Squing Universal liquid level switch

CABLE WARNING:
GLAND If this equipment is used in a manner not
specified by the manufacturer, the protection
provided may be impaired.

Installation, operation and maintenance


instructions
OPERATION INSTALLATION
The forks are driven to resonance by an integral electronic Squing may be installed in a pipe or vessel using the thread, flange
circuit, which also monitors the frequency of vibration. When or connection provided. Use PTFE tape when thread mounting
the forks are covered by a liquid, the reduced frequency of and use only the hexagon when tightening to achieve a seal, do
vibration is detected by the electronics and Squing switches the not use the body. The body may be rotated after tightening to
load, acting as a simple 2 wire SPST switch. leave the cable gland ( M16 provided) in a suitable orientation.
The red LED viewed through the end cover will flash when When mounting horizontally it is preferable that the fork gap be
Squing is 'off' and will glow continuously when Squing is 'on', vertical to allow liquid to drain off the forks, and if the liquid is
thus giving a positive indication at all times that Squing is very viscous it is advisable to ensure maximum fork protrusion
operating. into the tank to prevent build-up between the tank wall and the
There is a fixed time delay of nominally 1-2 seconds when forks (see fig. i overleaf) If mounting in a pipe, the fork gap
switching from one state to the other. should be parallel to the pipe run.
WIRING: DIRECT LOAD SWITCHING MODEL Typical part no. 730TDS00000
2-Wire direct load switching or 3-wire PLC switching

i) Direct load switching PLC. The small standing current drawn by Squing is supplied
Squing is a piece of permanently installed equipment and as from the PLC in this case. Depending upon the PLC being used,
such a switch or circuit breaker is required in the installation. the standing current may prevent the voltage dropping below the
The device should be in close proximity to the equipment required 'off' voltage at the PLC input.
and be marked as its disconnecting device. When using Squing with a PLC, 3 core instrument cable must be
The Squing should be connected to a supply that is fused at used as shown above. Squing has an integral pull down resistor
no more than 3A. The wire should be adequately rated for between terminals 1 & 4 to ensure the voltage at the PLC input
250V 3A. terminal in the 'off' state is kept low. Different manufacturers
A protective earth (terminal 3) is required for all applications PLCs have different off voltages. If difficulty is experienced,
where the supply voltage exceeds 30Vrms ac or 60V dc. consult Solartron Mobrey.
NOTE: APPLICATION DATA
a) Squing must always be used in series with a load. Operating pressure: 50 bar to +500C/45 bar at 1300C
b) Squing draws a small (<2.5mA) standing current through Operating temp.: Wetside: -400C to +1300C
the load at all times, even in the 'off' state, so should not be Will withstand 1500C CIP cycles
Ambient: See graph below
used with relays having low drop-out voltages or with loads 0
C
which are not able to pass current in the off state, such as gas
neon discharge lamps.
c) Max wire size is 2.5mm2
d) The terminal block must be wired prior to fitting to the
pcb and care must be taken not to bend or flex the pcb when
terminal block is fitted.
ii) Using the load switching model with a PLC
It is possible to use the load switching model connected to a Liquid viscosity: 5000cSt max. (may increase response time)
COMMISSIONING ELECTRICAL DATA
i) Mode switch Direct load switching models
Squing has a mode switch to the left of the LED, revealed Operating voltage: 24 to 240V (+/- 10%) DC or 50/60 Hz AC
when the cover is removed. plc connection: 30V DC max.
Set to 'DRY-ON' when using Squing as a high level alarm Voltage drop: Approximate voltage drop (RMS)
to give maximum fail safety. This will then energise the Supply On current
load when Squing is dry, so any damage to Squing or its voltage 20mA 50mA 100mA 500mA
wiring will cause the load to drop out to the alarm state. 24V DC 6,5V 4,5V 3,5V 2,5V
Conversely, setting the mode switch to 'WET-ON' gives 110V AC 5,5V 3,5V 3,0V 2,5V
maximum fail safety when using Squing as a low level 240V AC 5,0V 4,0V 3,5V 3V
alarm, when the forks are wet in normal operation. Switched load: 500mA max. continuous
7.5mA min. continuous 5.0A for 40ms peak
Each Squing is factory set to give correct performance in a Current drawn: (load off) <2.5mA
wide range of liquids without the need for site adjustment. Enclosure rating: IP66/67 NEMA 4
Setting is made using the set point potentiometer seen Max. altitude: 2000m (for higher altitudes consult manf)
below the terminal block when the cover is removed. This Installation category: Category II - IEC664
pot is sealed with a label and when Squing is used in most Pollution degree: Pollution degree 2 - IEC664
common liquids, should not require adjustment. However, PNP 24Vdc PLC switching models
in extreme applications such as very light liquids at Operating voltage: 24Vdc (18-30Vdc)
elevated temperatures or very viscous liquids which cause Max. switched load: 100mA continuous
excessive 'wet to dry' response times, it may be possible to
improve perfomance. Consult Solartron Mobrey before Orientation mark

adjustment of set point potentiometer.


EXPLANATION OF SYMBOLS
The IEC symbols used on Squing are as follows:
Protective earth symbol - IEC 417 (501g)

Caution, refer to accompanying documents -


! 1503864 (B3.1) Fig. i < >
Maximum fork protrusion

SPARES
Spare PCB assembly, kit no. SK269
WIRING: PNP OUTPUT FOR 24Vdc PLC SWITCHING WIRING: RELAY OUTPUT
TYPICAL PART NO. 30TPS01000 TYPICAL PART NO. 730TDS02000

When using PNP Squing with a PLC, , 3 core instrument


cable must be used. Note that PNP Squing must always be
earthed in the field using safety earth terminal 2.
The small standing current drawn by PNP Squing is
supplied from the PLC. PNP Squing has an internal
“pull-up” transisitor which is designed to be connected to
the input terminal of a PLC as shown alongside.
Alternatively, PNP Squing may be used to operate a light
load such a small relay coil or filament bulb. We The module 1 PNP electronics will switch loads up to 100mA.
recommend that a diode such as IN4002 is connected The output transistor is an FZT751 which has a leakage current
across any inductive load such as a relay coil to prevent of less than 10 microamps. This model is capable of use with
back e.m.f. damage to the output transisitor. your PLC input card.

Solartron Mobrey Limited


158 Edinburgh Avenue Slough Berks England SL1 4UE
Tel: 01753 756600 Fax: 01753 823589
e-mail: sales@solartron.com www.solartron.com
a Roxboro Group Company

abcdef
Bestobell Mobrey GmbH Deutschland tel: 0211/99 808-0
Solartron Mobrey Ltd China tel: 021 6353 5652
Mobrey sp z o o Polska tel: 022 871 7865
Mobrey AB Sverige tel: 08-725 01 00
Mobrey SA France tel: 01.34.30.28.30
Mobrey SA-NV Belgium tel: 02/465 3879 The right is reserved to amend details
Solartron Mobrey USA tel: (281) 398 7890 given in this publication without notice IP222
Nov 00