1 2 3 4 5 6 7 8 9 10 11 12

SA09C2-TR-JVE-HAC-11047

2.658°
N
A A

LEGEND:
B B

C C

DIESEL GENERATOR BUILDING


D D

SMALL POWER, LIGHTING & TELECOM SYSTEM


DRAWINGS
E E

F F

NOTES

1. ALL DIMENSIONS ARE IN MILLIMETERS , AND LEVELS ARE IN METERS UNLESS


G G
NOTED OTHERWISE.

2. ALL DIMENSIONS TO BE VERIFIED ON SITE APPROVED BY THE ENGINEER

3. SMALL POWER, LIGHTING & TELECOM SYSTEM DESIGN ARE PRELIMINARY


AND SUBJECT TO UPDATE ACCORDING TO THE SUPPLIER`S DOCUMENTATION

4. ALL SMALL POWER, LIGHTING & TELECOM SYSTEM SHALL BE PROVIDED IN


ACCORDANCE WITH SMALL POWER, LIGHTING & TELECOM SYSTEM
STANDARS AND RECOMENDATIONS (TO BE APPROVED BY AUTHORIZED
INSUREANCE COMPANY AND LOCAL AUTHORITIES).

5. TO HVAC EQUIPMENT DETAIL SEE DRAWING No


SA10C2-JVE-33-XX-DR-IH-00001

6. TO FIRE FIGHTING EQUIPMENT DETAIL SEE DRAWING No


SA10C2-JVE-33-XX-DR-IF-00001

H Signature Designed D.R.B. FEB-2022 No REVISION DWN DATE Project Sheet Size Project Numer
Vendor Company H
Drawn E.P.M. FEB-2022 0 Issued for Construction E.P.M. 2023-08-11 BURAYDAH 2 ISTP SA09C2
Checked R.C.P. FEB-2022 1 Issued for Construction E.P.M. 2023-09-18 A1
SA09C2-TR-JVE-HAC-11047 Approved A.G.G. FEB-2022
Title Drawing Number
Shet Number 00
Initials Date DIESEL GENERATOR BUILDING
Scale
-
SMALL POWER, LIGHTING & TELECOM SYSTEM. DRAWINGS SA09C2-JVE-33-XX-DR-IE-00002
COVER SHEET

1 2 3 4 5 6 7 8 9 10 11 12
1 2 3 4 5 6 7 8 9 10 11 12

SA09C2-TR-JVE-HAC-11047

2.658°
N
A A

LEGEND:
B B

C C

LIST OF STRUCTURAL DRAWINGS


SHEET No. SHEET TITLE SCALE

D D
01 LIST OF DRAWINGS N.T.S.
02 GENERAL DETAILS N.T.S.
03 LIGHTING. GROUND FLOOR PLAN VIEW 1:50
04 EMERGENCY LIGHTING. GROUND FLOOR PLAN VIEW 1:50
05 SMALL POWER. GROUND FLOOR PLAN VIEW 1:50
06 HVAC POWER. GROUND FLOOR PLAN VIEW 1:50
07 HVAC POWER. ROOF FLOOR PLAN VIEW 1:50
08 SINGLE LINE DIAGRAMS N.T.S.
09 SINGLE LINE DIAGRAMS N.T.S.
10 TELECOM SYSTEM. GROUND FLOOR 1:50
11 TELEPHONE SCHEMATIC N.T.S.

E E

F F

NOTES

1. ALL DIMENSIONS ARE IN MILLIMETERS , AND LEVELS ARE IN METERS UNLESS


G G
NOTED OTHERWISE.

2. ALL DIMENSIONS TO BE VERIFIED ON SITE APPROVED BY THE ENGINEER

3. SMALL POWER, LIGHTING & TELECOM SYSTEM DESIGN ARE PRELIMINARY


AND SUBJECT TO UPDATE ACCORDING TO THE SUPPLIER`S DOCUMENTATION

4. ALL SMALL POWER, LIGHTING & TELECOM SYSTEM SHALL BE PROVIDED IN


ACCORDANCE WITH SMALL POWER, LIGHTING & TELECOM SYSTEM
STANDARS AND RECOMENDATIONS (TO BE APPROVED BY AUTHORIZED
INSUREANCE COMPANY AND LOCAL AUTHORITIES).

5. TO HVAC EQUIPMENT DETAIL SEE DRAWING No


SA10C2-JVE-33-XX-DR-IH-00001

6. TO FIRE FIGHTING EQUIPMENT DETAIL SEE DRAWING No


SA10C2-JVE-33-XX-DR-IF-00001

H Signature Designed D.R.B. FEB-2022 No REVISION DWN DATE Project Sheet Size Project Numer
Vendor Company H
Drawn E.P.M. FEB-2022 0 Issued for Construction E.P.M. 2023-08-11 BURAYDAH 2 ISTP SA09C2
Checked R.C.P. FEB-2022 1 Issued for Construction E.P.M. 2023-09-18 A1
SA09C2-TR-JVE-HAC-11047 Approved A.G.G. FEB-2022
Title Drawing Number
Shet Number 01
Initials Date DIESEL GENERATOR BUILDING
Scale
-
SMALL POWER, LIGHTING & TELECOM SYSTEM. DRAWINGS SA09C2-JVE-33-XX-DR-IE-00002
LIST OF DRAWINGS

1 2 3 4 5 6 7 8 9 10 11 12
1 2 3 4 5 6 7 8 9 10 11 12

SA09C2-TR-JVE-HAC-11047

2.658°
N
CONDUIT

A A
LUMINAIREFIXEDTOSLABSOFFIT COUNTER FLASHING
WITHSCREWSANDEXPANSIONINSERT SEALED AND CLAMPED
ROOF SHEET TO CONDUIT FLASHING
FLEXIBLE FIXTURE ROOF PURLIN STANDARD CONDUIT BOX
CONDUIT BOX PITCH POCKET CREATED IN
ROOF PURLIN HANGER, SEE DETAIL
CONDUIT SUPPORT ROOFING PITCH FILLED PERMANETLY FLEXIBLE CONDUIT
EXTENSION RING INSULATION AND WHEN CONDUIT IN PLACE ACOUSTIC CAULKING
STRUCTURAL SLAB ROOFING FIBREGLASS
FINISHED ROOF PACKING FLEXIBLE CONNECTION
OUTLET BOX MIN.6"
CONDUIT
HEAVY GAUGE WATER PROOF MEMBRANE (150mm)
FINISHED FLOOR
STEEL FLANGE CONTINUED UP PIPE SLEEVE
WELDED TO
SLEEVE

19 MM ∅

CONDUIT FLEXIBLE FIXTURE FLEXIBLE


NIPPLE FLOOR SLAB INSULATION AND
HANGER STEEL PIPE SLEEVE
CAULKING
19 MM ∅ PIPE SLEEVE
CONDUIT STRUCTURAL HEAVY GAUGE STEEL
TYPICAL DETAIL OF CONDUIT FLOOR SLAB FLANGE WELDED TO STEEL CONNECTOR OUTLET BOX
LUMINAIRE FIXED TERMINAL BLOCK
GENERAL INSTALLATIONS DETAILS

SLEEVE THROUGH ROOF INSULATION PROVIDED


HANGER DETAIL PARTITON WALL IN PARTITON WALL LEGEND:
B LIGHT FIXTURE SINGLE CORE PVC CABLES B
HEAT RESISTANT SLEEVING PASS THROUGH HOLE WITH
OVER SINGLE CORE CABLES GROMMET IN LUMINAIRE 13A SINGLE
SOCKET OUTLET
WITHIN LUMINAIRE ENCLOSURE ENCLOSURE SURFACE
MOUNTED

HIGHBAY LIGHT MOUNTING DETAIL SURFACE MOUNTED LIGHTING FIXTURE TYPICAL DETAIL OF SPECIAL PIPE TYPICAL MOUNTING DETAIL OF
PVC CONDUIT SLEEVE TRHOUGH FLOOR BACK TO BACK OUTLETS

SPACEBAR
400mm
SADDLE CLAMP
F.F.L

O/U
CONCRETE SLAB
DOOR
INSTALLATION OF SURFACE
MOUNTED SOCKET OUTLET
C EMT CONDUIT 150 110 C
GALVANIZED STEEL
CHANNEL SUPPORT
SWITCH FOR LIGHTS
WEATHERPROOF CABLES
DISCONNECT SWITCH IN FLEXIBLE WATERTIGHT
CONDUIT 13A TWIN SOCKET OUTLETS
JUNCTION BOX DP SWITCH
13A SINGLE SOCKET OUTLET
DISTRIBUTION BOARD
TO steel / block work / concrete wall DATA OUTLET
ADDRESSABLE DETECTOR BASE RESPECTIVE DB 1800mm 300mm
I/U MECHANICAL
EQUIPMENT 1200mm
ADDRESSABLE DETECTOR RGS CONDUIT
CABLE GLAND
EXPANSION MULTICORE SUB-MAIN CABLE 140 110
ANCHOR BOLTS
CABLE CLEATS/TAGS

CABLE TRAY 400mm


FINISHED FLOOR LEVEL
CABLE RACK CABLE TO BE LOCATED and
FILLED WITH FIRE RATED SEALING
FFL
CONCRETE PAD
TOP OF
D STRUCTURAL SLAB D
TYPICAL INSTALLATION DETAIL POWER CONNECTION DETAILS ROOFING
DETECTOR DEVICE SURFACE MOUNTED FOR SINGLE PHASE A/C SYSTEM
PVC SLEEVE
FIXATION DETAILS FOR DISCONNECT SWITCHES. (MAIN CABLE ENTRY FROM BOTTOM) FLOOR SLAB SCREED

CONCRETE INSPECTION SURFACE MOUNTED DISTRIBUTION BOARD TYPICAL STD. MOUNTING HEIGHT
COVER
ON STEEL /BLOCK WORK/ CONCRETE WALL. OF WIRING ACCESSORIES.
TYPICAL EQUIPMENT F.G.L.

REINFORCING STEEL BAR

600mm
ROD TO CABLE
CLAMP
EARTHING DETAILS

TYPICAL EQUIPMENT
TERMINAL LUG CONNECTOR
CONCRETE
INSPECTION
TAPE CLIP PIT
TYPICAL EQUIPMENT
E ROD TO CABLE E
CLAMP 70SQ.MM BARE CU CABLE
70SQ.MM BARE CU CABLE TERMINAL LUG
CABLE TO EQUIPOTENTIAL BONDING( TO COPPER TAPE ON PARAPET
FROM EARTH BAR (EQUIPMENT)/DOWN GROUNDING LOOP) CONNECTOR
BARE COPPER
3000mm

CONDUCTOR
CONDUCTOR ROOF PARAPET
TO EARTHING BAR 20mm Ø ROD
COUPLING
TO EARTH ROD

COPPER PVC INSULATE CABLE


70mm ² BARE COPPER CABLE IN 25MM PVC
20mm Ø EARTH CONDUIT EMBEDDED INSIDE CONCRETE
ROD COLUMN
TO EARTHING BAR

EARTHING DOWN CONDUCTOR CONNECTION


SQUARE TAPE CLAMP BONDED TO EQUIPMENT TYPICAL EARTH PIT DETAILS 5 HOLE EARTH BAR
WITH STEEL REINFORCING CONCRETE COLUMN COPPER PVC INSULATE CABLE Made Out of 30 x 3 mm Pure Copper Bar Pre-fitted on
Epoxy Powder Coated Metal Base Mounted on Insulators .
PART NO. EBAR 005
Concrete
F inspection cover F
AIR TERMINAL GRADE
CABLE WITH DC CLAMP 320 mm
146 mm F.G.L.
METALLIC DC CLIP AT EVERY AIR TERMINAL BASE
1500mm DISTANCE STRANDED BARE

192 mm
METAL LADDER 25x3mm BARE COPPER TAPE CONCRETE
MECHANICAL INSPECTION PIT
EQUIPMENT AT ROOF PARAPET BASE FIXED WITH PART NO. CP 001
SQUARE TAPE CLAMP
ROOF FLASHER and SCREW COPPER GROUND CONDUCTOR
SQUARE TAPE WIRE/CLAMP PARAPET WALL INTERCONNECTING ROD TO CABLE CLAMP
(COPPER ALLOY )
LIGHTNING DETAILS

METAL LADDER BONDED GROUND WELLS


TO LIGHTNING DC TAPE CLIP PART NO. ART 0016
PROTECTION
SYSTEM
METAL LADDER 70SQ.MM BARE CU CABLE TO
SQUARE TAPE SQUARE TAPE
CLAMP (CT-105FU) EQUIPOTENTIAL BONDING (TO
CLAMP GROUNDING LOOP)
70mm² BARE COPPER CABLE PART NO. BCS 0070
25x3mm BARE COPPER IN 25MM PVC CONDUIT
TAPE(TYPICAL). EMBEDDED INSIDE
25x 3mm BARE FOOT FOR LADDER CONCRETE COLUMN Ø 20mm. ROD COUPLING
COPPER TAPE
Ø 20mm. EARTH ROD NOTES
3m,LONG

1. ALL DIMENSIONS ARE IN MILLIMETERS , AND LEVELS ARE IN METERS UNLESS


G 25x 3mm BARE G
COPPER TAPE NOTED OTHERWISE.
70mm² BARE COPPER CABLE IN
25MM PVC CONDUIT EMBEDDED 2. ALL DIMENSIONS TO BE VERIFIED ON SITE APPROVED BY THE ENGINEER
INSIDE CONCRETE COLUMN

3. SMALL POWER, LIGHTING & TELECOM SYSTEM DESIGN ARE PRELIMINARY


SQUARE TAPE
CLAMP (CT-105FU)
AND SUBJECT TO UPDATE ACCORDING TO THE SUPPLIER`S DOCUMENTATION

4. ALL SMALL POWER, LIGHTING & TELECOM SYSTEM SHALL BE PROVIDED IN


EQUIPMENT BONDING DETAIL AT ROOF TO LIGHTNING PROTECTION INSTALLATION ACCORDANCE WITH SMALL POWER, LIGHTING & TELECOM SYSTEM
ROOF METAL EQUIPMENTS BONDING PARAPET CONDUCTOR INSTALLATION DETAIL
LIGHTNING PROTECTION SYSTEM CONNECTIONS AIR TERMINAL DETAILS ARRANGEMENT STANDARS AND RECOMENDATIONS (TO BE APPROVED BY AUTHORIZED
(TYPICAL)
INSUREANCE COMPANY AND LOCAL AUTHORITIES).

5. TO HVAC EQUIPMENT DETAIL SEE DRAWING No


SA10C2-JVE-33-XX-DR-IH-00001

6. TO FIRE FIGHTING EQUIPMENT DETAIL SEE DRAWING No


SA10C2-JVE-33-XX-DR-IF-00001

H Signature Designed D.R.B. FEB-2022 No REVISION DWN DATE Project Sheet Size Project Numer
Vendor Company H
Drawn E.P.M. FEB-2022 0 Issued for Construction E.P.M. 2023-08-11 BURAYDAH 2 ISTP SA09C2
Checked R.C.P. FEB-2022 1 Issued for Construction E.P.M. 2023-09-18 A1
SA09C2-TR-JVE-HAC-11047 Approved A.G.G. FEB-2022
Title Drawing Number
Shet Number 02
Initials Date DIESEL GENERATOR BUILDING
Scale
-
SMALL POWER, LIGHTING & TELECOM SYSTEM. DRAWINGS SA09C2-JVE-33-XX-DR-IE-00002
GENERAL DETAILS

1 2 3 4 5 6 7 8 9 10 11 12
1 2 3 4 5 6 7 8 9 10 11 12

SA09C2-TR-JVE-HAC-11047

2.658°
N
A 2.66° A

A B C E F

LEGEND:
B B
TRUNKING AND CONDUIT SYSTEM LEGEND:
MATERIALS
CONDUIT CABLE TRAY
01
1 1 ELECTRICAL CONDUIT

* INDOOR EXPOSED CONDUITS ARE EMT. PERFORATED CABLE TRAY


* OUTDOOR EXPOSED CONDUITS ARE RGS. HOT DIP GALVANIZED
01
VERTICAL TRAY MOUNTING TYPE VIZUALIZATION FOR CONDUITS AND CABLE TRAYS
600x100 SURFACE OR SUSPENDED MOUNTING
UNDERGROUND, EMBEDDED OR HIDDEN (IN CEILING/TECHNICAL FLOOR)

NOTE:REFER TO MATERIAL OF EACH CONDUIT OR CABLE TRAY TOGETHER


WITH MOUTING TYPE
LIGHTING TAG LEGEND:

KKS CODE PANEL BOARD ASSIGNMENT


CIR LT LIGHTING FIXTURE TYPE
C C
CIRCUIT

KKS CODE KKS CODE KKS CODE KKS CODE


L4 T11 L3 T11 L2 T11 L1 T11
LIGHTING SWITCH: 15A ONE WAY ONE GANG

LIGHTING SWITCH: 15A TWO WAY ONE GANG

KKS CODE
FACP FIRE ALARM CONTROL PANEL
LEXT T1

DISTRIBUTION BOARD

D D

2 2
GENERATORS ROOM

DAILY FUEL TANKS 01

600x100
TRAY 3
E E
KKS CODE KKS CODE KKS CODE KKS CODE
KKS CODE
L4 T11 L3 T11 L2 T11 L1 T11
LEXT T1

01

F TRAY 2 F
300x100 01

600x100
TRAY 1
3 3

KKS CODE KKS CODE KKS CODE KKS CODE


LEXT T1 LEXT T1 LEXT T1 LEXT T1

NOTES
A B C E F
1. ALL DIMENSIONS ARE IN MILLIMETERS , AND LEVELS ARE IN METERS UNLESS
G G
NOTED OTHERWISE.
PLAN VIEW 2. ALL DIMENSIONS TO BE VERIFIED ON SITE APPROVED BY THE ENGINEER
1 : 50 3. SMALL POWER, LIGHTING & TELECOM SYSTEM DESIGN ARE PRELIMINARY
AND SUBJECT TO UPDATE ACCORDING TO THE SUPPLIER`S DOCUMENTATION

4. ALL SMALL POWER, LIGHTING & TELECOM SYSTEM SHALL BE PROVIDED IN


ACCORDANCE WITH SMALL POWER, LIGHTING & TELECOM SYSTEM
STANDARS AND RECOMENDATIONS (TO BE APPROVED BY AUTHORIZED
INSUREANCE COMPANY AND LOCAL AUTHORITIES).
LUMINOUS CONNECTE
TYPE INDEX ARTICLE NAME QTY
(Lm) LOAD(W) 5. TO HVAC EQUIPMENT DETAIL SEE DRAWING No
SA10C2-JVE-33-XX-DR-IH-00001
T1 PFM F2 AREA 72W 840 AS4M 48x92 BK 10000 72 6
6. TO FIRE FIGHTING EQUIPMENT DETAIL SEE DRAWING No
SA10C2-JVE-33-XX-DR-IF-00001
T11 HB P 190W 840 110DEG IP65 27000 190 8

H Signature Designed D.R.B. FEB-2022 No REVISION DWN DATE Project Sheet Size Project Numer
Vendor Company H
Drawn E.P.M. FEB-2022 0 Issued for Construction E.P.M. 2023-08-11 BURAYDAH 2 ISTP SA09C2
Checked R.C.P. FEB-2022 1 Issued for Construction E.P.M. 2023-09-18 A1
SA09C2-TR-JVE-HAC-11047 Approved A.G.G. FEB-2022
Title Drawing Number
Shet Number 03
Initials Date DIESEL GENERATOR BUILDING
Scale
1/50
SMALL POWER, LIGHTING & TELECOM SYSTEM. DRAWINGS SA09C2-JVE-33-XX-DR-IE-00002
LIGHTING. GROUND FLOOR PLAN VIEW

1 2 3 4 5 6 7 8 9 10 11 12
1 2 3 4 5 6 7 8 9 10 11 12

SA09C2-TR-JVE-HAC-11047

2.658°
N
A 2.66° A

A B C E F

LEGEND:
B B
TRUNKING AND CONDUIT SYSTEM LEGEND:
MATERIALS
CONDUIT CABLE TRAY
01
1 1 ELECTRICAL CONDUIT

* INDOOR EXPOSED CONDUITS ARE EMT. PERFORATED CABLE TRAY


E1200 * OUTDOOR EXPOSED CONDUITS ARE RGS. HOT DIP GALVANIZED
E1200
01
KKS CODE
VERTICAL TRAY MOUNTING TYPE VIZUALIZATION FOR CONDUITS AND CABLE TRAYS
KKS CODE
L0 0
600x100 SURFACE OR SUSPENDED MOUNTING
L0 0
UNDERGROUND, EMBEDDED OR HIDDEN (IN CEILING/TECHNICAL FLOOR)

NOTE:REFER TO MATERIAL OF EACH CONDUIT OR CABLE TRAY TOGETHER


WITH MOUTING TYPE
LIGHTING TAG LEGEND:

KKS CODE PANEL BOARD ASSIGNMENT


CIR LT LIGHTING FIXTURE TYPE
C C
CIRCUIT

D D

2 2
GENERATORS ROOM

DAILY FUEL TANKS 01

600x100
TRAY 3
E E

KKS CODE
L0 0

KKS CODE
E1200

E1200

L0 0

01

F TRAY 2 F
300x100 01

600x100
TRAY 1
3 KKS CODE KKS CODE KKS CODE KKS CODE
3
E1200 E1200 E1200 E1200
L0 0 L0 0 L0 0 L0 0

NOTES
A B C E F
G PLAN VIEW 1. ALL DIMENSIONS ARE IN MILLIMETERS , AND LEVELS ARE IN METERS UNLESS
NOTED OTHERWISE.
G

1 : 50 2. ALL DIMENSIONS TO BE VERIFIED ON SITE APPROVED BY THE ENGINEER

3. SMALL POWER, LIGHTING & TELECOM SYSTEM DESIGN ARE PRELIMINARY


AND SUBJECT TO UPDATE ACCORDING TO THE SUPPLIER`S DOCUMENTATION

4. ALL SMALL POWER, LIGHTING & TELECOM SYSTEM SHALL BE PROVIDED IN


ACCORDANCE WITH SMALL POWER, LIGHTING & TELECOM SYSTEM
STANDARS AND RECOMENDATIONS (TO BE APPROVED BY AUTHORIZED
ELECTRICAL LUMINOUS INSUREANCE COMPANY AND LOCAL AUTHORITIES).
TYPE INDEX ARTICLE DESCRIPTION WATTS (W) Hz IP RATING QTY
DATA (V) FLUX (Lm)
5. TO HVAC EQUIPMENT DETAIL SEE DRAWING No
- EMERGENCY LIGHT SA10C2-JVE-33-XX-DR-IH-00001
- WALL SURFACE MOUNTED, NON MAINTAINED SELF CONTAINED
T0 E1200 - WEATHER PROOF ENCLOSURE 220-240 12 1200 50-60 IP65 8 6. TO FIRE FIGHTING EQUIPMENT DETAIL SEE DRAWING No
- 3 HOURS DURATION SA10C2-JVE-33-XX-DR-IF-00001
- POLYAMIDE

H Signature Designed D.R.B. FEB-2022 No REVISION DWN DATE Project Sheet Size Project Numer
Vendor Company H
Drawn E.P.M. FEB-2022 0 Issued for Construction E.P.M. 2023-08-11 BURAYDAH 2 ISTP SA09C2
Checked R.C.P. FEB-2022 1 Issued for Construction E.P.M. 2023-09-18 A1
SA09C2-TR-JVE-HAC-11047 Approved A.G.G. FEB-2022
Title Drawing Number
Shet Number 04
Initials Date DIESEL GENERATOR BUILDING
Scale
1/50
SMALL POWER, LIGHTING & TELECOM SYSTEM. DRAWINGS SA09C2-JVE-33-XX-DR-IE-00002
EMERGENCY LIGHTING. GROUND FLOOR

1 2 3 4 5 6 7 8 9 10 11 12
1 2 3 4 5 6 7 8 9 10 11 12

SA09C2-TR-JVE-HAC-11047

2.658°
N
A 2.66° A

A B C E F

LEGEND:
B B
TRUNKING AND CONDUIT SYSTEM LEGEND:
MATERIALS
CONDUIT CABLE TRAY
01
1 1 ELECTRICAL CONDUIT

* INDOOR EXPOSED CONDUITS ARE EMT. PERFORATED CABLE TRAY


* OUTDOOR EXPOSED CONDUITS ARE RGS. HOT DIP GALVANIZED
01
VERTICAL TRAY MOUNTING TYPE VIZUALIZATION FOR CONDUITS AND CABLE TRAYS
600x100 SURFACE OR SUSPENDED MOUNTING
UNDERGROUND, EMBEDDED OR HIDDEN (IN CEILING/TECHNICAL FLOOR)

NOTE:REFER TO MATERIAL OF EACH CONDUIT OR CABLE TRAY TOGETHER


WITH MOUTING TYPE
ELECTRICAL TAG LEGEND:

KKS CODE PANEL BOARD ASSIGNMENT


C CIR CIRCUIT C

BOX FOR 8 ELEMENTS WITH 2 DOUBLE SOCKETS, 1 DUAL UPS AND 2


PLATES RJ45

ADJUSTABLE FLOOR BOX FOR FLOOR 8 ELEMENTS WITH 2 DOUBLE


SOCKETS, 1 DUAL UPS AND 2 PLATES RJ45

16AMP DUPLEX SOCKET OUTLET 2P+E, WALL MOUNTED

32AMP INDUSTRIAL SOCKET OUTLET 3P+N+E, WALL MOUNTED


KKS CODE
F2
16AMP SIMPLEX SOCKET OUTLET 2P+E, WALL MOUNTED
KKS CODE
WP
F1
32AMP INDUSTRIAL SOCKET OUTLET 3P+N+E, WALL MOUNTED
D D
WP
16AMP SIMPLEX SOCKET OUTLET 2P+E, WALL MOUNTED

2 2 FACP FIRE ALARM CONTROL PANEL

GENERATORS ROOM
DISTRIBUTION BOARD

DAILY FUEL TANKS 01

600x100
TRAY 3
E E

FACP
KKS CODE
FACP

01

F KKS CODE KKS CODE KKS CODE KKS CODE KKS CODE KKS CODE TRAY 2 KKS CODE KKS CODE KKS CODE F
F2 F1 F2 F1 F2 F1 300x100 F2 F1 F1 01

600x100
TRAY 1
3 KKS CODE
3
F2

NOTES
A B C E F
G PLAN VIEW 1. ALL DIMENSIONS ARE IN MILLIMETERS , AND LEVELS ARE IN METERS UNLESS
NOTED OTHERWISE.
G

1 : 50 2. ALL DIMENSIONS TO BE VERIFIED ON SITE APPROVED BY THE ENGINEER

3. SMALL POWER, LIGHTING & TELECOM SYSTEM DESIGN ARE PRELIMINARY


AND SUBJECT TO UPDATE ACCORDING TO THE SUPPLIER`S DOCUMENTATION

4. ALL SMALL POWER, LIGHTING & TELECOM SYSTEM SHALL BE PROVIDED IN


ACCORDANCE WITH SMALL POWER, LIGHTING & TELECOM SYSTEM
STANDARS AND RECOMENDATIONS (TO BE APPROVED BY AUTHORIZED
INSUREANCE COMPANY AND LOCAL AUTHORITIES).

5. TO HVAC EQUIPMENT DETAIL SEE DRAWING No


SA10C2-JVE-33-XX-DR-IH-00001

6. TO FIRE FIGHTING EQUIPMENT DETAIL SEE DRAWING No


SA10C2-JVE-33-XX-DR-IF-00001

H Signature Designed D.R.B. FEB-2022 No REVISION DWN DATE Project Sheet Size Project Numer
Vendor Company H
Drawn E.P.M. FEB-2022 0 Issued for Construction E.P.M. 2023-08-11 BURAYDAH 2 ISTP SA09C2
Checked R.C.P. FEB-2022 1 Issued for Construction E.P.M. 2023-09-18 A1
SA09C2-TR-JVE-HAC-11047 Approved A.G.G. FEB-2022
Title Drawing Number
Shet Number 05
Initials Date DIESEL GENERATOR BUILDING
Scale
1/50
SMALL POWER, LIGHTING & TELECOM SYSTEM. DRAWINGS SA09C2-JVE-33-XX-DR-IE-00002
SMALL POWER. GROUND FLOOR

1 2 3 4 5 6 7 8 9 10 11 12
1 2 3 4 5 6 7 8 9 10 11 12

SA09C2-TR-JVE-HAC-11047

2.658°
N
A 2.66° A

A B C E F

LEGEND:
B B
TRUNKING AND CONDUIT SYSTEM LEGEND:
MATERIALS
CONDUIT CABLE TRAY
01
1 1 ELECTRICAL CONDUIT

* INDOOR EXPOSED CONDUITS ARE EMT. PERFORATED CABLE TRAY


* OUTDOOR EXPOSED CONDUITS ARE RGS. HOT DIP GALVANIZED
01 VERTICAL TRAY MOUNTING TYPE VIZUALIZATION FOR CONDUITS AND CABLE TRAYS
600x100 SURFACE OR SUSPENDED MOUNTING
UNDERGROUND, EMBEDDED OR HIDDEN (IN CEILING/TECHNICAL FLOOR)

NOTE:REFER TO MATERIAL OF EACH CONDUIT OR CABLE TRAY TOGETHER


WITH MOUTING TYPE
ELECTRICAL TAG LEGEND:

KKS CODE PANEL BOARD ASSIGNMENT


C CIR CIRCUIT C

EQUIPMENT

FACP FIRE ALARM CONTROL PANEL

DISTRIBUTION BOARD

D D

2 2
GENERATORS ROOM

DAILY FUEL TANKS 01

600x100
TRAY 3
E E

FACP
01

F KKS CODE KKS CODE KKS CODE


TRAY 2 KKS CODE F
FAN 04 FAN 03 FAN 02 300x100 FAN 01 01

600x100
TRAY 1
3 3

NOTES
A B C E F
G PLAN VIEW 1. ALL DIMENSIONS ARE IN MILLIMETERS , AND LEVELS ARE IN METERS UNLESS
NOTED OTHERWISE.
G

1 : 50 2. ALL DIMENSIONS TO BE VERIFIED ON SITE APPROVED BY THE ENGINEER

3. SMALL POWER, LIGHTING & TELECOM SYSTEM DESIGN ARE PRELIMINARY


AND SUBJECT TO UPDATE ACCORDING TO THE SUPPLIER`S DOCUMENTATION

4. ALL SMALL POWER, LIGHTING & TELECOM SYSTEM SHALL BE PROVIDED IN


ACCORDANCE WITH SMALL POWER, LIGHTING & TELECOM SYSTEM
STANDARS AND RECOMENDATIONS (TO BE APPROVED BY AUTHORIZED
INSUREANCE COMPANY AND LOCAL AUTHORITIES).

5. TO HVAC EQUIPMENT DETAIL SEE DRAWING No


SA10C2-JVE-33-XX-DR-IH-00001

6. TO FIRE FIGHTING EQUIPMENT DETAIL SEE DRAWING No


SA10C2-JVE-33-XX-DR-IF-00001

H Signature Designed D.R.B. FEB-2022 No REVISION DWN DATE Project Sheet Size Project Numer
Vendor Company H
Drawn E.P.M. FEB-2022 0 Issued for Construction E.P.M. 2023-08-11 BURAYDAH 2 ISTP SA09C2
Checked R.C.P. FEB-2022 1 Issued for Construction E.P.M. 2023-09-18 A1
SA09C2-TR-JVE-HAC-11047 Approved A.G.G. FEB-2022
Title Drawing Number
Shet Number 06
Initials Date DIESEL GENERATOR BUILDING
Scale
1/50
SMALL POWER, LIGHTING & TELECOM SYSTEM. DRAWINGS SA09C2-JVE-33-XX-DR-IE-00002
HVAC POWER. GROUND FLOOR

1 2 3 4 5 6 7 8 9 10 11 12
1 2 3 4 5 6 7 8 9 10 11 12

SA09C2-TR-JVE-HAC-11047

2.658°
N
A 2.66° A

A B C E F

LEGEND:
B B
TRUNKING AND CONDUIT SYSTEM LEGEND:
MATERIALS
01
CONDUIT CABLE TRAY
01
1 1 ELECTRICAL CONDUIT

* INDOOR EXPOSED CONDUITS ARE EMT. PERFORATED CABLE TRAY


* OUTDOOR EXPOSED CONDUITS ARE RGS. HOT DIP GALVANIZED

01 MOUNTING TYPE VIZUALIZATION FOR CONDUITS AND CABLE TRAYS


SURFACE OR SUSPENDED MOUNTING
TRAY 3 UNDERGROUND, EMBEDDED OR HIDDEN (IN CEILING/TECHNICAL FLOOR)
VERTICAL TRAY 01
KKS CODE
KKS CODE
600x100 KKS CODE
NOTE:REFER TO MATERIAL OF EACH CONDUIT OR CABLE TRAY TOGETHER
KKS CODE 600x100
A/A 01 A/A 04 WITH MOUTING TYPE
A/A 02 A/A 03
ELECTRICAL TAG LEGEND:

KKS CODE PANEL BOARD ASSIGNMENT


C CIR CIRCUIT C

EQUIPMENT
10.3%

FACP FIRE ALARM CONTROL PANEL

10.3%
DISTRIBUTION BOARD

D D

2 2

E E

10.3%
F F

3 3

NOTES
A B C E F
G PLAN VIEW 1. ALL DIMENSIONS ARE IN MILLIMETERS , AND LEVELS ARE IN METERS UNLESS
NOTED OTHERWISE.
G

1 : 50 2. ALL DIMENSIONS TO BE VERIFIED ON SITE APPROVED BY THE ENGINEER

3. SMALL POWER, LIGHTING & TELECOM SYSTEM DESIGN ARE PRELIMINARY


AND SUBJECT TO UPDATE ACCORDING TO THE SUPPLIER`S DOCUMENTATION

4. ALL SMALL POWER, LIGHTING & TELECOM SYSTEM SHALL BE PROVIDED IN


ACCORDANCE WITH SMALL POWER, LIGHTING & TELECOM SYSTEM
STANDARS AND RECOMENDATIONS (TO BE APPROVED BY AUTHORIZED
INSUREANCE COMPANY AND LOCAL AUTHORITIES).

WIDTH LENGTH HEIGHT PRESSURE MOTOR 5. TO HVAC EQUIPMENT DETAIL SEE DRAWING No
CODE DESCRIPTION AIR FLOW (m3/h) QTY SA10C2-JVE-33-XX-DR-IH-00001
(mm) (mm) (mm) DROP (Pa) POWER (Kw)
6. TO FIRE FIGHTING EQUIPMENT DETAIL SEE DRAWING No
SA10C2-JVE-33-XX-DR-IF-00001
ACOU3340 ROOFTOP PACKAGE UNIT 2257 5300 2421 36000 250 81.90 4

H Signature Designed D.R.B. FEB-2022 No REVISION DWN DATE Project Sheet Size Project Numer
Vendor Company H
Drawn E.P.M. FEB-2022 0 Issued for Construction E.P.M. 2023-08-11 BURAYDAH 2 ISTP SA09C2
Checked R.C.P. FEB-2022 1 Issued for Construction E.P.M. 2023-09-18 A1
SA09C2-TR-JVE-HAC-11047 Approved A.G.G. FEB-2022
Title Drawing Number
Shet Number 07
Initials Date DIESEL GENERATOR BUILDING
Scale
1/50
SMALL POWER, LIGHTING & TELECOM SYSTEM. DRAWINGS SA09C2-JVE-33-XX-DR-IE-00002
HVAC POWER. ROOF FLOOR PLAN VIEW

1 2 3 4 5 6 7 8 9 10 11 12
1 2 3 4 5 6 7 8 9 10 11 12

SA09C2-TR-JVE-HAC-11047

2.658°
N
A A

LEGEND:
B B

RESIDUAL CURRENT CIRCUIT BREAKER (R.C.C.B)

RESIDUAL CURRENT CIRCUIT BREAKER WITH OVERCURRENT


PROTECTOR (R.C.B.O)

MAGNETOTHERMIC CIRCUIT BREAKER (MCB)

1PH+N+E, 220V RECEPTACLE

3PH+N+E, 380V RECEPTACLE


C C
33 DIESEL GENERATOR BUILDING FIRE ALARM CONTROL PANEL

CONNECTED LOAD: 398.4 KW

DEMAND LOAD : 315.4 KW IMPULSE RELAY

AC CONTACTOR WITH 3 POSITION ROTATED SWITCH


(ON, OFF & AUTOMATIC)
4x630A 01

20A, 15kA ON/OFF SWITCH


Up: 1.2kV
Imax:40kA EARTHING

TIME SCHEDULER

2x10A 2x10A 4x63A 4x63A 4x63A 4x63A 4x200A 4x200A 4x200A 4x200A
D 2x25A 2x25A 2x25A 2x25A 4x30A 4x40A 2x25A 2x25A D
30mA 100mA 100mA 30mA 30mA 30mA 100mA 100mA
2x25A 2x25A 4x63A 4x63A 4x63A 4x63A 4x200A 4x200A 4x200A 4x200A
30mA 30mA 2x10A 2x10A 2x10A 2x10A 2x10A 2x10A 2x10A 4x40A 100mA 100mA 100mA 100mA 100mA 100mA 100mA 100mA 2x10A 2x10A 2x10A 2x10A

10A 10A 10A 10A 10A 10A 10A 10A 10A 30A 40A 63A 63A 63A 63A 200A 200A 200A 200A 10A 10A 10A 10A

SPARE

SPARE

SPARE

SPARE
CU XLPE + PVC FIRE RESISTANTCABLE

CU XLPE + PVC FIRE RESISTANTCABLE

CU XLPE + PVC FIRE RESISTANTCABLE

CU XLPE + PVC FIRE RESISTANTCABLE

CU XLPE + PVC FIRE RESISTANTCABLE

CU XLPE + PVC FIRE RESISTANTCABLE

CU XLPE + PVC FIRE RESISTANTCABLE

CU XLPE + PVC FIRE RESISTANTCABLE

CU XLPE + PVC FIRE RESISTANTCABLE

CU XLPE + PVC FIRE RESISTANTCABLE

CU XLPE + PVC FIRE RESISTANTCABLE

CU XLPE + PVC FIRE RESISTANTCABLE

CU XLPE + PVC FIRE RESISTANTCABLE

CU XLPE + PVC FIRE RESISTANTCABLE

CU XLPE + PVC FIRE RESISTANTCABLE

CU XLPE + PVC FIRE RESISTANTCABLE

CU XLPE + PVC FIRE RESISTANTCABLE

CU XLPE + PVC FIRE RESISTANTCABLE


CU XLPE + PVC FIRE RESISTANTCABLE
E E
4x2.5mm²+E=2.5mm²

4x2.5mm²+E=2.5mm²
2x2.5mm²+E=2.5mm²

2x2.5mm²+E=2.5mm²

2x2.5mm²+E=2.5mm²

2x2.5mm²+E=2.5mm²

2x2.5mm²+E=2.5mm²

2x2.5mm²+E=2.5mm²

4x16mm²+E=16mm²

4x16mm²+E=16mm²

4x16mm²+E=16mm²

4x16mm²+E=16mm²

4x95mm²+E=95mm²

4x95mm²+E=95mm²

4x95mm²+E=95mm²

4x95mm²+E=95mm²
4x10mm²+E=10mm²
4x6mm²+E=6mm²
2x4mm²+E=4mm²
(0.096 KW)

(0.432 KW)

(16.00 KW)

(16.00 KW)

(16.00 KW)

(16.00 KW)

(81.90 KW)

(81.90 KW)

(81.90 KW)

(81.90 KW)
TELECOM

(2.633 KW)
(0.50 KW)

(0.05 KW)

(0.38 KW)

(0.38 KW)

(0.38 KW)

(0.38 KW)

(0.50 KW)

(0.50 KW)

FAN 01

FAN 02

FAN 03

FAN 04
34-BLA

A/A 01

A/A 02

A/A 03

A/A 04
FACP

Lext

F1

F2
L0

L1

L2

L3

L4

F F

NOTES

1. ALL DIMENSIONS ARE IN MILLIMETERS , AND LEVELS ARE IN METERS UNLESS


G G
NOTED OTHERWISE.

2. ALL DIMENSIONS TO BE VERIFIED ON SITE APPROVED BY THE ENGINEER

3. SMALL POWER, LIGHTING & TELECOM SYSTEM DESIGN ARE PRELIMINARY


AND SUBJECT TO UPDATE ACCORDING TO THE SUPPLIER`S DOCUMENTATION

4. ALL SMALL POWER, LIGHTING & TELECOM SYSTEM SHALL BE PROVIDED IN


ACCORDANCE WITH SMALL POWER, LIGHTING & TELECOM SYSTEM
STANDARS AND RECOMENDATIONS (TO BE APPROVED BY AUTHORIZED
INSUREANCE COMPANY AND LOCAL AUTHORITIES).

5. TO HVAC EQUIPMENT DETAIL SEE DRAWING No


SA10C2-JVE-33-XX-DR-IH-00001

6. TO FIRE FIGHTING EQUIPMENT DETAIL SEE DRAWING No


SA10C2-JVE-33-XX-DR-IF-00001

H Signature Designed D.R.B. FEB-2022 No REVISION DWN DATE Project Sheet Size Project Numer
Vendor Company H
Drawn E.P.M. FEB-2022 0 Issued for Construction E.P.M. 2023-08-11 BURAYDAH 2 ISTP SA09C2
Checked R.C.P. FEB-2022 1 Issued for Construction E.P.M. 2023-09-18 A1
SA09C2-TR-JVE-HAC-11047 Approved A.G.G. FEB-2022
Title Drawing Number
Shet Number 08
Initials Date DIESEL GENERATOR BUILDING
Scale
1/50
SMALL POWER, LIGHTING & TELECOM SYSTEM DRAWINGS SA09C2-JVE-33-XX-DR-IE-00002
SINGLE LINE DIAGRAMS

1 2 3 4 5 6 7 8 9 10 11 12
1 2 3 4 5 6 7 8 9 10 11 12

SA09C2-TR-JVE-HAC-11047

2.658°
N
A A

LEGEND:
B B

RESIDUAL CURRENT CIRCUIT BREAKER (R.C.C.B)

RESIDUAL CURRENT CIRCUIT BREAKER WITH OVERCURRENT


PROTECTOR (R.C.B.O)

MAGNETOTHERMIC CIRCUIT BREAKER (MCB)

1PH+N+E, 220V RECEPTACLE

3PH+N+E, 380V RECEPTACLE


C C
FIRE ALARM CONTROL PANEL

IMPULSE RELAY

01 AC CONTACTOR WITH 3 POSITION ROTATED SWITCH


(ON, OFF & AUTOMATIC)

Voltage Drop (TOTAL)


Simultaneous Power

ON/OFF SWITCH

Circuit Breaker
Total Intensity
Simultaneous

Voltage Drop
Power Factor
Circuit Code

Total Power

Wiring tipe
Coefficient
EARTHING

Intensity

Conduit
I Wiring
Voltage

Section
Length

TIME SCHEDULER

D D

(W) (W) (V) m Simult. (A) mm2 (A) (%) (% MAX) A


TOTAL 315416 398440 380 0.85 1.00 564 712.2 630
FIRE FIGHTING
FACP 500 500 220 5.00 0.85 1.00 2.7 2.50 36.00 XLPE 2 [E] 0.09 2.5 10 25
LIGHTING 0
L0 0 96 220 62.00 0.90 1.00 0.5 2.50 36.00 XLPE 2 [E] 0.21 2.0 10 25
L1 380 380 220 45.00 0.90 1.00 1.9 2.50 36.00 XLPE 2 [E] 0.59 2.0 10 25
L2 380 380 220 51.00 0.90 1.00 1.9 2.50 36.00 XLPE 2 [E] 0.67 2.0 10 25
L3 380 380 220 5.00 0.90 1.00 1.9 2.50 36.00 XLPE 2 [E] 0.07 2.0 10 25
L4 380 380 220 62.00 0.90 1.00 1.9 2.50 36.00 XLPE 2 [E] 0.82 2.0 10 25
Lext 432 432 220 42.00 0.90 1.00 2.2 2.50 36.00 XLPE 2 [E] 0.63 2.0 10 25
SMALL POWER
E XLPE 2 [E] E
F1 500 500 220 43.00 0.85 1.00 2.7 2.50 36.00 0.79 2.5 10 25
F2 500 500 400 43.00 0.85 1.00 2.7 2.50 36.00 XLPE 2 [E] 0.79 2.5 10 32
33-BLA 2214 2633 380 200.00 0.85 1.00 4.7 10.00 75.00 XLPE 3 [E] 0.69 3.5 40 32
HVAC POWER 0
FAN01 16000 16000 380 14.00 0.85 1.25 35.7 16.00 100.00 XLPE 3 [E] 0.23 2.5 63 32
FAN02 16000 16000 380 19.00 0.85 1.25 35.7 16.00 100.00 XLPE 3 [E] 0.32 2.5 63 32
FAN03 16000 16000 380 25.00 0.85 1.25 35.7 16.00 100.00 XLPE 3 [E] 0.42 2.5 63 32
FAN04 16000 16000 380 31.00 0.85 1.25 35.7 16.00 100.00 XLPE 3 [E] 0.52 2.5 63 32
A/A 01 0 81900 380 28.00 0.85 1.25 183.0 95.00 298.00 XLPE 3 [E] 0.42 2.5 200 75
A/A 02 81900 81900 380 33.00 0.85 1.25 183.0 95.00 298.00 XLPE 3 [E] 0.50 2.5 200 75
A/A 03 81900 81900 380 39.00 0.85 1.25 183.0 95.00 298.00 XLPE 3 [E] 0.59 2.5 200 75
A/A 04 81900 81900 380 45.00 0.85 1.25 183.0 95.00 298.00 XLPE 3 [E] 0.68 2.5 200 75
TELECOM, DATA & CCTV
F TELECOM 50 50 220 5.00 0.85 1.25 0.3 2.50 36.00 XLPE 2 [E] 0.01 2.5 10 25 F
"20% power lighting
609
& small power reserve"

NOTES

1. ALL DIMENSIONS ARE IN MILLIMETERS , AND LEVELS ARE IN METERS UNLESS


G G
NOTED OTHERWISE.

2. ALL DIMENSIONS TO BE VERIFIED ON SITE APPROVED BY THE ENGINEER

3. SMALL POWER, LIGHTING & TELECOM SYSTEM DESIGN ARE PRELIMINARY


AND SUBJECT TO UPDATE ACCORDING TO THE SUPPLIER`S DOCUMENTATION

4. ALL SMALL POWER, LIGHTING & TELECOM SYSTEM SHALL BE PROVIDED IN


ACCORDANCE WITH SMALL POWER, LIGHTING & TELECOM SYSTEM
STANDARS AND RECOMENDATIONS (TO BE APPROVED BY AUTHORIZED
INSUREANCE COMPANY AND LOCAL AUTHORITIES).

5. TO HVAC EQUIPMENT DETAIL SEE DRAWING No


SA10C2-JVE-33-XX-DR-IH-00001

6. TO FIRE FIGHTING EQUIPMENT DETAIL SEE DRAWING No


SA10C2-JVE-33-XX-DR-IF-00001

H Signature Designed D.R.B. FEB-2022 No REVISION DWN DATE Project Sheet Size Project Numer
Vendor Company H
Drawn E.P.M. FEB-2022 0 Issued for Construction E.P.M. 2023-08-11 BURAYDAH 2 ISTP SA09C2
Checked R.C.P. FEB-2022 1 Issued for Construction E.P.M. 2023-09-18 A1
SA09C2-TR-JVE-HAC-11047 Approved A.G.G. FEB-2022
Title Drawing Number
Shet Number 09
Initials Date DIESEL GENERATOR BUILDING
Scale
1/50
SMALL POWER, LIGHTING & TELECOM SYSTEM DRAWINGS SA09C2-JVE-33-XX-DR-IE-00002
SINGLE LINE DIAGRAMS

1 2 3 4 5 6 7 8 9 10 11 12
1 2 3 4 5 6 7 8 9 10 11 12

SA09C2-TR-JVE-HAC-11047

2.658°
N
A 2.66° A

A B C E F

telecom Conduits to TB
LEGEND:
B B

RJ45 SIMPLEX OUTLET WALL MOUNTED FOR TELEPHONE

WP
1 1 RJ45 SIMPLEX OUTLET (WATER PROOF) WALL MOUNTED FOR
TELEPHONE

TB TELEPHONE BOX

∅25mm. CONDUIT SURFACE MOUNTING ON WALL 2 PAIR CAT -3 CABLES


(TYPICAL)

2 Ø 50mm - PVC DUCT AT LEVEL = -600mm FROM F.F.L FED FROM MDF
-AD @ADMIN. BUILDING (TO TELEPHONE SYSTEM INSTALLED IN ADMIN.
BUILDING (FOR CONTINUATION REFER TO SITE LAYOUT LOW CURRENT
CABLES DUCT BANK)

C C

ELECTRICAL
16
10
4 6
2.5 R N
R N N R
R N N R

S T P P T S S T P P T S S T P

TELECOM

DETAIL MOUNTING TRAYS

D D

2 2
GENERATORS ROOM

DAILY FUEL TANKS

E E

WP
KKS CODE TB
TELECOM

F F

3 3

NOTES
A B C E F
1. ALL DIMENSIONS ARE IN MILLIMETERS , AND LEVELS ARE IN METERS UNLESS
G G
PLAN VIEW NOTED OTHERWISE.
1 : 50 2. ALL DIMENSIONS TO BE VERIFIED ON SITE APPROVED BY THE ENGINEER

3. SMALL POWER, LIGHTING & TELECOM SYSTEM DESIGN ARE PRELIMINARY


AND SUBJECT TO UPDATE ACCORDING TO THE SUPPLIER`S DOCUMENTATION

4. ALL SMALL POWER, LIGHTING & TELECOM SYSTEM SHALL BE PROVIDED IN


ACCORDANCE WITH SMALL POWER, LIGHTING & TELECOM SYSTEM
STANDARS AND RECOMENDATIONS (TO BE APPROVED BY AUTHORIZED
INSUREANCE COMPANY AND LOCAL AUTHORITIES).

5. TO HVAC EQUIPMENT DETAIL SEE DRAWING No


SA10C2-JVE-33-XX-DR-IH-00001

6. TO FIRE FIGHTING EQUIPMENT DETAIL SEE DRAWING No


SA10C2-JVE-33-XX-DR-IF-00001

H Signature Designed D.R.B. FEB-2022 No REVISION DWN DATE Project Sheet Size Project Numer
Vendor Company H
Drawn E.P.M. FEB-2022 0 Issued for Construction E.P.M. 2023-08-11 BURAYDAH 2 ISTP SA09C2
Checked R.C.P. FEB-2022 1 Issued for Construction E.P.M. 2023-09-18 A1
SA09C2-TR-JVE-HAC-11047 Approved A.G.G. FEB-2022
Title Drawing Number
Shet Number 10
Initials Date DIESEL GENERATOR BUILDING
Scale
1/50
SMALL POWER, LIGHTING & TELECOM SYSTEM DRAWINGS SA09C2-JVE-33-XX-DR-IE-00002
TELECOM SYSTEM. GROUND FLOOR

1 2 3 4 5 6 7 8 9 10 11 12
1 2 3 4 5 6 7 8 9 10 11 12

SA09C2-TR-JVE-HAC-11047

2.658°
N
A A

LEGEND:
B B

RJ45 SIMPLEX OUTLET WALL MOUNTED FOR TELEPHONE

WP
RJ45 SIMPLEX OUTLET (WATER PROOF) WALL MOUNTED FOR
TELEPHONE

TB TELEPHONE BOX

∅25mm. CONDUIT SURFACE MOUNTING ON WALL 2 PAIR CAT -3 CABLES


(TYPICAL)

2 Ø 50mm - PVC DUCT AT LEVEL = -600mm FROM F.F.L FED FROM MDF
-AD @ADMIN. BUILDING (TO TELEPHONE SYSTEM INSTALLED IN ADMIN.
BUILDING (FOR CONTINUATION REFER TO SITE LAYOUT LOW CURRENT
CABLES DUCT BANK)

C C

1 nos.
WP

D D

PVC DUCTS FROM MDF IN CENTRAL ADMINISTRATION BUILDING


(FOR CONTINUATION REFER DUCT BANK SITE LAYOUT) CAT 6e IN Φ25mm (TYPICAL)

TB
~

DIESEL GENERATOR BUILDING (5 PAIRS)


E E

TELEPHONE SCHEMATIC
N.T.S.

F F

NOTES

1. ALL DIMENSIONS ARE IN MILLIMETERS , AND LEVELS ARE IN METERS UNLESS


G G
NOTED OTHERWISE.

2. ALL DIMENSIONS TO BE VERIFIED ON SITE APPROVED BY THE ENGINEER

3. SMALL POWER, LIGHTING & TELECOM SYSTEM DESIGN ARE PRELIMINARY


AND SUBJECT TO UPDATE ACCORDING TO THE SUPPLIER`S DOCUMENTATION

4. ALL SMALL POWER, LIGHTING & TELECOM SYSTEM SHALL BE PROVIDED IN


ACCORDANCE WITH SMALL POWER, LIGHTING & TELECOM SYSTEM
STANDARS AND RECOMENDATIONS (TO BE APPROVED BY AUTHORIZED
INSUREANCE COMPANY AND LOCAL AUTHORITIES).

5. TO HVAC EQUIPMENT DETAIL SEE DRAWING No


SA10C2-JVE-33-XX-DR-IH-00001

6. TO FIRE FIGHTING EQUIPMENT DETAIL SEE DRAWING No


SA10C2-JVE-33-XX-DR-IF-00001

H Signature Designed D.R.B. FEB-2022 No REVISION DWN DATE Project Sheet Size Project Numer
Vendor Company H
Drawn E.P.M. FEB-2022 0 Issued for Construction E.P.M. 2023-08-11 BURAYDAH 2 ISTP SA09C2
Checked R.C.P. FEB-2022 1 Issued for Construction E.P.M. 2023-09-18 A1
SA09C2-TR-JVE-HAC-11047 Approved A.G.G. FEB-2022
Title Drawing Number
Shet Number 11
Initials Date DIESEL GENERATOR BUILDING
Scale
-
SMALL POWER, LIGHTING & TELECOM SYSTEM DRAWINGS SA09C2-JVE-33-XX-DR-IE-00002
TELEPHONE SCHEMATIC

1 2 3 4 5 6 7 8 9 10 11 12