VERSION : LNAH40XX
RELEASED : 05.04.2004
Department : ATDD3
Issued by : HL, ML, TB
Approved by : TB
Revision : A
Control Panel
Fieldbus Interface:
e.g.:
Profibus
Modbus
Modbus +
DeviceNet
PC – Tools:
e.g.:
DriveWindow
Drive Debug
Table of Contents
HISTORY TABLE OF SIGNAL AND PARAMETER TABLE ...................................................................................... 4
1.05 VOLTAGE %
Index Description: Actual supply network voltage level in percent of the nominal voltage level.
Unit: % Type: Min: Max: Int. scaling: 10 == 1%
2.01 DC VOLTAGE
Index Description: DC link voltage of the intermediate circuit (lower plus upper half).
Unit: V Type: Min: Max: Int. scaling: 1 == 1V
2.02 DC VOLTAGE %
Index Description: DC link voltage of the intermediate circuit (lower plus upper half) in percent.
Unit: % Type: Min: Max: Int. scaling: 10 == 1%
2.05 NP VOLTAGE
Index Description: Neutral Point (NP) voltage of the intermediate circuit (lower minus upper half).
Unit: V Type: R Min: Max: Int. scaling: 1 == 1V
2.06 NP VOLTAGE %
Index Description: Neutral Point (NP) voltage in percent of ??? (the nominal DC link voltage).
Unit: % Type: R Min: Max: Int. scaling: 10 == 1%
3.01 ID REFERENCE %
Index Description: Actual ID Reference in %
Unit: % Type: R Min: Max: Int. scaling: 10 == 1%
3.02 IQ REFERENCE %
Index Description: Actual IQ Reference in %
Unit: % Type: R Min: Max: Int. scaling: 10 == 1%
NOTE: This FLT is indicated in ARU only when the state is RDY RUN. Otherwise a loop
of faults is possible at the PFF-link.
Please, check also to the appendix part of the INU manual (‘PFF –link’).
Unit: Type: B, B Min: Max: Int. scaling:
5. 05 StatusINU1
Index Description: INU1 status word. This word is sent from INU1 via PFF link for ARU.
Please, check also to the appendix part of the INU manual (‘PFF –link’).
Unit: Type: PB Min: Max: Int. scaling:
5. 06 StatusARU
Index Description: ARU status word. This word is sent from aru to PFF link for INU1.
Please, check also to the appendix part of the INU manual (‘PFF –link’).
Unit: Type: PB Min: Max: Int. scaling:
5. 07 PHASE A LOST
Index Description: Phase A Lost
Unit: Type: B Min: Max: Int. scaling:
5. 08 PHASE B LOST
Index Description: Phase B Lost
Unit: Type: B Min: Max: Int. scaling:
5. 09 PHASE C LOST
Index Description: Phase C Lost
Unit: Type: B Min: Max: Int. scaling:
5. 10 ASE STATUS
Index Description: Anti saturation equipment status
Unit: Type: B Min: Max: Int. scaling:
Please, check also to the appendix part of the INU manual (‘PFF –link’).
Please, check also to the appendix part of the INU manual (‘PFF –link’).
Please, check also to the appendix part of the INU manual (‘PFF –link’).
Please, check also to the appendix part of the INU manual (‘PFF –link’).
Please, check also to the appendix part of the INU manual (‘PFF –link’).
Please, check also to the appendix part of the INU manual (‘PFF –link’).
9.20 (R / 183.02)
FAULT WORD COMMUNICATION
Index Description: Communication fault word.
Bit Name Meaning Part
1 B0 PPCS Communication PPCS Communication Fault Common
2 B1 PFF Communication PFF Communication Fault Common
4 B2 INT0 PPCS Link INT0 PPCS Link Fault Common
8 B3 NT0 FT Link INT0 FT Link Fault Common
16 B4 INT1 PPCS Link INT1 PPCS Link Fault 2nd INV Common
32 B5 INT1 FT Link INT1 FT Link Fault 2nd INV Common
64 B6 INT2 PPCS Link INT2 PPCS Link Fault 3rd INV Common
128 B7 INT2 FT Link INT2 FT Link Fault 3rd INV Common
256 B8 PUB: Communication PUB Communication Fault Common
512 B9 GRAY Missing GRAY Communication Fault SD, AD
1024 B10 NTAC Missing NTAC Communication Fault SD, AD
2048 B11 CCB Communication CCB Communication Fault SD, AD
4096 B12 EXU: Communication EXU Communication Fault SD
8192 B13 EXU: PAI Communica EXU PAI Communication Fault SD
16384 B14 PPCC LnkConfigFault PPCC Link Configuration Fault Common
32768 B15 NOT USED
Unit: Type: PB Min: -32768 Max: 32767 Int. scaling: 1 == 1
9.21 (R / 183.03)
FAULT WORD 1 COMMUNICATION
Index Description: Communication 1 fault word.
Bit Name Meaning Part
1 B0 INT0 Fault Link INT0 Fault Link Fault Common
2 B1 INT1 Fault Link INT1 Fault Link Fault 2nd INV Common
4 B2 INT2 Fault Link INT2 Fault Link Fault 3rd INV Common
8 B3 INT3 Fault Link INT3 Fault Link Fault 4th INV Common
16 B4 INT3 PPCS Link INT3 PPCS Link Fault Common
32 B5 INT3 FT Link INT3 FT Link Fault Common
64 B6
128 B7
256 B8
512 B9
1024 B10
2048 B11
4096 B12
8192 B13
16384 B14
32768 B15 NOT USED
Unit: Type: PB Min: -32768 Max: 32767 Int. scaling: 1 == 1
9.22 (R / 183.04)
FAULT WORD 2 COMMUNICATION (RESERVED)
Index Description: Communication 2 fault word.
Bit Name Meaning Part
1 B0
2 B1
4 B2
8 B3
16 B4
32 B5
64 B6
128 B7
256 B8
512 B9
1024 B10
2048 B11
4096 B12
8192 B13
16384 B14
32768 B15 NOT USED
Unit: Type: PB Min: -32768 Max: 32767 Int. scaling: 1 == 1
9.23 (R / 183.07)
FAULT WORD CONTROL HARDWARE
Index Description: Control Hardware fault word.
Bit Name Meaning Part
1 B0 Delayed GUSP AuxPow Delayed GUSP Auxiliary Power Fault Common
2 B1 INT0 AuxiliaryPower INT0 Auxiliary Power Fault Common
4 B2 INT0 GUSP AuxPower INT0 GUSP Aux Power Fault Common
8 B3 INT0 VLU GUSP INT0 VLU GUSP Fault SD, AD
16 B4 INT0 VLU Control INT0 VLU Control Fault SD, AD
32 B5 INT0 LSU DiodeFault INT0 LSU Diode Fault SD, AD
64 B6 INT1 AuxiliaryPower INT1 Auxiliary Power Fault 2nd INV Common
128 B7 INT1 GUSP AuxPower INT1 GUSP Aux Power Fault 2nd INV Common
256 B8 INT1 VLU GUSP INT1 VLU GUSP Fault 2nd INV SD, AD
512 B9 NT1 VLU Control INT1 VLU Control Fault 2nd INV SD, AD
1024 B10 INT1 LSU DiodeFault INT1 LSU Diode fault 2nd INV SD, AD
2048 B11 EXU: Control HW EXU Control Hardware Fault SD
(including CCB Powerfail or PAI1 power low
or PAI GDR feedback or MUB fault)
4096 B12
8192 B13
16384 B14
32768 B15 NOT USED
Unit: Type: PB Min: -32768 Max: 32767 Int. scaling: 1 == 1
9.24 (R / 183.08)
FAULT WORD 1 CONTROL HARDWARE
Index Description: Control Hardware 1 fault word.
Bit Name Meaning Part
1 B0 INT2 AuxiliaryPower INT2 Aux Power Fault 3rd INV Common
2 B1 INT2 GUSP AuxPower INT2 GUSP Aux Power Fault 3rd INV Common
4 B2 INT2 VLU GUSP INT2 VLU GUSP Fault 3rd INV SD, AD
8 B3 INT2 VLU Control INT2 VLU Control Fault 3rd INV SD, AD
16 B4 INT2 LSU DiodeFault INT2 LSU Diode Fault 3rd INV SD, AD
32 B5 PUB: AuxiliaryPower PUB Auxiliary Power Fault Common
64 B6 INT3 AuxiliaryPower INT3 Aux Power Fault 4th INV Common
128 B7 INT3 GUSP AuxPower INT3 GUSP Aux Power Fault 4th INV Common
256 B8 INT3 VLU GUSP INT3 VLU GUSP Fault 4th INV SD, AD
512 B9 INT3 VLU Control INT3 VLU Control Fault 4th INV SD, AD
1024 B10 INT3 LSU DiodeFault INT3 LSU Diode Fault 4th INV SD, AD
2048 B11
4096 B12
8192 B13
16384 B14
32768 B15 NOT USED
Unit: Type: PB Min: -32768 Max: 32767 Int. scaling: 1 == 1
9.25 (R / 183.09)
FAULT WORD 2 CONTROL HARDWARE
Index Description: Control Hardware 2 fault word.
Bit Name Meaning Part
1 B0 EXU: Fuse/TmpSwich EXU Fuse Failure /Temperature switch SD
2 B1 IGCT Supervision IGCT checked failed AD
4 B2
8 B3
16 B4
32 B5
64 B6
128 B7
256 B8
512 B9
1024 B10
2048 B11
4096 B12
8192 B13
16384 B14
32768 B15 NOT USED
Unit: Type: PB Min: -32768 Max: 32767 Int. scaling: 1 == 1
9.26 (R / 183.10)
FAULT WORD 3 CONTROL HARDWARE (RESERVED)
Index Description: Control Hardware 3 fault word.
Bit Name Meaning Part
1 B0
2 B1
4 B2
8 B3
16 B4
32 B5
64 B6
128 B7
256 B8
512 B9
1024 B10
2048 B11
4096 B12
8192 B13
16384 B14
32768 B15 NOT USED
Unit: Type: PB Min: -32768 Max: 32767 Int. scaling: 1 == 1
9.27 (R / 183.12)
FAULT WORD DC LINK VOLTAGE
Index Description: DC link voltage fault word.
Bit Name Meaning Part
1 B0 DC Overvoltage DC Overvoltage Common
2 B1 DC OvervoltageMCB DC Overvoltage opening MCB Common
4 B2 DC Undervoltage DC Undervoltage Common
8 B3 NP Voltage NP Voltage Deviation Common
16 B4 INT0 Overvoltage INT0 Overvoltage Common
32 B5 DC Overvoltage1 DC Overvoltage 2nd INV Common
64 B6 DC OvervoltageMCB1 DC Overvoltage open MCB 2nd INV Common
128 B7 DC Undervoltage1 DC Undervoltage 2nd INV Common
256 B8 NP Voltage1 NP Voltage Deviation 2nd INV Common
512 B9 INT1 Overvoltage INT1 Overvoltage 2nd INV Common
1024 B10 DC Overvoltage2 DC Overvoltage 3rd INV Common
2048 B11 DC OvervoltageMCB2 DC Overvoltage open MCB 3rd INV Common
4096 B12 DC Undervoltage2 DC Undervoltage 3rd INV Common
8192 B13 NP Voltage2 NP Voltage Deviation 3rd INV Common
16384 B14
32768 B15 NOT USED
Unit: Type: PB Min: -32768 Max: 32767 Int. scaling: 1 == 1
9.28 (R / 183.13)
FAULT WORD 1 DC LINK VOLTAGE
Index Description: DC link voltage 1 fault word.
Bit Name Meaning Part
1 B0 INT2 Overvoltage INT2 Overvoltage 3rd INV Common
2 B1 EXU: BOD Activation EXU: BOD Activation Fault SD
4 B2 DC Overvoltage FT DC Overvoltage with Firing through AD, SD
8 B3 DC Overvoltage3 DC Overvoltage 4th INV Common
16 B4 DC OvervoltageMCB3 DC Overvoltage open MCB 4th INV Common
32 B5 DC Undervoltage3 DC Undervoltage 4th INV Common
64 B6 NP Voltage3 NP Voltage Deviation 4th INV Common
128 B7 INT3 Overvoltage INT3 Overvoltage 4th INV Common
256 B8
512 B9
1024 B10
2048 B11
4096 B12
8192 B13
16384 B14
32768 B15 NOT USED
Unit: Type: PB Min: -32768 Max: 32767 Int. scaling: 1 == 1
9.29 (R / 183.14)
FAULT WORD 2 DC LINK VOLTAGE (RESERVED)
Index Description: DC link voltage 2 fault word.
Bit Name Meaning Part
1 B0
2 B1
4 B2
8 B3
16 B4
32 B5
64 B6
128 B7
256 B8
512 B9
1024 B10
2048 B11
4096 B12
8192 B13
16384 B14
32768 B15 NOT USED
Unit: Type: PB Min: -32768 Max: 32767 Int. scaling: 1 == 1
9.30 (R / 183.16)
FAULT WORD CURRENT
Index Description: Current fault word.
Bit Name Meaning Part
1 B0 Overcurrent Overcurrent Common
2 B1 Phase A Lost Phase A lost Common
4 B2 Phase B Lost Phase B lost Common
8 B3 Phase C Lost Phase C lost Common
16 B4 INT0 2nd EarthFault INT0 2nd Earth Fault Common
32 B5 INT0 Overcurrent INT0 Overcurrent Common
64 B6 Overcurrent 1 Overcurrent 2nd INV Common
128 B7 Phase A Lost 1 Phase A lost 2nd INV Common
256 B8 Phase B Lost 1 Phase B lost 2nd INV Common
512 B9 Phase C Lost 1 Phase C lost 2nd INV Common
1024 B10 INT1 2nd EarthFault INT1 2nd Earth Fault 2nd INV Common
2048 B11 INT1 Overcurrent INT1 Overcurrent 2nd INV Common
4096 B12 Overcurrent 2 Overcurrent 3rd INV Common
8192 B13 Phase A Lost 2 Phase A lost 3rd INV Common
16384 B14 Phase B Lost 2 Phase B lost 3rd INV Common
32768 B15 NOT USED
Unit: Type: PB Min: -32768 Max: 32767 Int. scaling: 1 == 1
9.31 (R / 183.17)
FAULT WORD 1 CURRENT
Index Description: Current 1 fault word.
Bit Name Meaning Part
1 B0 Phase C Lost 2 Phase C lost 3rd INV Common
2 B1 INT2 2nd EarthFault INT2 2nd Earth Fault 3rd INV Common
4 B2 INT2 Overcurrent INT2 Overcurrent 3rd INV Common
8 B3 EXU: Overcurrent Excitation Overcurrent SD
16 B4 EXU: Alpha Min Flt Excitation Alpha Min Fault SD
32 B5 HighCurrent High Current (SW Overcurrent retry failed) ARU
64 B6 Overcurrent 3 Overcurrent 4th INV Common
128 B7 Phase A Lost 3 Phase A lost 4th INV Common
256 B8 Phase B Lost 3 Phase B lost 4th INV Common
512 B9 Phase C Lost 3 Phase C lost 4th INV Common
1024 B10 INT3 2nd EarthFault INT3 2th Earth Fault 4th INV Common
2048 B11 INT3 Overcurrent INT3 Overcurrent 4th INV Common
4096 B12
8192 B13
16384 B14
32768 B15 NOT USED
Unit: Type: PB Min: -32768 Max: 32767 Int. scaling: 1 == 1
9.32 (R / 183.18)
FAULT WORD 2 CURRENT (RESERVED)
Index Description: Current 2 fault word.
Bit Name Meaning Part
1 B0
2 B1
4 B2
8 B3
16 B4
32 B5
64 B6
128 B7
256 B8
512 B9
1024 B10
2048 B11
4096 B12
8192 B13
16384 B14
32768 B15 NOT USED
Unit: Type: PB Min: -32768 Max: 32767 Int. scaling: 1 == 1
9.33 (R / 183.20)
FAULT WORD SHORT CIRCUIT
Index Description: Short circuit fault word.
Bit Name Meaning Part
1 B0 CBU Short Circuit CBU Short Circuit Common
2 B1 INT0 ShortCircuit INT0 Short Circuit Common
4 B2 INT0 VLU ShortCirc INT0 VLU Short Circuit SD, AD
8 B3 INT1 ShortCircuit INT1 Short Circuit 2nd INV Common
16 B4 INT1 VLU ShortCirc INT1 VLU Short Circuit 2nd INV SD, AD
32 B5 INT2 ShortCircuit INT2 Short Circuit 3rd INV Common
64 B6 INT2 VLU ShortCirc INT2 VLU Short Circuit 3rd INV SD, AD
128 B7 INT0 DI/DT SuperVi INT0 DI/DT Supervision Common
256 B8 INT1 DI/DT SuperVi INT1 DI/DT Supervision 2nd INV Common
512 B9 INT2 DI/DT SuperVi INT2 DI/DT Supervision 3rd INV Common
1024 B10 INT3 DI/DT SuperVi INT3 DI/DT Supervision 4th INV Common
2048 B11 INT3 ShortCircuit INT3 Short Circuit 4th INV Common
4096 B12 INT3 VLU ShortCirc INT3 VLU Short Circuit 4th INV SD, AD
8192 B13
16384 B14
32768 B15 NOT USED
Unit: Type: PB Min: -32768 Max: 32767 Int. scaling: 1 == 1
9.34 (R / 183.21)
FAULT WORD 1 SHORT CIRCUIT (RESERVED)
Index Description: Short circuit 1 fault word.
Bit Name Meaning Part
1 B0
2 B1
4 B2
8 B3
16 B4
32 B5
64 B6
128 B7
256 B8
512 B9
1024 B10
2048 B11
4096 B12
8192 B13
16384 B14
32768 B15 NOT USED
Unit: Type: PB Min: -32768 Max: 32767 Int. scaling: 1 == 1
9.35 (R / 183.23)
FAULT WORD SWITCHING
Index Description: Switching fault word.
Bit Name Meaning Part
1 B0 SwitchingFreq 1ms Switching Frequency 1ms Common
2 B1 SwitchingFreq 50ms Switching Frequency 50ms Common
4 B2 SwitchingFreq250ms Switching Frequency 250ms Common
8 B3 SwitchingFreq 1s Switching Frequency 1s Common
16 B4 SwitchingFreq 1ms1 Switching Frequency 1ms 2nd INV Common
32 B5 SwitchingFreq 50ms1 Switching Frequency 50ms 2nd INV Common
64 B6 SwitchingFreq250ms1 Switching Frequency 250ms 2nd INV Common
128 B7 SwitchingFreq 1s 1 Switching Frequency 1s 2nd INV Common
256 B8 PUB: WrongSwitch 1 PUB: Wrong switching INT1 Common
512 B9 SwitchingFreq 1ms2 Switching Frequency 1 ms 3rd INV Common
1024 B10 SwitchingFreq 50ms2 Switching Frequency 50 ms 3rd INV Common
2048 B11 SwitchingFreq250ms2 Switching Frequency 250 ms 3rd INV Common
4096 B12 SwitchingFreq 1s 2 Switching Frequency 1 s 3rd INV Common
8192 B13 PUB: WrongSwitch 2 PUB: Wrong switching INT2 Common
16384 B14
32768 B15 NOT USED
Unit: Type: PB Min: -32768 Max: 32767 Int. scaling: 1 == 1
9.36 (R / 183.24)
FAULT WORD 1 SWITCHING
Index Description: Switching 1 fault word.
Bit Name Meaning Part
1 B0 SwitchingFreq 1ms3 Switching Frequency 1 ms 4th INV Common
2 B1 SwitchingFreq 50ms3 Switching Frequency 50 ms 4th INV Common
4 B2 SwitchingFreq250ms3 Switching Frequency 250 ms 4th INV Common
8 B3 SwitchingFreq 1s 3 Switching Frequency 1 s 4th INV Common
16 B4
32 B5
64 B6
128 B7
256 B8
512 B9
1024 B10
2048 B11
4096 B12
8192 B13
16384 B14
32768 B15 NOT USED
Unit: Type: PB Min: -32768 Max: 32767 Int. scaling: 1 == 1
9.37 (R / 183.26)
FAULT WORD NETWORK
Index Description: Network fault word.
Bit Name Meaning Part
1 B0 Network Disturbed Network Disturbance SD, AD
2 B1 Network Disturbed 1 Network Disturbance 1 SD, AD
4 B2 Network UnderVolt Network Undervoltage ARU
8 B3 Network OverVolt Network Overvoltage ARU
16 B4 Network Frequency Network Frequency ARU
32 B5 EXU: Undervoltage EXU: Undervoltage SD
64 B6 EXU: No Sync EXU: No Synchronization SD
128 B7 EXU: SupplyFreq EXU: Supply Frequency SD
256 B8
512 B9
1024 B10
2048 B11
4096 B12
8192 B13
16384 B14
32768 B15 NOT USED
Unit: Type: PB Min: -32768 Max: 32767 Int. scaling: 1 == 1
9.38 (R / 183.27)
FAULT WORD 1 NETWORK (RESERVED)
Index Description: Network 1 fault word.
Bit Name Meaning Part
1 B0
2 B1
4 B2
8 B3
16 B4
32 B5
64 B6
128 B7
256 B8
512 B9
1024 B10
2048 B11
4096 B12
8192 B13
16384 B14
32768 B15 NOT USED
Unit: Type: PB Min: -32768 Max: 32767 Int. scaling: 1 == 1
9.39 (R / 183.29)
FAULT WORD SPEED & POSITIONING
Index Description: Speed & Positioning fault word.
Bit Name Meaning Part
1 B0 Overfrequency Overfrequency SD, AD
2 B1 PositionMeasurement Position Measurement Fault SD, AD
4 B2 Speed Measurement Speed Measurement Fault SD, AD
8 B3 Encoder Mismatch Encoder Failure SD, AD
16 B4
32 B5
64 B6
128 B7
256 B8
512 B9
1024 B10
2048 B11
4096 B12
8192 B13
16384 B14
32768 B15 NOT USED
Unit: Type: PB Min: -32768 Max: 32767 Int. scaling: 1 == 1
9.40 (R / 183.30)
FAULT WORD 1 SPEED & POSITIONING (RES.)
Index Description: Speed & Positioning 1 fault word.
Bit Name Meaning Part
1 B0
2 B1
4 B2
8 B3
16 B4
32 B5
64 B6
128 B7
256 B8
512 B9
1024 B10
2048 B11
4096 B12
8192 B13
16384 B14
32768 B15 NOT USED
Unit: Type: PB Min: -32768 Max: 32767 Int. scaling: 1 == 1
9.41 (R / 183.32)
FAULT WORD GENERIC FAULTS
Index Description: Generic fault word.
Bit Name Meaning Part
1 B0 AMC: Fault Class 1 AMC: Fault Class 1 Common
2 B1 AMC: Fault Class 2 AMC: Fault Class 2 Common
4 B2 INT: Fault Class 1 INT: Fault Class 1 Common
8 B3 INT: Fault Class 2 INT: Fault Class 2 Common
16 B4
32 B5
64 B6
128 B7 CCB: Fault Class 1 CCB: Fault Class 1 SD
256 B8 CCB: Fault Class 2 CCB: Fault Class 2 SD
512 B9 CCB: Fault Class 3 CCB: Fault Class 3 SD
1024 B10 INT: MCB TripReq INT: MCB open command via INT – board. Common
2048 B11
4096 B12
8192 B13
16384 B14
32768 B15 NOT USED
Unit: Type: PB Min: -32768 Max: 32767 Int. scaling: 1 == 1
9.42 (R / 183.33)
FAULT WORD 1 GENERIC FAULTS (RESERVED)
Index Description: Generic 1 fault word.
Bit Name Meaning Part
1 B0
2 B1
4 B2
8 B3
16 B4
32 B5
64 B6
128 B7
256 B8
512 B9
1024 B10
2048 B11
4096 B12
8192 B13
16384 B14
32768 B15 NOT USED
Unit: Type: PB Min: -32768 Max: 32767 Int. scaling: 1 == 1
9.43 (R / 183.35)
FAULT WORD OTHER FAULTS
Index Description: Other faults fault word.
Bit Name Meaning Part
1 B0 Operating System AMC Operating System Fault Common
2 B1 INT0 Internal INT0 Internal Fault Common
4 B2 INT1 Internal INT1 Internal Fault Common
8 B3 INT2 Internal INT2 Internal Fault Common
16 B4 EXU: OperatingSys EXU: Operating System Fault SD
32 B5 EXU: Illegal Fault EXU: Illegal Fault SD
64 B6 EXU: CSM1 Timeout EXU: CSM1 Timeout SD
128 B7 EXU: BCO Fault EXU: BCO Fault SD
256 B8
512 B9
1024 B10
2048 B11
4096 B12
8192 B13
16384 B14
32768 B15 NOT USED
Unit: Type: PB Min: -32768 Max: 32767 Int. scaling: 1 == 1
9.44 (R / 183.36)
FAULT WORD 1 OTHER FAULTS (RESERVED)
Index Description: Other faults 1 fault word.
Bit Name Meaning Part
1 B0
2 B1
4 B2
8 B3
16 B4
32 B5
64 B6
128 B7
256 B8
512 B9
1024 B10
2048 B11
4096 B12
8192 B13
16384 B14
32768 B15 NOT USED
Unit: Type: PB Min: -32768 Max: 32767 Int. scaling: 1 == 1
9.49 (R / 183.01)
ALARM WORD COMMUNICATION
Index Description: Communication alarm word.
Bit Name Meaning Part
1 B0 EXU: PAI Communication EXU PAI Communication Fault SD
2 B1
4 B2
8 B3
16 B4
32 B5
64 B6
128 B7
256 B8
512 B9
1024 B10
2048 B11
4096 B12
8192 B13
16384 B14
32768 B15 NOT USED
Unit: Type: PB Min: -32768 Max: 32767 Int. scaling: 1 == 1
9.50 (R / 183.05)
ALARM WORD CONTROL HARDWARE
Index Description: Control Hardware alarm word.
Bit Name Meaning Part
1 B0 INT0 ASE Fault INT0 ASE Fault ARU
2 B1 INT0 Wrong EPLD Ver INT0 Wrong EPLD Version Common
4 B2 INT0 Wrong PUPA Ver INT0 Wrong PUPA Version Common
8 B3 INT0 PUPA Corrupted INT0 PUPA FLASH Corrupted Common
16 B4 INT3 ASE Fault INT3 ASE Fault ARU
32 B5 INT3 Wrong EPLD Ver INT3 Wrong EPLD Version Common
64 B6 INT3 Wrong PUPA Ver INT3 Wrong PUPA Version Common
128 B7 INT3 PUPA Corrupted INT3 PUPA FLASH Corrupted Common
256 B8 INT0 Internal INT0 Internal Fault Common
512 B9 INT1 Internal INT1 Internal Fault Common
1024 B10 INT2 Internal INT2 Internal Fault Common
2048 B11 INT3 Internal INT3 Internal Fault Common
4096 B12
8192 B13
16384 B14
32768 B15 NOT USED
Unit: Type: PB Min: -32768 Max: 32767 Int. scaling: 1 == 1
9.51 (R / 183.06)
ALARM WORD 1 CONTROL HARDWARE
Index Description: Control Hardware 1 alarm word.
Bit Name Meaning Part
1 B0 INT1 ASE Fault INT1 ASE Fault 2nd INV ARU
2 B1 INT1 Wrong EPLD Ver INT1 Wrong EPLD Version 2nd INV Common
4 B2 INT1 Wrong PUPA Ver INT1 Wrong PUPA Version 2nd INV Common
8 B3 INT1 PUPA Corrupted INT1 PUPA FLASH Corrupted 2nd INV Common
16 B4 INT2 ASE Fault INT2 ASE Fault 3rd INV ARU
32 B5 INT2 Wrong EPLD Ver INT2 Wrong EPLD Version 3rd INV Common
64 B6 INT2 Wrong PUPA Ver INT2 Wrong PUPA Version 3rd INV Common
128 B7 INT2 PUPA Corrupted INT2 PUPA FLASH Corrupted 3rd INV Common
256 B8 PUB: Wrong EPLD Ver PUB Wrong EPLD Version Common
512 B9 INT EPLD Versions INT PLD Versions Mismatch Common
1024 B10 INT PUPA INT PUPA Versions Mismatch Common
2048 B11
4096 B12
8192 B13
16384 B14
32768 B15 NOT USED
Unit: Type: PB Min: -32768 Max: 32767 Int. scaling: 1 == 1
9.52 (R / 183.11)
ALARM WORD DC LINK VOLTAGE
Index Description: DC link voltage alarm word.
Bit Name Meaning Part
1 B0 Ridethrough Ridethrough Common
2 B1
4 B2
8 B3
16 B4
32 B5
64 B6
128 B7
256 B8
512 B9
1024 B10
2048 B11
4096 B12
8192 B13
16384 B14
32768 B15 NOT USED
Unit: Type: PB Min: -32768 Max: 32767 Int. scaling: 1 == 1
9.53 (R / 183.15)
ALARM WORD CURRENT
Index Description: Current alarm word.
Bit Name Meaning Part
1 B0 High Current High Current Common
2 B1
4 B2
8 B3
16 B4
32 B5
64 B6
128 B7
256 B8
512 B9
1024 B10
2048 B11
4096 B12
8192 B13
16384 B14
32768 B15 NOT USED
Unit: Type: PB Min: -32768 Max: 32767 Int. scaling: 1 == 1
9.54 (R / 183.19)
ALARM WORD SHORT CIRCUIT
Index Description: Short Circuit alarm word.
Bit Name Meaning Part
1 B0 INT0 DI/DT SuperVi INT0 DI/DT Supervision (Alarm) Common
2 B1 INT1 DI/DT SuperVi INT1 DI/DT Supervision 2nd inv (Alarm) Common
4 B2 INT2 DI/DT SuperVi INT2 DI/DT Supervision 3rd inv (Alarm) Common
8 B3 INT3 DI/DT SuperVi INT2 DI/DT Supervision 4th inv (Alarm) Common
16 B4
32 B5
64 B6
128 B7
256 B8
512 B9
1024 B10
2048 B11
4096 B12
8192 B13
16384 B14
32768 B15 NOT USED
Unit: Type: PB Min: -32768 Max: 32767 Int. scaling: 1 == 1
9.55 (R / 183.22)
ALARM WORD SWITCHING (RESERVED)
Index Description: Switching alarm word.
Bit Name Meaning Part
1 B0
2 B1
4 B2
8 B3
16 B4
32 B5
64 B6
128 B7
256 B8
512 B9
1024 B10
2048 B11
4096 B12
8192 B13
16384 B14
32768 B15 NOT USED
Unit: Type: PB Min: -32768 Max: 32767 Int. scaling: 1 == 1
9.56 (R / 183.25)
ALARM WORD NETWORK
Index Description: Network alarm word.
Bit Name Meaning Part
1 B0 HighNetworkVoltage High Network Voltage ARU
2 B1 FrequencyNotNominal Frequency Not Nominal ARU
4 B2 No Synchronization No Synchronization ARU
8 B3
16 B4
32 B5
64 B6
128 B7
256 B8
512 B9
1024 B10
2048 B11
4096 B12
8192 B13
16384 B14
32768 B15 NOT USED
Unit: Type: PB Min: -32768 Max: 32767 Int. scaling: 1 == 1
9.57 (R / 183.28)
ALARM WORD SPEED & POSITIONING
Index Description: Speed and Position Alarm Word.
Bit Name Meaning Part
1 B0 Speed Measurement Speed Measurement Alarm AD, SD
2 B1 PositionMeasurement Position Measurement Alarm SD
4 B2
8 B3
16 B4
32 B5
64 B6
128 B7
256 B8
512 B9
1024 B10
2048 B11
4096 B12
8192 B13
16384 B14
32768 B15 NOT USED
Unit: Type: PB Min: -32768 Max: 32767 Int. scaling: 1 == 1
9.58 (R / 183.31)
ALARM WORD GENERIC ALARMS
Index Description: Network alarm word.
Bit Name Meaning Part
1 B0 PUB: INT0 Faulted PUB: INT0 Faulted Common
2 B1 PUB: INT1 Faulted PUB: INT1 Faulted Common
4 B2 PUB: INT2 Faulted PUB: INT2 Faulted Common
8 B3 PUB: INT3 Faulted PUB: INT3 Faulted Common
16 B4
32 B5
64 B6
128 B7
256 B8
512 B9
1024 B10
2048 B11
4096 B12
8192 B13
16384 B14
32768 B15 NOT USED
Unit: Type: PB Min: -32768 Max: 32767 Int. scaling: 1 == 1
9.59 (R / 183.34)
ALARM WORD OTHER ALARMS (RESERVED)
Index Description: Other alarm word.
Bit Name Meaning Part
1 B0
2 B1
4 B2
8 B3
16 B4
32 B5
64 B6
128 B7
256 B8
512 B9
1024 B10
2048 B11
4096 B12
8192 B13
16384 B14
32768 B15 NOT USED
Unit: Type: PB Min: -32768 Max: 32767 Int. scaling: 1 == 1
16.02 ParameterLock
Index Description: Unauthorised parameter changes via control panel CDP 312 or DrivesWindow can be inhibited
using the “ParameterLock” for parameter groups 10 … 99.
Locked parameter changes are disabled
Open parameter changes are enabled
unit: type: B Min: 0 Max: 1 Def: OPEN Int. scaling: 1 == 1
16.03 Passcode
Index Description: This parameter selects the pass code for the Parameter Lock. The default value of this parameter is 0.
In order to open the Parameter Lock change the value to 358. After the Parameter Lock is opened the
value is automatically changed back to 0.
unit: type: I Min: 0 Max: 9999 Def: 0 Int. scaling: 1 == 1
If both 16.07 and 16.08 are set to ‘YES’, ARU starts automatically only when any of the multidrive
INUs is running. If no INU is running, ARU will also stop itself.
NOTE: Similar command can be given on INU1 side, which is lead to ARU control through the
PFF-link. If diode mode of the ARU is really used, the request is recommended to be done at the
master INU side.
MCB
(PFF Link) YES
1 &
Control
INU1_MCB_Status_closed b15 b15
OR
ARU
Run - Control
>
READY REF
RdyRef
REC STATUS BITS 1
Group name:
19 DATA STORAGE
Description: This parameter group consists of the unconnected parameters for linking, testing and commissioning
purposes.
Example:
APC2, AC80 AMC3
Application DataSet Table
Controller
Software DS VAL Address
A*
ACSRX : : Assignment For
DS14 : : of DataSet Drives Window
Index: 1 1 Group Index Tool
Index: 2 14 2 92 08 19.01
A* : Value assigned
for drive control, for Index: 3 3
example tension
controller output : :
Address of DataSet 14 Index 2 is 92.08. By setting parameter 92.08 to value 19.01, the value A*
can be trended with DrivesWindow monitor tool.
APC2, AC80 AMC3
Application DataSet Table
Controller
Software DS VAL Address
B*
ACSRX : : Assignment For
DS15 : : of DataSet Drives Window
Index: 1 1 Group Index Tool
19.01 DATA 1
Index Description: Parameter setting or reading from the overriding system.
Example:
Signal from the Dataset 18 Index 3 is required for the trending measurement in the DrivesWindow
tool. Set parameter 90.15 DATASET 18 VAL 3 to the value 1901 (group19 + index 01). Assign
parameter 19.01 DATA 1 to the selected trending channel in DrivesWindow.
unit: Type: R Min: -32768 Max: 32767 Int. scaling: 1 == 1
19.02 DATA 2
Index Description: See 19.01 DATA 1
unit: Type: R Min: -32768 Max: 32767 Int. scaling: 1 == 1
19.03 DATA 3
Index Description: See 19.01 DATA 1
unit: Type: R Min: -32768 Max: 32767 Int. scaling: 1 == 1
19.04 DATA 4
Index Description: See 19.01 DATA 1
unit: Type: R Min: -32768 Max: 32767 Int. scaling: 1 == 1
19.05 DATA 5
Index Description: See 19.01 DATA 1
unit: Type: R Min: -32768 Max: 32767 Int. scaling: 1 == 1
19.06 DATA 6
Index Description: See 19.01 DATA 1
unit: Type: R Min: -32768 Max: 32767 Int. scaling: 1 == 1
19.07 DATA 7
Index Description: See 19.01 DATA 1
unit: Type: R Min: -32768 Max: 32767 Int. scaling: 1 == 1
19.08 DATA 8
Index Description: See 19.01 DATA 1
unit: Type: R Min: -32768 Max: 32767 Int. scaling: 1 == 1
32.02 DischargeTimeout
Index Description: Timeout for the discharging sequence. Maximum elapsed time for the DC-link discharging, before
the fault will occure.
Unit: s Type: R Min: 0 Max: 120 Def: 60 Int. scaling: 1==1
32.03 DischargedLevel
Index Description: DC Voltage level at which the DC link is considered as discharged.
Before the DC-link is considered as a discharged (and for example the cabinet door locking is
released), all the following three conditions has to be fullfilled (true):
- the measured DC voltage level (161.08) has to be below the level defined by this parameter 32.05
- the voltage controller status "voltage controller discharge active" (172.02 bit0) has to be "0"
- the voltage controller status "voltage controller discharge finished" (172.02 bit1) has to be "1"
Unit: V Type: R Min: 0 Max: 50 Def: 50 Int. scaling: 1==1
This group name identifies which communication hardware module is connected to the ACS 1000
drive. Some option modules support multiple protocols which can be selected with a parameter. The
setup parameters can be modified either by using the drive panel or by PC software, e.g. Drives
Window.
Note:
The changes to the parameters in group 51 do not come into effect immediately but only when the
power of the fieldbus adapters was switched off and then switched on again.
CAUTION!
! Handle the fibre optic cable with care. Do not touch the ends with bare hands, as fibre
optic cables are extremely sensitive to dirt.
Fieldbus
FIELDBUS CONNECTION
The ACS6000 can be connected to an external control system – usually a fieldbus – using an adapter module. The fieldbus adapter
module (FBA) is connected to Channel 0 (CH0) on the ACS6000 AMC3 board by using a DDCS-protocol fibre optic link. The
drive can receive all of its control information from the fieldbus.
Data Flow
Fieldbus
Parameter R/W Requests
Master (PLC)
Actual Values (ACT1)
Control Word (OCW)
Fieldbus
Fieldbus Other
Adapter devices
ACS6000
AC70, AC80 & FCI Module - Bus The Position can be calculated as follow:
Position Par. 70.01
16 x hundred number in position
101 17
number + rest of position number
: :
112 28 For example:
201 33 DRIENG / Position = 711
: :
212 44 711 Þ 7 x 16 + 11 = 123
701 113
: : Þ 70.01 = 123
712 124
75.01 CommModule
Index Description: This parameter is used, if a FBA module (Field Bus Adapter) or an ABB Advant controller (AF100-
Bus) is used to communicate with ARU. The module is connected channel 0 (CH0).
1 = None ARU is controlled by MASTER INU (INU1) or locally by ARU control
panel.
2 = Dset1 R/W ARU is controlled through the communication link (channel CH0) by using
data sets 1 to 8. This is a typical setting for the use of a fieldbus adapter
module.
Note!
If parameter 75.01 COMM MODULE is set to “DSET1 R/W”, Parameter
Group 90 (DATASET RECEIVE ADDRESS) and Group 91 (DATASET
TRANSMIT ADDRESS) will be opened.
3 = Dset1 R Read only mode (from AMC). Datasets 2, 4, 6 and 8 can be used for reading
data from the drive to the advant control or the fieldbus.
4 = Dset10 R/W The drive is controlled through the communication link (channel CH0) by
using data sets 10 to 31. This is a typical setting for use with a ABB Advant
controlled AF100-Bus adapter module (for example APC2 , AC70, AC80,
FCI, NPBA-02, NCSA-01).
Note!
If parameter 75.01 COMM MODULE is set to “DSET10 R/W”, Parameter
Group 92 & 93 (DATASET RECEIVE ADDRESS) and Group 94 & 95
(DATASET TRANSMIT ADDRESS) will be open.
5 = Dset10 R Read only mode (from AMC). Odd datasets 11, 13, 15... 31 can be used for
reading data from the drive to the advant control or the fieldbus.
6 = Dset1_10 R Read only mode (from AMC). All the datasets defined for transporting data
from the AMC (in groups 91, 94, 95) can be used for reading data from the
drive to the advant control or the fieldbus.
Overriding
System AMC 3
Address
DataSet Assignment AMC
Table of DataSet Table
Group
DDCS link
1 90.01...90.12
3
CH0 5
7
NOTE !
This group 90 is visible only if the FBA Dset1 is selected (75.01).
Group name:
91 D SET TR ADDR
Description: Signal addresses for the data transmitted to the overriding system.
The format is x(xyy), where (x)x = Group and yy = Index.
Overriding
System AMC 3
Address
DataSet Assignment AMC
Table of DataSet Table
Group
DDCS link
2 91.01...91.12
4
CH0 6
8
NOTE !
This group 91 is visible only if the FBA Dset1 is selected (75.01).
Parameter Setting
Parameter
Main Status Word Selection
Motor Current
100 2 (Index)
Index
Value
Par.: 91. 03 : 107 PAR
91 Group Read selected value
(Group 1.07) and
3 Index
transmitt it to Fieldbus
(free pro- InitValue
107
grammable)
D SET 2 VAL 3 Name
107 PARRD
1 (Group)
DIV Group
100 7 (Index)
Index
Value
Motor Torque
Par.: 91. 04 : 109 PAR
Read selected value
91 Group (Group 1.09) and
4 Index transmitt it to Fieldbus WriteDataSet values
Figure 91-2: (free pro- InitValue
to fieldbus
109
grammable)
D SET 4 VAL 1 Name
109 PARRD
1 (Group) DSWRITE
Overview: DIV
9 (Index)
Group
4 DataSet
100
Transmit data Index
Data Set 4 Value 1
Value Value 1
to fieldbus. Data Set 4 Value 2
Value 2
Data Set 4 Value 3
Value 3
Group name:
92 D SET REC ADDR
Description: Signal addresses for the data received from the overriding system.
The format is x(xyy), where (x)x = Group and yy = Index.
Overriding
System AMC 3
Address
DataSet Assignment AMC
Table of DataSet Table
Group
DDCS link 10
92.01 ... 92.33
12 93.01 ... 93.12
:
CH0 :
38
NOTE !
This group 92 is visible only if the FBA Dset10 is selected (75.01).
Group name:
93 D SET REC ADDR
Description: Signal addresses for the data received from the overriding system.
The format is x(xyy), where (x)x = Group and yy = Index.
(see Figure 92-1 Overview received data from fieldbus)
NOTE !
This group 93 is visible only if the FBA Dset10 is selected (75.01).
Group name:
94 D SET TR ADDR
Description: Signal addresses for the data transmitted to the overriding system.
The format is x(xyy), where (x)x = Group and yy = Index.
Overriding
System AMC 3
Address
DataSet Assignment AMC
Table of DataSet Table
Group
DDCS link 11
94.01 ... 94.33
13 95.01 ... 95.12
:
CH0 :
39
NOTE !
This group 93 is visible only if the FBA Dset10 is selected (75.01).
Group name:
95 D SET TR ADDR
Description: Signal addresses for the data transmitted to the overriding system.
The format is x(xyy), where (x)x = Group and yy = Index.
(see Figure 94-1 Overview transmit data to fieldbus)
NOTE !
This group 93 is visible only if the FBA Dset10 is selected (75.01).
Parameter Setting
Parameter
Main Status Word Selection
Motor Current
100 2 (Index)
Index
Value
Par.: 94. 03 : 107 PAR
94 Group Read selected value
(Group 1.07) and transmitt
3 Index
it to AF100-Bus
(free pro- InitValue
107
grammable)
Name
107 PARRD
D SET 11 VAL 3 1 (Group)
DIV Group
100 7 (Index)
Index
Value
Motor Torque
Par.: 94. 04 : 109 PAR
94 Group Read selected value
(Group 1.09) and transmitt WriteDataSet values
4 Index it to AF100-Bus
(free pro-
to AF100-Bus
109 InitValue
grammable)
Name
109 PARRD
D SET 13 VAL 1 1 (Group) DSWRITE
DIV Group
100 9 (Index) 13 DataSet
Index
Data Set 13 Value 1
Value Value 1
Data Set 13 Value 2
Value 2
Data Set 13 Value 3
Value 3
98.01 YEAR
Index Description: Present year.
unit: type: I Min: 1997 Max: 2096 Def: 1997 Int. scaling: 1 == 1
98.02 MONTH
Index Description: Present month.
unit: type: I Min: 1 Max: 12 Def: 1 Int. scaling: 1 == 1
98.03 DAY
Index Description: Present day.
unit: type: I Min: 1 Max: 31 Def: 1 Int. scaling: 1 == 1
98.04 HOUR
Index Description: Present hour.
unit: type: I Min: 0 Max: 23 Def: 0 Int. scaling: 1 == 1
98.05 MINUTE
Index Description: Present minute.
unit: type: I Min: 0 Max: 59 Def: 0 Int. scaling: 1 == 1
98.06 SECOND
Index Description: Present second.
unit: Seconds type: I Min: 0 Max: 59 Def: 0 Int. scaling: 1 == 1
99.01 InitializationDly
Index Description: Delay time for the Main State Machine (MSM) initialisation sequence (= sequence after connecting
AMC3 24VDC aux power). During this delay time all the FCB faults and alarms are masked (S800
I/O system has to have time to initialise)
Unit: s Type: R Min: 2 Max: 30 Def: 25 Int. scaling: 1 == 1
99.03 TrafoAntiSaturDev
Index Description: Main transformer antisaturation equipment functionality enable/disable.
0 = ASE NotUsed ASE will be not used (not automatically enabled after run command).
1 = ASE Enable ASE is enabled after an start (run) command (after modulation started).
Unit: Type: B Min: 0 Max: 1 Def: 1 Int. scaling: 1 == 1
10 MOTOR CURRENT
Index: Description: Measured motor current absolute value (rms).
Unit: A Type: R Min: Max: Int. scaling: 10 == 1 A
scaling factor
Each parameter has two different gateways to write the value: integer format or decimal. Finally, the result is exactly
same in the AMC program. This relation is always shown in the signal and parameter table as shown above.
For the ARU control, it is not recommended to use any Advant Controller nor fieldbus module etc., because the option
‘MSTR INU1’ (default) in the parameter 11.01 ‘EXT STRT STOP’ is handling the ARU controlling . As this option is
selected, the master INU takes automatically care of the right operation and starting of the ARU via Power Feed Forward –
link (ARU AMC channel nr 6). Additionally, the ARU behaviour can be configured in the parameters of group 16.
If for some reason ARU controlling has to be done by some Advant Controller, it can be established similar way like for the
INU. Then the timing and co-operation of the INU and ARU have to be observed separately. Please refer to the appendix
part of the INU manual.
If data needs to be read from the ARU control to the automation e.g. for monitoring purposes, it can be easily done by
selecting ‘R’ (read only) options of the parameter 75.01 ‘CommModule’.
AF100 - Bus
Fieldbus (e.g. Profibus)
Fieldbus (Modbus)
MODBUS (RS485)
Service Tool
e.g. Drive Window
X3 X1
RS485 AC80
NMBC-01 Drive Bus
(Modbus-Interface)
CDP 80 CDP 80
X2 X4
I/O Interface
DDCS Protocol
CDP80 - Panel
For example:
receive DataSet 1 from overriding system
transmit Data Set 2 to overriding system
FIELDBUS
AF100 APPL
Gr.94 Data Set 11
Data Word 1 Data Word 2 Data Word 3
SW ACT1 ACT2
For example:
receive Dataset 10 from overriding system
transmit Dataset 11 to overriding system
AF100 BUS
can be activated
from every test state VOLTAGE
OFF
TEST_FAILED
ON INHIBIT
NOT RDY ON
Emergency Emergency
OFF (OFF 1) STOP (OFF 3) OFF (OFF 2)
NOT ON NOT OFF_3_N NOT OFF_2_N
(NOT ON) & (OFF_2_N) & (OFF_3_N)
2 TEST SEQ
8 OFF1 STOP 10 OFF3 STOP 12 OFF2 SEQ
Operation inhibit SEQ SEQ
(ON - ) &
block pulses main power off RDY ON
(TEST_PRG_ACTIVE) & (NOT RUN) & (MCB_ON) (NOT RUN) & (NOT MCB_ON)
WAIT OFF1 WAIT OFF3
(NOT TEST_FAILED)
STOP STOP
(ON - ) &
(NOT TEST_PRG_ACTIVE)
6 DRV STOP1 7 DRV STOP2 ZERO_SPEED & ZERO_CURRENT
SEQ SEQ
3 AUX ON SEQ
AUX ON
READY FOR
TEST
(FIELD_ON) OR (MCB_ON)
(RESET- ) &
NOT TEST_PRG_RUN TRIPPED_4 TRIPPED
(NOT FAULT_PENDING) &
RUN -
(ON) &
(RESET- ) &
(NOT MCB_ON)(1)
(NOT FAULT_PENDING)
1nn3 TEST END SEQ
test states 5 DRV START SEQ
(RESET- ) &
RDY REF (NOT FAULT_PENDING) &
(NOT ON)(1)
(RESET- ) &
(NOT FAULT_PENDING) &
(ON) &
(MCB_ON) (1)