Professional Documents
Culture Documents
net/publication/228675474
CITATIONS READS
27 654
4 authors, including:
All content following this page was uploaded by Holger Wrede on 22 May 2014.
István Erlich
University of Duisburg-Essen
Duisburg, Germany
istvan.erlich@uni-due.de
Abstract - This paper describes two new control ap- Since large OWF have capacities comparable to con-
proaches for DFIG-based offshore wind farms connected ventional power plants, grid operators require them to par-
through voltage source converter (VSC) based HVDC link ticipate in grid voltage support in steady state and also dur-
with extended fault ride-through (FRT) capability. These ing faults. The latter requirement means that OWF have to
control strategies establish a coordination between the ride through grid faults and supply reactive currents to the
HVDC terminals and the wind turbines, allow safe operation grid as stated in the grid codes (e.g. the German E.ON
of the wind farm during grid faults and also fulfill the actual grid code [1, 2]). This grid voltage support is the task of
grid code requirements. Both introduced FRT methods uti- the grid side HVDC converter. Since the converters are
lize different means for a fast and reliable power reduction using self-commutated IGBT valves, the decoupled con-
in the wind farm to protect the HVDC transmission against trol of active and reactive current is simple (section 3.1).
overvoltages, which may occur as a result of a power imbal- But if the wind farm is operating close to rated power
ance between sending and receiving end during grid faults. when the fault occurs, the current limitation of the grid
This way the costs for a high rated DC chopper can be saved. side HVDC converter with reactive current priority may
For evaluation of these approaches detailed simulation mod- lead to a reduction of its active current. Together with
els of the HVDC and the wind turbines are presented. The the reduced grid voltage, the resulting active power flow
simulations are carried out in MATLAB/Simulink with Sim- to the grid may become very small. Without a coordi-
PowerSystems Toolbox. The simulation results show an ex- nated control of the HVDC link and the wind turbines this
ample of a severe three-phase grid fault, which proves the would lead to a significant unbalance between sending and
good performance of the proposed control strategies. receiving end power of the HVDC. As a result, the DC
transmission voltage would increase rapidly, which is un-
Keywords - Offshore Wind Energy, Doubly Fed acceptable. One way to limit the HVDC voltage is the
Induction Generator, VSC-based HVDC, Fault Ride- use of a huge DC chopper to dissipate the excess power.
Through, Coordinated control But this solution requires a chopper rated for the full WF
power, leading to higher investment costs. With the pro-
posed control the active power output of the DFIG wind
1 Introduction
turbines can be reduced very fast and the DC transmission
voltage can be maintained at an acceptable level without
T HE wind energy sector experiences a huge growth all
over the world. While in the early 90’s only sin-
gle turbines with power ratings of less than a hundred
the need for a full-rated DC chopper.
Section 2 gives a short introduction to some requirements
kW were installed, today offshore wind farms (OWF) are of the German E.ON grid code. Section 3 describes the
planned with capacities of more than 1000 MW. These HVDC system and its control. In section 4 the DFIG sys-
OWF may be located far away from shore and an HVDC tem is explained. In section 5 two methods for FRT of the
link (Figure 1) should be considered for their grid con- system are introduced. Section 6 shows simulaton results
nection, because AC transmission length and capacity is and section 7 finally gives some conclusions.
limited due to the large charging currents of the cables.
Wind Farm 2 Grid Code Requirements
y
u DC psend
Additional
reactive current magnitude
ǻIQ/IN u AC
Within dead band, e.g. limitation
const. power factor control
Dead band around Voltage limitation Activation of voltage control slow setpoint tracing
reference voltage (under-excited mode) by exceeding dead band
§ 1 ·
Continuation of voltage u AC _ ref K P ¨¨1 ¸¸ iq_ugref
control after return into dead © sTI ¹
zone at least about 500 ms -
u AC
-50% -10% 10% 20% Voltage ǻU/UN
Voltage support
(over-excited mode) Control characteristics
K P ¨¨1 ¸¸ ud_ugref
3~
i d_ugref © sTI ¹ -
-
i dug ZL Back-to-Back PWM Converter
magnitude L
limitation
iqug ZL
-
§ 1 ·
-
iq_ugref K P ¨¨1 ¸¸
-
uq_ugref Crowbar
© sTI ¹
Figure 8: DFIG based wind turbine system
u gq In a DFIG system the function of the grid side con-
Figure 6: Feed-forward Decoupled Current Control verter is to maintain the DC voltage and to support the
grid with reactive power during a fault. Especially when
3.2 Sending End Converter the machine rotor is short circuited through the crowbar
resistors, the generator consumes reactive power. This re-
The SEC is responsible for transmitting the active active power has to be compensated by the grid side con-
power produced by the wind farm, while maintaining the verter. The rotor side converter controls active and reactive
AC voltage in the wind farm grid. Furthermore, it can be power of the DFIG and follows a tracking characteristic to
used for frequency control which in turn controls the slip adjust the generator speed for optimal power generation
of the DFIGs connected to the wind turbines. This may depending on wind speed. Both converter controls are us-
be used for reduction of active power transfer through the ing a feed-forward decoupled current control [10] similar
fractional rated converter in the DFIG rotor circuit [8]. As to that used for the REC of the VSC-based HVDC. When
the power control is performed by the wind turbines, a the wind speed exceeds its nominal value, the pitch control
simple voltage magnitude controller can be used for the reduces the mechanical torque by pitching the rotor blades
SEC, thus fulfilling the aforementioned requirements. The to recover the generator rated speed. A detailed descrip-
frequency can be directly regulated without the need for a tion of the complete DFIG control system can be found in
closed loop structure. Figure 7 shows the control structure [11].
of the SEC.
u max 5 FRT methods
ug
§ 1 · u gd _ ref To secure fault ride-through of the described system it
u AC _ ref K P ¨¨1uf ¸¸
jug
- © sTI ¹ ug
u gq _ ref e u g_0 ref has to be ensured that the generated wind power can be
0 dissipated through the HVDC. Otherwise the HVDC volt-
u AC u min age would increase above the acceptable limits. This can
be avoided by use of a DC chopper rated for the full WF
2S ug power, but this means higher investment costs. Another
f ref
s
way, which is favoured here, is a coordinated control of
Figure 7: Sending end VSC control REC, SEC and the DFIG WTs with a WF power reduc-
tion after fault detection.
Since no current control is used, a current limitation
When a fault occurs on the HV grid side, the receiving
can only be achieved with an indirect method or by block-
end HVDC converter can only deliver a small portion of
ing the IGBTs during a severe fault in the wind farm grid.
the generated power to the grid, according to the following
The voltage control capability of the SEC can be used to
relationship:
initiate a controlled voltage drop to reduce the WF power
during FRT in HV grid. pRC = |uRC |ia,RC (1)
0.5 0.5
-0.5 -0.5
-1.5 -1.5
1.0 1.0
0.0 0.0
-1.0 -1.0
-2.0 -2.0
1.5 1.5
Active and reactive power at receiving end (p.u.) Active and reactive power at receiving end (p.u.)
0.5 0.5
Q Q
-0.5 -0.5
P P
-1.5 -1.5
Wind farm grid voltages (p.u.) Wind farm grid voltages (p.u.)
1.5 1.5
0.5 0.5
-0.5 -0.5
-1.5 -1.5
2.5
Wind farm grid currents (p.u.) Wind farm grid currents (p.u.)
1.5
1.5
0.5
0.5
-0.5
-0.5
-1.5 -1.5
P -1.0 P
-1.5
-2.0
2.0
HVDC voltages at receiving end (p.u.) 2.0
HVDC voltages at receiving end (p.u.)
1.0
1.0
0.0
0.0
-1.0
-1.0
-2.0
-2.0
2.0
HVDC voltages at sending end (p.u.) 2.0
HVDC voltages at sending end (p.u.)
1.0
1.0
0.0
0.0
-1.0
-1.0
-2.0
-2.0
0.5
Wind turbine electromagnetic torque (p.u.) 0.5
Wind turbine electromagnetic torque (p.u.)
-0.5
-0.5
-1.5
-1.5
0.45 0.5 0.55 0.6 0.65 0.7 0.75 0.8 0.85 0.9
0.45 0.5 0.55 0.6 0.65 0.7 0.75 0.8 0.85 0.9
time (s)
time (s)
Figure 11: Simulation results for a three-phase fault in the HV grid with Figure 12: Simulation results for a three-phase fault in the HV grid with
coordination of HVDC and WF with output power reduction through coordination of HVDC and WF with output power reduction through
current control voltage control