The vacuum gauge measures negatives
/ guidelines in force. pressures and get collapsed with positive
pressures. Warranty is void if the pump is
Connection for evacuation connected to a positive pressure.
Shorter hose length or wider ID, as well as straight 4. connect the pump to the system to be evacuated
path, reduce the evacuation time as the pump by the necessary equipment (quality hoses,
will reach the desired vacuum more quickly. To quality manifolds,etc). The evacuation quality
prevent backflow of lubricant from the pump into will be directly related to the way of conecction
the evacuated system in case of unexpected power and to the equipment quality.
failure, a solenoid non-return valve is provided at the In case of malfunctioning, stop the pump and call the
suction connection. Service- After-Sales.
12 ENGLISH
INSTRUCTIONS FOR USE
Routine maintenance the pump must be switched off. For changing the oil
proceed as follows:
Periodic and correct maintenance of the vacuum 1. Unscrew the oil drainage plug located on the
pump will ensure a long operation life and constant lower part of the pump
performance. 2. Check that oil comes out completely from the
pump
Lubrication 3. Tightly screw the oil drainage plug back on
The oil provided with the pump has been specially 4. Re-fill the pump with oil (see “Filling of oil”)
formulated & manufactured to lubricate vacuum
pumps; it is special as it features minimum viscosity WARNING: Do not pollute the environment by
fluctuation when in use under a wide temperature spilling oil; the lubricant oil is a special waste and
range. The type of lubricant supplied with the must be disposed of according to relevant local law
pump allows the evacuation of systems operating / guidelines in force.
with CFC, HCFC and HFC refrigerants. Working with
ROTHENBERGER POE synthetic oil is also feasible. Extraordinary maintenance / repair
Both ROTHENBERGER oil types available after order.
Volumes to be filled into the pumps are specified in Conduct extraordinary maintenance or repair
section 1.1. Replace the initial oil charge no later than whenever serious faults occur such as overheating,
150-200 hours of operation; further replacements poor ultimate vacuum, persistent loudness / noise,
should be carried out every 600 hours of correct blocked pump or any other irregular functioning.
usage. In that case, the pump needs to be disassembled,
Oil could be polluted by other oil, humidity, parts need to be cleaned, repaired or replaced.
refrigerants, etc. It is mandatory to use oil in perfect Only qualified service staff shall carry out such
conditions to assure a perfect performance of the maintenance or repair work; otherwise the warranty
pump. will be void. For any information please contact our
Service-After-Sales.
Oil-change
Over-used lubrication oil damages the pumps’
mechanism; make sure to replace oil as soon as it
starts to turn cloudy. For conducting the oil-change,
ENGLISH 13
INSTRUCTIONS FOR USE
Problem Solution
The pump doesn’t work 1. Check that the pump is connected to the power supply.
2. Check that the plug and cable are not damaged.
3. Check that the power supply is suitable for the pump requirements
(see the label of the pump).
4. Check that the pump is filled up with oil (see section 2.1).
5. Contact our Service-After-Sales.
Overheating 1. Check that the pump is filled up with oil (see section 2.1).
2. Check that the pump is bot covered and that air could flow easily.
3. Check that the power supply is suitable for the pump requirements
(see the label of the pump).
4. Contact our Service-After-Sales.
Poor ultimate vacuum 1. Check that the pump has been working for the enough time. The
final vacuum level is directly related with the time of performance.
The time must be according to the volume to be evacuated.
2. Check that there is no leak in the connection or in the system to be
evacuated. Switch off the pump and check that the vacuum level
remains.
3. Check that all the connections and the equipment used are the
appropriate ones.
4. Contact our Service-After-Sales.
Persistent loudness / noise 1. Check that there are not damages on the fun cover. Any impact on
this area could affect in the fun movement.
2. Check that the pump is perfectly srewed.
3. Contact our Service-After-Sales.
Blocked pump 1. Contact our Service-After-Sales.
Oil overconsumption 1. Check that the oil is ROTHENBERGER oil.
2. Check that the drainage plug is perfectly closed and there is not oil
spill.
3. Check that there is no leak in the connection or in the system to be
evacuated. Open systems increase the oil consuption.
4. Contact our Service-After-Sales.
The vacuum gauge doesn’t move 1. Check that the pump sucks air in. If the pump sucks air in, it is posible
but the engine is running. that the vacuum gauge is damaged. If the pump doesn’t suck air in,
it is posible that the non-return solenoid valve is bloqued.
2. Contact our Service-After-Sales.
14 ENGLISH
Notes
35
36
ITEM CODE QTY ITEM CODE QTY
1 R17A601 1 27 R17A627 1
2 R17A602 1 28 R17A628 2
3 R17A603 1 29 R17A629 1
4 R17A604 4 30 R17A630 1
5 R17A605 1 31 R17A631 1
6 R17A606 1 32 R17A632 1
7 R17A607 1 33 R17A633 1
8 R17A608 1 34 R17A634 1
9 R17A609 1 35 R17A635 1
10 R17A610 1 36 R17A636 1
11 R17A611 8 37 R17A637 1
12 R17A612 8 38 R17A638 2
13 R17A613 1 39 R17A639 1
14 R17A614 2 40 R17A640 1
15 R17A615 1 41 R17A641 1
16 R17A616 1 42 R17A642 4
17 R17A617 1 43 R17A643 1
18 R17A618 1 44 R17A644 1
D Spare parts - ROAIRVAC 1.5
19 R17A619 1 45 R17A645 1
20 R17A620 1 46 R17A646 1
21 R17A621 4 47 R17A647 1
22 R17A622 4 48 R17A648 4
23 R17A623 2 49 R17A649 1
24 R17A624 1 50 R17A650 1
25 R17A625 1 51 R17A651 1
26 R17A626 1 52 R17A652 1
D
C
19 R17A619 1 45 R17A645 1
20 R17B620 1 46 R17B646 1
21 R17A621 4 47 R17A647 1
22 R17A622 4 48 R17A648 4
23 R17A623 2 49 R17B649 1
24 R17B624 1 50 R17A650 1
25 R17B625 1 51 R17A651 1
26 R17B626 1 52 R17B652 1
37
38
ITEM CODE QTY ITEM CODE QTY
1 R17B601 1 27 R17A627 1
2 R17B602 1 28 R17A628 2
3 R17B603 1 29 R17B629 1
4 R17A604 4 30 R17B630 1
5 R17B605 1 31 R17B631 1
6 R17A606 1 32 R17B632 1
7 R17B607 1 33 R17B633 1
8 R17A608 1 34 R17B634 1
9 R17A609 1 35 R17B635 1
10 R17A610 1 36 R17A636 1
11 R17A611 8 37 R17A637 1
12 R17A612 8 38 R17A638 2
13 R17B613 1 39 R17A639 1
14 R17A614 2 40 R17A640 1
15 R17C615 1 41 R17A641 1
16 R17C616 1 42 R17A642 4
17 R17B617 1 43 R17B643 1
18 R17A618 1 44 R17A644 1
F Spare parts - ROAIRVAC 6.0
19 R17A619 1 45 R17A645 1
20 R17C620 1 46 R17B646 1
21 R17A621 4 47 R17A647 1
22 R17A622 4 48 R17A648 4
23 R17A623 2 49 R17B649 1
24 R17B624 1 50 R17A650 1
25 R17B625 1 51 R17A651 1
26 R17B626 1 52 R17B652 1
D
G
23 R17D621 1 46 R17D639 1
39
40
ITEM CODE QTY ITEM CODE QTY
1 R17A601 1 27 R17A627 1
2 R17A602 1 28 R17A628 2
3 R17A603 1 29 R17A629 1
4 R17A604 4 30 R17A630 1
5 R17A605 1 31 R17A631 1
6 R17A606 1 32 R17A632 1
7 R17A607 1 33 R17A633 1
8 R17E608 1 34 R17A634 1
9 R17A609 1 35 R17A635 1
10 R17A610 1 36 R17A636 1
11 R17A611 8 37 R17A637 1
12 R17A612 8 38 R17A638 2
13 R17A613 1 39 R17A639 1
14 R17A614 2 40 R17A640 1
15 R17E615 1 41 R17E641 1
16 R17E616 1 42 R17A642 4
17 R17A617 1 43 R17A643 1
18 R17A618 1 44 R17A644 1
19 R17A619 1 45 R17A645 1
H Spare parts - ROAIRVAC 1.5J
20 R17C620 1 46 R17A646 1
21 R17A621 4 47 R17A647 1
22 R17A622 4 48 R17A648 4
23 R17A623 2 49 R17A649 1
24 R17A624 1 50 R17A650 1
25 R17A625 1 51 R17E651 1
26 R17A626 1 52 R17A652 1
D
ITEM CODE QTY ITEM CODE QTY
1 R17B601 1 27 R17A627 1
2 R17B602 1 28 R17A628 2
3 R17B603 1 29 R17B629 1
4 R17A604 4 30 R17B630 1
5 R17B605 1 31 R17B631 1
6 R17A606 1 32 R17B632 1
7 R17B607 1 33 R17B633 1
8 R17E608 1 34 R17B634 1
9 R17A609 1 35 R17B635 1
10 R17A610 1 36 R17A636 1
11 R17A611 8 37 R17A637 1
12 R17A612 8 38 R17A638 2
13 R17B613 1 39 R17A639 1
14 R17A614 2 40 R17A640 1
15 R17B615 1 41 R17E641 1
16 R17F616 1 42 R17A642 4
17 R17B617 1 43 R17B643 1
18 R17A618 1 44 R17A644 1
CI Spare parts - ROAIRVAC 2.5J
19 R17A619 1 45 R17A645 1
20 R17F620 1 46 R17B646 1
21 R17A621 4 47 R17A647 1
22 R17A622 4 48 R17A648 4
23 R17A623 2 49 R17B649 1
24 R17B624 1 50 R17A650 1
25 R17B625 1 51 R17E651 1
26 R17B626 1 52 R17B652 1
41
42
ITEM CODE QTY ITEM CODE QTY
1 R17B601 1 27 R17A627 1
2 R17B602 1 28 R17A628 2
3 R17B603 1 29 R17B629 1
4 R17A604 4 30 R17B630 1
5 R17B605 1 31 R17B631 1
6 R17A606 1 32 R17B632 1
7 R17B607 1 33 R17B633 1
8 R17E608 1 34 R17B634 1
9 R17A609 1 35 R17B635 1
10 R17A610 1 36 R17A636 1
11 R17A611 8 37 R17A637 1
12 R17A612 8 38 R17A638 2
13 R17B613 1 39 R17A639 1
14 R17A614 2 40 R17A640 1
15 R17C615 1 41 R17E641 1
16 R17G616 1 42 R17A642 4
17 R17B617 1 43 R17B643 1
18 R17A618 1 44 R17A644 1
19 R17A619 1 45 R17A645 1
J Spare parts - ROAIRVAC 4.0J
20 R17G620 1 46 R17B646 1
21 R17A621 4 47 R17A647 1
22 R17A622 4 48 R17A648 4
23 R17A623 2 49 R17B649 1
24 R17B624 1 50 R17A650 1
25 R17B625 1 51 R17E651 1
26 R17B626 1 52 R17B652 1
D
K
17 R17H615 1 40 R17A642 4
18 R17D616 1 41 R17D635 1
19 R17D617 1 42 R17D636 2
20 R17D618 1 43 R17A647 1
21 R17D619 1 44 R17D637 1
22 R17D620 1 45 R17D638 1
23 R17D621 1 46 R17D639 1
43
04.09