You are on page 1of 29

Swegon ESBO 160311

User Manual

INTRODUCTION............................................................ 1
PORTAL PAGE............................................................... 2
SOFTWARE................................................................... 3
CONNECTING TO PROSELECT....................................... 4
VENTILATION................................................................ 6
START INSTANCE.......................................................... 7
TEMPLATE ROOMS....................................................... 9
Hotel room............................................................. 10
Classroom............................................................... 12
Office, 1 person (airborne)...................................... 14
Office, 1 person (waterborne)................................. 16
Office, 2 persons (airborne)..................................... 18
Office, 2 persons (waterborne)................................ 20
Conference room, 6 person (airborne)..................... 22
Conference room, 6 person (waterborne)................ 24
Conference room, 12 persons (airborne)................. 26
Conference room, 12 persons (waterborne)............ 28

INTRODUCTION
This manual is a supplement to the main user guide for
ESBO written by EQUA. This manual primarily describes
the feature unique to Swegon that are not included in the
main user guide, yet some features are also mentioned in
the EQUA documentation for ESBO and IDA ICE.
The manual applies to all versions of Swegon ESBO, i.e.
both the Light version and the full paid version.

We reserve the right to alter specifications. www.swegon.com 1


Swegon ESBO 160311

PORTAL PAGE
The portal page, where the user can choose how Swegon 5. Open saved project
ESBO is to be displayed, opens when the software is Selecting the option Open saved project opens File Explorer
started. The page has the same appearance in all versions on the computer where you select the project to open. The
of Swegon ESBO. file format is .idm. If Swegon ESBO is installed on the com-
puter the last used folder is opened, while when using the
1. Software version cloud version you start from the system’s standard folder.
Once you have installed Swegon ESBO on your computer
you can quickly see which version you have and whether 6. Language setting
any updates are available to download. The desired language can be set directly on the portal
page. The unit for air flow is adjusted at the same time.
2. Create simple room
The function Create simple room opens the software with 7. Order Swegon ESBO
an simplified view. Here there are not so many options or It is possible to order the full paid version of Swegon ESBO
settings that can be made, and it is not possible to make directly on the portal page.
energy calculations. Ideally the function is used at an early
stage, when you do not have a great deal of information 8. Support
or to make a quick calculation.
There are various possibilities of user support.
3. Create project • Send e-mail to the address supportesbo@swegon.com
If you select Create project the software opens in an • Via the ESBO forum where users can discuss and assist
advanced view. All functions are available via the Room, each other. Here you can read frequently asked questions
Building and Simulation tabs. In this view it is possible • Contact with the local support team
to make detailed selections and settings as well as make
energy calculations. Internet access
Several functions on the portal page will be unavailable
4. Create a project from template if you do not have an Internet connection when Swegon
The function Create project from template allows you to ESBO is installed on the computer. Clear information is
quickly get started by using an existing solution from the shown for the relevant functions.
list. Products, settings and conditions can then be adapted
for the project at hand.

2 3 4 5

7 8

2 www.swegon.com We reserve the right to alter specifications.


Swegon ESBO 160311

SOFTWARE

Back to the portal page File Window Help

Use the button on the menu bar to return to the portal


page from inside the software. This function may be useful
if, for example, you wish to change language, flow unit
etc. after you have started the software.

Palette
The palette is shown when you create a new project with
the function Create project. The palette consists of two
tabs, By type and By manufacturer.
• The By type tab contents all building elements,
materials, heating system, cooling system, ventilation
etc. Swegon systems and products are also available
here. Selecting one of these starts Swegon’s product
selection program ProSelect where you can configure
and select a product which is then added to the list for
each system.
• The By manufacturer tab contents the Swegon
products you have created and collected in your
own library. Some products are included from the
offset, and more are added as you make your own
configurations in ProSelect.

We reserve the right to alter specifications. www.swegon.com 3


Swegon ESBO 160311

CONNECTING TO PROSELECT
Clicking on either a Swegon system or a Swegon product
starts an adapted version of ProSelect. Here it is possible to
select and configure products for the project in question.
This version of ProSelect is solely available via Swegon
ESBO while the full version is available on Swegon.com.

First choose Product group and then the required product.

Once you have selected the product group select the


required product. In this example PARASOL is selected.

See the next page for possible settings.

4 www.swegon.com We reserve the right to alter specifications.


Swegon ESBO 160311

ProSelect , example

PARASOL

11 12 13
1
14 15 16
2

10

4 3 17

5 6
7

19

8 9

18 20

1. Comfort modules; select type - Recessed or Sus- 11. Image; shows an image of the product
pended 12. Rendered Picture; shows an animated product image
LF = Low flow, MF = Medium flow, HF = High flow
13. Wireframe sketch; shows a drawing with measurements
2. Function; Cooling, Cooling and heating or only
14. Sound diagram; shows a diagram with sound curves
Supply air
15. Calculation result; shows the calculated data after
3. Primary air flow; state the air flow in the unit l/s
you have pressed the button Update results
4. Air Connection; duct connectionRight or Left
16. Flow pattern; shows the flow pattern for a room at
5. Size; state the size 592 or 1192 different air velocities
6. Air Flow Config; state whether the configuration for 17. When all settings have been made you need to press
the air flow should be Symmetric (equal air flows) or the button Update results
Asymmetric (different air flows in each direction)
18. The product is now ready to transfer to Swegon ESBO,
7. Air flow/side; state the nozzle setting - Low, Medium, which is done by pressing the button Add to ESBO. A
High or Closed. For symmetric air flow configuration all confirmation dialogue box appears.
sides are adjusted according to the selection above
19. Click OK in the dialogue box
8. Capacity Setup; state the capacity - High or Normal
20. Close ProSelect with the button in the lower right-
9. ADC Air Pattern; state the distribution pattern -
hand corner
Fan shape = all-round, Straight = straight ahead
10. Adjusted settings; state the temperature and water
flow that forms the basis of the calculation
10

We reserve the right to alter specifications. www.swegon.com 5


Swegon ESBO 160311

VENTILATION
In the standard Ventilation dialogue it is possible to select
between Constant air volume (CAV) and Variable air
volume (VAV).

The dialogue appears differently in instances when you


select a Swegon product. Here you select Variable air
volume (DCV) by checking the check box.. For the selection
of DCV you need to state Ventilation air flow, Occupied air
flow and Non-occupied air flow.

Check whether CO2/VOC should be a part of the control.


It is also possible to select the type of sequence to be acti-
vated first. Select either Cool/heat with air before water or
Cool/heat with water before air.

6 www.swegon.com We reserve the right to alter specifications.


Swegon ESBO 160311

START INSTANCE
According to the start instance, a room is adapted for 1
person and equipped with general factory independent
products. The climate system has individual control and
comprises heating, cooling and ventilation.

Temperature
Set point heating: 20°C
Set point cooling: 24°C

Geometry
Length: 4.2 m
Width: 2.4 m
Height: 2.6 m
Façade direction: South

Window
Area: 1.8 m2
U-/G-value: 2.88/0.77
Window screening: Interior blinds

Outer wall
U-value: 0.23
Thermal bridges: Good

Internal heating
Equipment: 150W
Persons: 1
Lighting: 90W

Occupancy
Percentage of
internal loads for
the energy calculation: 60%

We reserve the right to alter specifications. www.swegon.com 7


Swegon ESBO 160311

Start instance continued

Ventilation
Supply and extract air in the room Ventilation unit with
rotary heat exchanger with 83% recovery of heating and
cooling energy.
Constant air flow 15 l/s
Infiltration: 0.1 Chge/h
Control: Constant supply air temperature
Supply air temperature: 17°C

Hot tap water


Not included in the calculation

Heating
Source: District heating
Heating water, temp: 60-40°C

Cooling
Source: General chiller, average COP 3
Cooling water, temp: 14-17°C

Distribution
Products: General supply air diffuser

Unlimited heating and cooling.

8 www.swegon.com We reserve the right to alter specifications.


Swegon ESBO 160311

TEMPLATE ROOMS
Template rooms in Swegon ESBO are started or completed
calculations that aim to:
• Enable the user to quickly make calculations
• Give tips about common values for different room
types when not all the conditions are known
• Give proposals of solutions for different types of
rooms
• Give the user opportunities to compare his own solu-
tion with template rooms to determine whether the
outcome is reasonable
• Enable new users to get started quickly by starting
from a template room and correcting known details
• A template room called “water” must handle the
cooling output waterborne. The level for the air flow
is only the min. flow
• A template room called “air” must handle the cool-
ing output airborne. The room has no waterborne
cooling, but the cooling output usually comes from a
central air cooler in the air handling unit
When updating template rooms the information will be
available on Swegon ESBO’s portal page.
Additional template rooms will be added continuously.
Contact Swegon if you require a room type by sending an
e-mail to the address supportesbo@swegon.com

We reserve the right to alter specifications. www.swegon.com 9


Swegon ESBO 160311

Hotels
Hotel room
A hotel room as standard is designed for 1-2 persons
where the hotel has up to four stars. The climate system
has individual control and comprises heating, cooling and
ventilation.
Hotel rooms in Swegon ESBO are based on the system
solution Swegon Hotel Solution, which won the “Major
Indoor Climate Prize” in 2011 with the following
motivation:
”The jury selected Swegon for an intelligent, innovative
and commercial available total solution for climate control
of hotels, an application of climate technology where
users make large demands. The system is based on tried Geometry
and tested and interacting components that give the hotel Length: 5.8 m
guests a good indoor climate with low noise level and
Width: 3.7 m
no draughts. The system has low energy consumption, is
adaptable to various climate requirements and the outside Height: 2.7 m
climate and is easy to maintain. The market potential Façade direction: South
of the solution appears to be great both in Sweden and
abroad. Swegon is a worthy recipient of the 2011 prize.”
Window
Area: 2.5 m2
Temperature
U-/G-value: 2.88/0.77
Set point heating: 21°C (20°C for no occupancy)
Window screening: Interior blinds
Requirement 20°C as coldest
Set point cooling: 24°C (27°C for no occupancy)
Outer wall
Requirement 24°C as warmest
U-value: 0.23
Thermal bridges: Good

Internal heating
Equipment: 150W
Persons: 1
Lighting: 75W

Occupancy
Percentage of internal loads for the energy calculation:
60%

10 www.swegon.com We reserve the right to alter specifications.


Swegon ESBO 160311

Hotel rooms continued

Ventilation
Supply air in the room and extract air in the bathroom
Ventilation unit with rotary heat exchanger with 83%
recovery of heating and cooling energy.
No occupancy: 3 l/s
Occupancy, (min): 8 l/s
Occupancy, (max): 28 l/s
Infiltration: 0.1 Chge/h
Control: Supply air as a function of the
outdoor air
Supply air temperature: 20°C to 15°C

Hot tap water


Volume: 9 litres per person and day

Heating
Source: District heating
Heating water, temp: 45-35°C

Cooling
Source: General chiller, average COP 3
Cooling water, temp: 14-17°C

Distribution
Product: Comfort module PARAGON 1100

Quick facts
• Cooling, heating and ventilation
• Low installation height
• High capacity
• Integrated control equipment
• Easy installation
• Closed unit
• Flexible air flow (VariFlow)
• Adjustable air direction ADC and adjustable grille louvres
• CCO valve for maximum capacity

We reserve the right to alter specifications. www.swegon.com 11


Swegon ESBO 160311

Schools
Classroom
According to the standard a classroom is designed for 30
persons. The climate system has individual control and
comprises ventilation and free cooling. The heating system
is supplied by an outside party but is integrated in the
climate system’s control. The system solution is suitable for
most climate zones in world.

Temperature
Set point heating: 21°C (20°C for no occupancy)
Requirement 20°C as coldest Geometry
Set point cooling: 24°C (27°C for no occupancy) Length: 6 m
Requirement 25°C as warmest Width: 10 m
Height: 2.7 m
Façade direction: South

Window
Area: 6.0 m2
U-/G-value: 2.88/0.77
Window screening: Interior blinds

Outer wall
U-value: 0.23
Thermal bridges: Good

Internal heating
Equipment: 900W
Persons: 30
Lighting: 540W

Occupancy
Percentage of
internal loads for
the energy calculation: 60%

12 www.swegon.com We reserve the right to alter specifications.


Swegon ESBO 160311

Classrooms continued

Ventilation
Supply and extract air in the classroom Ventilation unit
with rotary heat exchanger with 83% recovery of heating
and cooling energy.
No occupancy: 20 l/s
Occupancy, (min): 40 l/s
Occupancy, (max): 300 l/s
Infiltration: 0.1 Chge/h
Control: Supply air as a function of the
outdoor air
Supply air temperature: 20°C to 15°C
CO2 control: Max 1000 ppm

Hot tap water


Not included in the calculation

Heating
Source: District heating
Heating water, temp: 60-40°C

Cooling
Source: No cooling production,
free cooling from outdoor air
Cooling water, temp: --

Distribution
Products: Suspended supply air diffuser,
2 x EAGLE Free
DCV damper, ADAPT D
School WISE package

We reserve the right to alter specifications. www.swegon.com 13


Swegon ESBO 160311

Office, 1 person (airborne)


An office designed for 1 person. The climate system has
individual control and comprises ventilation and cooling.
The heating system is supplied by an outside party but
is integrated in the climate system’s control. The system
solution is suitable for most climate zones in world.

Temperature
Set point heating: 21°C (20°C for no occupancy)
Requirement 20°C as coldest
Set point cooling: 24°C (27°C for no occupancy)
Requirement 25°C as warmest

Geometry
Length: 4.2 m
Width: 2.4 m
Height: 2.6 m
Façade direction: South

Window
Area: 1.2 m2
U-/G-value: 2.88/0.77
Window screening: Interior blinds

Outer wall
U-value: 0.23
Thermal bridges: Good

Internal heating
Equipment: 150W
Persons: 1
Lighting: 90W

Occupancy
Percentage of internal loads for
the energy calculation: 60%

14 www.swegon.com We reserve the right to alter specifications.


Swegon ESBO 160311

Office, 1 person (airborne) continued

Ventilation
Supply and extract air in the room Ventilation unit with
rotary heat exchanger with 83% recovery of heating and
cooling energy.
No occupancy: 5 l/s
Occupancy, (min): 10 l/s
Occupancy, (max): 50 l/s
Infiltration: 0.1 Chge/h
Control: Supply air as a function of the
outdoor air
Supply air temperature: 20°C to 15°C

Hot tap water


Not included in the calculation

Heating
Source: District heating
Heating water, temp: 60-40°C

Cooling
Source: General chiller, average COP 3
Cooling water, temp: No water cooling

Distribution
Products: Recessed supply air diffuser,
ADAPT C 250

We reserve the right to alter specifications. www.swegon.com 15


Swegon ESBO 160311

Office, 1 person (waterborne)


An office designed for 1 person. The climate system has
individual control and comprises heating, cooling and
ventilation. The system solution is suitable for most climate
zones in world.

Temperature
Set point heating: 21°C (20°C for no occupancy)
Requirement 20°C as coldest
Set point cooling: 24°C (27°C for no occupancy)
Requirement 25°C as warmest

Geometry
Length: 4.2 m
Width: 2.4 m
Height: 2.6 m
Façade direction: South

Window
Area: 1.2 m2
U-/G-value: 2.88/0.77
Window screening: Interior blinds

Outer wall
U-value: 0.23
Thermal bridges: Good

Internal heating
Equipment: 150W
Persons: 1
Lighting: 90W

Occupancy
Percentage of internal loads for
the energy calculation: 60%

16 www.swegon.com We reserve the right to alter specifications.


Swegon ESBO 160311

Office, 1 person (waterborne) continued

Ventilation
Supply and extract air in the room Ventilation unit with
rotary heat exchanger with 83% recovery of heating and
cooling energy.
Constant air flow 15 l/s
Infiltration: 0.1 Chge/h
Control: Supply air as a function of the
outdoor air
Supply air temperature: 20°C to 15°C

Hot tap water


Not included in the calculation

Heating
Source: District heating
Heating water, temp: 45-35°C

Cooling
Source: General chiller, average COP 3
Cooling water, temp: 14-17°C

Distribution
Products: Comfort module, PARASOL 600

We reserve the right to alter specifications. www.swegon.com 17


Swegon ESBO 160311

Office, 2 persons (airborne)


An office designed for 2 persons. The climate system has
individual control and comprises ventilation and cooling.
The heating system is supplied by an outside party but
is integrated in the climate system’s control. The system
solution is suitable for most climate zones in world.

Temperature
Set point heating: 21°C (20°C for no occupancy)
Requirement 20°C as coldest
Set point cooling: 24°C (27°C for no occupancy)
Requirement 25°C as warmest
Geometry
Length: 4.2 m
Width: 3.6 m
Height: 2.7 m
Façade direction: South

Window
Area: 1.2 m2
U-/G-value: 2.88/0.77
Window screening: Interior blinds

Outer wall
U-value: 0.23
Thermal bridges: Good

Internal heating
Equipment: 300W
Persons: 2
Lighting: 136W

Occupancy
Percentage of
internal loads for
the energy calculation: 60%

18 www.swegon.com We reserve the right to alter specifications.


Swegon ESBO 160311

Office, 2 persons (airborne) continued

Ventilation
Supply and extract air in the room Ventilation unit with
rotary heat exchanger with 83% recovery of heating and
cooling energy.
No occupancy: 5 l/s
Occupancy, (min): 10 l/s
Occupancy, (max): 80 l/s
Infiltration: 0.1 Chge/h
Control: Supply air as a function of the
outdoor air
Supply air temperature: 20°C to 15°C

Hot tap water


Not included in the calculation

Heating
Source: District heating
Heating water, temp: 60-40°C

Cooling
Source: General chiller, average COP 3
Cooling water, temp: No water cooling

Distribution
Products: Recessed supply air diffuser,
ADAPT C 250

We reserve the right to alter specifications. www.swegon.com 19


Swegon ESBO 160311

Office, 2 persons (waterborne)


An office designed for 2 persons. The climate system
has individual control and comprises heating, cooling
and ventilation. The system solution is suitable for most
climate zones in world.

Temperature
Set point heating: 21°C (20°C for no occupancy)
Requirement 20°C as coldest
Set point cooling: 24°C (27°C for no occupancy)
Requirement 25°C as warmest

Geometry
Length: 4.2 m
Width: 3.6 m
Height: 2.7 m
Façade direction: South

Window
Area: 1.2 m2
U-/G-value: 2.88/0.77
Window screening: Interior blinds

Outer wall
U-value: 0.23
Thermal bridges: Good

Internal heating
Equipment: 300W
Persons: 2
Lighting: 136W

Occupancy
Percentage of internal loads for
the energy calculation: 60%

20 www.swegon.com We reserve the right to alter specifications.


Swegon ESBO 160311

Office, 2 persons (waterborne) continued

Ventilation
Supply and extract air in the room Ventilation unit with
rotary heat exchanger with 83% recovery of heating and
cooling energy.
Constant air flow 25 l/s
Infiltration: 0.1 Chge/h
Control: Supply air as a function of the
outdoor air
Supply air temperature: 20°C to 15°C

Hot tap water


Not included in the calculation

Heating
Source: District heating
Heating water, temp: 45-35°C

Cooling
Source: General chiller, average COP 3
Cooling water, temp: 14-17°C

Distribution
Products: Comfort module, PARASOL 600

We reserve the right to alter specifications. www.swegon.com 21


Swegon ESBO 160311

Conference room, 6 person (airborne)


A conference room designed for 6 persons. The climate
system has individual control and comprises ventilation
and cooling. The heating system is supplied by an outside
party but is integrated in the climate system’s control. The
system solution is suitable for most climate zones in world.

Temperature
Set point heating: 21°C (20°C for no occupancy)
Requirement 20°C as coldest
Set point cooling: 24°C (27°C for no occupancy)
Requirement 25°C as warmest
Geometry
Length: 4.2 m
Width: 2.4 m
Height: 2.7 m
Façade direction: South

Window
Area: 1.2 m2
U-/G-value: 2.88/0.77
Window screening: Interior blinds

Outer wall
U-value: 0.23
Thermal bridges: Good

Internal heating
Equipment: 250W
Persons: 6
Lighting: 70W

Occupancy
Percentage of internal loads for
the energy calculation: 60%

22 www.swegon.com We reserve the right to alter specifications.


Swegon ESBO 160311

Conference room, 6 person (airborne)


continued

Ventilation
Supply and extract air in the room Ventilation unit with
rotary heat exchanger with 83% recovery of heating and
cooling energy.
No occupancy: 5 l/s
Occupancy, (min): 10 l/s
Occupancy, (max): 100 l/s
Infiltration: 0.1 Chge/h
Control: Supply air as a function of the
outdoor air
Supply air temperature: 20°C to 15°C
CO2 control: Max 1000 ppm

Hot tap water


Not included in the calculation

Heating
Source: District heating
Heating water, temp: 60-40°C

Cooling
Source: General chiller, average COP 3
Cooling water, temp: No water cooling

Distribution
Products: Recessed supply air diffuser,
EAGLE C 250

DCV damper, ADAPT D 200

We reserve the right to alter specifications. www.swegon.com 23


Swegon ESBO 160311

Conference room, 6 person (waterborne)


A conference room designed for 6 persons. The climate
system has individual control and comprises heating,
cooling and ventilation. The system solution is suitable for
most climate zones in world.

Temperature
Set point heating: 21°C (20°C for no occupancy)
Requirement 20°C as coldest
Set point cooling: 24°C (27°C for no occupancy)
Requirement 25°C as warmest

Geometry
Length: 4.2 m
Width: 2.4 m
Height: 2.7 m
Façade direction: South

Window
Area: 1.2 m2
U-/G-value: 2.88/0.77
Window screening: Interior blinds

Outer wall
U-value: 0.23
Thermal bridges: Good

Internal heating
Equipment: 250W
Persons: 6
Lighting: 70W

Occupancy
Percentage of internal loads for
the energy calculation: 60%

24 www.swegon.com We reserve the right to alter specifications.


Swegon ESBO 160311

Conference room, 6 person (waterborne)


continued

Ventilation
Supply and extract air in the room Ventilation unit with
rotary heat exchanger with 83% recovery of heating and
cooling energy.
No occupancy: 5 l/s
Occupancy, (min): 10 l/s
Occupancy, (max): 45 l/s
Infiltration: 0.1 Chge/h
Control: Supply air as a function of the
outdoor air
Supply air temperature: 20°C to 15°C
CO2 control: Max 1000 ppm

Hot tap water


Not included in the calculation

Heating
Source: District heating
Heating water, temp: 45-35°C

Cooling
Source: General chiller, average COP 3
Cooling water, temp: 14-17°C

Distribution
Products: Comfort module, PARASOL 1200

DCV damper, ADAPT D 160

We reserve the right to alter specifications. www.swegon.com 25


Swegon ESBO 160311

Conference room, 12 persons (airborne)


A conference room designed for 12 persons. The climate
system has individual control and comprises ventilation
and cooling. The heating system is supplied by an outside
party but is integrated in the climate system’s control. The
system solution is suitable for most climate zones in world.

Temperature
Set point heating: 21°C (20°C for no occupancy)
Requirement 20°C as coldest
Set point cooling: 24°C (27°C for no occupancy)
Requirement 25°C as warmest
Geometry
Length: 4.2 m
Width: 6.0 m
Height: 2.7 m
Façade direction: South

Window
Area: 3.6 m2
U-/G-value: 2.88/0.77
Window screening: Interior blinds

Outer wall
U-value: 0.23
Thermal bridges: Good

Internal heating
Equipment: 250W
Persons: 12
Lighting: 176W

Occupancy
Percentage of internal loads for
the energy calculation: 60%

26 www.swegon.com We reserve the right to alter specifications.


Swegon ESBO 160311

Conference room, 12 persons (airborne)


continued

Ventilation
Supply and extract air in the room Ventilation unit with
rotary heat exchanger with 83% recovery of heating and
cooling energy.
No occupancy: 10 l/s
Occupancy, (min): 40 l/s
Occupancy, (max): 200 l/s
Infiltration: 0.1 Chge/h
Control: Supply air as a function of the
outdoor air
Supply air temperature: 20°C to 15°C
CO2 control: Max 1000 ppm

Hot tap water


Not included in the calculation

Heating
Source: District heating
Heating water, temp: 60-40°C

Cooling
Source: General chiller, average COP 3
Cooling water, temp: No water cooling

Distribution
Products: Recessed supply air diffuser,
2 x EAGLE C 250

DCV damper, ADAPT D 250

We reserve the right to alter specifications. www.swegon.com 27


Swegon ESBO 160311

Conference room, 12 persons (waterborne)


A conference room designed for 12 persons. The climate
system has individual control and comprises heating,
cooling and ventilation. The system solution is suitable for
most climate zones in world.

Temperature
Set point heating: 21°C (20°C for no occupancy)
Requirement 20°C as coldest
Set point cooling: 24°C (27°C for no occupancy)
Requirement 25°C as warmest

Geometry
Length: 4.2 m
Width: 6.0 m
Height: 2.7 m
Façade direction: South

Window
Area: 3.6 m2
U-/G-value: 2.88/0.77
Window screening: Interior blinds

Outer wall
U-value: 0.23
Thermal bridges: Good

Internal heating
Equipment: 250W
Persons: 12
Lighting: 176W

Occupancy
Percentage of internal loads for
the energy calculation: 60%

28 www.swegon.com We reserve the right to alter specifications.


Swegon ESBO 160311

Conference room, 12 persons (waterborne)


continued

Ventilation
Supply and extract air in the room Ventilation unit with
rotary heat exchanger with 83% recovery of heating and
cooling energy.
No occupancy: 5 l/s
Occupancy, (min): 10 l/s
Occupancy, (max): 94 l/s
Infiltration: 0.1 Chge/h
Control: Supply air as a function of the
outdoor air
Supply air temperature: 20°C to 15°C
CO2 control: Max 1000 ppm

Hot tap water


Not included in the calculation

Heating
Source: District heating
Heating water, temp: 45-35°C

Cooling
Source: General chiller, average COP 3
Cooling water, temp: 14-17°C

Distribution
Products: Comfort module,
2 x PARASOL 1200

DCV damper, ADAPT D 200

We reserve the right to alter specifications. www.swegon.com 29