You are on page 1of 2

STRUCTURAL LOAD CALCULATIONS

for

GRID TIE SOLAR PV SYSTEM


SM CITY BATAAN
Lerma St. Brgy. Ibayo Balanga City, Bataan
Prepared for:

UGE Philippines
Unit KLM Crossroads Mall, Gov. M. Cuenco Ave., Kasambagan, Cebu City

March 26, 2024

Prepared by:

ENGR. LEONARD L. LAURENA


PRC : 0090464
Validity 01-30-2026
PTR No.: 3197272
Date Issued: 01-10-2024
Issued at: Mandaluyong City
TIN No.: 222-433-249
CALCULATION OF THE ADDITIONAL SUPERIMPOSED DEAD LOAD OF
INVERTER STATION AT ROOF DECK OF THE EXISTING SM BATAAN
STRUCTURE

(FINITE ELEMENT ANALYSIS OF EXISTING BEAMS AND SLABS TO FOLLOW)

1. SUPER IMPOSED DEAD LOADS:

a. CONCRETE PAD (100mm thick) = 20.31m x 2.675m x .10m x 3.28 ft3 x 150 lbs/ft3
=28,757.19 lbs.
b. STEEL FRAME = 5,015.73 lbs.
c. ROOFING = 739.33 lbs.
d. INVERTER = 19 pcs. x 294.16 = 5,589.04 lbs.
e. DISTRIBUTION PANEL = 2 x 1,542.70 lbs = 3,085.4 lbs.
f. BRACKET = 22 pcs. x 1.80 lbs. = 39.6 lbs.
g. CABLE TRAY DC = 1,516.85 lbs.
h. CABLE TRAY AC = 1,635.96 lbs.
i. DC WIRES = 880.90 lbs.
j. AC WIRES = 880.90 lbs.

TOTAL SUPER IMPOSED DEAD LOAD = 48,140.90 lbs.

2. UNIFORM LOAD CALCULATIONS:

a. AT EXISTING SERVICE ROOF DECK

δ = 48,140.99 = 82.05 psf < 100 psf OK


20.31 X 2.675 X 10.8