Professional Documents
Culture Documents
Operation Manual
for
ALM 35
Portable Energy & Harmonics Analyser
Thank you for purchasing the ALM 35 Power & Harmonics analyser.
To obtain the best service from your unit:
Read these operating instructions carefully,
Comply with the precautions for use.
Meaning of the symbols used on the unit:
The CE marking guarantees conformity with European directives and with regulations covering EMC.
2
MEASUREMENT CATEGORIES
Definition of measurement categories according to the IEC standard 61010-1:
CAT I: Measurement category I corresponds to measurements taken on circuits not directly connected to the network.
CAT II: Measurement category II corresponds to measurements taken on circuits directly connected to the installation.
Example: measurement for electrodomestic units, portable tools and analogue devices
CAT III: Measurement category III corresponds to measurements on building installations.
Example: measurement on distribution panels, cabling, etc.
CAT IV: Measurement category IV corresponds to measurements taken at the source of low-voltage installations
Example: metering and measurements on overvoltage protection devices...
GUARANTEE
Our guarantee is applicable, unless otherwise stated, for one year following the date of supply of the equipment.
GENERAL INFORMATION
Manaco EnerGy Solutions Pvt Ltd. (MES) has a strategic alliance with Alacrity Electronics Ltd. for promoting KRYKARD
range of Load Managers and Energy Management Solutions.
.
KRYKARD and KRYKARD Load Manager are registered trade marks of Alacrity.
.
The KRYKARD Load Manager ALM 35 is marketed by MES, under an exclusive arrangement with Chauvin Arnoux, France.
3
CONTENTS
1. INTRODUCTION .................................................... 6 8.1 Available submenus............................................ 41
2. PACKAGING.......................................................... 6 8.2 Alarm mode configuration........................ 41
8.3 Programming an alarm campaign ........... 42
3. PRESENTATION ................................................... 7
8.4 Displaying alarm log ................................ 42
3.1 Overview .............................................................. 7
3.2 On/Off key ............................................................ 7 8.5 Deleting alarm log ................................... 43
3.3 Display screen...................................................... 7
3.4 Keypad keys......................................................... 8 9. TREND MODE KEY .................................... 44
3.5 Connectors........................................................... 9 9.1 Available sub-menus .......................................... 44
3.6 Power ................................................................... 9
3.7 The stand ........................................................... 10 9.2 Programming and initiating recording...... 44
3.8 Summary of functions......................................... 10 9.3 Trend mode configuration........................ 45
3.9 Abbreviations...................................................... 10 9.4 Displaying recording list........................... 46
9.5 Deleting recordings................................... 47
4. CONFIGURATION KEY ........................ 12
4.1 Available sub-menus .......................................... 12 10. POWER AND ENERGY KEY ...................... 48
4.2 Display language................................................ 12
10.1 Available sub-menus .......................................... 48
4.3 Date/Time..................................................... 12
10.2 Energy consumed .................................... 48
4.4 Contrast/Brightness ...................................... 12
10.3 Energy generated..................................... 49
4.5 Colours ........................................................ 13
10.4 Start of energy metering .......................... 50
4.6 Calculation methods ................................... 13
10.5 Stop of energy metering........................... 50
4.7 Connection ................................................... 13
10.6 Zero resets of energy metering ............... 50
4.8 Current sensor......................................... 13
4.9 Trend mode ............................................... 14 11. SCREEN SNAPSHOT KEY ........................... 51
4.10 Alarm Mode .............................................. 15 11.1 Screen shots....................................................... 51
11.2 Handling of screen snapshots ............................ 51
4.11 Deleting data............................................... 16
Information ................................................... 16 12. HELP KEY ............................................................ 53
4.12
13. USE ...................................................................... 54
5. KEY WAVEFORM CAPTURE..................... 17
13.1 Start-up............................................................... 54
5.1 Available sub-modes .......................................... 17 13.2 Configuration of the ALM 35 ............................... 54
5.2 Transient mode ......................................... 17 13.3 Installation of leads ............................................. 55
5.3 Inrush current mode .................................. 20 13.4 Wave shape capture ................................... 55
13.5 Display of harmonics ................................... 55
6. HARMONICS KEY ...................................... 24 13.6 Measuring wave shapes ............................. 55
13.7 Alarm detection ........................................... 56
6.1 Available sub-menus .......................................... 24
13.8 Recording .................................................... 56
6.2 Single voltage ........................................ 24 13.9 Measurement of energy .............................. 56
6.3 Current ................................................... 26 13.10 Transfer of data to the PC ............................ 56
13.11 Deleting data ................................................ 56
6.4 Apparent power...................................... 27 13.12 Turning the ALM 35 off ................................. 56
6.5 Composite voltage .................................. 28 13.13 Supply of the ALM 35 ................................... 56
6.6 Expert mode .............................................. 29 14. MAINTENANCE ................................................... 57
14.1 Important recommendation................................. 57
7. WAVEFORM KEY ....................................... 31
14.2 Battery recharge ................................................. 57
7.1 Available sub-menus .......................................... 31 14.3 Cleaning the casing ............................................ 57
7.2 Measurement of true effective value ........ 31 14.4 Replacing the screen film ................................... 57
14.5 Metrological verification ...................................... 57
7.3 Measurement of total harmonic distortion33
14.6 Repairs ............................................................... 57
7.4 Measurement of the peak factor ............ 34 14.7 Updating of the internal software ........................ 57
7.5 Measurement of extreme and average 14.8 Sensors .............................................................. 57
voltage and current values ......................................... 36
15. GENERAL SPECIFICATIONS ............................. 58
7.6 Simultaneous display................................ 38
15.1 Casing ................................................................ 58
7.7 Display of Fresnel diagram...................... 39
15.2 Power supply ...................................................... 58
15.3 Range for use ..................................................... 58
8. ALARM MODE KEY.................................... 41 15.4 User safety ......................................................... 59
16. FUNCTIONAL CHARACTERISTICS ................... 60
16.1 Reference Conditions......................................... 60
16.2 Electrical characteristics..................................... 60
17. APPENDICES ...................................................... 67
17.1 Mathematical formulae ....................................... 67
17.2 Hysteresis........................................................... 69
17.3 Minimum scale values for waveforms and
minimum RMS values ................................................ 70
17.4 Diagram of the 4 quadrants................................ 70
17.5 Mechanism for triggering transient sensors........ 71
17.6 Sensor conditions in Ringing Current mode. ...... 71
17.7 Glossary ............................................................. 72
18. TO ORDER........................................................... 73
18.1 ALM 35 power analyser ..................................... 73
18.2 Accessories ........................................................ 73
18.3 Spare parts......................................................... 73
5
1. INTRODUCTION
The ALM 35 Portable Analyser is a three-phase AC+DC Voltage and current minimal and maximal half-period
1000 VRMS category III or 600 VRMS category IV values
(IEC 61010-1) graphic display network analyser. Peak values for voltages and current (neutral
included)
It has a triple role. It: Frequency of 50 Hz and 60 Hz networks
measures electric distribution network values, powers Current and voltage peak factor (excluding neutral)
and disruptions Calculation of the K factor (KF) (application to
provides an instant image of the main characteristics transformers in the presence of harmonic currents)
of a triple phase network Distortion factor (DF) for current and voltage
monitors variations i the different parameters over (excluding neutral)
time Global harmonics rate for current and voltage
The uncertainty of the ALM 35 is better than 1% (error (excluding neutral).
due to current sensors not included). In addition, it Active, reactive (capacitive and inductive) and
provides great flexibility with a choice of different apparent power by phase and cumulative (excluding
sensors to measure from hundreds of milliamps neutral).
(MN93A) to several kiloamps (AmpFLEX™). Power factors (PF) and displacement power factors
(DPF) (excluding neutral).
The unit is compact and shock resistant. The ergonomy Short-term voltage flicker (PST) (excluding neutral).
and simplicity of its user interface make it easy and Active, reactive (capacitive and inductive) and
intuitive to use. apparent (excluding neutral) energy.
The ALM 35 is aimed at technicians and engineers in Harmonics and voltages (excluding neutral) up to 50:
installation and electric network control and RMS value, percentages in relation to fundamental,
maintenance teams. minimum and maximum and harmonics sequences.
Harmonics for apparent power up to rank 50: value,
The main measurements made are: percentage in relation to the fundamental, minimum
The values of alternative voltages up to 1000 V and maximum.
between terminals Motor start-up currents
The values of alternative currents up to 6500 amps
(neutral included)
Continuous value of voltages and currents (neutral
included)
2. PACKAGING
Verification certificate 1
Safety record 1
6
3. PRESENTATION
8
Figure1: ALM 35 general view
7
3.3.2 Icons
The display uses the following icons: 3.4 Keypad keys
Icon Designation
3.4.1 Function keys (yellow keys)
Single voltage mode These 6 keys activate the function or told represented
by the corresponding icon on the screen (See para
Simple current mode 3.3.2)
Power mode 3.4.2 Navigation keys
Compound voltage mode A block of 4 direction keys, a validation key and a return
key enable navigation through the menus
Zoom in
Item Function
Zoom out
Up direction or navigation key
<> Left/right key prompt
<>
Recording mode
Confirms the selection
Recording display and selection mode
Return key: return to choice of
OK Validation prompt measurement to view
Shutdown function in progress prompt
3.4.3 Mode keys
Display current values and their These enable access to specific modes:
extremes
Item Mode Page
Display all voltage and current
measurements simultaneously (RMS, Display transients: view waveforms, 17
DC, THD, CF, PST, KF, DF). motor start-up currents, cut-offs
Display of Fresnel diagram of signals. Display curves linked to harmonics: 24
representation of voltage
Display of energy consumed. harmonics rates, currents and
powers range by range,
Display of energy generated. determination of harmonics
currents produced by non-linear
Page screen 1 of the help function charges, analysis of problems
engendered by harmonics
Page screen 2 of the help function according to their range (heating of
neutrals, conductors, motors...)
Page screen 1 of trend mode
configuration. Display of voltage and current 31
waveforms, display of minimum
Page screen 2 of trend mode and maximum values, summary
configuration. tables, determination of phase
rotation
Page screen 3 of trend mode
configuration.
Continuation of the table on the next page.
Page screen 4 of trend mode
configuration.
8
Viewing alarms: list of alarms 41
recorded according to thresholds
programmed during configurations,
a recording of network cutouts with
half-period resolution (VRMS, ARMS,
URMS), determination of energy 1
over-consumption, control of
compliance with energy supply
quality contract.
2
Trend mode: recording of paralysis 43
selected in the Configuration menu
1 4 current input connectors for Press to confirm. If you do not reconnect the ALM
amperemetric senses (MN clamp, C 35 to the mains, one minute after this message.
clamp, AmpFLEX™, PAC clamp, etc.). 3.6.2 Battery life
2 5 voltage input connectors Battery life is 10 hours when the battery delivered with
the unit is completely charged. If no recording is in
3.5.2 Side connectors progress, battery life is then 35 hours stop
Located on the right side of the ALM 35, these 3.6.3 Battery recharge
connectors are used as follows: See also paragraph 14.2, page 57. The battery
recharged using the mains supply delivered with the
unit. It connects to the ALM 35 by the jack socket
(Figure 4, item 2).
9
Only not use the mains supply provided with the unit. Global harmonics rate for current and voltage
This supplier is specific and maintains electric safety. (excluding neutral).
For completely empty accumulators, the charge last Active, reactive (capacitive and inductive) and
about five hours. As soon as the battery is recharged, apparent power by phase and cumulative (excluding
the unit uses the mains sector prior without discharging neutral).
the battery. Power factors (PF) and displacement power factors
(DPF) (excluding neutral).
3.6.4 Changing the battery
Short-term flicker (PST) (excluding neutral).
Disconnect the ALM 35 from the mains supply and the Active, reactive (capacitive and inductive) and
network measured to change the battery. The unit must apparent (excluding neutral) energy.
have no connection. The ALM 35 maintains the date Harmonics and voltages (excluding neutral) up to 50:
and time for about 24 hours. RMS value, percentages in relation to fundamental,
minimum and maximum and harmonics sequences.
3.6.5 The battery Harmonics for apparent power up to rank 50: value,
The ALM 35 is powered by a specific 8-element battery percentage in relation to the fundamental, minimum
(see below, item 2) minimum capacity 4000 mAh. and maximum.
Motor start-up currents
Selection of the TI (or TC) report for MN93A (caliber
5 A) clamps and the 5 A adapter.
Automatic recognition of types of current sensor
(every second)
3.8.2 Display function
1
Display of waveforms (voltages and currents)
“Cut-in current” function: displays the parameters
used in the study of a motor start-up.
- Instantaneous value of the current at the instant
2 pointed to by the cursor.
- Maximum instantaneous value of the current
(over the entire start-up period).
- RMS value of the half-period (or lobe) of the
current (excluding neutral) on which the cursor is
positioned
Figure 5 : Battery access flap - Maximum half-period RMS value of the current
(over the entire start-up period).
3.6.6 Mains operation - Motor start-up time
The battery is not essential when the unit is running on Screen captures (50 maximum)
mains supply. However, if the mains power is cut off, Transient functions. Detection and recording of
data may be lost during the recording process, for transcients (up to 300) for a period and at a date
example. chosen (programming start and end of the search for
transcients). Recording of 4 complete periods (1
The On/Off button is on continuously (green LED) when before the event triggering the transient and 3
the mains power is active. afterwards) on the acquiring paths.
Data logging function (2Gb memory with date and
time and programming the start and end of recording
3.7 The stand – 100 records maximum). Representation in
histogrammes or curves of the average value of many
A retractable stand (Figure 5, item1) located on the parameters according to time.
back of the ALM 35 keeps the unit at a 53° angl e. Alarm function. Listing of alarms recorded (log of
10000 alarms maximum) according to thresholds
programmed in the configuration menu. Programming
3.8 Summary of functions the start and end of an alarm monitoring session.
3.8.3 Configuration function
3.8.1 Measurement functions
Date and time settings
The values of alternative voltages up to 1000 V
Screen brightness and contrast settings
between terminals of any voltage.
Choice of curve colours
The values of alternative currents up to 6500 amps
Choice of reactive power and energy calculation
(neutral included)
mode (with or without harmonics)
Continuous value of voltages and currents (neutral
Choice of connection (one phase, two phase, three
included)
phase with or without neutral).
Voltage and current minimal and maximal half-period
Configuration of records and alarms
values
(Total or partial) data removal
Peak values for voltages and current (neutral
Display software and hardware identifiers
included)
Choice of language
Frequency of 50 Hz and 60 Hz networks
Current and voltage peak factor (excluding neutral)
Calculation of the K factor (KF) (application to
transformers in the presence of harmonic currents)
3.9 Abbreviations
Distortion factor (DF) for current and voltage
(excluding neutral) Meaning of symbols and abbreviations used:
10
Unit Designation Uh Compound voltage harmonic
−{}−−
{}−−{}
−−{} Sum of the values Vcf Voltage peak factor (compound if 3φ).
−Σ
Vrms True effective phase voltage
L Phases (Line)
Vthd Full harmonic distortion of line-to-neutral
% Percentage voltage.
KF See Akf.
PF Power factor.
t Time factor
Tan Tangent.
11
4. CONFIGURATION KEY
4.3 Date/Time
This parameter defines the system date and time. The
display is as follows:
1 SU00
Colours Definition of voltage curve 4.5 The Date/Time field is underlined in yellow
and current curve colours To change the date/time, press . The arrows
show the value that can be changed. To change a
Calculation Choice of reactive 4.6 value, press or .
method parameters (with or To move from one field to another, press . To
without harmonics) confirm, press .
Connection Choice of typeof 4.7 To modify the dating system, position the yellow
connection to the network cursor on the field with keys or . Press . The
(attention: certain arrows show the value that can be changed.
calculations depend of the Select DD/MM/YY or MM/DD/YY, press then
connection). confirm by pressing .
Current sensor Choice of sensors (clamp 4.8 To modify the dating system, position the yellow
MN, C, PAC, AmpFlex™, cursor on the field with keys or been
adapter). confirmed by pressing .. The arrows show the
value that can be changed.
Trend mode Choice of paramters to 4.9 To select the 12-hour or 24-hour clock 12/24 press
record for . .
then confirm by pressing
Alarm Mode Definition of alarms used 4.10 Note: 12/24 : display the time in 24-hour format.
by .
AM/PM: display the time in 12-hour format. The
time is followed by AM or PM.
To return to the Configuration menu, press .
4.4 Contrast/Brightness
Defines the contrast and brightness of the display. The
display is as follows:
12
4.6 Calculation methods
Defines the use or non-use of harmonics in calculating
reactive parameters (powers and energies).
SU
SUCOL
The selected field is highlighted in yellow. Figure 11: the Connection menu
To select the colour of the voltage and current curves,
To configure the type of connection, proceed as follows:
press .
1. Select One Phase, Two Phase, 3 or 4 lead Three
To move to the next field, press .
Phase or 5 lead Three Phase by pressing and
To select the curve colour, press .
.
To return to the Configuration menu, press .
2. Validate by pressing (this validation is
compulsory for the configuration application). Return
to the Configuration menu is immediate.
13
SUCC 1 SUMT
Figure 12: Current sensor menu Figure 13: In this example, the Urms values are
recorded for configuration 1
The possibilities are:
Clamp MN93: 200A. Clamp MN93A: 100 A or 5 A. To define configuration 1, press the yellow key on the
Clamp C193: 1000 A. Clamp PAC93: 1000 A keypad corresponding to the icon . The icon
AmpFLEX™ A193: 6500 A. Mini-AmpFLEX MA193: appears on a yellow background.
6500 A.
Three phase adapter: 5 A. To select the values, move the yellow cursor with the
and keys. Press to validate. The red
Caution: if a Clamp MN93A calibre 5 A or an Adapter is item confirms validation.
used, it is configured as follows:
The recordable values are:
Definition of the transformation ratio.
- For a 5A clamp: to configure the primary circuit Unit Designation
current transformation ratio (1 A to 2999
Urms Efficient line voltage (2φ, 3φ).
A)/secondary circuit current (1 A or 5 A), press
. To select the fields, use the keys. Vrms Efficient line-to-neutral voltage.
To select the values, use the keys. Proceed
in the same manner for primary and secondary Arms Efficient current.
circuit currents.
- Adapter: to configure the primary circuit current W Active power.
transformation ratio (1 A to 2999 A)/secondary
PF Power factor.
circuit current (1 A or 5 A), press . To select
the fields, use the keys. Uthd Harmonic distortion of line voltage (2φ, 3φ).
To select the values, use the keys. Proceed
in the same manner for primary and secondary Vthd Full harmonic distortion of line-to-neutral
circuit currents. voltage.
To validate, press (this validation is compulsory for Athd Full harmonic distortion of current.
the configuration application).
VAR Reactive power.
To return to the Configuration menu, press .
DPF Displacement factor.
KF K factor.
14
Specific features for the last two lines
These are set out below:
Press to switch to the following field. To select the values (Vah, Ah, Uh, etc. See table in
paragraph 4.9), press then confirm with .
To select the starting harmonic range: the line is The field is highlighted in yellow.
underlined in yellow, press . Arrows appear.
Select the rank from which harmonics shall be To navigate horizontally in the fields, use the keys
recorded via , then validate via . then confirm pressing . Arrows appear. Enter
the values then confirm pressing . Do the
Press to switch to the following field. same for all values to be entered in fields.
To select the last harmonic: The second field For each alarm to define, select:
(above or equal to the start harmonic rank) is
highlighted in yellow. Press . Select the last - The type of alarm (Vah, Ah, Uh, Vh, Tan, PF,
harmonic rank to be recorded via , then validate DPF, VA, VAR, W, Athd, Uthd, Vthd, KF, Hz,
via . Aunb, Vunb, Vrms, Acf, Ucf, Vcf, PST, Arms
Urms and Vrms – see the table of abbreviations
Press to switch to the following field. in paragraph 3.9).
Odd harmonics only: to select or deselect a field, press - The harmonics range (between zero and 50 for
The red item shows your selection: Vah, Ah, Uh and Vh).
- selected, only odd harmonics between the two - The alarm filter (3L: 3 individually monitored
ranks of harmonics specified in the previous phases or N: monitoring neutral or Sigma/2 or
points shall be recorded. Sigma/3 or Sigma).
- Not selected, all harmonics (even and odd) - The meaning of the alarm (> or < for Arms,
between the two ranks of harmonics specified in Urms, Vrms, Hz only, otherwise the direction is
the previous points shall be recorded. unique).
To return to the Configuration menu, press . - The threshold for triggering the alarm (setting of
Proceed in the same manner to defined the other the alarm to 10 possible in the following cases:
configurations. W, VAR and VA).
- The minimum duration for exceeding the alarm
validation threshold (in minutes, seconds or only
4.10 Alarm Mode for Vrms, Urms and Arms in hundredths of
seconds).
This screen defines alarms used by the Alarm Mode
- The hysteresis value (corresponds to the
(see chapter 8, page 41). You can configure 40
percentage added or taken away from the alarm
types of alarm.
threshold chosen that will stop the alarm in the
event of overrun - Value 1, 2, 5 or 10% - See
para 17.2).
- Activating the alarm (read item) or deactivating it
(see below).
To activate the configured alarm, position the yellow
cursor on the first column of the list using the key
(Figure 15, item 1) and press . Activation is marked
by the red item The alarm can be triggered.
To display in the alarm screen pages, press the
yellow buttons corresponding to the icons
(Figure 15, item2).
15
To return to the Configuration menu, press . 4.12 Information
This screen displays the unit serial number, the
4.11 Deleting data firmware version, the loader version, the basic card
version, the CPLD (Complex Programmable Logic
Partially or totally deletes the data recorded in the unit Device) version.
(configurations, transients, motor startup, alarms and
detected, screen captures, records)
SUA
Figure 16: Deleting data menu To return to the Configuration menu, press .
To delete partially:
1. Select the parameters that you want to delete
pressing the keys. The selected field is
highlighted in yellow.
2. Confirm the selection by pressing . The red item
confirms validation.
Note: If the Configuration parameter is selected, the
"after deleting the configuration, the unit will be turned
off" information appears on the screen
3. Press the yellow button on the keypad (Figure 16,
item1) corresponding to the icon , then press
to confirm. The deletion has been completed.
To return to the Configuration menu, press .
To delete all:
1. To select all parameters, press the yellow key on
the keypad corresponding to the icon . The
selection is identified with the red item The "after
deleting the configuration, the unit will be turned off"
information is displayed.
Note: If the Configuration parameter is selected, the
"after deleting the configuration, the unit will be turned
off" information appears on the screen
2. Press the yellow button on the keypad (Figure 16,
item1) corresponding to the icon , then press
to confirm. The deletion has been completed.
To untick the selection 1, press the yellow key on the
keypad corresponding to the icon .
To return to the Configuration menu, press .
16
5. KEY WAVEFORM CAPTURE
WFC01
1
6 7 8
2 Figure 19: the Programming a search screen in
Transient mode.
Item Function
WFC00
17
1 2 3 4 appear. Choose the value with the keys
and then confirm by pressing .
Proceed in the same way for the Current threshold,
Number and Series name fields.
5.2.1.2 STAGE 2: start of programming
5
To start programming a search between the start and
end times which you have defined press the yellow
6 keypad key for the OK icon.
The OK icon disappears and the icon appears
7 instead.
18
1 2 3
Item Function
1 Reminder of the mode used : zoom in. To zoom in press the yellow
keypad key for the icon.
2 Display of sub-mode used.
3 Memory indicator. The black bar shows used 3. Select the graphs to be displayed by pressing the
memory; the white bar shows available keys. Le champ sélectionné est surligné en
memory. jaune (Figure 22, item1). Confirm by pressing .
1 WFC05
Figure 22: example of display of transients in the form 3. Press to confirm the deletion.
of graphs with a 5-wire triphase connection
Note: The icons (Figure 23, item 1) let you
browse through the previous and next screens. Press
the yellow keys corresponding to these icons to display
the pages.
To leave this screen without deleting press one of the
mode keys ( ).
To return to the Waveform capture screen, press the
key.
19
5.3 Inrush current mode 5.3.1.1 STAGE 1: configuration of characteristics
Perform the following:
This mode enables the waveform of the current to be
1. Select the Activation threshold field using the
recorded, and the capture made to be displayed and
keys. The selected field is highlighted in yellow.
deleted. In capture display mode, two sub-menus,
Press to enter the type of values. The
and , are available (See para 5.3.2). The ALM
arrows appear in the Activation threshold field.
35 keeps in memory only a single current waveform
capture. Press to increment or decrement a value and
press to switch to the following data.
Note: when Inrush current mode is started the
displayed screen will depend on the following 2. Press to confirm programming of the activation
conditions: threshold.
If … then … Proceed in the same manner for the Activation filter,
no capture has been the Programming the Hysteresis and Start fields.
made capture screen is Note: for more information on the hysteresis, refer to
displayed. section 17.2.
a capture has been the Characteristics of the 5.3.1.2 STAGE 2: starting the capture
made capture screen is To start programming the capture at the start date and
displayed. time you have defined press the yellow keypad key for
the OK icon.
5.3.1 Programming the capture The OK icon disappears and the icon appears
To program the capture of the current's waveform instead.
proceed as follows: The message capture pending is displayed until the
start time is reached and the icon flashes in the
Select the submenu by pressing the icon’s
yellow key. The Programming the capture screen is screen's upper display bar.
displayed. When the activation conditions are met and the start
1 2 3 4 time is reached, the message Capture pending is
displayed and the memory occupation indicator
appears in the upper part of the screen as follows:
20
5.3.3.1 The RMS display screen in 3A
Information is displayed as follows:
1 2 3 4
WFI01
1 2
Figure 25: the Characteristics of the capture screen 7
WFI02
Item Function See
para. 8 9 10
1 Display in RMS mode. 5.3.3 Figure 26: the RMS display screen in 3A
2 Display in PEAK mode. 5.3.4 Item Function
21
5.3.3.2 The RMS display screen in A2 5.3.4.1 The PEAK display screen in 3A
Information is displayed as follows: The screen of 3A filter appears only when the
waveforms are displayed.
1 Information is displayed as follows:
1 2 3 4
2 6
WFI03
3 4
Figure 27: the RMS display screen in A2 7
WFI04
Item Function
8 9 10
1 MAX: maximum half-period RMS value of the
start-up. Figure 28: the PEAK display screen in 3A
: indicator of number attributed to the Item Function
displayed graph.
1 Display of mode used
A: value of the measured current.
2 Display of sub-mode used
2 t: temporal position relative to the cursor (t=0
corresponds to the start of the start-up). 3 Current date and time.
A2: instantaneous value of current 1 at the 4 Battery charge level.
cursor position (item 3).
5 MAX: maximum half-period RMS value of the
3 Instantaneous measurement cursor at a point start-up.
in the graph. Use the keys to move the
cursor. : indicator of number attributed to the
displayed graph.
4 : zoom out. To zoom in press the
A: value of the measured current.
yellow keypad key for the icon.
6 Selection of graphs to be displayed:
: zoom in. To zoom in press the yellow
keypad key for the icon. -3 A: displays the 3 currents and the neutral
current during the transient.
Note: Filters A1 and A3 display the record of the trend - A1, A2 or A3: displays the current
of the half-period true effective value of the current over successively in phases 1, 2 and 3.
phases 1 and 3. The screen is identical to the one
7 t: temporal position relative to the cursor (t=0
displayed for filter A2.
corresponds to the start of the start-up).
5.3.4 Instantaneous value of inrush current
A1, A2, A3: instantaneous values of currents
This mode enables the envelope of the inrush current to 1, 2 and 3 at the position of the cursor (item
be displayed. 9).
22
5.3.4.2 The PEAK display screen in A3
Information is displayed as follows:
2
WFI05
3 4
Figure 29: the PEAK display screen in A3
Item Function
23
6. HARMONICS KEY
MHA00
1 2 3 4 5 6
Figure 30: screen of Harmonics mode
MHA01
5 zoom out. To zoom in press the - This information is relative to the harmonic
yellow keypad key for the icon. under the cursor (Figure 31, item 7).
6 zoom in. To zoom in press the - Vh 05: number of harmonic.
yellow keypad key for the icon.
% : rate of harmonic relative to the
7 Select filters and expert mode. Use - fundamental value.
the keys to select the display. V: effective voltage of the harmonic in
question.
+000°: phase displacement relative to
fundamental value (rank 1).
24
6 Item Function
Rank (1 to 25): rank of harmonics. When the +000°: phase displacement relative to
cursor exceeds rank 25 range 26 to 50 fundamental value (rank 1).
appears. max – min: maximum and minimum
indicators of the rate of harmonics in question
7 Harmonic ranks selection cursor. Use the (reset whenever the harmonic number is
keys to move the cursor. changed).
8 Display of expert mode (triphase connection THD: total harmonic distortion.
only - See para 6.6) of the 3 x 3L phases, or
of L1, L2 and L3 (*). To select the display 2
press the keys.
25
6.3 Current 7 Harmonic ranks selection cursor. Use the
keys to move the cursor.
This sub-menu displays the harmonics of the current.
8 Display of expert mode (triphase connection
6.3.1 The current harmonics display screen in 3L only - See para 6.6) of the 3 x 3L phases, or
The displayed information is read as follows: of L1, L2 and L3 (*). To select the display
press the keys.
1 2 3 4 5
(*) With a single-phase connection this display is not
available. With a diphase connection the available
information is: 2L, L1 and L2.
6.3.2 The current harmonics display screen in L1
The displayed information is read as follows:
1
MHA03
6 7 8
Figure 33: example of display of harmonics of current
(harmonic n° 5: Ah05) in 3L
Item Function
2 Instantaneous frequency. 2 3 4
Item Function
This information is relative to the harmonic
under the cursor (Figure 33, item 7). 1
26
2 Item Function
2 Instantaneous frequency.
27
6.4.1.1 The display screen of the apparent power
harmonics in L1 3 Harmonic ranks selection cursor. Use the
keys to move the cursor.
The information is:
1 4 Display of expert mode (triphase connection
only - See para 6.6) of the 3 x 3L phases, or
of L1, L2 and L3 (*). To select the display
press the keys.
Item
2 Instantaneous frequency.
Rank (1 to 25): rank of harmonics. When the v: effective voltage of the harmonic in
cursor exceeds rank 25 range 26 to 50 question.
appears. +000° : phase displacement relative to the
fundamental harmonic (rank 1).
Display of energy consumed.
Continuation of the table on the next page.
28
4 Current date and time. Item Function
(*) With a single-phase connection this display is not The horizontal axis indicates the ranks of the
available. With a diphase connection the available harmonics (uneven marking).
information is: 2L, L1 and L2.
Display of the level of the harmonics as a
6.5.2 The display screen of the line voltage percentage relative to the fundamental value
harmonics in L1 (rank 1).
Information is displayed as follows: DC rank: direct component.
1 Rank (1 to 25): rank of harmonics. When the
cursor exceeds rank 25 range 26 to 50
appears.
MHA08
6.6 Expert mode
2 3 4
This mode is available with a triphase connection only.
Figure 38: example of display of harmonics of line It enables the influence of the harmonics on the heating
voltage (harmonic n° 03: Uh03) in L1 of the neutral or on the rotating machines to be
displayed. To display expert mode press the keys
of the keypad. The selection is underlined in yellow and
the screen simultaneously displays the expert mode.
29
6.6.1 The screen displaying expert mode
for phase voltage
This sub-menu displays the influence of the harmonics
of the phase voltage on the heating of the neutral or on
the rotating machines.
Information is displayed as follows:
1 2 3
MHA09
4
Figure 39: the expert mode screen for phase voltage
Item Function
MHA10
4
Figure 40: the expert mode screen for current
30
7. WAVEFORM KEY
This key enables the current and voltage graphs to be • Single-phase: no choice (L1)
displayed, together with the values measured and • Diphase: 2V, 2A, L1, L2
calculated from the voltages and currents (except for • Triphase 3 or 4 wires: 3U, 3V, 3A, L1, L2, L3
power, energy and harmonics). • Triphase 5 wires:
- For , and : 3U, 3V, 3A, L1, L2
and L3
7.1 Available sub-menus - For , and : 3U, 4V, 4A, L1, L2, L3
and N
Submenus are listed on the screen below and
individually processed in the following paragraphs. The screen captures shown as examples are those
obtained with a triphase 5-wire connection.
The measurement type is selected using the yellow
keys of the keypad under the screen. 7.2.1 The RMS display screen in 3U
This screen displays the three line voltages of a
triphase system.
Information is displayed as follows:
1 2 3 4 5
WF00
1 2 3 4 5 6
Figure 41: Waveform mode screen
para.
6 7 8 9
1 Measurement of the true effective 7.2 Figure 42: the RMS display screen in 3U
value (current or voltage)
Item Function
2 Measurement of total harmonic 7.3
distortion. 1 Reminder of the mode used
3 Measurement of the peak factor 7.4 2 Instantaneous frequency of network.
(current or voltage).
3 Effective values of line voltages.
4 Display of maximum, average and 7.5
minimum values (current, voltage 4 Current date and time.
and current and voltage peak).
5 Battery charge level.
5 Simultaneous display of all voltage 7.6
and current measurements (RMS, 6 Axis of voltage values with automatic scaling.
DC, THD, DF, CF, PST).
7 Instantaneous value cursor. To move the
6 Display of Fresnel diagram of 7.7 cursor use the keys.
signals.
8 Display of the waveforms of the line voltage.
7 Select filters and expert mode. Use -
the keys to select the display. Continuation of the table on the next page.
31
7.2.3 The RMS display screen in 4A
Instantaneous value of the signals at the
intersection of the cursor (Figure 42, item 7) This screen displays the three phase currents and the
9 and of the graphs. neutral current of a triphase system.
t: time relative to the start of the period The displayed information is read as follows:
(expressed in milliseconds).
U1: instantaneous value of the line voltage
between phases 1 and 2 (U12).
U2: instantaneous value of the line voltage
between phases 2 and 3 (U23).
U3: instantaneous value of the line voltage
between phases 3 and 1 (U31).
Item Function
4 Instantaneous values of the signals at the 7.2.4 The RMS display screen for neutral
intersection of the cursor (above, item 3) and
of the graphs. This screen displays the neutral voltage relative to earth
and the current of the neutral.
t: time relative to the start of the period
(expressed in milliseconds).
V1: instantaneous value of the phase voltage
of graph 1.
V2: instantaneous value of the phase voltage
of graph 2.
V3: instantaneous value of the phase voltage
of graph 3.
VN: instantaneous value of neutral.
32
The displayed information is read as follows: The displayed information is read as follows:
1 2 3 1 2 3 4 5
WF04 WF05*
6 7 8 9
4 5 Figure 46: the THD display screen in 3U
Figure 45: the RMS display screen for neutral
Item Function
Item Function
1 Reminder of the mode used
1 Axis of voltage values of current and of
voltage with automatic scaling. 2 Harmonic distortion rate for each graph.
33
7.3.2 The THD display screen in 3V The displayed information is read as follows:
This screen displays the waveforms of a period of the 1 2
phase voltages and the total harmonic distortion rates.
The displayed information is read as follows:
1 2
WF07*
3 4
Figure 48: the THD display screen in 3A
CW07*
Item Function
3 4
Figure 47: the THD display screen in 3V 1 Axis of current values with automatic scaling.
34
The displayed information is read as follows: The displayed information is read as follows:
1 2 3 4 5 1
WF08 WF09
6 7 8 9 2 3 4
Figure 49: the CF display screen in 3U Figure 50: the display screen in 3V
2 Peak factor for each graph. 2 Axis of voltage values with automatic scaling
WF10
2 3 4
Figure 51: the CF display screen in 3A
35
Item Function Item Function
2 Axis of current values with automatic scaling. 2 Columns of values relative to each graph (1, 2
and 3).
3 Instantaneous value cursor. To move the
cursor use the keys. MAX: RMS value of the maximum line voltage
from powering of the ALM 35 or from the
4 Instantaneous values of the signals at the last time the key is pressed.
intersection of the cursor (Figure 51, item 3)
RMS : true effective value of line voltage
and of the graphs.
MIN: RMS value of the minimum line voltage
t: time relative to the start of the period measured from powering of the ALM 35 or
(expressed in milliseconds). from the last time the key is pressed.
A1: instantaneous value of the current of PEAK+: maximum peak value of the line
graph 1. voltage.
A2: instantaneous value of the current of PEAK-: minimum peak value of the line
graph 2. voltage.
WF12
WF11
36
Item Function Item Function
1 Columns of values relative to each voltage 1 Columns of values relative to each current
graph (1, 2, 3). graph (1, 2, 3).
MAX: RMS value of the maximum phase MAX: maximum RMS value of the current
voltage from powering of the ALM 35 or from powering of the ALM 35 or from the
from the last time the key is pressed. last time the key is pressed.
RMS : true effective value of phase voltage. RMS : true effective value of the current.
MIN: RMS value of the minimum phase MIN: minimum RMS value of the current from
voltage from powering of the ALM 35 or powering of the ALM 35 or from the last time
from the last time the key is pressed. the key is pressed.
PEAK+: maximum peak value of the phase PEAK+: maximum peak value of current.
voltage.
PEAK-: minimum peak value of current.
PEAK-: minimum peak value of the phase
voltage. 2 Column of values relative to neutral: RMS,
PEAK+ and PEAK-
2 Column of values relative to neutral: RMS, parameters (see point 1).
PEAK+ and PEAK-
parameters (see point 1). Note: The Max. and Min. RMS measurements are
calculated every half-period (i.e. every 10 ms for a
Note: The Max. and Min. RMS measurements are signal at 50 Hz). The measurements are refreshed
calculated every half-period (i.e. every 10 ms for a every 250 ms.
signal at 50 Hz). The measurements are refreshed
7.5.4 The Max.-Min. display screen in L1
every 250 ms.
7.5.3 The Max.-Min. display screen in 4A This screen displays the RMS, maximum, minimum and
average values and the instantaneous positive and
This screen displays the RMS, maximum, minimum and negative peak values of the phase voltage and of the
average values and the instantaneous positive and current for phase 1.
negative peak values of the phase currents and of
neutral. The following data is displayed:
1 2
WF14
37
7.6.1 Simultaneous Display screen in 3U
Item Function
This screen displays the RMS, DC, THD, DF and CF
1 Column of values relative to voltage. values of the line voltages.
MAX: maximum RMS value of the voltage The displayed information is read as follows:
from powering of the ALM 35 or from the
1 2 3 4 6
last time the key is pressed.
RMS : true effective value of voltage.
MIN: minimum RMS value of the voltage from
powering of the ALM 35 or from the last time
the key is pressed.
PEAK+: maximum peak value of the voltage.
PEAK-: minimum peak value of the voltage.
L2 and L3 display the RMS, maximum, minimum and 1 Reminder of the mode used
average values and the instantaneous positive and
negative peak values of the voltage and of the current 2 Column of values relative to line voltage
respectively for phases 2 and 3. (graphs 1, 2 and 3).
7.5.5 The Max.-Min. display screen of neutral RMS : true effective value calculated over 1
second.
This screen displays the RMS values and those of the
instantaneous positive and negative peaks of neutral DC: direct component.
relative to earth. THD: total harmonic distortion rate.
The following data is displayed: DF: distortion factor.
1 2 CF: peak factor calculated in relation to the
displayed waveform.
WF15
Item Function
38
The displayed information is read as follows: DF: distortion factor.
1 2 CF: peak factor calculated in relation to the
displayed waveform.
KF: K factor. Oversizing of transformer
relative to harmonics.
39
currents and the unbalances of the voltages and currents relative to one another and the unbalance of
currents. the currents.
7.7.1 The screen Displaying the Fresnel diagram in The displayed information is identical to that described
3U in point 7.7.1 but relative to the current.
This screen displays the absolute value of the voltage 7.7.4 The screen Displaying the Fresnel diagram in
at the fundamental frequency, the phase displacement L1
of the line voltages relative to the currents and the
unbalance of the line voltages. This screen displays the absolute value of the current
and of the voltage at the fundamental frequency and the
The displayed information is read as follows: phase displacement of the voltage relative to the
current in relation to phase 1.
1 2 3 4 6
The displayed information is read as follows:
WF20
WF21
4 Fresnel diagram.
40
8. ALARM MODE KEY
Submenus are listed on the screen below and Figure 64: Configuration from alarm mode screen
individually processed in the following paragraphs.
Item Function
Sub-menus are selected using the yellow keys on the
keypad under the screen. 1 Reminder of the mode used.
This submenu displays the list of configured alarms Table continued on the next page
(See para 4.10, page 15). This shortcut key enables
you to define or change alarm configurations.
Information is displayed as follows:
41
values. The arrows appear in the date and time
12 Hysteresis value (corresponds to the
field of the programming campaign start.
added or cut percentage of the chosen
alarm threshold that shall stop the Press to increment or decrement a value and
alarm if exceeded – Value of 1, 2, 5 or press to switch to the following data.
10%).
Note: The start timestamp must exceed present
Icon for browsing in the 1,365 video timestamp.
pages. Press the yellow keys
2. Press to validate the programming of Start date
corresponding to these icons to
and time.
display the pages.
3. Select the End field via keys. The selected field
Reminder: Use keys to browse vertically in fields. is highlighted in yellow. Press to enter the type of
Use .keys to browse horizontally in fields. values. The arrows appear in the date and time
field of the programming campaign end.
Perform the following to configure an alarm:
Press to increment or decrement a value and
1. Select the field by pressing . Arrows appear. press to switch to the following data.
2. Enter values (Vah, Ah, Uh, etc.) by pressing Note: The end timestamp must exceed start timestamp.
then validate via . The field is highlighted in
yellow. 4. Press to validate the programming of End date
and time.
Do the same for all values to be entered in fields.
8.3.2 Stage 2: Starting alarm campaign
3. Activate the configured alarm by placing the yellow
cursor on the browsing column (Figure 64, item 5) Press the OK icon’s yellow key to launch the alarm
and press . Activation is marked by the red item campaign between the start and end times that you
The alarm can be triggered. specified.
Note: Repeat Stage 3 if you wish to deactivate the The OK icon disappears and the icon appears
alarm. instead.
Press to return to the Programming a campaign The Campaign on standby message is displayed
screen. while awaiting start time and the icon blinks on
the screen’s top display bar.
The Campaign running message is displayed when
8.3 Programming an alarm start time begins.
campaign The Programming a campaign screen with the OK
icon (bottom right-hand side of the screen) are
This submenu specifies the time schedule for the start displayed when the end time is reached. You can
and end of an alarm campaign. then program a new campaign.
8.3.3 Voluntary alarm campaign stop
The alarm campaign can be voluntarily stopped before
the end timestamp by pressing the icon’s yellow
key (bottom right-hand side of the screen). The OK icon
shall then reappear in the same place.
42
The following data is displayed:
1 2
To be
changed
AM02
To be
changed Figure 67: Alarm log in deletion mode screen
AM01
3 4 5 6
Figure 66: Alarm log screen
Item Function
3 Alarm filter.
6 Alarm duration.
43
9. TREND MODE KEY
44
(no more than 8 characters). Several recordings can
carry the same name.
1 2 3 4
Available alphanumeric characters are A...Z, space
and 0 to 9. Use keys to display a character and
to switch to the contiguous character.
7. Press to validate the name.
9.2.2 STAGE 2: Start programming a recording.
Press the OK icon’s yellow key (bottom right-hand
side of the screen) to begin recording between your
specified start and end times. The OK icon
disappears and the icon appears instead.
The Recording on standby message is displayed
while awaiting start time and the icon (figure 8, SUMT
Figure 70: Display screen during a current recording Types of configuration icon ( to ).
Press these icons’ yellow keys to display
The Programming a recording screen and OK icon screen pages.
(bottom right-hand side of the screen) reappear when
the end time is reached. You can then program a new
recording. Perform the following to configure a recording:
The recording can be voluntarily stopped before the end 1. To zoom in press the yellow keypad key
timestamp by pressing the icon’s yellow key corresponding to the icon. It is displayed
(bottom right-hand side of the screen). The OK icon against a yellow background.
shall then reappear in the same place. 2. Select values by moving the yellow cursor via
and keys, then press to validate. The red item
confirms validation.
9.3 Trend mode configuration
This submenu displays the recording list (See para 4.9,
page 14). This shortcut key enables you to specify or
change the configuration of recordings.
Information is displayed as follows:
45
Reminder: You can record the following values: Press to switch to the following field.
Tan Tangent.
Hz Network frequency.
KF K factor.
3 4 5
Specific features for the last two lines
These are set out below: Figure 73: Recording list display screen
Item Function
These two lines involve the recording of VAh, Ah, Vh 2 Current date and time.
and Uh variable harmonics. You can select the ranks of
harmonics to be recorded (between 0 and 50) for each Continuation of the table on the next page.
of these harmonics and possibly only odd harmonics
within this range. Perform the following:
46
3 Recording name.
TREND03
47
10. POWER AND ENERGY KEY
This key displays measurements for power and This screen displays the following information:
energies.
MPE01
Unit Designation
2 Display of energy consumed. 10.2 10.2.2 The Energy consumed display for phase L1
3 Display of energy generated. 10.3 This screen displays the following information:
Unit Designation
48
WARh Reactive energy consumed:
Inductive.
Capacitive.
PF Power factor.
Tan Tangent. Figure 79: the Energy generated display for the 3
phases (3L)
Note: The information displayed for filters L2 and L3 is
Unit Designation
identical to the information described above, but relates
to phases 2 & 3. The filter screen also displays the W Active power (total if 3φ)
Σsame information, but relates to total values.
10.2.3 Display screen Wh Active energy generated.
This screen page is only available for the 3L filter. To VAR Inductive reactive power .
display information, press the yellow key on the keypad
with the icon . WARh Reactive energy generated:
MPE03
Figure 78: the Peak factor display for the 3 phases (3L)
Unit Designation
PF Power factor.
49
PF Power factor. 10.6 Zero resets of energy
metering
DPF Displacement factor.
Tan Tangent. To reset metering, press the yellow key on the keypad
with the icon and the key to confirm.
All energy values (consumed and generated) are reset.
Note: the information displayed for filters L2 and L3 is
identical to the information described above, but relates Note: refer to the diagram of the 4 quadrants for powers
to phases 2 & 3. The filter screen also displays the in paragraph 17.4, p 70.
Σsame information, but relates to total values.
10.3.3 Display screen
This screen page is only available for the 3L filter (see
Figure 78). To display information, press the yellow key
on the keypad with the icon .
This page displays:
• The power factor
• The power displacement factor
• Tangent
MPE06
50
11. SCREEN SNAPSHOT KEY
51
11.2.3 View of a snapshot from the list 11.2.4 Deletion of a snapshot from the list
To display a snapshot, proceed as follows: To delete a snapshot, proceed as follows:
1. Press . The icon is active and the list of 1. The screen presents the list of snapshots (see
snapshots is displayed (see Figure 83). Figure 83 for example). Select the sub-menu
2. Select the snapshot to be viewed using the (bottom of the screen) by pressing the yellow key on
keys. The date and time of the selected snapshot the keypad with this icon.
are noted in bold. 2. Select the snapshot to be deleted using the
keys. The date and time of the selected snapshot
3. Press to display the selected snapshot. The top
are noted in bold.
left hand side of the screen displays the icon,
alternating with the icon corresponding to the active 3. Press to delete the selected snapshot. The
snapshot has been deleted from the list.
mode ( ).
Press to return to the list of screen snapshots.
Press to return to the list of screen snapshots.
52
12. HELP KEY
HELP
5 6 7
Figure 84: example of the help page for the power and
energy mode, page 1
Item Function
5 Help page 1 .
6 Help page 2 .
7 List of information.
53
13. USE
The ALM 35 must be configured in accordance with 13.2 Configuration of the ALM 35
chapter 4 prior to measurements.
The following precautions for use must be complied To configure the ALM 35, proceed as follows:
with:
1. Press when the device is on. The
Do not connect any voltages exceeding 1,000V RMS configuration screen will appear.
in relation to the earth.
When connecting and disconnecting accumulators, 2. Press to select the parameter to be modified.
check that measuring leads are disconnected. Press to enter the selected sub-menu.
13.1 Start-up
Press the key on the keypad to start the ALM 35.
The illuminated indicator (green LED) will light up when
pressed and then go out.
The home page will be displayed during the loading of
the software application. The version of the software
application and the serial number of the ALM 35 are
indicated in the lower left hand part of the screen.
SU00
WF22
54
13.3 Installation of leads Figure 91: 3 or 4 wire three-phase connection
13.3.4 5-wire three phase network
Insert the leads as follows:
1 2
Current measurement: 4-point connector (item 1). Do 13.4.2 Display of the inrush current mode
not forget to define the transformation ratio on the See para 5.3, page 20.
current sensor (See para 4.8 page 13).
Measurement of the voltage (item 2): L1/A, L2/B,
L3/C & N/D terminals. 13.5 Display of harmonics
Measuring leads are connected to the circuit to be Reminder: all screens can be saved (screen snapshot)
studied according to the following diagrams.
by pressing the key. See chapter 11, page 51.
13.3.1 Single phase network
Press when the ALM 35 has a power supply and
is connected to the network (current and voltage
measuring leads).
13.5.1 Single voltage display
See para 6.2, page 24.
13.5.2 Current display
See para 6.3, page 26.
Figure89: single phase connection
13.3.2 Two phase network 13.6 Measuring wave shapes
Reminder: all screens can be saved (screen snapshot)
by pressing the key. See chapter 11, page 51.
55
13.6.5 Simultaneous display 13.10 Transfer of data to the PC
See para 7.6, page 38.
The PAT transfer software automatically defines the
13.6.6 Display of Fresnel diagram communication speed between the PC and the ALM 35.
See para 7.7, page 39. All measurements taken by the ALM 35 will be
saved. These measurements may be transferred to a
PC for future reference.
13.7 Alarm detection Note: the transfer will not delete the data saved.
Use the function in accordance with paragraph 8.3.3, Select Yes or No using the keys, and press to
page 42. validate.
13.7.5 Display of the alarm log • If No is selected, the recording will continue.
• If Yes is selected, the data recorded until that point
See para 8.4, page 42. will be saved and the device will turn off.
13.7.6 Deletion of the alarm log
See para 8.5, page 43. 13.13 Supply of the ALM 35
13.13.1 Battery recharge
13.8 Recording
See para 3.6.3, page 9.
Reminder: all screens can be saved (screen snapshot) 13.13.2 Mains operation
by pressing the key. See chapter 11, page 51.
See para 3.6.6, page 10.
Press when the ALM 35 has a power supply and
is connected to the network (current and voltage
measuring leads).
13.8.1 Configuration of recording
See para 9.3, page 45.
13.8.2 Programming of recording
See para 9.2, page 44.
56
14. MAINTENANCE
Battery charging is managed by the device when Fax: (044) 4231 6165
connected to the AC network via the specific mains
supply.
Accumulator batteries must be changed off-load for 14.7 Sensors
safety reasons and to ensure the correct operation
of the charger. Current sensors must be maintained and calibrated as
follows:
Do not throw accumulators into flames.
Clean with a sponge and soapy water, rinse with
Do not expose accumulators to heat in excess of clean water and dry rapidly.
100 °C.
Keep the clamp spacers (MN93, MN93A, C193 &
Do not short circuit accumulator terminals. PAC93) in an entirely clean condition using a cloth.
Lightly oil visible metal parts to avoid rust.
Note: the date and time of the device will be retained
for one minute after the removal of the battery.
57
15. GENERAL SPECIFICATIONS
Stand: to maintain the device at 53° from Display-free stand-by mode: 100 mA
the horizontal.
58
15.3.1.2 Altitude Conducted RF interference (as per IEC 61000-4-6)
Use: [0 m; 2,000 m] Gravity: 3 V on voltage input and supply
Sanctions: CRITERION A
Storage: [0 m; 10,000 m]
Voltage interruption (as per IEC 61000-4-11)
15.3.2 Mechanical conditions
Gravity: 100% loss over a supply period
According to IEC 61010-1, the ALM 35 is considered Sanctions: CRITERION A
as a MOBILE DEVICE (HAND-CARRIED).
15.3.3.2 Emission as per NF EN 61326 - 1 A3
Operating position: indifferent. Class A equipment (no supply – mains).
Reference position during operation: on a horizontal Class B equipment (with supply – mains - unit wire
plane, resting on its stand or lying flat. failure).
Rigidity (IEC 61010-1): force of 30 N applied to the
entire envelope of the supported device (at 40 °C).
15.4 User safety
Chute (IEC 61010-1): 1 m in the position assumed to
be the most damaging; the chute sanction is: no Application of safety rules as per IEC 61010-1.
permanent mechanical damage and no functional (Isolation of voltage input using protective
damage. impedances).
Impermeability: IP 50 as per NF EN 60529 A1 Pollution type 2.
(electric IP2X for terminals).
Installation category IV* and service voltage 600
15.3.3 Electromagnetic compatibility VRMS.
15.3.3.1 Immunity as per NF EN 613261 - 1 A3 Double isolation on I/O in relation to the earth (symbol
Resistance to electrostatic discharges ).
(IEC 61000-4-2)
Double isolation between the voltage and supply
1st level : Gravity : 4 kV in contact input and other I/O (symbol ).
Sanctions : CRITERION A
Indoor use
2nd level : Gravity : 8 kV in the air
(*) Caution: the assigned voltage and measuring
Sanctions : CRITERION A category of the "device + current sensor" unit may differ
Resistance to radiation (as per IEC 61000-4-3 and from the characteristics of the device alone.
IEC 61000-4-8) - the use of AmpFLEX™, of Mini-AmpFLEX and
Gravity: 10 V.m
-1 C clamps mains the "device + current sensor"
Sanctions: CRITERION B (THDA altered on the unit at 600 V category IV or 1000 V category
Rogowsky chain) III.
- the use of PAC, MN93 and MN93A clamps
Resistance to rapid transient bursts (IEC 61000-4-4)
damages the "device + current sensor" unit at
Gravity: 2 kV on voltage input and 300 V category IV or 600 V category III.
supply
- the use of the downgraded 5A adapter damages
1 kV on current input the "device + current sensor" unit at 150 V
Sanctions: CRITERION A category IV or 300 V category III.
Resistance to electric shocks (as per IEC 61000-4-5)
Gravity: 2 kV on voltage input in differential mode
1 kV on voltage input in collective mode
Sanctions: CRITERION A
59
16. FUNCTIONAL CHARACTERISTICS
This table indicates reference conditions for sizes to be used by default in the characteristics indicated in
paragraph16.2.4.
Ambient temperature 23 °C ± 3 K
Operating range: [0 V; 1 V]
Input impedance : 1 MΩ.
60
16.2.3 Bandwidth
61
Measurement scope
Maximum error in
Display
Measuring the
resolution
field of reference
Minimum Maximum
(1) In 1000 VRMS, category III, providing that voltage between each of the terminals and the earth does not exceed
1000 VRMS.
(2) Two phase (opposite phases) – same note as (1).
(3) Limitation of the PAC clamp.
(4) 1, 2 × I nom × 2 = 1, 7 × I nom
62
Measurement scope
Maximum error
Display
Measuring in
resolution
the field of reference
Minimum Maximum
0.1 V
Phase voltage TRMS V < 1000 V
±(0.8 % + 1 V)
(1)
10 V 1,000 V
half-period(3) 1V
V ≥ 1000 V
0.1 V
Composite voltage TRMS U < 1000 V
±(0.8 % + 1 V)
(2)
10 V 2,000 V
half-period(3) 1V
U ≥ 1000 V
Excluding ±(1 %)
AmpFLEX™ 1V Cos φ ≥ 0.8
0Ω 9999 kW
& U ≥ 1000 V ±(1.5 %+10 pts)
Mini-AmpFLEX 0,2 ≤ Cos φ < 0.8
Active power
±(1 %)
AmpFLEX™ Cos φ ≥ 0.8
& 0Ω 9999 kW 4 digits
Mini-AmpFLEX ±(1.5 %+10 pts)
0.5 ≤ Cos φ < 0.8
Excluding ±(1 %)
AmpFLEX™ Sin φ ≥ 0.5
Reactive 0 VAR 9999 kVAR 4 digits
& ±(1.5 %+10 pts)
powers Mini-AmpFLEX
0.2 ≤ Sin φ < 0.5
inductive ±(1.5 %)
& AmpFLEX™ Sin φ ≥ 0.5
capacitive & 0 VAR 9999 kVAR 4 digits
Mini-AmpFLEX ±(2.5 %+20 pts)
0.2 ≤ Sin φ < 0.5
±(1.5 %)
Cos φ ≥ 0.5
Power factor -1 1 0,001
±(1.5 %+10 pts)
0,2 ≤ Cos φ < 0.5
(1) In 1000 VRMS, category III, providing that voltage between each of the terminals and the earth does not exceed
1000 VRMS.
(2) Two phase (opposite phases) – same note as (1).
(3) Caution: The absolute value of offset must not exceed 95% of peak amplitude.
In other words, s(t) = S × sin(ωt) + O, we have |O| ≤ 0.95 × S (with positive S).
MAX and MIN values in wave shape mode and the values VRMS and ARMS (excluding neutral channels) in Alarm and Inrush
current modes are half-period values.
Note: the uncertainties given for power and energy measurements are maximum for |Cos φ| = 1 or |Sin φ| = 1 and are
typical for other phase displacement values.
63
Measurement scope
Maximum error
Display
Measuring in
resolution
Minimum Maximum the field of reference
Excluding ±(1 %)
AmpFLEX™ Cos φ ≥ 0.8
0 Wh 9999 MWh 4 digits
& ±(1,5 %)
Active Mini-AmpFLEX 0,2 ≤ Cos φ < 0.8
energy ±(1 %)
AmpFLEX™
Cos φ ≥ 0.8
& 0 Wh 9999 MWh 4 digits
Mini-AmpFLEX ±(1,5 %)
0,5 ≤ Cos φ < 0.8
Excluding ±(1 %)
AmpFLEX™ Sin φ ≥ 0.5
Reactive 0 VARh 9999 MVARh 4 digits
& ±(1,5 %)
energies Mini-AmpFLEX 0,2 ≤ Sin φ < 0.5
inductive ±(1.5 %)
& AmpFLEX™ Sin φ ≥ 0.5
capacitive & 0 VARh 9999 MVARh 4 digits
Mini-AmpFLEX ±(2,5 %)
0,2 ≤ Sin φ < 0.5
Apparent energy 0 VAh 9999 MVAh 4 digits ±(1 %)
Dephasing -179° 180° 1° ±(2°)
0.001
Tangent Tan φ < 10
-32.76 32.76 ±(1°) for φ
VA ≥ 50 VA 0.01
Tan φ ≥ 10
±(1°) for φ
Displacement factor
-1 1 0.001 &
(DPF)
±(5 pts) for DPF
Harmonic rates
∈ [1; 50]
(VRMS > 50 V)
Excluding AmpFLEX™
&
Mini-AmpFLEX 0% 999,9 % 0,1 % ±(1 % + 5 pts)
(IRMS > 3 × Inom ÷ 100)
AmpFLEX™
&
Mini-AmpFLEX
(IRMS > Inom ÷ 10)
Harmonic angles
(VRMS > 50 V)
±(3°)
Excluding AmpFLEX™
& ∈ [1; 25]
Mini-AmpFLEX -179° 180° 1°
(IRMS > 3 × Inom ÷ 100)
AmpFLEX™
& ±(10°)
Mini-AmpFLEX ∈ [26; 50]
(IRMS > Inom ÷ 10)
Global harmonic rate
(THD or THD-F) 0% 999,9 % 0,1 % ±(1 % + 5 pts)
rank ≤ 50
Distorsion factor
(DF or THD-R) 0% 999,9 % 0,1 % ±(1 % + 10 pts)
≤ 50
Unbalance
0% 100 % 0,1 % ±(1 %)
(three phase network)
64
16.2.5 Current sensor characteristics (after The RMS current measurement error and phase error
linearisation) correspond to additional errors (added to device errors)
indicated as parameters for the calculations carried out
Sensor errors are offset by typical correction inside the by the analyser (power, energy, power factors,
device. This typical correction is applied for phase and tangents, etc.).
amplitude depending on the type of sensor connected
(detected automatically) and the gain in the current
acquisition channel required.
65
Maximum
Maximum
Type of sensor Current TRMS error
φ
error forφ
for IRMS
[1 A; 10 A] N.S.
±(1.5 % + 1 A)
[10 A; 100 A] ±(2°)
PAC93 clamp
1000 A [100 A; 800 A] ±(3 %)
±(1,5°)
[800 A; 1200 A] ±(5 %)
[1 A; 3 A] N.S.
±(0,8 %)
C193 clamp
[3 A; 10 A] ±(1°)
1000 A [10 A; 100 A] ±(0,3 %) ±(0,5°)
[100 A; 1200 A] ±(0,2 %) ±(0,3°)
AmpFLEX™ A193 [10 A; 100 A] ±(3 %) ±(1°)
6500 A [100 A; 6500 A] ±(2 %) ±(0,5°)
Mini-AmpFlex MA193 [10 A; 100 A] ±(3 %) ±(1°)
6500 A [100 A; 6500 A] ±(2 %) ±(0,5°)
[0.5 A; 2 A] N.S.
±(3 % + 1 A)
MN93 clamp [2 A ; 10 A[ ±(6°)
200 A [10 A; 100 A] ±(2.5 % + 1 A) ±(3°)
[100 A; 240 A] ±(1 % + 1 A) ±(2°)
[100 mA; 300 mA] N.S.
MN93A clamp ±(0.7 % + 2 mA)
[300 mA; 1 A] ±(1,5°)
100 A
[1 A; 120 A] ±(0,7 %) ±(0,7°)
[5 mA; 50 mA] ±(1 % + 0.1 mA) ±(1,7°)
MN93A clamp
[50 mA ; 500 mA[ ±(1 %)
5A ±(1°)
[500 mA; 6 A] ±(0,7 %)
Adapter [5 mA; 50 mA] ±(1 %) ±(1°)
5A [50 mA; 6 A] ±(0,5 %) ±(0°)
66
17. APPENDICES
This chapter presents the mathematical formulae used 17.1.3 Minimum and maximum half-cycle efficient
for calculating different parameters for C.A.8335. values (excluding neutral)
Vmax i = max( Vdem i ) , Vmin i = min( Vdem i )
17.1 Mathematical formulae Umax i = max( Udem i ) , Umin i = min( Udem i )
17.1.1 Network frequency and sample Amax i = max( Adem i ) , Amin i = min( Adem i )
The sample is applied to the network frequency to 17.1.4 Flicker for voltages (ex neutral)
obtain 256 samples per period of 40Hz to 70Hz.
Feedback is essential for calculating reactive power, Method inspired by the CEI 61000 – 4 –15 standard.
imbalance and harmonic rates and angles.
Input values are simple half-cycle voltages. Blocks 3
Frequency measurement is determined by analysing and 4 are created digitally. The classifier of block 5 has
seven passes by zero positive and consecutive on the 128 levels.
first voltage channel (V1) or the first current channel (I1)
The Vflk[i] values are updated every 10 minutes.
after digital low-pass filtering and deletion of the
continuous component. 17.1.5 Peak values for voltages and currents
The precise temporal measurement of the zero pass i=3 neutral – except for Upp and Upm
point is achieved by linear interpolation between two
Vpp i = max( V i n ) , Vpm i = min( V i n ) n ∈ 0..NECHPER -1
samples to achieve better solution than 0.002%.
Upp i = max( U i n ) , Upm i = min( U i n ) n ∈ 0..NECHPER -1
Signals are acquired with a 16 bit converter and (in the
event of current acquisition) dynamic gain switches. App i = max( A i n ) , Apm i = min( A i n ) n ∈ 0..NECHPER -1
NECHPER n =0
Zéro suivant
Adem [i ] = ⋅ ∑ A[i ][n ]
1 2
NECHPER n =0
NechSec n=0
67
Efficient composite voltage phase i+1
17.1.9 Harmonic distortions (ex neutral)
NechSec−1
1
Urms i = ⋅ ∑U i n
2
Te Two global values giving the relative quality of
NechSec n =0 harmonics are calculated: The THD in proportion of the
fundamental and the DF in proportion to the RMS value.
Efficient current phase i+1
50 50 50
∑n ⋅ Aharm i n
2 2
1 1024 kπ
bk = 512 ∑ Fs × sin 512 s + ϕ k
harmonics.
s =0 Reactive powers are calculated by using filtered signals
with
1 1024
kπ (without harmonics) in accordance with EDF rules or
ak = ∑
512 s =0
Fs × cos
512
s + ϕk
from apparent and active energies (with harmonics).
The choice of calculation is left up to the user.
1 1024
Total active power
c0 =
∑ Fs
1024 s =0 W[3] = W[0] + W[1] + W[2]
Total apparent power
Ck : amplitude of the component with a frequency of VA[3] = VA[0] + VA[1] + VA[2]
k
f k = f1 Total reactive power
4 VAR[3] = VAR[0] + VAR[1] + VAR[2]
Fs : sample signal
Co : continuous component
K ordinal number (spectral line range)
68
Generated apparent power phase i+1
17.1.12 Different rates (ex neutral)
VA[i ]
Wi VAh [1][i ] = ∑
PF i = Facteur de puissance phase i +1 Tint 3600
VA i
DPF i = cos( φ i ) Facteur de déplacement phase i +1 Generated inductive reactive power phase i+1
VAR [i ]
Tan i = tan( φ i ) Tangente phase i + 1 VARhL [i ] = ∑ for VAR [i ] ≥ 0
Tint 3600
∑VF i n ⋅ ∑ AF i
2 2
n Total generated active power
n =0 n=0
Wh[1][3] = Wh[1][0] + Wh[1][1] + Wh[1][2]
PF[0] + PF[1] + PF[2]
PF[3] = Facteur de puissance total Total generated apparent power
3
DPF[0] + DPF[1] + DPF[2]
DPF[3] =
VAh[1][3] = VAh[1][0] + VAh[1][1] + VAh[1][2]
Facteur de déplacemen t total
3
Tan [0] + Tan[1] + Tan[2]
Tan[3] = Tangente totale Total generated reactive capacitive power
3
VARhC[1][3] = VARhC[1][0] + VARhC[1][1] + VARhC[1][2]
17.1.13 Different energies (ex neutral)
Total generated reactive inductive power
• Case 1 consumed energy (W[i] ≥ 0) VARhL[1][3] = VARhL[1][0] + VARhL[1][1] + VARhL[1][2]
Consumed active power phase i+1
W [i ]
Wh [0][i ] = ∑ 17.2 Hysteresis
Tint 3600
69
17.3 Minimum scale values for waveforms and minimum RMS values
Type of current sensor Min RMS current value [A] Min scale value for current [A]
AmpFLEX™ 6500 A 30 60
Mini-AmpFLEX 6500 A 30 60
MN93A clamp probe 5 A (Primary × 5) ÷ (Secondary × 1000) (Primary × 5 x 10) ÷ (Secondary × 1000)
ARMS < [minimum value of displayed current] ⇒ [ARMS = APP = APM = W = VA = VAR = W DC = AMAX = AMIN = AhMOD = AhANG =
0] AND [flattening of displayed current rates] AND [ACF = KF = ATHD = ADF = not calculated and not displayed] AND [VAFANG =
AFANG = PF = DPF = Tan = not calculated and not displayed]
[minimum displayed current value] <0.2⇒ [minimum displayed current value] = 0.2
[minimum current scale value] < 1 ⇒ [minimum current scale value] = 1
VRMS < 10 V ⇒ [VRMS = VPP = VPM = W = VA = VAR = W DC = VMAX = VMIN = VhMOD = VhANG = 0] AND
[flattening of displayed voltage rates] AND [VCF = PST = VTHD = VDF = not calculated and not displayed] AND [VAFANG =
VFANG = PF = DPF = Tan = not calculated and not displayed]
URMS < 10 V ⇒ [URMS = UFRMS = UPP = UPM = UMAX = UMIN = UhMOD = UhANG = 0] AND [flattening of displayed voltage
rates] AND
[UCF = UTHD = UDF = not calculated and not displayed] AND [UFANG = not calculated and not displayed]
Note: the minimum RMS voltage value is 10V. The minimum scale value for the waveform is 20V
70
17.5 Mechanism for triggering transient sensors
The sample rate is a constant value equivalent to 256 samples per cycle. When a transient search is launched, each
sample is compared to the sample from the preceding cycle. The preceding cycle matches the middle of the tube; it is
used as a reference. As soon as a sample leaves the tube, the trigger event comes; representation of the transient is
then captured by the ALM 35. The cycle preceding the event and the three following cycles are saved to memory.
Here is a graphical representation of the transient capture trigger mechanism:
71
17.7 Glossary Temporary surge at industrial frequency: temporary
increase in the voltage amplitude at a point in the
Ampere: unit of electrical current intensity (A symbole). electrical power network above a given threshold.
Bandwidth: frequency range on which an instrument Nominal voltage: voltage by which a network is named
supplies a precise measurement. or identified.
Fundamental component: component whose THD: Total Harmonic Distortion. Total harmonic
frequency is the fundamental frequency. distortion. The rate of total harmonic distrotion gives
the influence of harmonic components in a signal.
Cut: reduction in voltage at a point in the electrical
power network below the cut threshold. RMS value square root of the average squares of
values for a specified interval.
Voltage dip: temporary reduction in the voltage
amplitude at a point in the electrical power network Measurement method: all measurement methods
below a given threshold. associated to an individual measurement.
72
Manaco EnerGy Solutions Pvt. Ltd.
c o n s e r v a t i o n b e g i n s h e r e
Head Office: A-6, Shanti Apts., 21&22, 1St Cross St, TTK Road, Alwarpet, Chennai -18.
Tel: 44- 42316164 Fax: 44- 42316165 Email: sales@mes.co.in www.mes.co.in
Branches:
Ahmedabad : ahm@mes.co.in; Ph: +91- 93271 02033
Bangalore : blr@mes.co.in; Ph: +91- 93410 03147
Chennai : chn@mes.co.in; Ph: +91- 93805 73027
Coimbatore : cbe@mes.co.in; Ph: +91- 93666 22334
Delhi : del@mes.co.in; Ph: +91- 93125 46020
Hyderabad : hyd@mes.co.in; Ph: +91- 93940 43970
Mumbai : mmb@mes.co.in; Ph: +91- 93233 14156