Professional Documents
Culture Documents
All configurations of the QUEST HF Series X-ray Generators have not yet been certified as being compliant with the regulatory and
design standards or EMI/EMC compatibility as per this manual. Please contact Quantum regarding the certification status of specific
configurations.
In the table below, an “X” indicates that the applicable standard is certified as being met for that configuration of the QUEST HF
Series X-ray Generators.
MODEL
REGULATORY
STANDARD
QG-25
QG-32
QG-40
QG-50
QG-25-5
QG-32-2
QG-32-3
QG-32-5
QG-40-2
QG-40-3
QG-40-5
QG-50-3
QG-20-SE
QG-32-SE
QG-40-SE
QG-50-SE
EC Directive
93/42/EEC
concerning X X X X X X X X X X X X
medical devices *
UL60601-1, IEC
60601-1 X X X X X X X X X X X X X
EMC compatibility
per MDD X X X X X X X X X X X X
* All models denoted above meet CE when equipped with External High Speed Starter Option (QG-HSS); the Internal High Speed
Starter Option (Q-HSS) has not yet been qualified for CE mark
Service Manual
This manual is copyrighted and all rights are reserved. No portion of this document
may be copied, photocopied, reproduced, translated, or reduced to any electronic
medium or machine readable form without prior consent in writing from Quantum
Medical Imaging, LLC. (QMI)
G 5/15/02 Incorporated ECO 0642, 0748, 0753, 0770, 0787, 0803, 0809,
0821, 0827, 0829, 0830, 0847, 0859, 0881, 0888
J 11/11/02 Incorporated ECO 0936, 1003, 1009, 1010, 1017, 1028, 1030
K 3/31/03 Incorporated ECO 1093, 1102, 1103, 1107, 1115, 1124, 1146
N 12/19/03 Incorporated ECO 1144, 1216, 1347, 1359, 1362, 1380, 1383,
1400
CHAPTER 1 - SPECIFICATIONS
SYSTEM CONFIGURATIONS ................................................................. 1-3
PHYSICAL SPECIFICATIONS ................................................................. 1-5
GENERATOR CABINET SPECIFICATIONS ......................................... 1-5
OPERATOR CONTROL PANEL SPECIFICATIONS ............................... 1-5
QUEST HF Control Panel: ........................................................ 1-5
SYSTEM SPECIFICATIONS .............................................................. 1-5
POWER REQUIREMENTS ...................................................................... 1-6
SINGLE-PHASE X-RAY GENERATORS ............................................... 1-7
25 kW Single Phase (Model QG-25) ........................................... 1-7
25 kW Single Phase (Model QG-25-5)* ...................................... 1-7
32 kW Single Phase (Model QG-32) ........................................... 1-7
32 kW Single Phase (Model QG-32-5)* ...................................... 1-7
40 kW Single Phase (Model QG-40) ........................................... 1-7
40 kW Single Phase (Model QG-40-5)* ...................................... 1-7
20 kW Single Phase, Stored Energy ........................................... 1-8
32 kW Single Phase, Stored Energy ........................................... 1-8
40 kW Single Phase, Stored Energy ........................................... 1-8
50 kW Single Phase, Stored Energy ........................................... 1-8
THREE-PHASE X-RAY GENERATORS ................................................ 1-9
32 kW Three Phase (Model QG-32-2) ........................................ 1-9
32 kW Three Phase (Model QG-32-3) ........................................ 1-9
40 kW Three Phase (Model QG-40-2) ........................................ 1-9
40 kW Three Phase (Model QG-40-3) ........................................ 1-9
50 kW Three Phase (Model QG-50-2) ........................................ 1-9
50 kW Three Phase (Model QG-50-3) ........................................ 1-9
65 kW Three Phase (Model QG-65) ..........................................1-10
80 kW Three Phase (Model QG-80) ..........................................1-10
HIGH-SPEED STARTER POWER REQUIREMENTS ............................1-10
GENERATOR AUXILIARY POWER SUPPLIES ..........................................1-15
PERFORMANCE SPECIFICATIONS ........................................................1-15
SYSTEM OPTIONS ..............................................................................1-19
SYSTEM OPERATING ENVIRONMENT ...................................................1-19
NON-OPERATING ENVIRONMENT ........................................................1-19
CHAPTER 3 - CALIBRATION
OVERVIEW .......................................................................................... 3-3
REQUIRED TOOLS AND MATERIALS ............................................... 3-3
SYSTEM CONFIGURATION ............................................................. 3-6
Printer On/Off Setting .............................................................. 3-7
Generator Configuration/Derating Settings ................................ 3-8
AEC Setting ............................................................................. 3-9
Rotor Drive Setting .................................................................3-10
CHAPTER 6 - DIAGRAMS
Single-Phase (Non-STORED ENERGY) X-ray Generators,
25, 32 and 40 kW Parts Location Diagram ............................................ 6-3
Single-Phase (STORED ENERGY) X-ray Generators,
20, 32 40 and 50 kW Parts Location Diagram ........................................ 6-5
Three-Phase X-ray Generators, 32 and 40 kW Parts Location Diagram ..... 6-7
Three-Phase X-ray Generators, 50, 65 and 80 kW Parts Location Diagram 6-9
Three-Phase X-ray Generators, 50, 65 and 80 kW (with QMI-HSS)
Parts Location Diagram ..................................................................... 6-11
System Cabling Diagram (Non-HSS Systems) ....................................... 6-13
SPECIFICATIONS
1-1
1-2
Chapter 1 Specifications
SYSTEM CONFIGURATIONS
The tables below show the model numbers of the components in each type of QUEST
HF SeriesTM X-ray Generator system (hereinafter referred to as the "HF Series X-ray
Generators"):
Single-Phase Model Generators
GENERATOR X-RAY
SYSTEM CATALOG SYSTEM
CABINET CONTROL
TYPE NO. MODEL
MODEL MODEL
GENERATOR X-RAY
SYSTEM CATALOG SYSTEM
CABINET CONTROL
TYPE NO. MODEL
MODEL MODEL
QUEST HF
QG-200-SE QG-20-SE QG-20G-SE QG-200
20 kW
QUEST HF
QG-320-SE QG-32-SE QG-32G-SE QG-320
32 kW
QUEST HF
QG-400-SE QG-40-SE QG-40G-SE QG-400
40 kW
Three-Phase Model Generators
GENERATOR X-RAY
SYSTEM CATALOG SYSTEM
CABINET CONTROL
TYPE NO. MODEL
MODEL MODEL
GENERATOR X-RAY
SYSTEM CATALOG SYSTEM
CABINET CONTROL
TYPE NO. MODEL
MODEL MODEL
PHYSICAL SPECIFICATIONS
The following are physical specifications of the HF Series X-ray Generators:
GENERATOR CABINET SPECIFICATIONS
Width: 24.0 inches (609.6 mm)
Depth: 20.0 inches (508.0 mm)
Height: 34.7 inches (881.4 mm)
Weights:
Single-Phase (non-SE units): 298 lbs. (135.2 kg)
20 kW STORED ENERGY unit: 344 lbs. (156.0 kg)
32, 40 and 50 kW Stored
Energy (SE) units: 431 lbs. (195.5 kg
50, 65, 80 kW Three-Phase
units): 380 lbs. (712.4 kg) w/o internal HSS
388 lbs. (176.0 kg) w/internal HSS
OPERATOR CONTROL PANEL SPECIFICATIONS
QUEST HF Control Panel:
Width: 13.75 inches (349.3 mm)
Depth: 11.6 inches (294.6 mm)
Height (without pedestal): 3.17 inches (80.5 mm)
Height (with pedestal): 36.5 inches (927.4 mm)
Weight (without pedestal): 4 lbs. (1.8 kg)
Weight (with pedestal): 24 lbs. (10.9 kg)
SYSTEM SPECIFICATIONS
System Compatibility: Compatible with all Quantum Medical
Imaging tube stands, overhead tube
cranes, radiographic tables and wall stands
Tube Compatibility: Toshiba Models E7239X, E7242X, E7252X,
E7254X, E7255X, E7813X, E7869X
Varian Models RAD-8, RAD-13, RAD-14,
RAD-21, RAD-44, RAD-56, RAD-60,
RAD-68, RAD-74, RAD-92, A192, A272,
A292
Dunlee Models PX 1302, PX 1429, PX 1436,
PX 1312, DU 309, DA 1092
(For tube types not listed, consult factory.)
Collimators: Huestis Manual, Model 150MC
Huestis Automatic, Model 150PBL
Huestis Selectable, Model 150A,
Progeny Linear MC150 (Manual)
Progeny Linear II and Linear IV
(Automatic)
Note: The HF Series radiographic systems are compatible with any
automatic collimating system that provides an isolated nor-
mally open switch that closes when the Automatic Collima-
tion System presents an “EXPOSURE READY” mode to the
*RECOMMENDED
TO GENERATOR
TRANSFORMER
VOLTAGE (VAC)
(AT FULL-LOAD
NOMINAL LINE
DISTRIBUTION
CATALOG NO.
OUTPUT (kW)
MAX. POWER
DISCONNECT
GENERATOR
GENERATOR
RESISTANCE
MODEL NO.
CAPACITY
*SERVICE
RATING
RMS)
208 #4 AWG 100 AMPS 30 KVA 0.06 OHMS
QG-250 QG-25 25
240 #4 AWG 80 AMPS 30 KVA 0.08 OHMS
NOTE: All installations must meet the requirements of local electrical codes.
*
*RECOMMENDED
TO GENERATOR
TRANSFORMER
VOLTAGE (VAC)
(AT FULL-LOAD
NOMINAL LINE
DISTRIBUTION
CATALOG NO.
OUTPUT (kW)
MAX. POWER
DISCONNECT
GENERATOR
GENERATOR
RESISTANCE
MODEL NO.
CAPACITY
*SERVICE
RATING
RMS)
380 #6 AWG 60 AMPS 32 KVA 0.028 OHMS
QG-320-5,
QG-32-5 32
QG-3200-5 415 #6 AWG 70 AMPS 40 KVA 0.024 OHMS
QG-400-5,
QG-40-5 40
QG-4000-5 415 #4 AWG 90 AMPS 50 KVA 0.020 OHMS
*NOTE: All installations must meet the requirements of local electrical codes.
*
*RECOMMENDED
TO GENERATOR
TRANSFORMER
VOLTAGE (VAC)
NOMINAL LINE
DISTRIBUTION
CATALOG NO.
OUTPUT (kW)
MAX. POWER
DISCONNECT
GENERATOR
GENERATOR
RESISTANCE
MODEL NO.
CAPACITY
*SERVICE
RATING
380 #6 AWG 60 AMPS 50 KVA 0.23 OHMS
QG-320, 32
QG-400, QG-32-3, (QG-32-3)
440 #6 AWG 60 AMPS 50 KVA 0.33 OHMS
QG-3200, 40
QG-40-3
QG-4000 (QG-40-3) #6 AWG 50 AMPS 50 KVA 0.4 OHMS
480
QG-500
QG-50 50 440 #6 AWG 80 AMPS 65 KVA 0.20 OHMS
QG-5000
QG-8000 QG-80 80 440 #4 AWG 100 AMPS 100 KVA 0.14 OHMS
*NOTE: All installations must meet the requirements of local electrical codes.
*
*RECOMMENDED
TO GENERATOR
TRANSFORMER
VOLTAGE (VAC)
(AT FULL-LOAD
NOMINAL LINE
DISTRIBUTION
CATALOG NO.
OUTPUT (kW)
MAX. POWER
DISCONNECT
GENERATOR
GENERATOR
RESISTANCE
MODEL NO.
CAPACITY
*SERVICE
RATING
RMS)
208 #6 AWG 70 AMPS 40 KVA 0.026 OHMS
QG-320, QG-32-2 32
QG-3200 240 #6 AWG 60 AMPS 40 KVA 0.023 OHMS
*NOTE: All installations must meet the requirements of local electrical codes.
*
Refer to Table 1-6 for performance specifications of single-phase stored energy (SE) HF
Series Generators.
* Maximum exposure time is a function of kV and mAs settings and the age of the
batteries; Time measured at 75% of the peak kVp waveform
NOTE: AEC TECHNIQUES SHOULD HAVE EXPOSURE TIMES EXCEEDING 8
MILLISECONDS.
I mAs is tube dependent; the generator may not reach maximum mAs due to tube type.
In AEC mode, the mAs is limited to 600.
Accuracy Specifications
mA Accuracy: mA = ± ( 5.0% mA + 1 mA )
SYSTEM OPTIONS
The following lists the available options for HF Series X-Ray Generators. Note that
some options, such as QG-150 and QG-HSS, may only be used on certain generator
models (refer to Tables 1-5 through 1-7 for compatibility):
• R80-HS: Exposure Hand Switch
• QG-PDL: Operator Control Panel Pedestal Mount
• QG-WM: Operator Control Panel Wall Mount
• QG-150: 150 kV High Voltage Transformer (standard equipment on Models
QG-65 and QG-80)
• QG-HSS: ExternalInternal High (Dual) Speed Starter Unit (standard
equipment on Models QG-65 and QG-80)
• QG-28VPS: Internally mounted Auxiliary +28 VDC/8A Power Supply (this
option only available on three-phase input generators: Models QG-32-2,
QG-32-3, QG-40-2, QG-40-3, QG-50, QG-50-2, QG-65, and QG-80)
• TechVision: Supplementary x-ray control panel, mounts on tube support
device. Refer to the TechVision Remote Control Panel Service and
Operator’s Manuals for complete installation and operation instructions.
NOTE: The use of ACCESSORY equipment not complying with the
equivalent safety requirements of this equipment may lead to
a reduced level of safety of the resulting system. Consider-
ation relating to the choice shall include:
-use of the accessory in the PATIENT VICINITY
-evidence that the safety certification of the ACCESSORY has
been performed in accordance with the appropriate IEC 601-1
and/or IEC 601-1-1 harmonized national standard.
SYSTEM OPERATING ENVIRONMENT
Ambient Temperature: +10°C to +40°C
Relative Humidity: 30 to 75%, non-condensing
Atmospheric Pressure: 700 hPa to 1060 hPa
Typical Heat Output of
Generator Cabinet: 3600 BTU per hour
Typical Heat Output of
operator control panel (OCP): 130 BTU per hour
NOTE: The above calculations are typical, based upon average usage.
Air circulation around the electronic cabinet must be provided.
This includes the sides, back, front and top of cabinet.
NON-OPERATING ENVIRONMENT
Ambient Temperature: -18°C to +70°C
Relative Humidity: 20 to 95%, non-condensing
Atmospheric Pressure: 500 hPa to 1060 hPa
ASSEMBLY &
INSTALLATION
2-1
2-2
Chapter 2 Assembly & Installation
OVERVIEW
This chapter provides procedures for installing the HF Series x-ray generator, from
pre-installation guidelines to final system inspection prior to operational readiness.
These procedures should be reviewed carefully before beginning the actual installa-
tion. Preparing the X-ray generator for operation requires completion of the following
tasks:
• Installing the X-ray generator cabinet
• Installing the Operator Control Panel (OCP)
• Making the Electrical Cable Connections
• Power-up
• Calibrating the generator
• Inspecting the system
• Verifying programmed techniques
PRE-INSTALLATION GUIDELINES
While site planning is the customer's responsibility, the following are recom-
mended guidelines.
Verify Equipment Location
In radiology site preparation, it is essential to verify the location and space
allocated for the equipment is sufficient. See Figures 1-1 and 1-2 for HF
Series x-ray generator dimensions. The room plan should show the following
for the equipment:
• All working and parked positions
• Overall dimensions
• Total equipment weights and power outputs
• Structural mounting and attachment methods
Ensure sufficient air circulation space is provided between the rear side of
Generator Cabinet and wall (4.0" min.). The floor where the generator is
installed should be flat and approximately level (minor shimming is accept-
able) and capable of supporting a load of 500 lbs. (226.8 kg).
Electrical Requirements
In addition to providing for the physical requirements of the equipment, it is
also vital to prepare for the power requirements. Refer to Chapter 1, SPECI-
FICATIONS for model-dependent power specifications. This information
should be used to prepare system wiring and cabling.
UNPACKING
The HF Series x-ray generator is shipped in a single crate. To unpack, proceed as
follows:
1. Remove packing list and use it as a guide to open the remaining cartons. Do
not dispose of packing material until packing list is matched with actual parts NOTE
received. Should there be a shortage or damage, notify Quantum Medical
Imaging, LLC.’s customer service department immediately. The manufacturer Examine all car-
is relieved of any responsibility for damage during shipment after unit is tons and crates
picked up by the carrier. carefully at time
of delivery. If
WARNING! The X-ray generator cabinet can damage is appar-
weigh as much as 430 lbs. (195 kg), depending on ent, have deliv-
configuration. Use lifting straps and hoist or ery driver write a
"Damaged Ship-
other suitable lifting device to transport genera-
ment Note" on
tor. The H.V. Tank weighs approximately 100 lbs. copies of freight
and requires two persons to lift. bill, sign it, and
file appropriate
2. Remove the Generator Cabinet from its crate (lifting straps and hoist or other carrier claim.
suitable lifting device is recommended). Should you dis-
cover concealed
3. Using a hand truck from the rear side of the cabinet, lift the generator and damage, immedi-
place it as close to its final installation location as possible. ately notify the
transporting
WARNING! When unpacking the generator; keep agent and ask
upright at all times. Verify there is no damage for an
caused during shipping, with no apparent oil leak- "Inspection of
age from H.V. Tank; check that the tank lid and oil Damage". Carrier
will not accept
plug (in tank lid) are secure.
concealed dam-
age claim if filed
4. Locate the OCP and Pedestal (optional) or Wall Mount Bracket (optional) and after 15 days
place on the side. from date of
receipt of mer-
chandise.
INSTALLATION
The following paragraphs provide information necessary for installing the Generator
Cabinet and Operator Control Panel (OCP), including all required external equipment
cable connections with the X-ray generator.
2. On stored energy (SE) units, open the two (2) modular fuse holders located
on the front of each battery tray. Note that there are two pairs of fuses on 32
kW and 40 kW units, one pair for each battery tray.
3. If mounting generator to floor, mark locations of the four mounting holes on
floor in accordance with dimensions given in Figure 2-2. Drill four holes using
proper diameter drill bit (depending on mounting hardware used).
TAP ADJUSTMENT
LEADS
208 VAC
220 VAC
240 VAC
198 VAC
208 VAC
220 VAC
240 VAC
198 VAC
208 VAC
220 VAC
240 VAC
380 VAC
415 VAC
440 VAC
480 VAC
380 VAC
415 VAC
440 VAC
480 VAC
380 VAC
415 VAC
440 VAC
480 VAC
2 3 4 5 2 3 4 5 2 3 4 5 5 6 7 8 5 6 7 8 5 6 7 8
LA40-056 REV. C LA40-033 REV. F
208-240 VAC LINE INPUT CONFIGURATION 380-480 VAC LINE INPUT CONFIGURATION
All electrical connections must be made in compliance with local and/or NEC
requirements. The generator is factory configured to accept line input speci-
fied when the order was placed. However, if it is necessary to change the
generator line input configuration, refer to the previous procedure entitled
"Transformer Line Tap Adjustment".
Non-STORED ENERGY (SE) version generators require a mains disconnect
box (with switch) before the x-ray generator (refer to your local code). This
switch should be within reach of the operator. A separate earth ground, #6
AWG insulated wire, must be installed. This wire must be the only wire con-
nected to the generator ground terminal.
LINE INPUT
CABLE CLAMP
(TYPICAL)
GENERATOR
CHASSIS
TERMINAL
BLOCK TB1
GROUND
LUG
4. On three-phase systems:
a. Connect Phase A, B and C wires to TB1 terminals L1 through L3,
respectively. Do not turn mains power on at this time. (See
Figure 2-9).
TERMINAL
BLOCK TB1
GROUND
LUG
1. Loosen four (4) screws securing the clear plastic high-voltage acrylic pro-
tection panel from the generator chassis and remove panel.
2. Position H.V. Tank on Tank Mounting Brackets so mounting holes in tank
align with those in mounting brackets. Secure tank to brackets using four
(4) 1/4-20 x 3/4" hex head screws, flat washers and lock washers.
3. Connect H.V. Tank cable terminal PC1 to Power Module A19 IGBT lower
right terminal. Tighten screw securely.
4. Connect H.V. Tank cable terminal PC2 to right terminal lug on Capacitor
C7. Tighten nut securely.
5. Connect H.V. Tank cable terminal PA1 to left terminal lug on Capacitor C4.
Tighten nut securely.
6. Connect H.V. Tank cable terminal PA2 to Power Module A18 lower left
IGBT terminal. Tighten screw securely.
7. Locate ground wires for H.V. Tank (yellow/green) and securely fasten to
H.V. Tank ground stud (GND) using 8/32 kep nut (provided on stud).
8. Insert plug A17P1 (16-pin plug on Cable Assembly AY51-017) into con-
nector A17J1 on the H.V. Tank and tighten plug securely.
9. Re-install the clear plastic high-voltage protection panel on the generator
chassis and re-tighten four (4) mounting screws.
BEFORE INSERTING
CABLE, LOOSEN
SET SCREW
COAT WITH
INSULATING
COMPOUND
BEFORE
INSERTING
FULLY TIGHTEN
SET SCREW
Figure 2-13. Routing High Voltage Cables into the Generator Cabinet
1. If not already done so, assemble onto the High Voltage Cable end a cable
retaining nut, grounding washer and strain relief (see Figure 2-14).
Ensure the 10-32 x 1/4" locking screw is turned out so as not to interfere
with engagement.
CO L R D Y
C H ASSIS
15V RTN
15 VDC
24V RTN
SPARE
24 VAC
24VDC
24VAC
GN D.
G ND.
SLO-BLO
250 VAC
8 AM P
EXPOSURE
HOLD
CONNECTIONS
(AUTO COLL.)
TUBE ROTOR
110VAC
BOOST VOLTAGE
JUMPER
(REV. R AND
220VAC
HIGHER BOARDS
ONLY)
COLLIMATOR TUBESTAND
CONNECTIONS TERMINAL DOOR INTERLOCK TUBE ROTOR BOOST
TERMINAL BLOCK TB1 BLOCK TB2 TERMINAL BLOCK TB6 VOLTAGE JUMPER
(REV. J AND HIGHER
BOARDS ONLY)
COLL RDY
24V RTN
15V RTN
CH GND
24VAC
SPARE
24VAC
GND
15V
24V
D8
D12
R19
R16
F13
F18
F19
D20
D19
D13
D7
EXPOSURE
D2
HOLD
CONNECTIONS
R17
D4
(AUTO COLL.)
D14
K3
R11
R12
1
TB5
WALL STAND BUCKY POWER TABLE BUCKY POWER X-RAY ON LIGHT
TERMINAL BLOCK TB7 TERMINAL BLOCK TB3 TERMINAL BLOCK TB5
Collimator Connections
Terminal block TB1 (see Figures 2-15 or 2-16 for terminal block TB1 location)
provides 24 VAC (TB1-1 and TB1-2) and chassis ground (TB1-3) outputs for
connection to a collimator. On systems equipped with a manual collimator,
verify jumper A9JP1 is installed; remove A9JP1 if system is equipped with an
automatic collimator.
Also available on terminal block TB2 is the COL RDY terminal (at TB2-4) for
connection to automatic collimator with "exposure hold" interlock (use CHAS-
SIS GND terminal TB2-7 for return). Refer to collimator manual for specific
connection details.
Tube Stand/Peripheral Equipment Connections
Interface Board A9 Terminal block TB2 (see Figures 2-15 or 2-16 for terminal
board TB2 location) provides +28 VDC (TB2-1) and +28 VDC RTN (TB2-2)
terminals for connection of a tube stand power input cable, when applicable.
Maximum load current is 1.5A at these terminals.
Internal +28 VDC Power Supply Option (QG-28VPS)
If generator is equipped with +28 VDC Internal Power Supply Option
(QG-28VPS), see Figure 2-16A and connect the tubestand/wallstand’s power
supply input leads as follows:
1. Positive lead to terminal P2-1 (+) on power supply
2. Negative lead to terminal P2-2 (-) on power supply
Figure 2-16a. Internal +28 VDC Power Supply Option (QG-28VPS) Location
The output of the +28 VDC Power Supply is adjusted depending on the type
of Quantum product it will supply power to, as indicated below:
Table 2-1a: Internal +28 VDC Power Supply Option (QG-28VPS) Adjustment
When using the +28 VDC Power Supply Option to provide power for a Model
RS-580 Overhead Tube Crane, the +30 VDC output is intended for operating
the tube crane’s transverse and longitudinal electromagnetic locks (brakes).
Refer to the RS-580 Service Manual for connection instructions.
All others (220 VAC stator) Pins 2-3 220 VAC Stator
E7239X, E7242X 25 uF
E7813X, E7252X 45 uF
2 10
1 9
TEST POINT 7 PD1
J4 J3
PD4
U4
R25
Q4 Q1
R20 D4 R24 D5
MOV4
T1 G
T1 G
POTENTIOMETER R20 T2
T2
MOV1
TUBE CURRENT ADJ. TP4 TEST POINT 3
AC RETURN
J5
POTENTIOMETER R24 3 TP3
TUBE CURRENT ADJ.
1 C6 C2
TEST POINT 4
R2
PHASE MOV3
R14
10W
10W J1
4
TEST POINT 12
TP2 TP13 1
K2 200 VAC
R37 D18
TP12
C8
MOV2
TERMINAL SIGNAL R35
1 MAIN C14
2 PHASE 1
5 NOT USED 7
TEST POINT 13
6 GROUND 60 VAC
7 TEMP
Tube Rotor Cable (Systems with AID External High Speed Starter QG-HSS
Option Only)
Refer to Figure 2-18, the AID High Speed Starter installation manual and/or the
appropriate interconnection diagram in Chapter 6, DIAGRAMS for high speed starter
connections. Note: This procedure applies only to systems equipped with
the externally-connected AID High Speed Starter option.
1. Connect one end of X-ray Tube Rotor Cable AY51-032T to the appropriate con-
nector/terminals on AID High Speed Starter LC102 terminal block TS2 (see Figure
2-18).
2. Connect the opposite end to the X-ray tube’s terminal strip.
3. Route the X-ray Tube Rotor Cable AY51-033 (Toshiba tubes) through the middle
cable access opening located in the top rear wall of the generator chassis.
4. Connect one end of the High Speed Starter Cable AY51-033 to the appropriate
connector/terminals on AID High Speed Starter terminal strips TB1 and TB2 and
connect to Cable Assembly AY51-032T (temperature sense connector).
5. Connect the opposite end of the High Speed Starter Cable AY51-033 to connector
J8 on Logic Board A1, AY40-006S.
6. Connect 220 VAC power input to High Speed Starter.
7. The AID High Speed Starter was factory pre-configured for the x-ray tube sup-
plied with the generator. Verify boost and brake settings are correct according
tube manufacturer’s data sheets (refer to Table 2-3). Verify the high speed
starter is configured with the correct capacitors for the tube used with the sys-
tem: Toshiba E7252X and E7813X should be configured for 45 uF. All other tube
types require 30 uF.
TOSHIBA 490 VAC (use 165 VAC 2.0 seconds: 2.0 seconds:
E7254X, 370 VAC tap (75 VAC #3 SW1-1 = OFF SW2-1 = OFF
E7255X #10*) tap*) SW1-2 = ON SW2-2 = ON
SW1-3 = OFF SW2-3 = OFF
SW1-4 = ON SW2-4 = ON
SW1-5 = OFF SW2-5 = OFF
E7813X, E7252X, Install one (1) 40 uF cap (low speed), two (2) 12 uF in series
E7869X (high speed)
E7254X, all Varian, Install one (1) 25 uF cap (low speed), two (2) 12 uF in series
all Dunlee (high speed)
Table 2-3b: HSS Driver Board AY40-036S Boost and Run Voltage Requirements: Transformer
Input Wires to Terminal Block Plug TB1
Table 2-3b: HSS Driver Board AY40-036S Boost and Run Voltage Requirements: Transformer
Input Wires to Terminal Block Plug TB1
NOTE 1: Stow unused WIRE #2 (60 VAC) or WIRE #2A (80 VAC) in unused terminal block
TB1-2 location.
NOTE 2: Terminal block location TB1-4 is not used.
ROTOR CABLE
A20A2TB2
WHT
RED
BLK
GRN
L5A
TB1
L4A
ORN
D4
D31
R28
L5
L4
L5B
A20A2TB4
R16
L4B
R11C17
TP2
D6
R5
R68
MAIN (BLK) TO A20A2TB2-1
HIGH VOLTAGE
BE
C2
HIGH VOLTAGE
R73 R72
R71
DANGERC21
DANGER
TP1
R13
R15
E
R67
R2
R17
D12
R18
BE
J1
R64
R66
C28
R50
R43
C42
C29
TP10
U9
C27
C37
R58
20
C30
R54
R47
R42
C47
J3
1
D22
R55 R60
TP8
TP6
R63
C49
C51
A20A2TB2
BLK 0
BLK 2
BLK 1
WHT
L5A
TB1
L4A
BLK
D4
D31
R28
L5
L4
L5B
A20A2TB4
R16
L4B
R11C17
TP2
D6
R5
C2
HIGH VOLTAGE
R73 R72
R71
DANGERC21
DANGER
TP1
R13
R15
E
R67
R2
R17
D12
R18
BE
J1
R64
R66
C28
R50
R43
C42
C29
TP10
U9
C27
C37
R58
20
C30
R54
R47
R42
C47
J3
1
D22
R55 R60
TP8
TP6
R63
C49
C51
9-PIN SUB-D
FUNCTION
CONNECTOR PIN
1 NONE
2 FIELD 2 SELECT
3 FIELD 1 SELECT
4 RESET
5 OUTPUT
6 FIELD 3 SELECT
7 NEGATIVE SUPPLY
8 POSITIVE SUPPLY
9 GROUND
61135A W2, W3, W4 1-2 & 3-4 LOW ACTIVE FIELD SELECT
For systems equipped with universal type AEC (AEC Board AY40-027S):
Up to four ion chambers can be used. Connect ion chambers as follows:
• Wall#1 ion chamber to A11J8
• Wall#2 ion chamber to A11J12
• Table ion chamber to A11J10
• Auxiliary ion chamber to A11J13
Note that to connect a Siemens ion chamber AEC cable to universal AEC
Board A11 requires an interface cable assembly AY51-061 for each chamber.
This cable assembly adapts the ion chamber connector to 9-pin D-Sub type
used on the AEC Board, and provides a separate 300 VDC wire for connection
to A11TB1.
Route the ion chamber cable(s) as necessary to exit through the access open-
ing in top rear side of generator chassis, and secure as required. DO NOT
route through an opening containing a High Voltage Cable (see Figure 2-13).
Interfacing to Canon Digital Radiographic Receptor (When
Applicable)
The digital radiographic receptor is interconnected to the HF Series x-ray gen-
erator via Interface Board A9, P/N AY40-034T terminal blocks A9TB7 (Wall
Stand) and A9TB3 (Table), respectively, using 4-conductor, 18AWG cable.
Refer to the digital receptor manufacturer’s installation manual for more
detailed wiring instructions.
Secure the ion chamber cables to the PCB Door using cable ties as shown in
Figure 2-20.
SECURE OTHER
ION CHAMBER
CABLE CONNECTOR
HERE
8. If mounting OCP to floor, either transfer drill four mounting holes in floor
using the OCP base plate as a guide or mark the floor in accordance with
dimensions given in Figure 2-23, and then drill holes where marked. Drill
holes using a #W drill bit (0.390" diameter). After OCP cable connection
is complete, secure OCP to floor using 3/8" hardware suitable for floor
type.
(DIMENSIONS SHOWN
IN INCHES)
1.00
10.25
.44
11.01
2X 6.50 6.50 O.203 THRU
1.00 6X
15.00
5. Position the OCP on the Wall Mount bracket aligning the mounting holes
in the bottom of OCP with the mounting holes in the wall bracket.
6. Secure the OCP to the Wall Mount Bracket using four (4) 1/4-20 x 3/4"
pan head phillips screws, flat washers and nuts.
7. Re-install four (4) OCP front panel screws.
8. Connect one end of the OCP serial cable (P/N AY51-018) to connector J3
on the OCP. Route the OCP serial cable through the access opening in
the Wall Mount Bracket and connect to connector J5 on CPU Board A1
(P/N AY40-006T). Ensure the connector screws are fully tightened. DO
NOT route serial cable through an opening containing a High Voltage
Cable (see Figure 2-13).
Optional Remote Expose Switch Connection
Optional remote expose switch (R80-HS) is wired into the OCP Board A16A1
(P/N AY40-004S) at TB1 as shown in Figure 2-25, below. If desired, remov-
ing jumpers JP6 and JP7 on OCP Control Board A16A1 (AY40-004S1) disables
the operation of the PREP and EXPOSE buttons on the operator control panel
(see figure below).
DANGER HIGH VOLTAGE
1
TP10
R18C41
4
C43 R23
R37 JP12
1
1
R34 R35
PD6 PD7
C27
U19
TP9
1
1
D16
JP11
U10
1
RS-232
D19
TP1
D2 D3 D4
RESET
JP16 20
10
1
R13 R12
R16 R11
JP6
JP7
11
1
COMM
EXPOSE
PREP
GND
TB1
Figure 2-25. Operator Control Panel (OCP) Control Board Terminal Block TB1
Connections for Remote Expose Switch
INITIAL POWER UP
With the generator completely assembled and when electrical checks are com-
plete, the system is ready for initial power up. Proceed as follows:
1. Set ON/OFF circuit breaker CB1 on the generator cabinet to ON position.
2. Set the power on/standby switch on the Operator Control Panel (OCP) to the
on ( ) position.
3. The system begins the start up sequence (the "Welcome Screen" is displayed
and "Testing. Standby." is flashing). After a few seconds, the Manual, AEC or
APR Mode menu will display.
2.5 - 3.0 ms
14.0 to
15.0V(peak)
A10TP15
Waveform
14.0 to
15.0V(peak)
A10TP14
Waveform
CALIBRATION
3-1
3-2
Chapter 3 Calibration
OVERVIEW
This chapter provides instructions for configuring and calibrating the HF Series X-ray
generator following installation. For additional information, NEMA Standards Publica-
tion/No. XR8-1979(R1994), Test Methods for Diagnostic X-ray Machines for Use Dur-
ing Initial Installation is recommended as a reference.
REQUIRED TOOLS AND MATERIALS
The following lists the tools and materials required to perform the procedures
contained in this chapter:
• Digital Voltmeter: Fluke Model 87 (or equivalent)
• kV and mAs meter: Radcal Dynalyzer III (or equivalent)
• Radiation meter (0-1000 mR)
• Oscilloscope, 50 Mhz storage: Tek 2210 (or equivalent)
• 5 CM, 10 CM, 15 CM, 25 and 30 CM acrylic phantoms (required for
calibrating systems equipped with QG-AEC option).
SYSTEM CONFIGURATION/CALIBRATION
The HF Series x-ray generator has been factory configured and calibrated. It is nec-
essary, however, to perform the following procedures to validate system compliance.
Perform the procedures in the sequence presented, unless otherwise instructed.
PRESS TO
ACCESS
PASSWORD
MENU
FIELD SELECT
KEYS
(58623) using the field select keys next to the corresponding numbers.
(This password enables access to Service Mode for modification of system
configuration, calibration and settings and for access to the APR Edit utility.)
6. Upon validation of the password, the Service Mode Menu displays:
SYSTEM CONFIGURATION
Press the key next to the Configuration field to access system configuration
functions. The Service Configuration Menu displays:
PRESS THIS
KEY TO SET
THE POWER
OUTPUT
DERATING
PERCENTAGE
AEC Setting
The Service Configuration menu, shown below, displays the generator’s cur-
rent AEC setting.
PRESS
THIS KEY
TO SELECT
AEC
SETTING
PRESS THIS
KEY TO
RESET ALL
TUBE
CALIBRA-
TION
VALUES
1. Press the key located next to the Model field until the correct tube model
is displayed.
2. The Tube Derating key provides derating of the generator’s maximum
mAs output in percentages of 80%, 85%, 90%, 95% or 100% (i.e., no
derating). For example, if at a particular kV and mA the tube normally
allows a 10 mAs exposure, then at 80% derating, the tube would permit
only an 8 mAs exposure. Derating the tube can extend the life of the
tube. Press the key next to the Tube % Derating field to choose a der-
ating percentage.
3. The Heat Alarm (Heat % Limit) key provides a heat protection function
for the x-ray tube. For example, setting the Heat Alarm for 80% will
cause the generator to produce an audible alarm and a visual "Heat
Alarm" indication on the OCP when the tube has reached 80% of its total
heat unit capacity. The total tube heat unit capacity is dependent on the
tube type. The Heat Alarm setting has an adjustment range of anywhere
between 50% up to 100% in 10% increments. Note: At 100% setting,
the heat alarm is effectively disabled. Press the key next to the Heat %
Limit field to select the percentage of the total tube heat capacity at
which alarm activation will occur.
4. If the tube type has been changed, press the Save Tube key. The tube
model setting is saved in non-volatile random access memory (NVRAM)
and the system returns to the Service Configuration Menu (see Figure
3-4). Note that if the Previous, No Save key is pressed when the tube
type is changed, any changes made in the Tube Configuration Screen will
not be saved (i.e., the previous tube’s calibration values will be retained).
Edit Digital Settings
The Edit Digital Screen, shown below, contains the Digital Receptor settings,
including the digital receptor type, Universal System type, and "Prep Hold"
settings for the generator. To make these settings, proceed as follows:
PRESS
THIS KEY
TO
ENABLE
OR
DISABLE
PREP
HOLD
Release" signal from the DR system to proceed with the Expose cycle).
Setting the Prep Hold setting to Off configures the generator for "normal"
operation (i.e., non-interrupted Prep cycle).
4. To exit the screen and return to the Service Menu, press the key next to
the Previous Screen field.
Polarity + +
Invert No No
Polarity + +
Invert No No
Table 3-1 shows the ion chamber and receptor settings for the generator
when equipped with standard AEC (i.e., Standard AEC Board A11
(AY40-031S) is installed). Table 3-2 shows the ion chamber and receptor
settings for the generator when equipped with universal AEC (i.e., Univer-
sal AEC Board A11 (AY40-027S) is installed). Table 3-3 shows the ion
chamber and receptor settings for the generator when equipped with
standard AEC and "Digital Interface" option (i.e., Standard AEC Board
A11 (AY40-031S) and Digital Interface Board A9 (AY40-034T) are
installed). Detailed instructions are as follows:
1. Press the key located next to the ion chamber detector (Field A,
Field B or Field C) until the desired detector setting (1, 2, 3 or Off)
is indicated in corresponding box of ion chamber graphic on the right
side of the ION CHAMBER Configuration screen (see Figure 3-12).
2. The "Polarity" setting (+ or -) controls whether the ion chamber on
the selected receptor port is a (+) positive logic (i.e., active high) or
(-) negative logic (i.e., active low) model. The positive logic model
presents a DC voltage or ramp ranging from 0 to some positive volt-
age to indicate exposure value. The negative logic model presents a
DC voltage or ramp ranging from 0 to a negative voltage. This set-
ting is ignored unless the "Universal AEC" selection is chosen. The
"Standard AEC" board is always "positive".
3. The "Invert" setting controls the sense of the signals that select the
individual field for the chamber. If "Invert" is set to No, the idle
(non-PREP/EXPOSE) state of the individual field selection is "1" and
the state during PREP/EXPOSE is "0" if the field is selected (called
"Low Active"). If "Invert" is set to Yes the idle (non-PREP/EXPOSE)
state of the field selection is "0" and the state during PREP/EXPOSE is
"1" if the field is selected (called "High Active"). This setting is
ignored unless the "Universal AEC" selection is chosen. The "Stan-
dard AEC" board is always "Not Inverted".
SYSTEM SETTINGS
In the Service Menu (see Figure 3-3), press the key next to the Settings field
to access the Service Settings Menu, shown below:
The Film/Screen Defaults screen, shown below, displays the current receptor
film/screen combination settings. To change the default film/screen settings,
proceed as follows
THESE
KEYS ONLY
USE USED ON
THESE UNIVERSAL
KEYS TO TYPE AEC
SET SYSTEMS
FILM/
SCREEN
COMBIN
ATION
Language Setting
The Service Settings Menu, shown below, displays the current language set-
ting. The default language setting is English. To change the language setting,
proceed as follows:
NOTE
It may be
preferable to
set the
Language to
"English" prior
to performing
calibration
procedures,
then reset to
the desired PRESS THIS KEY TO
language after SELECT LANGUAGE
calibration is
completed.
Figure 3-21. Choosing Language and Date Format Settings
Press the key next to the Language field to scroll through available lan-
guages (English, French, Spanish, German, Italian, etc.) until desired lan-
guage is displayed.
SYSTEM CALIBRATION
CAUTION! Before calibrating unit, perform warm-up
procedures recommended by tube manufacturer or
the warm-up procedure described in Chapter 3 of the
Operator’s Manual.
Important! On generators that will be interfaced to a
tomography system; Set Tomo Mode to "Off" during
prior to performing generator calibration, then set
Tomo Mode back to "On" following calibration.
To access the system calibration functions, press the key next to the Calibration
field in the Service Menu (see Figure 3-3). The Service Calibration menu displays,
shown below:
The following notes apply in general to all calibration procedures, including AEC
calibration procedures. Please review these notes prior to performing calibration.
• The top right button typically is used to advance to the next step of a
particular calibration procedure.
• Use the button next to the Next Calibrate field to advance to the next
calibration procedure.
• Use the button next to the Prev Calibrate field to return to the previous
calibration procedure.
• In calibration procedures having multiple "steps", the last step is indicated
when "Measure, Calibrate" appears in the top right screen field. Pressing
the key next to "Measure, Calibrate" field saves the calibration values.
After saving the calibration values, press either the Next Calibrate key to
proceed with the next calibration procedure
IMPORTANT! Following a calibration procedure,
unless the "Measure, Calibrate" key is pressed, no
change is made to the currently saved calibration
value(s).
• The screen always displays the correct KV, MA, time and thickness (in CM)
value required for performing each calibration procedural step. Ensure the
correct values are set prior to performing each procedural step.
• On QUEST systems: If you prefer to view exposure mAs instead of exposure
time on the display, press the fourth function key located immediately above
the LCD display screen to toggle between mAs and time display settings.
• Throughout AEC calibration, the film/screen being calibrated is displayed on
every AEC calibration screen in the top left field.
• When calibrating AEC using a wall stand mounted receptor, ensure that the
x-ray beam is perpendicular to image receptor and that the correct ion
chamber detector(s) is selected.
• Upon completing calibration procedures, it is recommended that Q-Ware
program be used to upload calibration data (and APR technique data if
editing was performed) as a backup in case a problem occurs requiring re-
calibration of the generator. To obtain a copy of the Q-Ware program,
contact Quantum Medical Imaging’s Customer Service Department.
FILM SPEED
ADJUSTMENT KEYS
A/D Calibration
The A/D (analog/digital converter) calibration utility is used to calibrate spe-
cific operating voltages within the x-ray generator against a traceable cali-
brated voltage measurement instrument, such as a DMM. Once A/D
calibration has been performed, the A/D calibration utility may then be used
as a diagnostic tool allowing the technician to "read" these voltage measure-
ments without having to remove the cover from the generator cabinet and
without connecting a meter.
Table 3-5 shows the various voltage levels (with tolerances) that can be cali-
brated using this utility, and it provides the location of the test point to which
a calibrated voltmeter must be connected for measuring the actual voltage
level:
+400V Anode ±8 VDC +/- bus bars on Capacitor Bank next to Power Mod-
ule A18 (right side looking into generator cabinet)
Proceed as follows:
VOLTAGE SELECTIONS
VOLTAGE SELECTIONS
SAVE A/D
INCREASE/DECREASE
CALIBRATION
VOLTAGE KEYS
Figure 3-28. Sample A/D Voltage Calibration Screen (+15 VDC is shown)
2. Verify the voltage displayed in the top center of the screen is the correct
voltage level to calibrate.
3. Refer to Table 3-5 and connect a voltmeter to the test point correspond-
ing to the voltage level selected for calibration.
4. On the voltmeter, observe the measured voltage value. Ideally, the value
appearing in the top right field will match the reading on the voltmeter. If
not, adjust the value in the increase/decrease voltage field up or down
by pressing the key next to the up or down arrow, respectively, until the
field is set to the value displayed on the voltmeter (to within Calibration
Accuracy ranges shown in Table 3-5). Each time the key is pressed
changes the voltage value up/down in one-tenth volt increments.
5. Press key next to the Calibrate field to save the calibration entry.
6. Press the key next to Previous Screen to return to the A/D Calibration
menu.
kV Calibration Function
This procedure calibrates the generator to verify accurate system measure-
ment of peak tube potential (kVp). The generator’s ability to measure peak
tube potential accurately is verified using a pre-calibrated kVp meter (Dyna-
lyzer or equivalent) as a benchmark. Access the KV Calibration Screen,
shown below, and proceed as follows:
CENTER
DISPLAY
BOX
50 KV SAVE 50 KV
INCREASE/ CALIBRATION
DECREASE
KEYS
1. Connect a kVp bleeder tank in series between X-ray tube and the genera-
tor’s H.V. Transformer (A17), or use a non-invasive kVp meter.
2. Verify 50 KVP appears in the center display box of the KV Calibration
Screen and First Measure appears in the top right field.
3. Take an exposure at the setting indicated in the center display box
(i.e., 50 kVp, 200L mA, 100 mS).
4. On the kVp meter, observe the measured kV value. (Ideally, this value
should be 50 kVp.)
5. If not 50 kVp, adjust the value in the Measure KVP#1 field up or down
by pressing the key next to the up or down arrow, respectively, until the
Measure KVP#1 field is set to the value displayed on the kVp meter.
Each time the key is pressed changes the kV value up/down in one-tenth
increments.
6. Press key next to the First Measure field to proceed to 100 kV calibra-
tion setting. The following screen should be displayed:
5. If not 75 mA, adjust the small filament offset value in the Small Fila-
ment field up or down (pressing up arrow increases mAs, pressing down
arrow decreases mAs). Note: The DAC value displayed in the field adja-
cent to the up/down arrows increases as the mAs value decreases, and
decreases as the mAs value increases.
6. Re-take exposure at same settings and adjust small filament offset value
if necessary. Repeat this step until measured mA is 75.
7. When measured mA is 75, press the key next to the Small Filament
field. The large filament calibration screen is displayed:
MA Calibration
This procedure calibrates the generator to verify accurate system measure-
ment of tube current (mA). Current measurement accuracy is verified using a
pre-calibrated mAs meter (Dynalyzer or equivalent) as a benchmark.
An oscilloscope may be used for mA measurement, however, this will not pro-
vide enough accuracy for performing mA calibration (mA Calibration must be
performed using a mAs meter). To use an oscilloscope for mA measurement,
connect scope leads between test point TP7 on KVP Control Board A2
(AY40-003S) and ground. Set scope for 1.0 volt/division, and 50 ms/division
time base. This will give a 100 mA/volt equivalent for mA measurement (see
Figure 3-34 for sample mA measurements using scope).
CENTER
DISPLAY
BOX
6. Press key next to the First Measure field to proceed to 400L mA calibra-
tion setting. The following menu should be displayed:
13. If the system is equipped with QG-AEC option, perform AEC Calibration
procedures. Otherwise, calibration is complete. To return to the Service
Calibration screen, press the key next to the Main field.
CAUTION! If using a mAs meter, re-connect the
green/yellow wire marked "MAS METER" to the
ground stud on top of the H.V. Transformer (see
Figure 3-32).
AEC CALIBRATION
IMPORTANT! Before performing each AEC calibra-
tion procedure, verify the correct Film/Screen is
displayed on the calibration screen (shown in top
left field). The Film/Screen setting is selected in
the AEC Calibration Menu.
Refer to Appendix A for instructions on AEC cali-
bration of systems using a digital receptor (DR) or
a computed radiographic (CR) film plate.
The following calibration procedures must be performed on systems equipped
with QG-AEC option (automatic exposure control). Each film/screen combination
used with the system requires calibration for AEC in order to ensure that when a
given film/screen combination is selected by the user, it produces films having a
preset optical density, referred to as the "base optical density".
NOTE
The HF Series X-ray generator provides for calibration of up to seven different
The factory
default Wall film/screen combinations (eight including "Digital" on systems with digital recep-
72", Wall 40" tor enabled). Each of the image receptors used with the system can be config-
and Table 40" ured to use a particular film/screen combination using the Service Settings Menu
film/screen (see Figure 3-16). (Refer to SYSTEM SETTINGS paragraph in this chapter for
combination instructions on system settings.) For example, when the operator presses the
names can be
changed, if WALL key on the operator control panel and selects the WALL 72" receptor, the
desired, using system can be programmed to use the "Wall 72"" designated film/screen combi-
the Edit F/S nation (i.e., the film/screen type used with the wall stand at 72" SID). On the
Name utility same system, a different film/screen type, designated as "Table 40" for example,
provided on could be be configured for use with the TABLE receptor.
the AEC Cali-
bration Menu. Typically, on a system using a wall stand and radiographic table, three separate
This applies to film/screen combinations are used:
the factory
default "100 • Wall 72" - Used when the operator selects wall receptor at 72 inch
Speed", "200 source-to-image distance (SID)
Speed", "800
Speed", and • Wall 40" - Used when the operator selects wall receptor at 40 inch
"Film/Screen source-to-image distance (SID)
7" film/screen • Table 40" - Used when the operator selects table receptor at 40 inch
combination
names as well. source-to-image distance (SID)
On generators equipped with "Universal" type AEC (AEC Board A11 AY40-027S
installed), two additional image receptors and their corresponding film/screens
(default names are "WALL2" and "AUXILLIARY") can also be configured similar to
those listed above. It is important to note that each different type of film/screen
combination used with the receptors be calibrated in accordance with the AEC
Calibration procedures described in this chapter.
The design of the HF Series x-ray generator assumes that a limited number of
films and screens are used in a facility (up to seven). Whether or not AEC is
used, the only method of specifying film speed is in the AEC Calibration Menu
(see Figure 3-40). With seven available film/screens, the operator should have a
sufficient selection of film/screen options for use with the system.
FILM SPEED
ADJUST-
MENT KEYS
The AEC Calibration menu provides access to the system's various AEC
calibration functions, briefly described as follows:
• Film Screen/Combination Selection Key - Selects the film/
screen combination you want to calibrate (system default
choices are Wall 72", Wall 40", Table 40", 100 Speed, 200
Speed, 800 Speed, Film/Screen 7, and DIGITAL (if "Digital
Receptor" is enabled in the Service Configuration Menu)
• AEC OD Calibration - Calibrates the optical density for the
currently selected film/screen and ion chamber combination
• Reciprocity Calibration - Calibrates the reciprocity failure law
correction factor for the currently selected film/screen and ion
chamber combination
• AEC KV Calibration - Calibrates the tube voltage settings used
in conjunction with the currently selected film/screen and ion
chamber combination
• Main - Returns to the Service Calibration Menu (see Figure
3-27)
10. Repeat above steps with UPPER RIGHT ion chamber detector
selected and UPPER LEFT and UPPER CENTER detectors covered with
lead. The measured mAs reading should be within 5% of the mAs
reading noted in the previous step. If not, adjust the UPPER RIGHT
detector gain potentiometer, re-take exposure and verify it is within
tolerance. Repeat as necessary.
11. Access Service Settings Menu and select Back Up Time/MAS.
Return the AEC Backup Setting to desired back up mAs.
3. Press the key adjacent to the Edit F/S Name field. The film/screen
name Edit Sentence screen appears:
Film/Screen
Table 40 Wall 40 Wall 72 Other1 Other2
Combination:
AEC OD CALIBRATION
Setting: 50 kVp, 200L mA, 5 cm
Optical Density:
AEC Ref.
RECIPROCITY
Setting: First Cal. - 50 kVp, 400L mA, 15 cm
Optical Density:
Setting: Middle Cal. - 50 kVp, 75S mA, 15 cm
Optical Density:
Setting: Save Cal. - 50 kVp, 25S mA, 15 cm
Optical Density:
AEC KV CALIBRATION
Setting: Step 1 - 50 kVp, 200L mA, 5 cm
Optical Density:
Setting: Step 2 - 60 kVp, 200L mA, 10 cm
Optical Density:
Setting: Step 3 - 80 kVp, 200L mA, 15 cm
Optical Density:
Setting: Step 4 - 100 kVp, 200L mA, 20 cm
Optical Density:
Setting: Step 5 - 110 kVp, 200L mA, 25 cm
Optical Density:
Setting: Step 6 - 120 kVp, 200L mA, 30 cm
Optical Density:
Setting: *Step 7 - 130 kVp, 200L mA, 30 cm
Optical Density:
Setting: *Step 8 - 140 kVp, 200L mA, 30 cm
Optical Density:
1. Place a film cassette in the tray and collimate down to film size.
2. If not already done so, access the AEC Calibration Menu (see Figure
3-37).
3. Press the key next to the Film/Screen Combination field (upper
left field) to select a film/screen combination to calibrate. Verify the
receptor in which the film cassette is inserted is selected as indicated
on the AEC Calibration Menu screen.
4. The FILM SPEED field shows the current film speed setting for the
selected film/screen combination. To select a different film speed,
press the up or down keys next to the FILM SPEED field until the
desired film speed setting is displayed.
5. When film/screen combination name and film speed settings are cor-
rect, press the key next to the AEC OD Calibration field to proceed
with AEC Calibration. The AEC Optical Density Calibration Screen,
shown below, is displayed:
BASE
OPTICAL
DENSITY
SELECT KEYS
AEC REF
ADJUSTMENT
KEYS
sure. Continue until the measured optical density equals the base
optical density setting (at least to within 5% of base optical den-
sity setting).
10. Press the key next to the Next Calibrate field to advance to Reci-
procity Calibration.
IMPORTANT! To ensure AEC optical density is cor-
rectly calibrated to the desired "base" optical density
setting, either the AEC Ref value must be adjusted to
obtain the desired base optical density (which is veri-
fied in the exposed film using a densitometer) or the
Optical Density setting in the AEC Optical Density
Calibration Menu must be set to the actual measured
film density. For example, the calibrator would like
the system AEC optical density setting to be "1.30".
The calibrator must then adjust the "AEC Ref" value
until the actual measured optical density of the film
is 1.30. However, if the actual measured optical den-
sity is 1.29 and you decide not to continue to adjust
the AEC Ref to achieve exactly 1.30 film optical den-
sity, then change the Optical Density setting in the
AEC Optical Density Calibration Menu to "1.29". Note
that 1.29 is now the "base" AEC optical density for
the film/screen being calibrated.
KVP MEASURE
SELECT FIELD
NOTE
Calibration of the Figure 3-41. AEC KV Calibration Screen
first step (50 kVp) Proceed as follows:
is not required as
long as AEC 1. Place indicated thickness of acrylic (5 CM for first calibration point) in
Optical Density the X-ray beam.
Calibration
2. Place a film cassette in the tray and collimate down to film size.
procedure in the
previous steps 3. Verify the receptor in which the film cassette is inserted is selected as
was performed indicated on the AEC KV Calibration screen.
prior to AEC KV
Calibration. A 4. Take an exposure at the setting indicated in the center display box
verification that (i.e., 50 kVp, 200L mA).
the "Measured 5. Develop the film and measure the optical density using a calibrated
OD" is the same
densitometer.
as the "Optical
Density" setting is 6. Press the up or down key located next to the Measured OD field
all that is until the optical density value displayed equals the measured optical
required. density value (the Measured OD up arrow key increases the optical
density value and the Measured OD down arrow key decreases the
optical density value). DO NOT TAKE ANY FURTHER EXPOSURES AT
THIS SETTING.
7. Press the key next to the Measure OD field to save the first kV cali-
bration point entry (50 kV, 5 CM). The AEC KV Calibration screen is
updated for the next kV calibration point (60 kV, 10 CM).
8. Repeat the previous steps for the 60, 80, 100, 110, 120, and, if 150
kV system, 130 and 140 kV calibration points, placing the specified
thickness of acrylic in the x-ray beam as indicated on the AEC KV Cal-
ibration screen for each kV calibration point. NOTE
The series of
9. Upon completion of final kV calibration point (i.e., 120 kV on 125 kV AEC kV
systems, 140 kV on 150 kV systems), press key next to the Measure calibration
OD field. The field will now display Save Calibrate. Press this key exposures and
again to save the calibration data for the final kV calibration point. optical density
measurements
IMPORTANT! Data will be lost if Save Calibrate is may be
not pressed! repeated as
many times as
desired to
improve
10. Press the key next to the Next Calibrate field to return to the AEC calibration
Calibration menu (see Figure 3-37). precision.
11. The series of six AEC KV calibration exposures (with optical density
measurements) may be repeated as many times as desired to
improve calibration accuracy. Repeating is recommended if the
desired and measured optical densities differ significantly.
12. This completes AEC calibration for this particular film/screen combi-
nation. Repeat AEC calibration procedures for all additional film/
screen combinations that will be used with the system.
DISPLAYS
DESTINATION
FILM/SCREEN
NAME
6. Press the key next to the Copy Film/Screen field. All AEC calibra-
tion data is now copied from the Wall 40" film/screen combination to
the Table 40" film/screen combination. To abort without copying,
press the key next to the MAIN field. The AEC Calibration Menu is
displayed.
IMPORTANT NOTES:
1. Upon completing calibration procedures, it is
recommended that the Q-Ware program be used
to upload calibration data (and APR technique
data, if APR editing was performed) as a backup
in case a problem occurs that requires re-calibra-
tion of the generator. To obtain a copy of the Q-
Ware program, contact Quantum Medical Imag-
ing’s Customer Service Department.
4. After the tenth exposure, select (coefficient of variation) COEFF VAR on Dyn-
alyzer; reading must be less than or equal to 0.05. If a Dynalyzer is not used,
calculate the C.O.V. (coefficient of variation) according to the following:
1/2
s 1
n
(xi - x)2
C= =
X X i=1
n-1
Where
C= Coefficient of Variation
s = standard deviation
x = Mean value of mR readings
xi = ith observation sampled
n = number of observations sampled
Accuracy Specifications
mA Accuracy: mA = ± ( 5.0% mA + 1 mA )
Page 1 of 4
Exposure Number mR
1
2
3
4
5
6
7
8
9
10
MEAN VALUE (x)
C.O.V.
Exposure Number mR
1
2
3
4
5
6
7
8
9
10
MEAN VALUE (x)
C.O.V.
Page 2 of 4
SAMPLE 1 mA SAMPLE 2 mA
(From Table 3-9) = _______ (From Table 3-9) = _______
EXPOSURE mR mAs EXPOSURE mR mAs
1 1
2 2
3 3
4 4
5 5
6 6
7 7
8 8
9 9
10 10
SUM SUM
MEAN VALUES MEAN VALUES
= SUM ÷ 10 = SUM ÷ 10
X1 = mR ÷ mAs _______ ÷ _______ X2 = mR ÷ mAs _______ ÷ _______
X1 = _______ X2 = _______
X1 - X 2 = _______ X1 + X 2 = _______
LINEARITY =
= ________________ must be < 0.1
Page 3 of 4
SAMPLE 1 mA SAMPLE 2 mA
(From Table 3-9) = _______ (From Table 3-9) = _______
EXPOSURE mR mAs EXPOSURE mR mAs
1 1
2 2
3 3
4 4
5 5
6 6
7 7
8 8
9 9
10 10
SUM SUM
MEAN VALUES MEAN VALUES
= SUM ÷ 10 = SUM ÷ 10
X1 = mR ÷ mAs _______ ÷ _______ X2 = mR ÷ mAs _______ ÷ _______
X1 = _______ X2 = _______
X1 - X 2 = _______ X1 + X2 = _______
LINEARITY =
= ________________ must be < 0.1
Page 4 of 4
SETTING 45 200L 50 mS 10
1
MEASURED
MEASURED
THEORY
OF OPERATION
4-1
4-2
Chapter 4 Theory of Operation
OVERVIEW
The following paragraphs provide theory of operation for QUEST HF SeriesTM Genera-
tors. Each circuit description references a functional block diagram contained in
Chapter 6, Diagrams.
OPERATOR CONTROL PANEL CIRCUIT
The Operator Control Panel Circuit controls the X-ray generator’s exposure set-
tings and exposure sequence, and controls the display of settings on the Front
Panel liquid crystal display (LCD). Exposure setting data is input to the Operator
Control Panel Circuit through the Front Panel key switches. The READY, PREP,
and EXPOSE LEDs located on the Front Panel are used to indicate the status of
the exposure sequence. The Operator Control Panel Circuit includes an RS-232
service connection, which allows service personnel to download data to Flash
Memory, perform X-ray generator diagnostics, and to upload non-volatile random-
access memory (NVRAM) settings.
Microcontroller U3 Operation
Microcontroller U3 is the primary controller of Operator Control Panel Circuit
functions. It has it own internal read-only memory (ROM) and random-
access memory (RAM). The 32 MHZ output from Oscillator U18 provides the
clocking input to drive Microcontroller U3. The Reset Circuit U1 monitors the
+5 VDC supply voltage; when it falls below +4.5 VDC, Microcontroller U3 is
placed in the "reset state". When the voltage returns to a level above 4.5
VDC, the Microcontroller restarts.
Data is sent to the generator via a 9-pin connector and cable connected to
the generator Logic Board. The 9-pin cable includes RS-485 communication,
hardware control lines, and power supply voltage from the generator. PREP
and EXPOSE hardware lines are routed from Open Collector Driver U16 to the
generator to indicate the state of the system to the generator.
Flash Memory U2
Flash Memory U2 holds part of the main program and all of the tables for the
LCD display screens. Flash Memory is accessed by Microcontroller U3
through the DATA/ADDRESS bus and Control Signals. On the first memory
read/write clock cycle, the Flash Memory address is stored in Latches U4 and
U5. On the second clock state, Microcontroller U3 reads or writes the data to
Flash Memory U2.
The Flash Memory is programmable using a personal computer via the RS-
232 port (connector J4).
NVRAM U17 Operation
Non-volatile random-access memory (NVRAM) U17 stores all data changes
that occur during X-ray generator operation, and contains configuration set-
tings, calibration data, and Anatomical Programmed Regions (APR) technique
data. This data is retained even when power to the generator is shut down.
NVRAM data is accessed in two steps:
generator, based on states and settings set by the master Microcontroller U9.
Microcontroller U14 has it own internal ROM and RAM. It is driven by a crystal
oscillator at a clock speed of 32 MHz.
There is a communication link between the master and slave for data and
status exchange. The Reset Circuit U8 monitors the +5 VDC supply voltage;
when it falls below +4.5 VDC, Microcontrollers U9 and U14 enter a reset
state. When the +5 VDC supply voltage returns to a level above +4.5 VDC,
the microcontrollers restart.
The master Microcontroller U9 has external Flash memory. The EPROM holds
part of the main program. The EPROM is accessed by U9 through the DATA/
ADDRESS bus of Microcontroller U9, with required Control Signals. On the
first clock cycle, the Flash memory address is stored in Latches U12 and U13.
On the second clock cycle, Microcontroller U9 reads data from Flash memory.
Microcontroller U9 communicates with the KVP & Filament Control Circuit to
set the digital-to-analog (D-A) converters and to read analog signals from
analog-to-digital (A-D) converters.
In addition, there are hardware signals that control the Filament Regulator
Control Circuit and KVP & Filament Control Circuit. Some of the key signals
are isolated using opto-couplers. On systems utilizing the AEC option, the
same connector (J1) is connected to the AEC board in parallel.
The interface board controls all external signals needed to interface to the
tube stand, wall stand, and table. Some of the signals coming are isolated by
opto-couplers. J2 interfaces to the line monitor board. The line monitor board
supplies the 24VDC for the brakes. The line monitor supplies a sample of the
400 VDC bus for monitoring by Microcontroller U14, which uses an internal A-
D converter to monitor key voltages including the +5V, 15V, 24V, 24V brake
supply voltages. U16 is the 4.8V voltage reference for Microcontroller U14
internal A-D. Microcontroller U14 controls the Rotor Board; it provides the
necessary signals for boost and run, and it monitors the tube rotation signal
and rotor temperature.
FILAMENT CONTROL REGULATOR CIRCUIT
The Filament Control Regulator circuit is a high frequency, pulse-width-modu-
lated-based system. The circuit receives signals from the KVP & Filament Control
circuit and outputs filament current to the High-voltage Tank, which then pro-
duces the small or large filament currents for the X-ray tube. The detailed opera-
tion of the Filament Control Regulator circuit (see Filament Regulator Control
Circuit Block Diagram in Chapter 6, DIAGRAMS) is as follows:
A signal from the KVP & Filament Control circuit that controls filament current is
input to Filament Current Opto-isolator U2A. Varying the voltage of this signal
will cause the output of U2A to vary between 0 and 5 volts. This varying voltage
is fed to the input of Pulse Width Modulator U1. The output of the Pulse Width
Modulator is input to Transformer Driver U3. The Transformer Driver buffers the
output of the Pulse Width Modulator in order to supply enough current to drive
Transformer T1. Transformer T1 drives an H-bridge circuit consisting of Q1-Q4.
The output of the H-bridge is a 20 kHz signal that is output through Filament
Select K1 and Q5 to drive the filament transformer in the High-voltage Tank. The
duty cycle of the 20 kHz signal is varied by the Pulse Width Modulator depending
on the amount of filament current required by the particular exposure.
In order to complete the filament current control loop, the 20 kHz signal is run
through the primary of Current Sample Transformer T2. The Current Sample
Transformer's turn ratio is configured such that 1 amp flowing through its primary
will result in 1 volt at its secondary. The output of Current Sample Transformer
T2 is fed to the input of RMS-to-DC Converter U4. The output from RMS-to-DC
Converter U4 is a dc signal that is proportional to the RMS current flowing
through the primary of the filament transformer (in the High-voltage Tank). The
RMS-to-DC Converter's output is buffered and amplified by Amplifier/Buffer U5A
before being sent to the KVP & Filament Control circuit.
U5B is configured as a full-wave rectifier whose output is filtered by R19, R32 and
C14. The resulting voltage is input to U1 as a filament current limit signal. R25
can be adjusted to limit the maximum filament current.
The large or small filament is selected by the FIL SIZE signal from the KVP & Fila-
ment Control circuit. A high level FIL SIZE signal applied to the Filament Select
circuit turns on transistor Q5, which energizes relay K1. When K1 is energized,
the small filament is selected. A low level FIL SIZE signal will keep K1 turned off
and the large filament will be selected.
KVP & FILAMENT CONTROL CIRCUIT
The KVP & Filament Control circuit controls the high voltage and tube current
supplied to the x-ray tube. The x-ray tube current is a function of its filament cur-
rent. The filament current is controlled by a feedback loop consisting of the KVP
& Filament Control circuit and the Filament Control Regulator circuit. The KVP &
Filament Control Circuit operates as follows:
The output of the kVp divider within the High Voltage (H.V.) Transformer is input
to Anode Amplifiers U1A, U1B and Cathode Amplifiers U2A, U2B as the ANODE
FDBK and CATHODE FDBK signals, respectively. The outputs of the Anode and
Cathode Amplifiers are compared with the KV PROGRAM (from voltage at Com-
parators U1C, U2C) and are also sent to the Logic Circuit via Parallel to Serial A/D
U13. Comparator U1C's output varies the output frequency of Pulse-Width Modu-
lator U3, depending on the desired kVp voltage. The output of Pulse-Width Mod-
ulator U3 is sent to the anode IGBT Driver Board (part of Power Module
Assembly). This board drives the IGBT's, which in turn drive the H.V. Trans-
former, thus producing the high voltage for the x-ray tube. The cathode Amplifi-
ers (U2A, U2B), Comparators (U1C U2C) and Pulse-Width Modulator U4 work in a
similar manner. In lower-power systems, Pulse-Width Modulator U4 is not used,
and the outputs of Amplifiers U1B and U2B are summed together to control U4.
Comparators (U6A, U6B), Amplifiers (U1D, U2D) and Comparator U6C monitor
the high voltage to check for an over-voltage condition. A watchdog timer (Re-
triggerable One-Shot U7A) must be triggered every 50 msec. by the TRIGGER
input from the Logic Circuit (via Address Decoder U15) in order for an x-ray to
occur. If this pulse stream were missing, it would signal a failure condition thus
terminating the x-ray and the ERROR signal is output through D-Flip-Flop U12A
and Logic Inverter U21A to the Logic Circuit. The 7 TRIGGER signal from the
Logic Circuit (generated at the beginning of exposure cycle) is applied to 7-Sec-
ond One-Shot U7B, which produces a seven-second positive-going pulse. If the
exposure is not terminated within seven seconds, D-Flip-Flop U12A and Logic
Inverter U21A generate the ERROR signal.
Amplifiers (U10A, U10B), Amplifiers (U10C, U10D) and Driver Q3 monitor the x-
ray tube current via an mA sense resistor in the High Voltage Tank and compare
this value to the mA Program and Filament Program values (received from the
Logic Circuit via Serial to Parallel D/A U16. The FIL CURRENT output from this
circuit is a voltage that is sent to the Filament Control Regulator Circuit to vary
the filament voltage based on the selected x-ray tube current.
Address Decoder U15, Parallel to Serial A/D U13, and Serial to Parallel D/A U16
enable communication between the Logic Circuit and the KVP & Filament Control
Circuit. Parallel to Serial A/D U13 converts analog signals from the KVP & Fila-
ment Control Circuit to digital signals for input to the Logic Circuit. Serial to Par-
allel D/A U16 converts digital signals from the Logic Circuit to analog signals for
use by the KVP & Filament Control Circuit.
LINE MONITOR CIRCUIT (NON-SE SINGLE-PHASE AND THREE-PHASE SYSTEMS)
The Line Monitor Circuit consists of three circuits: an input line monitor circuit, a
circuit that bleeds off the high voltage from the IGBT capacitor banks and an
auto-shutoff circuit that turns off the generator after 1 hour of inactivity. The
auto-shutoff circuit also allows the microprocessor to turn off the generator in the
event a fault occurs in the system. The operation of the Line Monitor Circuit is as
follows:
Input Line Monitor Circuit
The Input Line Monitor Circuit monitors the incoming line voltage to ensure it
is at the correct voltage level required for taking an exposure. This circuit is
configurable for either single-phase systems (anode capacitor bank only) or
two identical voltage-monitoring circuits (anode and cathode capacitor banks)
for three-phase systems.
On three-phase systems, each circuit produces a VSENSE voltage that is pro-
portional to the voltage of the anode or cathode capacitor bank. (The ratio of
the voltage across either capacitor bank to the voltage at the output of the
line monitor circuit is 100:1.) The VSENSE (ANODE) and VSENSE (CATHODE)
voltages are sent to the Logic Circuit to determine if the line voltage is within
acceptable limits for proper system operation. On single-phase systems,
there is one capacitor bank each for the anode and cathode. In this case, the
capacitor bank is connected to the anode circuit only (JP1-2 is connected to
JP1-3) on the Line Monitor circuit board. The result will be that the micropro-
cessor will read the same capacitor bank voltage at VSENSE (ANODE) and
VSENSE (CATHODE).
The Battery Charger consists of two similar power supplies, one positive (+)
and one negative (-), both of which are necessary to charge a single battery
tray.
220VAC is fed from two independent secondary windings of the AC Mains
Power Transformer (T1) to two full-wave bridge rectifiers. The unfiltered
+/-283VDC outputs are fed to twin Triacs controlled by Pulse Width Modu-
lated (PWM) switching circuits that simultaneously and continuously direct
charging current to the weakest of the two trays (when two are present).
Together, these two power supplies provide the needed charging current to
each half of both battery arrays.
This arrangement permits the creation of dual, center-grounded, 410VDC
Anode and Cathode Stored Energy Power Supplies using just two 205VDC
regulated battery chargers. Each charger keeps its half of each battery tray
at precisely 205VDC by varying the duty-cycle of its Triac switch from 0% to
100%.
If the Battery Monitor circuit senses an over-voltage condition, it will turn off
relays K1 and K3, disconnecting the Triacs from the output of the bridge rec-
tifiers. The charging current will remain interrupted until the over-voltage
condition is corrected. An Over-voltage Fault signal is also sent to Logic
Board A1, which will return a separate shutdown command to the PWMs for
redundant safety.
POWER SUPPLY CIRCUIT
The power supply circuit (see Power Supply Board A6 (AY40-005T) Schematic
Diagram in Chapter 6, DIAGRAMS) consists of four power supplies that provide
the power needed to the control circuits. Two power supplies (+15VDC and
+48VDC) are switching power supplies. The other two power supplies (+24VDC
and -15VDC) are linear.
+48 VDC Power Supply
The +48 VDC and +15 VDC power supplies work with the same boost con-
cept design, but some of the components are different between the power
supplies.
The +48 VDC Power Supply consists of Bridge Rectifier DB1 that produces a
43 VDC (approximately) output (TP2), which is filtered by capacitor C2. The
43 VDC is chopped by transistor Q1 with inductor L1 in series. When Q1
turns off, the inductor and the DC voltage across C2 supplies voltage to the
output. The output is the sum of both voltages. Therefore, the output volt-
age will never be lower than +43 VDC (neglecting the voltages across compo-
nents). The time that transistor Q1 is on depends on the input DC voltage
and the output load. Pulse-Width Modulator (PWM) U1 samples the output
voltage, and it controls Q1 on time to maintain constant output voltage. The
output voltage is adjusted to +48 VDC (TP3) with R17 in case there is a prob-
lem supplying the filament current as a result of long length high-voltage
(H.V.) cables. The +48 VDC output can be adjusted to supply adequate fila-
ment current. The maximum adjusted voltage should not exceed +52 VDC.
+15 VDC Power Supply
The +15 VDC power supply works using the same boost concept design as
the +48 VDC power supply. The +15 VDC Power Supply bridge rectifier DB4
produces a DC voltage output, which is filtered by capacitor C18. The DC
voltage should be approximately +13 VDC (TP10). The DC voltage is
chopped by transistor Q2 with inductor L2 in series. When the transistor
turns off, the inductor and the DC voltage across C18 supplies voltage to the
output. The time that transistor Q1 is on depends on the input DC voltage
and the output load. PWM U2 samples the output voltage, and it controls Q2
on time to maintain constant output voltage. The output of the +15 VDC
supply has a resettable fuse (F2). When the load exceeds the limit of the
fuse, the output shuts off until the overload is removed.
+24 VDC Power Supply
The +24 VDC power supply uses a linear adjustable regulator that produces
regulated 24VDC (at TP8). The input DC voltage (approximately 35V) to the
regulator comes from bridge rectifier DB4 and filter capacitor C15.
The power supply that produces the -15VDC uses a linear fix output regulator
that produces the regulated -15VDC (TP8). The input negative DC voltage
(TP7 approximately -21V) to the regulator comes from the bridge rectifier
DB2 and filter capacitor C13.
ROTOR BOARD CIRCUIT (NON-HIGH SPEED STARTER SYSTEMS)
The Rotor Circuit (see Rotor Circuit Block Diagram in Chapter 6, DIAGRAMS) sup-
plies the power needed for the tube rotor running at 50/60 Hz. The 50/60 Hz
running frequency depends on the input AC line. The power consumption varies
depending on the tube. Different tubes need different phase shift capacitor (C1)
as recommended by the tube manufacturer. Changing the tube to a different
type may require changing the phase shift capacitor connected to J5 (check man-
ufacturer’s tube data sheet).
The boost and the run voltages are constant; boost is 220VAC and run is 60VAC.
The operation of the rotor starts during PREP. The ROTOR ON signal comes from
the Logic Circuit at J3-1, which is input to Control Circuits. This RELAY ON signal
from the Control Circuits turns on relay K2 generating the COM output, which
connects the common to the rotor (TP1). The BOOST ON signal (TP6) starts the
Boost state by generating the Q1 DRIVE signal to Q1 through the Control Circuits.
When the boost period is finished, the BOOST ON signal turns off and the RUN
ON signal turns on (J3-3). By turning on the RUN ON signal (TP7) and turning
BOOST ON off, Q1 turns off and Q2 turns On. The RUN ON signal will remain on
throughout the PREP and Expose states. In case the tube's thermal switch is acti-
vated (indicated by active TEMP. FAULT signal), Relay K2 will open removing
power to the rotor, and the Control Circuit will turn off either Q1 or Q2. A "Rotor
Thermal Error" will be displayed on the OCP.
The Main (TP2) and Phase (TP4) currents are sampled by the Control Circuits to
determine whether the rotor is rotating (when rotating, the ROTOR ROTATING
signal at J3-4 is active). If the ROTOR ROTATING signal is inactive, an error will
be displayed on the OCP. Power needed for operation of the Control Circuits and
Relay K2 is supplied through connector J4.
ROTOR BOARD CIRCUIT (QUANTUM INTERNAL HIGH SPEED STARTER SYSTEMS)
The following applies only to systems equipped with a Quantum-manufactured
High Speed Starter (Q-HSS). The Q-HSS functions to drive the rotating anode of
many types of 3" or 4" x-ray tubes. The tube anode rotates at either of two dis-
tinct speeds/frequencies; low speed operation (60 Hz) or high speed operation
(180 Hz).
All necessary settings for the high speed starter are configurable by accessing the
generator’s Service Configuration screen (refer to Chapter 3, CALIBRATION).
The Q-HSS consists of two circuit board assemblies: HSS Control Board A20A1
(AY40-035S) and HSS Drive Board A20A2 (AY40-036S).
All required settings needed for high speed starter timing and control are known
to Logic Board A1, The BOOST RUN/ BRAKE voltages are set based on tube
model.
Refer to Chapter 2, ASSEMBLY & INSTALLATION for HSS Driver Board AY40-036S
transformer input wire connections to terminal block TB1 plug and for wiring con-
figuration of rotor phase capacitor.
HSS Control Board A20A1 (AY40-035S)
The HSS Control Board A20A1 receives operating handshake commands
(such as SYSTEM ON/OFF) from the generator Logic Board A1 (AY40-004S)
through connector J2. The signals coming and going to the Logic board via J2
are optically isolated. The handshake signals control the high speed starter’s
Rotor On, Boost, Run and Brake sequence. The Boost and brake time settings
are based of the tube model selected for the generator.
ated. The TEMP signal is output through connector A20A2J2 to HSS Control
Board A20A1, which then activates a temperature signal to generator Logic
Board A1. In response, a "Rotor Temp" error is indicated on the Operator
Control Panel display.
The following are the ratings of the various fuses located on HSS Drive Board
A20A2:
• F1, F3: AC Input voltage - 15A/500VAC
• F4: Rotor output drive - 15A/500VAC
• F5: Temperature sense input - 0.1A/250V
AEC BOARD CIRCUIT
The automatic exposure control (AEC) option is available in either of two types:
Standard or Universal. The standard type provides for connection of up to two
ion chambers, one for a wall mounted image receptor and one for a table
mounted receptor. Both ion chambers must be of the same type, i.e., either
"slope" or "level". The universal type provides for connection of up to four sepa-
rate ion chambers, each one can be either type (slope or level). The following
paragraphs describe general circuit functions of each AEC type.
Standard Type AEC
The standard type AEC Board A11 (AY40-031S) controls the exposure time to
maintain uniform optical density (O.D.) with respect to various kV and mA
settings. Using AEC, the operator sets the desired kV and mA; the exposure
time is determined by the AEC circuit. AEC calibration is required in order
establish a desired or optimal optical density (refer to Chapter 3, AEC Calibra-
tion).
The AEC Board is designed for use with ion chambers having the following
characteristics:
• Positive slope
• Ion chamber selection signal: active low
• Ion chamber on signal: active low
The AEC Board can control two separate ion chambers; each of the ion cham-
ber connectors is a D-type connector (A11J2 = Wall 1 and A11J5 = Table).
The ion chamber is selected from the operator control console via the TABLE
and WALL receptor keys. These selections are input to control logic con-
tained on Logic Board A1 AY40-006S, which controls the selection of the ion
chamber and the detectors within the selected ion chamber. The AEC board
receives the voltage input from selected ion chamber, and processes the sig-
nal. The processed signal is compared continuously with a set reference volt-
age produced by KVP Board A2 AY40-003S. The reference voltage is a
function of kVp and the film/screen combination type. When the processed
signal is equal to the reference voltage, the exposure is terminated.
The AEC Board A11 AY40-031S "fine" gain adjustment potentiometers are as
follows:
• A11R22 Table gain adjustment
• A11R23 Wall 1 gain adjustment
• A11R24 Wall 2 gain adjustment (currently not used)
The above potentiometers provide fine gain adjustments for each of the ion
chamber detectors, coarse gain adjustment is performed by adjusting the
MASTER GAIN potentiometer located on the ion chamber. A11R12 provides
AEC dV/dT adjustment as described in the AEC calibration instructions in
Chapter 3. The following major test points and a brief description are:
• TP1- Wall 1 input from ion chamber
• TP2- Wall 2 input from ion chamber
• TP5- +15V supply to ion camber
• TP6- -15V supply to ion camber
• TP7- Table input from ion chamber
• TP9- Inverted polarity slope of selected ion chamber signal
• TP12- AEC output to KVP board
Universal Type AEC
The "universal" AEC Board A11 (AY40-027S) has the capability to work with
two ion chambers (four in the future), and provides necessary interface to
connect to the Siemens tomography system (or any other tomography sys-
tem having similar hand-shake protocol as Siemens). The universal AEC
Board is capable of working with ion cambers that have different type of out-
puts (Slop / Level), polarity (Positive / Negative), or logic levels. (active low,
active high.) The ion chamber configuration/ setting can be set through
setup menus in the calibration setup mode. The settings options to ion cham-
ber type that can be programmed are:
• Ion chamber cell selection
• Type of the ion chamber output slope/level
• Polarity of the AEC output signal
• The level of ion detectors selection signal (active low/active high). The
ion chamber ON (Reset) is always active low.
The board is divided into three major functions described in the following
paragraphs:
• +300 VDC power supply
• AEC Control Circuit
• Tomography Interface Circuit
Slope Level
dv/dt adjustment:
A11R82 - Adjust once for
either table or wall ion cham-
ber (both must be "level" type
ion chambers)
Slope Level
dV/dt adjustment:
Ion chamber output balance:
A11R87 - Adjust once for either
A11R61 - Field 1 (Center),
the table or wall ion chamber
A11R63 - Field 2 (Left)*,
(both must be "slope" type ion
chambers) A11R66 - Field 3 (Right)*
dv/dt adjustment:
A11R82 - Adjust once for
either table or wall ion cham-
ber (both must be "level" type
ion chambers)
Tomography Circuitry
The universal AEC Board provides interfacing circuitry to the Siemens tomog-
raphy system (and to other tomography systems that have similar hand-
shake interface). The Tomography circuitry contains the signal sequence
needed to take an exposure using a Siemens table (including a Tomo table)
or a Siemens wall stand. In addition, it includes the sweep time detection cir-
cuitry that detects tomography mode of operation.
When Tomo Mode is detected, the operator control panel automatically dis-
plays Tomo Mode screen. The Tomo Mode screen displays an icon indicating
Tomo Mode, and the exposure "time" is changed to "sweep time". The expo-
sure hand-shake control signals are received from the Logic Board and Inter-
face Board. These signals are activated during PREP and EXPOSE states, and
are sent and received from either the tomo table or wall stand. The Tomo
Mode detection circuitry receives the tomo sweep time from the tomo table.
The Universal AEC Board detects the selected tomo sweep time, and sends it
to the Logic Board. The Logic Board sends the data to the OCP via serial
communication protocol.
SERVICE
INSTRUCTIONS
5-1
5-2
Chapter 5 Service Instructions
OVERVIEW
The HF Series X-ray Generator will function reliably when maintained according to the
instructions provided in this chapter. Only properly trained service personnel should
service or maintain this equipment. Safe equipment performance requires the atten-
tion of service/support personnel who are specifically trained and experienced with
medical x-ray apparatus. Applicable preventive maintenance or any repair service
should be performed by these skilled individuals. Failure to follow manufacturer’s or
service personnel’s recommendations may result in serious injury. This chapter also
includes a detailed component listing of the generator’s replaceable parts.
SERVICE MAINTENANCE
Error Codes
Refer to the following descriptions for assistance in interpreting the error
code displayed on the Operator Control Panel:
Table 5-1. Error Messages and Possible Cause(s)
Error
Possible Cause(s) Remedial Action
Message
READY 1. Filament automatically shuts off Press PREP key. An error message
LED not after 60 minutes of inactivity. displays on the operator control
illuminated 2. The exposure setting(s) exceed panel. Refer to appropriate error
the tube or model limits. message listed in this table for error
3. Faulty communications details. Press any key to clear error.
between generator and OCP. System should now be ready for
4. Incorrect generator program or exposure.
generator is not working. Check serial cable connection
5. Lost communication between between OCP and generator cabinet
OCP and generator cabinet. and jumper settings on OCP Control
Board (AY40-004S1).
AEC Not No AEC hardware present. Check AEC cable is connected and/
Installed or is not defective.
Error
Possible Cause(s) Remedial Action
Message
Anode Indicates that the tube maximum Reduce technique factor(s) and/or
Heat or heat load capacity will be wait until tube cools sufficiently. Re-
Housing exceeded if exposure is taken at take exposure.
Heat current exposure factors.
Anode Indicates that there is a problem 1. Visually inspect the Anode Power
Volt with the anode kVp circuit, high Driver Module A18 (on right side)
voltage transformer, or Power for damage.
Driver Module. (Note: If the reme- 2. Check for output drive signal from
dial actions given do not correct KVP Control Board A2 as follows:
fault, refer to the "Cathode Volt" Disconnect plug from A2J7 and
error message and perform appli- A2J8. Connect oscilloscope probe
cable remedial actions.) (CHAN 1) to A2TP21 and CHAN 2
probe to A2TP22. Set oscilloscope
time base to 5 usec./div. and the
vertical amplitude to 5V/div. Take
an exposure. An "Anode Volt" error
will display and the following wave-
form should be obtained:
APPROX.
1.2 MS
DELAY
Error
Possible Cause(s) Remedial Action
Message
Error
Possible Cause(s) Remedial Action
Message
Sample waveform above is with operator control panel set for 50 kVp, 200L mA, 100 ms.
(Each volt measured represents 8.2 kV.) If spikes are present, this indicates arcing in
either the x-ray tube or high voltage transformer.
Error
Possible Cause(s) Remedial Action
Message
Backup Backup time was reached based 1. Reduce technique factor(s). Re-
on current technique factors. take exposure.
2. Verify ion chamber cable connec-
tions are correct and secure.
3. On AEC Control Board A11
(AY40-031S or AY40-027S), check
+15 VDC and -15 VDC outputs are
not loaded down. If so, remove ion
chamber cable connection and re-
check voltages. If +15 VDC and /or
-15 VDC outputs are now good, ion
chamber is at fault. If still loaded
down, replace AEC Control Board.
Error
Possible Cause(s) Remedial Action
Message
Battery Faulty stored energy cell in top 1.. Connect a DMM to Line Monitor/
Dis- battery tray (Cathode on two tray Charger Board A8 AY40-028T
charged systems) or Line Monitor/Charger test point TP2 and ground. Verify
board not adjusted correctly. voltage is +204 to +206 VDC. If
not, adjust A8R70 to obtain cor-
Battery 2 Faulty stored energy cell in bottom rect voltage. If voltage cannot be
Dis- battery tray (Anode on two tray adjusted to correct value, replace
charged systems) or Line Monitor/Charger Line Monitor/Charger Board A8.
board not adjusted correctly. 2. Connect a DMM between Line
Monitor/Charger Board A8 test
point TP3 and ground. Verify volt-
age is -204 to -206 VDC. If not,
adjust A8R66 to obtain correct
voltage. If voltage cannot be
adjusted to correct value, replace
Line Monitor/Charger Board A8.
3. Check each stored energy cell in
battery tray. Voltage of each cell
should be 12.5 VDC minimum. If
not, replace cell.
4. Check A8K1 and A8K3 operation
as follows: Turn A8R19 and
A8R60 fully counterclockwise.
Verify voltages between A8TP20
and GND and A8TP21 and GND
are less than 1.0 VAC. Turn
A8R19 and A8R60 fully clock-
wise. Verify voltage between
A8TP15 and GND and A8TP16
and GND are +283 VDC and -283
VDC, respectively.
5. Connect a DMM between A8TP21
and GND. Adjust A8R19 to mea-
sure +2.10 - +2.14 VDC.
6. Connect a DMM between A8TP20
and GND. Adjust A8R60 to mea-
sure +2.10 - +2.14 VDC.
Error
Possible Cause(s) Remedial Action
Message
Battery Battery voltage is too low. (This Wait until READY light on Operator
NotRdy warning message applies only to Control Panel is steady before taking
stored energy generators.) exposure.
Calibration Generator kV, mA, and/or filament Access Service Mode and perform
calibration settings are outside of kV, mA, and/or filament calibration.
acceptable limits for normal sys-
tem operation.
Error
Possible Cause(s) Remedial Action
Message
Cathode The filtered cathode volts are out- 1. Visually inspect the Cathode
Volt side of preset limits at any time. Power Driver Module A19 (on left
(Note: If the remedial actions side of cabinet) for damage.
given do not correct fault, refer to 2. Check for output drive signal from
the "Anode Volt" error message KVP Control board A2. Disconnect
and perform applicable remedial plug from A2J7 and A2J8. Connect
actions.) oscilloscope probe (CHAN 1) to
A2TP23 and CHAN 2 probe to
A2TP24. Set oscilloscope time
base to 5 usec./div. and the verti-
cal amplitude to 5V/div. Take an
exposure. An error will occur and
the same output drive waveform
shown in the "Anode Volt" proce-
dure on previous pages should be
obtained.
3. If waveform is correct proceed with
step 5.
4. If waveform is not as indicated,
replace KVP Control Board A2
and re-check drive signal as
described in previous step. If prob-
lem persists, replace Logic Board
A1 (AY40-006S) and re-check. If
still not corrected, check wiring.
5. Re-connect plugs into A2J7 and
A2J8.
6. On KVP Control Board A2 (AY40-
003S), connect oscilloscope probe
to TP2 (Cathode Sense) and take
exposure. The same voltage out-
put waveform shown in the "Anode
Volt" procedure on previous pages
should be obtained.
7. The equivalent kV value should be
approximately half the indicated
kV value on OCP. If kV value is
acceptable, check H.V.Trans-
former. If kV value is not accept-
able, perform steps 8 through 10.
Error
Possible Cause(s) Remedial Action
Message
Collimator Automatic collimator not respond- 1. Positive beam limitation (PBL) cir-
ing (only appears on systems cuit is open; check PBL cable con-
using an automatic collimator). nection between generator and
table.
2. Verify jumper JP1 is not installed
on Interface Board A9 (AY40-
023T).
Door Entrance door to x-ray room is Verify x-ray room door is closed and
open. re-take exposure.
Early Term Exposure terminated prematurely Press any key on Operator Control
because EXPOSE key was Panel to clear warning message. Re-
released before exposure was take exposure.
completed.
Error
Possible Cause(s) Remedial Action
Message
Filament The filtered Filament Amps are 1. Verify -15 VDC at TP5 on Power
Prog outside of preset limits at any Supply Board A6 (AY40-005T).
time. Indicates that there is a 2. Replace KVP Control Board A2
problem with either: (AY40-003S).
1. D-A circuit on the KVP Control 3. Check fuse F8 on Interface Board
Board A2. A9 (AY40-023T).
2. Filament Control Board A5 4. Check for loose connector A6P2.
(AY40-007T) regulator A-D. 5. Replace Filament Control Board
A5 (AY40-007T).
Error
Possible Cause(s) Remedial Action
Message
Filament The OCP sent a request to the 1. Verify that the tube selected in the
Too Low Generator to set a PREP value Service / Config / Tube is that
that is too low. which is physically installed in sys-
tem.
2. Make sure that Filament Calibra-
tion has been completed correctly.
3. Verify that "Reset Tube" has been
selected when exiting the Select
Tube screen.
4. Verify that the filament is working.
If it is not, go through the trouble-
shooting steps of "Filament Curr"
error.
Flash Flash memory returned incorrect Check A16U2. Call Technical Ser-
checksum. vice/Support.
Flash Not 1. Flash Memory (U2) on OCP 1. Verify version of the OCP Control
Loaded Control Board A16 (AY40- Board microcontroller U2 software
004S1) not loaded with pro- is correct by looking at the label on
gram that corresponds with the U2. A method of checking the
version of the Microcontroller installed software versions are
program in the OCP. accessing service mode menus
2. Flash Memory is experiencing a Service / Reports / Checksums.
read problem. (The Flash is The "Internal" and "External" ver-
continuously read during oper- sions must be the same and
ation and an error displayed if checksums valid or many func-
checksums or versions are not tions (such as PREP and
correct.) EXPOSE) are inhibited.
2. A16A1U2 may be damaged -
replace OCP Control Board.
Error
Possible Cause(s) Remedial Action
Message
Generator Operator Control Console lost On OCP Control Board A16 (AY40-
Comms communication with generator 004S1), connect oscilloscope to test
cabinet. Can be caused by: point TP2. With system turned on
1. Faulty or improperly installed and idling, verify waveform is as
OCP Serial Cable shown below. There should be a set
2. Improperly configured jumpers of two pulses approximately every
on OCP Control Board A16 second. The first pulse is sent from
(AY40-004S1) or Logic Board the OCP Control Board to the Logic
A1 (AY40-006S) Board. The second pulse is sent by
3. Failed transceivers on A1 and/ the Logic Board to the OCP Control
or A16 boards. Board in response to the first pulse.
4. Logic Board A1 microproces- If only one pulse is present, connect
sor A1U9 faulty, not properly oscilloscope to test point TP8 on
seated in socket, or loaded with Logic Board A1 (AY40-006S). If no
incorrect program. pulse is present, OCP Serial Cable is
faulty or not connected properly.
Note: Verify jumpers A16JP1,
A16JP4, A16JP10, and A16JP11 are
installed on OCP Control Board.
Error
Possible Cause(s) Remedial Action
Message
Generator 1. Generator entered Filament low 1. Press any key other than
Not Ready voltage state due to no opera- EXPOSE or PREP, then retry
tor activity for over 60 minutes. exposure.
2. Failed communication between 2. Check that serial cable between
generator cabinet and opera- OCP and generator cabinet is
tor control panel. properly connected.
3. Wrong program loaded into 3. Verify correct microcontroller pro-
OCP Control Board A16U3. gram has been loaded into OCP
Control Board A16U3.
4. On stored energy (SE) genera- 4. Allow batteries to re-charge.
tors, the batteries have not re-
charged to 400 VDC.
Heat Tube heat exceeded heat limit. Allow tube to cool until "Heat Alarm"
Alarm no longer appears.
HSS A High Speed Starter has been If High Speed starter is connected to
Detected detected when none is selected. generator, change setting in Service /
Config / Rotor to a HSS setting ("QMI
HSS" or "AID HSS").
Keybrd Indicates a key on the Front Panel 1. Verify a switch on the keyboard
is stuck on. was not accidentally depressed
during power up.
2.Check connection between OCP
Control Board A16A1 (AY40-
004S1) and Front Panel Overlay
(flat green cable).
3. Replace Front Panel. If front panel
replacement doesn't correct prob-
lem, then replace OCP Control
Board A16A1.
Error
Possible Cause(s) Remedial Action
Message
KVP 1. The anode and cathode KV are 1. On KVP Control Board A2 (AY40-
Error sufficiently different to cause 003S), check the difference
an error. between the Anode (TP1) and
Cathode (TP2) to determine if dif-
ference exists during an exposure.
2. The anode or cathode voltage 2. If anode (A2TP1) or cathode
sense is exceeding 15% of pro- (A2TP2) are above program volt-
gram voltage. age by 15% (1V=8.2 kVp), replace
KVP Control Board A2. If problem
persists, replace H.V. Transformer
A17, x-ray tube, or high-voltage
cables.
3. Communication between OCP 3. Refer to "Generator Comms" error
Control Board A16 (AY40- message for troubleshooting and
004S1) and Logic Board A1 correcting communications prob-
(AY40-006S) was interrupted. lems.
4. Arc in system (H.V. Trans- 4. Replace H.V. Transformer A17, x-
former, x-ray tube, or high-volt- ray tube, or high-voltage cables.
age cables).
5. Faulty/missing J1 connection 5. Check all connections on KVP
on KVP Control Board A2 Control Board A2.
(AY40-003S).
6. Failure of +5V, +15V, -15V or 6. Check voltages at A2TP8 (+5V)
+18V supply voltages. and A2TP9 (+18V). If not present,
replace KVP Control Board A2.
Check voltages at A2TP3 (+15V)
and A2TP5 (-15V). If not present,
replace Power Supply Board A6
(AY40-005T).
LBMast Logic Board master microproces- Check A1U9. Call Technical Service/
Micro sor A1U9 returned incorrect Support.
checksum.
LBSlave Logic Board slave microproces- Check A1U10. Call Technical Ser-
Micro sor A1U10 returned incorrect vice/Support.
checksum.
Error
Possible Cause(s) Remedial Action
Message
Error
Possible Cause(s) Remedial Action
Message
Error
Possible Cause(s) Remedial Action
Message
Error
Possible Cause(s) Remedial Action
Message
Long Prep PREP time exceeded the eigh- Press any key on the Operator Con-
teen-seconds limit. trol Panel to clear warning message.
Re-take exposure.
Error
Possible Cause(s) Remedial Action
Message
Lost Exposure sequence disabled due 1. Verify the EXPOSE switch remains
Expose to missing EXPOSE hardware line pressed throughout entire expo-
or the EXPOSE switch was lifted sure.
during an exposure. 2. On Logic Board A1 (AY40-006S),
monitor U4 pin 2 to determine if the
expose signal is present during
expose (should stay active low dur-
ing exposure cycle). If not, replace
Logic Board.
3. Replace KVP Control Board A2
(AY40-003S).
Error
Possible Cause(s) Remedial Action
Message
Error
Possible Cause(s) Remedial Action
Message
Model PREP was pressed while a combi- 1. Verify the KW (kV x mA) does not
Limits nation of the selected parameters exceed the rating of the generator.
is outside of the limits of the gen- 2. Verify the selected mAs does not
erator model or tube type. exceed the rating of the generator.
3. Verify the tube can support the kV,
mA, and/or time selected.
Error
Possible Cause(s) Remedial Action
Message
Not
Rotating
Error
Possible Cause(s) Remedial Action
Message
Tube rotor or generator rotor drive 1. Check boost and run voltages:
not functioning properly. Connect DVM across Rotor Drive
Board A10 (AY40-013T) terminals
TB1-1 and TB1-3. Press PREP.
Boost voltage should read 183-227
or 110-130 VAC, run voltage
should read 54-66 VAC. If not,
check for open fuse F7 on Inter-
face Board A9 AY40-023T (or
AY40-034T). If F7 is good, replace
Rotor Drive Board A10.
2. Check for correct adjustment of
Rotor Drive Board A10 potentiom-
eters R20 and R24 as described in
in the "Rotor Drive Board A10
(AY40-013T) Adjustment proce-
dure in Chapter 2, ASSEMBLY &
INSTALLATION.
Not
Rotating
Error
Possible Cause(s) Remedial Action
Message
Not
Rotating
Error
Possible Cause(s) Remedial Action
Message
Error
Possible Cause(s) Remedial Action
Message
Error
Possible Cause(s) Remedial Action
Message
NVRam Non-volatile random access mem- Check A16U17. Call Technical Ser-
ory (NVRAM) returned incorrect vice/Support.
checksum.
OCP Operator Control Panel micropro- Check A16U3. Call Technical Ser-
Micro cessor (A16U3) returned incor- vice/Support.
rect checksum.
Error
Possible Cause(s) Remedial Action
Message
Error
Possible Cause(s) Remedial Action
Message
Error
Possible Cause(s) Remedial Action
Message
Error
Possible Cause(s) Remedial Action
Message
Rotor Tube has been rotating for longer Set OCP power on/standby switch to
Overrun than 30 continuous seconds. standby; set ON/OFF circuit breaker
on generator cabinet to OFF. Call
Technical Service/Support.
Error
Possible Cause(s) Remedial Action
Message
Error
Possible Cause(s) Remedial Action
Message
Table The table bucky has been 1. Verify the following did not occur:
Bucky selected but did not return the The "TABLE" receptor key on the
ready signal to start exposure. OCP was selected on a system not
(This may take up to five seconds equipped with a table receptor.
after exposure is requested.) 2. Check the bucky cable connec-
tions at both ends (i.e., Interface
Board A9 (AY40-023T or AY40-
034T) terminal block TB3 and the
table bucky). Refer to bucky inter-
connection diagrams contained in
Chapter 6, DIAGRAMS for proper
wire connections.
3. On Interface Board A9, verify 120
VAC bucky power fuse F11 (2A,
250V slow-blow) is not open.
4. On Interface Board A9, check if
switch SW1 is in correct position
("M" position if table is equipped
with Midwest bucky, non-"M" posi-
tion for all other type buckies).
5. Verify fuse in bucky is not open.
Recycle bucky power by turning
generator off, then on. If error still
occurs, replace bucky control
board.
6. On Logic Board A1 (AY40-006S),
check for an active low signal at
J4-4 during expose. If not present,
replace Logic Board (including
firmware). If present, check cable
connection between Interface
Board A9J6 and Logic Board
A1J4. If connection is good,
replace Interface Board.
Tube Backup time was reached based 1. Modify technique factor(s) (e.g.,
Limits on current AEC technique factors reduce kVp). Re-take exposure.
exceeding exposure tube limits. 2. Verify ion chamber cable connec-
tions are correct and secure.
Error
Possible Cause(s) Remedial Action
Message
Error
Possible Cause(s) Remedial Action
Message
Wall The wall bucky has been selected 1. Verify the following did not occur:
Bucky but did not return the READY sig- The "WALL" receptor key on the
nal to start exposure. (This may OCP was selected on a system not
take up to five seconds after expo- equipped with a wall receptor.
sure is requested.) 2. Check the bucky cable connec-
tions at both ends (i.e., Interface
Board A9 (AY40-023T or AY40-
034T) terminal block TB4 and the
table bucky). Refer to bucky inter-
connection diagrams contained in
Chapter 6, DIAGRAMS for proper
wire connections.
3. On Interface Board A9 (AY40-023T
or AY40-034T), verify 120 VAC
bucky power fuse F12 (2A, 250V
slow-blow) is not open.
4. On Interface Board A9, check if
switch SW1 is in correct position
("M" position if wall stand is
equipped with Midwest bucky, non-
"M" position for all other type buck-
ies).
5.Verify fuse in bucky is not open.
Recycle bucky power by turning
generator off, then on. If error still
occurs, replace bucky control
board.
6. On Logic Board A1 (AY40-006S),
check for an active low signal at
J4-5 during expose. If not present,
replace Logic Board (including
firmware). If present, check cable
connection between Interface
Board A9J6 and Logic Board
A1J4. If connection is good,
replace Interface Board.
SERVICE REPORTS
The HF Series X-ray Generator provides a variety of service reports to assist the
Service Technician in maintaining the proper operation of the system, and to help
troubleshoot problems when they occur. Reports are accessed as follows:
5. Set the ON/OFF circuit breaker CB1 on the generator cabinet to ON position.
6. Set the power on/standby switch on the Operator Control Panel (OCP) to the
standby ( ) position, then to the on ( ) position.
7. The system begins the start up sequence ("Quantum Medical Imaging" is dis-
played and "Testing. Standby." is flashing). (See Figure 5-1.)
8. Within five seconds of start up, press the upper left field select key to access
the Password menu.
9. In the Password menu, enter the default Service/Support Technician pass-
word (58623) using the field select keys next to the corresponding numbers.
10. Upon validation of the password, the Service Mode Menu displays. Press the
key next to the Reports field. The Service Reports Menu displays:
The Service Reports Menu provides access to various types of system information.
The following briefly describes the various Service Report Menu selections:
• Generator Report: Provides total exposure count, average kV and mA
exposure settings, and the total time of all exposures taken on
generator.
• Last 100 Exposures Report: Provides a chronological listing of the last
100 exposures. Each exposure (event) can be viewed showing the time
and date the exposure occurred, and the exposure settings (i.e., kVp,
mA, time, AEC on/off status, and receptor selected). The Next Error
and Previous Error keys are used to "scroll" up or down through the
exposure report.
• Tube Report: Provides total exposure count, average kV and mA
exposure settings, and the total time of all exposures taken on currently
installed x-ray tube.
• Errors & Warnings Report: Provides a chronological listing of up to 100
error and/or warning messages. Each error or warning message (event)
can be viewed showing the event name, the time and date the event
occurred, and the exposure settings at the time the event occurred. The
Next Error and Previous Error keys are used to "scroll" up or down
through the exposure report.
• Diagnostic: Not functional at time this manual was printed.
• Checksums: Displays the software revision levels and checksums of
OCP Control Board A16A1 (AY40-004S1) Microcontroller U3 (referred to
as "Internal" program) and Flash Memory U2 ("External" program and
"Database").
To select a report, press the key next to the report you want to view. Otherwise,
press the key next to the Main field to return to the main Service Menu (see Fig-
ure 3-3).
The following paragraphs provide detailed descriptions of each of the various
report screen selections.
Generator Reports
Tube Reports
Events/Warnings Reports
ERROR
TYPE
PRESS
THESE KEYS
TO SCROLL
UP/DOWN
THROUGH
EVENTS
INTERNAL EXTERNAL
PROGRAMMED PROGRAMMED
MEMORY MEMORY
VERSION & VERSION &
CHECKSUM CHECKSUM
REMOVAL/REPLACEMENT PROCEDURES
The following procedures provide step-by-step instructions for removal and
replacement of the repairable components in the generator.
16. Remove the four (4) 1/4-20 x 3/4" socket head cap screws, flat
washers and lock washers securing the High Voltage Tank to Gen-
erator Chassis.
17. Carefully lift the High Voltage Tank out of the Generator Chassis.
If the High Voltage Tank is to be shipped, be sure to tighten the
vent screw in the front right corner of the tank.
High Voltage (H.V.) Tank A17 Installation
When installing H.V. Tank A17, keep tank upright at all times. Refer to
Figure 2-10 and 2-11 and proceed as follows:
POWER POWER
MODULE A19 MODULE A18
C7 C6 C3 C4 *NOTE: C5 AND C8
ONLY INSTALLED
ON QG-65 AND QG-80
*C8 *C5 GENERATORS
TERMINALS
PC1, PC2 TERMINALS
PA1, PA2
9. Press the EXPOSE key. Verify the pulses at each test point are
5.5 usec. wide and the rising edges of the pulses at A2TP21 are
12 usec. from the rising edges of the pulses at A2TP22 (see Fig-
ure 5-7 for correct waveforms).
APPROX.
1.2 MS
DELAY
1. On the replacement Line Monitor Board A8, verify all jumpers are
set to same configuration as removed Line Monitor Board.
2. Place new Line Monitor Board A8 on standoffs in PCB Door and
secure using four (4) screws.
3. Connect all cables (except A8J1) to Line Monitor Board. Remove
tags.
4. Access Service Mode>Calibration>AD Calibration menu. Verify
+400V Cathode and +400V Anode voltages are within tolerance
per Table 3-8. If not, calibrate in accordance with "A/D Calibra-
tion Procedure" in Chapter 3.
Stored Energy Systems Line Monitor/Charger Board A8 (AY40-
028T) Removal
CAUTION! The Line Monitor/Charger Board con-
tains electrostatic sensitive devices. Observe
proper grounding precautions before handling the
Line Monitor/Charger Board or any other circuit
board.
1. Set the power on/standby switch on the Operator Control Panel
(OCP) to the standby ( ) position.
2. Set the ON/OFF circuit breaker CB1 on the generator cabinet to
OFF position.
3. Using a DVM, confirm the voltage across both DC Power Supply
Capacitor Banks has been discharged to below 5VDC. This will
take several minutes following shutdown.
4. Each battery tray has mounted on its front center, two cartridge
fuses holders housing F1 and F2. Flip up the fuse holder release
levers on top of each holder to open the four battery circuits.
5. Tag and remove cables connected to Line Monitor/Charger Board
A8.
6. Remove four (4) hex nuts securing the Line Monitor/Charger
Board to PCB Door and remove the Line Monitor/Charger Board.
Stored Energy Systems Line Monitor/Charger Board (AY40-
028T) A8 Replacement
CAUTION! The Line Monitor Board contains elec-
trostatic sensitive devices. Observe proper
grounding precautions before handling the Line
Monitor Board or any other circuit board.
1. On the replacement Line Monitor/Charger Board A8, verify all
jumpers are set to same configuration as removed Line Monitor/
Charger Board.
13. Similarly, once this level has been achieved at A8TP3, adjust
A8R66 to produce Output Limiting, which is indicated when yel-
low LED A8D25 begins to blink.
Rotor Drive Board A10 (P/N AY40-013T) Removal
2. Place the new High-Speed Starter Driver Board A20A2 on the PCB
Door standoffs and secure using four (4) hex nuts.
3. Connect all cables to High-Speed Starter Driver Board A20A2.
4. Place clear plastic high-voltage shield on PCB Door standoffs and
secure using three (3) 6-32 hex nuts.
5. Set the ON/OFF circuit breaker CB1 on the generator cabinet to
OFF position.
6. Set the power on/standby switch on the Operator Control Panel
(OCP) to the standby ( ) position.
Stored Energy System - Battery Tray Removal
FUSE HOLDER
(2X ON 30/40
kW SYSTEMS)
BATTERY TRAY
BRACKET (2X CONNECTOR
ON 30/40 kW A20TB1
SYSTEMS)
CONNECTOR
A21TB1
Refer to Figures 6-1 through 6-4 in Chapter 6, DIAGRAMS for a listing of replace-
able parts for single phase, stored energy and three-phase X-ray generators and
for the locations of the replaceable parts within the system. Use only original
replacement parts as supplied or recommended by Quantum Medical Imaging,
LLC.
ORDERING INFORMATION
To order replacement parts for the generator, contact the Service/Support Depart-
ment at;
Quantum Medical Imaging, LLC.
2002-B Orville Drive North
Ronkonkoma, NY 11779-7661 USA
Phone: (631) 567-5800 (x2)
Fax: (631) 567-5074
email: info@qmiteam.com
When ordering replacement parts, supply the following information:
• Model and serial number of equipment
• Part number
• Part description
• Quantity required
• P.O. Number
• Shipping Instructions
When ordering components or parts not listed in the tables of Figures 6-1
through 6-4, a complete description of the part, including its function and loca-
tion should be provided with the model number and serial number of the unit.
Contact service@qmiteam.com for further information.
DIAGRAMS
6-1
6-2
Chapter 6 Diagrams
CB1
CIRCUIT
BREAKER
C13-C16
CAPACITORS
2400uF/450VDC
*NOTE 1: AY40-034T USED
WITH DIGITAL
RECEPTOR SYSTEMS
**NOTE 2: NOT PROVIDED ON DB1
SYSTEMS EQUIPPED WITH RECTIFIER
HIGH-SPEED STARTER
***NOTE 3: AY40-022T2 USED ON
380- 480 VAC 1-PHASE INPUT
SYSTEMS
***NOTE 4: CONTACTOR K3 USED ON
380- 480 VAC 1-PHASE INPUT C3, C4, C6, C7
SYSTEMS ONLY CAPACITORS
A6 1500V
POWER
F1, F2 (3.15A) SUPPLY BD.
SLO-BLO A17
AY40-005T
FUSES HIGH-VOLTAGE
TRANSFORMER
(125 KV = AY20-031,
150 KV = AY20-032)
R4A (50 ),
FL1
R4B (50 )
EMI FILTER
RESISTORS
R3A (50 ),
R3B (50 ) TB1
RESISTORS TERMINAL
BLOCK
C1 R1A (1.2K ), R2A (1.2K ), T1
CAPACITOR R1B (1.2K ) R2B (1.2K ) TRANS-
TB2
RESISTORS RESISTORS FORMER
TERMINAL
****K3 BLOCK
CONTACTOR
K1, K2
T2 CONTACTORS
TRANSFORMER
SINGLE-PHASE (NON-SE)
(MODELS QG-25, QG-32, QG-40)
PARTS LIST A16
OCP CONTROL BD. LCD DISPLAY
AY40-004S1 EL31-004
OCP CABLE
(50 FT.)
AY51-018
CABLE, OCP
ON/OFF SWITCH
AY51-026
AUX
AEC FIELD
CABLE, OCP
ON/OFF SWITCH
AY51-026
READY
•
***OPTIONAL***
A11 A5 A8 A19 A19A3/A18A3 A18
A2 AEC CONTROL BD. FILAMENT A1 A10 LINE MONITOR/ TB1 A9 T1 POWER IGBT POWER
KVP CONTROL BD. AY40-031S (STANDARD) CONTROL BD. LOGIC BD. ROTOR DRIVE BD. SOURCE CHARGER BD. TERMINAL INTERFACE BD. TRANS- MODULE DRIVE BD MODULE
AY40-003S AY40-027S (UNIVERSAL) AY40-007S AY40-006S AY40-013T AY40-028T BLOCK AY40-023T1 FORMER AY20-047 AY40-010T AY20-047
FL1
EMI FILTER
CB1
CIRCUIT
BREAKER
C8-C15
CAPACITORS
2400uF/450VDC
K1
CONTACTOR
C7A**
A6 CAPACITOR
POWER
SUPPLY BD. C7*
AY40-005T CAPACITOR
BATTERY A17
TRAY #2 HIGH-VOLTAGE
(32, 40 & 50 KW TRANSFORMER
UNITS ONLY) AY20-031
A16
OCP CONTROL BD. LCD DISPLAY
SINGLE-PHASE (STORED ENERGY) PARTS LIST AY40-004S1 EL31-004
OCP CABLE
(50 FT.)
AY51-018
SWITCH, OCP
ON/OFF
EL50-007-1
AUX
A16
OCP CONTROL BD. LCD DISPLAY
AY40-004S1 EL31-005
OCP CABLE
(50 FT.)
AY51-018
AEC FIELD
SWITCH, OCP
ON/OFF
EL50-007-1
READY
•
32, 40 kW THREE-PHASE
(MODELS QG-32-2, QG-32-3, QG-40-2, QG-40-3)
A16
PARTS LIST OCP CONTROL BD. LCD DISPLAY
AY40-004S1 EL31-004
OCP CABLE
(50 FT.)
AY51-018
SWITCH, OCP
ON/OFF
EL50-007-1
AUX
A16
OCP CONTROL BD. LCD DISPLAY
AY40-004S1 EL31-005
OCP CABLE
(50 FT.)
AY51-018
AEC FIELD
SWITCH, OCP
ON/OFF
EL50-007-1
READY
•
SWITCH, OCP
ON/OFF
EL50-007-1
AUX
A16
OCP CONTROL BD. LCD DISPLAY
AY40-004S1 EL31-005
OCP CABLE
(50 FT.)
AY51-018
AEC FIELD
SWITCH, OCP
ON/OFF
EL50-007-1
READY
•
***OPTIONAL***
A11 A5 A19 A18
A2 AEC CONTROL BD. FILAMENT A1 A20A2 **A8 DB2 ***A9 C9-C12 POWER A18A3/A19A3 POWER
KVP CONTROL BD. AY40-031S (STANDARD) CONTROL BD. LOGIC BD. HSS DRIVER BD. LINE MONITOR BD. RECT- INTERFACE BD. CAPACITORS MODULE IGBT DRIVE BD MODULE
AY40-003S AY40-027S (UNIVERSAL) AY40-007T AY40-006S AY40-036S AY40-053S IFIER AY40-061T 2400uF/450VDC AY20-047 AY40-010T AY20-047 ***OPTIONAL***
+28 VDC
POWER SUPPLY
CB1
CIRCUIT
BREAKER
C13-C16
CAPACITORS
2400uF/450VDC
DB1
C1* RECTIFIER
CAPACITOR
FL1
EMI FILTER
F1, F2
SLO-BLO TB2
FUSES (3.15A) TERMINAL
T2 BLOCK
R4A, R4B TRANSFORMER
RESISTORS R1A, R1B
R2A, R2B TB1
(50 OHM) TERMINAL
R3A, R3B RESISTORS T1A, T1B, T1C
(1.2 KOHM) TRANSFORMER BLOCK
RESISTORS
(50 OHM)
*NOTE 1:C1 VALUE IS DEPENDENT ON
TUBE TYPE (40 uF FOR E7813 &
E7252 TUBES, 25 uF ALL OTHERS)
**NOTE 2: AY40-053S1 USED ON
K1 - K3
GENERATOR CABINET MODEL QG-50-2 GENERATOR CABINET CONTACTOR
***NOTE 3: AY40-062T USED WITH
(PCB DOOR CLOSED) DIGITAL RECEPTOR SYSTEMS (PCB DOOR OPEN)
****NOTE 4: C5 AND C8 NOT USED ON
MODEL QG-50-2
SWITCH, OCP
ON/OFF
EL50-007-1
AUX
A16
OCP CONTROL BD. LCD DISPLAY
AY40-004S1 EL31-005
OCP CABLE
(50 FT.)
AY51-018
AEC FIELD
SWITCH, OCP
ON/OFF
EL50-007-1
READY
•
RS-580/QS-550/QV-800
TECH VISION
OCP ( Control Panel) D-Qix Mini Control HANDGRIP
8 PIN CIRCULAR PLUG
OPTION TechVision Power/Control Cable
OPTION
Serial Comm J1
5 PORT
REMOTE ON/OFF SWITCH BOX
J2 CAT 5 ETHERNET CABLE AY51-150
(CXDI 50G Only) OPTION
CN4 CONTROL PC
AC 120V/230V (CXDI-C3S)
INPUT POWER
TOUCH SCREEN MONITOR
Sensor Cable
5 PORT VGA
CAT 5
SWITCH BOX
LOGIC
CAT 5 LAN 2
BOARD POWER
(J5) SUPPLY
X-Ray I/F Receptor Cable
Interface Board
CXDI 50G/40EG/31G
TABLE TB3/ WALL TB4 KEYBOARD
IMAGING UNIT
1
1
2 MOUSE
2
3
Jumper
3
4 Jumper
4
5
5
6 A1
6
7 A2
7
8 B1
8
9
9
10
10
11 B2
11
12
12 AC120 +/- 10 60hZ 2A
AC230 +/- 10 50/60Hz 1.5A
INPUT POWER
NOTE:
ON SYSTEMS USING FOUR (4) WIRE MULTI-CONDUCTOR BUCKY
CABLE, CONNECT ’BUCKY ON’ SIGNAL (RED WIRE) TO LINE (B4)
TERMINAL ON BUCKY. (THE 115VAC (BLACK WIRE) CONNECTION
NOTE:
ON SYSTEMS USING FOUR (4) WIRE MULTI-CONDUCTOR BUCKY
CABLE, CONNECT ’BUCKY ON’ SIGNAL (RED WIRE) TO LINE (L)
TERMINAL ON BUCKY. (THE 115VAC (BLACK WIRE) CONNECTION
MAIN GROUND
STUD
GROUND TO HV TANK GREEN/YELLOW (10AWG)
WHT
BLK AY40-010T J5 1
RED A19,A1P5 IGBT DRIVE BD. ANODE 2
BLUE AY40-010T J5 1 3
A18,A1P5
IGBT DRIVE BD. CATHODE 2 C13 4
J9
J8
J7
J6
J4
J3
J2
J1
AY51-058 X2 AY51-007
+
F1 3.15A SB 440VAC R3 A,B 50 3
TB1 C9 4 X-RAY TUBE (SEE
J9
J8
J7
J6
J4
J3
J2
J1
OHM 50W
AY51-080
+
TUBE ROTOR CHART
AY51-080
F2 3.15A SB 440VAC R4 A,B 50 C14
SEE NOTE
AY51-023
LINE
LINE
C10 FOR ROTOR
OHM 50W
WHT
+
CONNECTION)
BLK
G2
E1
E2
G1
G2
E1
G1
L1
AY51-079
E2
WHT
CB1 AY25-001
BLK
AY51-073 (2X)
+
C15 3
+ +3
G2
E1
E2
E1
G1
G2
G1
E2
AY51-079
ROTOR CABLE
6
4
~
LOAD
LOAD
L2
AY51-066
3
+
6
C11 3
+ +3 + A18C1 A18C2
YEL/GRN (10AWG)
~ A+ C-
AY51-066
5
+
AY51-127 AY51-088 (2X) + A19C1 A19C2 C16 2
- - 2
8
(4X) 7
~
+
C12 2
AY51-127 10 - - 2 A18QB
A18R1
A18QA
9
~ SEE NOTE 1
+
K2 (4X) A19QB A19QA - 1 1
3
9
1 A19R1 AY51-065
K1 2 SEE NOTE 1
~
- 1 1
~ AY51-065 DB1
D1 A18 AY20-047 POWER MODULE AY51-128 (4X) SEE NOTE 2
10
4
1
2 1N4005 DB2
A19 AY20-047 POWER MODULE
1N4005
ANODE C7 C4
CATHODE AY51-128
D2
AY51-073
C6 C3 (4X) X-RAY TUBE ROTOR CONNECTION CHART
TOSHIBA VARIAN DUNLEE
AY51-073
ADJUST THESE JUMPERS A9P3 A10P1 J1 1- COMM. 5- COMM. OUTER- COMM.
ORN/BLK
BRN/YEL
TO THE NEAREST A9P7 J7 220VAC BROWN (16 AWG) 220VAC ROTOR MAIN 1 BLK
AY51-009-1P
1 1 1
INCOMING LINE AY51-016 2 60 VAV 2 RED (16 AWG) 2 60 VAV ROTOR PHASE 2 RED PC1 PC2 PA1 PA2 2- MAIN 4- MAIN CENTER- MAIN
BLACK/RED 0 VAC ORANGE (16AWG) 0 VAC ROTOR COMMON 3 WHT
3 3 3
GREY/WHITE 4 J3 4 AY51-010 4
4 3- PHASE 3- PHASE INNER- PHASE
AY51-070 (2X)
5 1
16 0VAC BLK (16AWG) 3 A10P5 J5 2 2. C3,C4,C6 AND C7 1UF 1500V. C5 AND C8 NOT USED.
CATH. FDBK
4 6 0VAC 2
220VAC 5 28VAC BLK (16AWG) COLL. READY 4 1
CATH. RTN
16
14
7 28VAC 1 3
0VAC BLK (16AWG) 15V RTN 5 3 3. C1 VALUE COULD CHANGE DEPENDING ON TUBE
5 240VAC
8 0VAC 2 4
MA FDBK
6 28VAC BLK (16AWG) 15VDC 6 TO TUBE STAND 4 MANUFACTURER OR MODEL. (SEE TUBE DATA SHEET)
15
MA RTN
9 28VAC 3 5
ANODE FDBK
280VAC
ANODE RTN
15 0VAC BLK (16AWG) 0VAC GROUND 7
8
6 260VAC 7 0 1 7 BLK (16AWG)
10
AY51-043 A10
6
4. DISCONNECT A17P1-9 AND 10 FROM GROUND AND CONNECT
SHIELD 7
11 7VAC 7
A17P1
WHT FIL.COMMON
FIL. LARGE
FIL. SMALL
BLK (16AWG) 12 0VAC AY40-013T 8 A17 1.5KE68CA
MAS METER TO THESE WIRES. (WARNING A17P1-9 AND 10
8 120 3 TB3 ROTOR DRIVE BD. AY20-031
YELLOW
7VAC
0VAC
9
60VAV
115 VAC 1
HV MODULE
GREEN
10
220 4 6 A9P4 J4 BUCKY T. ON 2
FIL. SHIELD
RED
AY51-012
AY51-023
AY51-015
LINE 20 220 VAC IN 4 C1 NON AEC GENERATORS USE AY51-019-1.
RED
1
BLK
LOAD 220 VAC IN GROUND 5
30UF/440VAC
1
2
3
4
5
6
7
8
9
2
17 60VAC ROTOR 6 6. 40KW SYSTEMS CB1 MUST BE 70 AMP.
AY51-017
GRN/YEL (16AWG)
3 (SEE NOTE 3)
GND 18 4 0 VAC ROTOR 7 TO TABLE 32.5 AND 25 KW SYSTEMS CB1 MUST BE 50AMP.
A10P3
LOAD
11 5 BUCKY READY 8
ORANGE
A2P1
YELLOW
BROWN
6
VIOLET
LINE AY51-017
WHITE
GREEN
GREY
GRN/YEL (16AWG)
BLUE
EMI BLACK (16AWG)
RED
FILTER 10 BLK (16AWG) TB4 WHITE (16AWG)
1
2
3
4
5
6
BLK (16AWG) 115 VAC 1
AY51-021 A5P1
5
3
6
1
2
7
4
9
8
10
J1
MA RTN
BLK (16AWG) 115 VAC RTN 3
MA SENSE
ANODE RTN
ANODE FDBK
CATHODE RTN
ORN/BLK
1
2
3
4
5
6
7
8
CATHODE FDBK
BRN/YEL
1
2
3
4
5
6
7
8
9
BLK (16AWG) 2 0 VAC OUT T2 GROUND 5
GROUND
BLK (16AWG) 120 VAC 24 VDC RTN 6 J8 J1
48VDCRTN
48VDC
WHT, C
RED, S
3
BLK (16AWG) 0VAC 24 VDC 7 TO WALLSTAND 1 J11 1 AY51-013
1 4 1 1
OUTPUT 0VAC SW.
BLK,
BRN
ICOM. L 220VAC
2 2
OUTPUT 220VAC SW.
INCOM. L 0VAC
2 5 BUCKY READY 8
2 2 1 1
3 RS 232 3 A2P7 RED
3 6 3 3 2 2
4 SLAVE RS 232 4 J7 ORN
4 4 4 3 3
A6P1 A9P2 J2 5 PORT MASTER 5 +18 VDC YEL
A8P6 J6 AY51-005 6
5 5
6
1 4 4
AY40-005T J1 TB5 X - RAY ON 6 PORT 6 2 GROUND 5 GRN 5
A6, POWER SUPPLY BD. 32VAC 1 WHITE (16AWG) 1 X-RAY IN USE 1 7 7 OUTPUT A BLU
1 1 7 7 3 6 6
32VAC RTN 2 BLACK (16AWG) 2 X-RAY IN USE RTN 2 8 8 OUTPUT B VIO
2 2 8 8 4 7 7
15VAC 3 VIOLET 3 9 J10 9 GRY
3 3 9 9 8 8
15VAC RTN 4 BLUE 4 A1P10 WHT AY40-007T
4 4 9 9
11VAC 5 RED 5 TB6 DOOR INTERLOCK A1P9 BLK A5, FILAMENT
5 5 10 10
11VAC RTN 6 BROWN/YELLOW 6 DOOR INTERLOCK 1 J9 A2P8 J8
6
7 7
6 1 CONTROL BD.
28VAC 7 BLUE/YELLOW 7 DOOR INTERLOCK RTN 2
2 1 +18 VDC J6 A2P6 A5P2 J2
28VAC RTN 8 BLACK/RED 8 A1P4 J4 GROUND
8 8 A9P6 3 2
J6 AY51-008 4 3 OUTPUT A J3 A2P3
BLACK(20AWG)
WHITE(20AWG)
1 1 5 4 1
BLUE(20AWG)
A11P4
48VDCRTN 3 4 GREEN/YELLOW 4 GROUND 8 4
A8P1 J1 48VDCRTN 4 BLUE BUCKY TABLE 15VDC
4 5 5 9 1 5
AY51-012
5
J2 A8P2 30VDC 5 6 VIOLET 6 BUCKY WALL 10 2 15VDC 6
VA+/2.4K 30VDC 6 WHITE PREP 15VDC RTN
1 6 7 7 3 7
1
2
3
4
5
6
7
8
9
10
12
13
14
15
16
-15VDC RTN
11
7
15VDC RTN
15VDC RTN
24VDC RTN
24VDC RTN
24VDC
24VDC
4 3 9 10 10 2 6 10
WHT (16AWG)
10 3 J2 1
BLK (16AWG)
AEC WALL 1
VC+/2.4K GREEN/BROWN K2, 24VDC 28VDC 6 24VDC RTN 4
8 7 14 14 6 10 14 4
BROWN EXPOSE GND 7 5
9 8 15 15 7 15 5
8 6
10
10 9 16 16 8 16 6
RED/GREEN 0VAC 9 AY40-003S A11P1 A11, AEC BD. 7
RED(20AWG)
11 10 17 17 GND 9 7
12 VC- 18 ORANGE/BLACK 18 7.5VAC J5 A2, KVP BD. J4 A2P4 (OPTIONAL) 8
8
AY40-023T BROWN/YELLOW 15VDC GRN/YEL 9
19 19 1 1 9
A9, INTERFACE BD. 20 GREEN/ORANGE 20 15VDC RTN J1 A1P1 2 2 J1
BLUE(20AWG)
BLUE(20AWG)
AY51-018-XX
2 2 4 6 6 2
ORANGE (22AWG) GROUND 3
3 3 5 7 7 3
AEC WALL 2
YELLOW (22AWG) 24VDC 4
4 4 6 8 8 4
GREEN (22AWG) AUTO SHUT OFF 5
5 5 7 9 9 5
R1A, R1B BLUE (22AWG) SYSTEM ON 6
6 6 8 10 10 6
R2A, R2B VIOLET (20AWG) 24VDC MAG. 7
7 7 9 11 11 7
1.2K/50W AY40-022T-1 GREY (20AWG) 24VDC MAG. RTN 8
8 8 10 12 12 8
A8, LINE WHITE (22AWG) NOT USED 9
9 9 11 13 13 9
BLACK (22AWG) FAULT RESET
MONITOR 10 10 12 14 14
BLACK/ORANGE (22 AWG) NOT USED J5
1
2
3
4
5
6
7
8
9
15
AY51-011 A1, CPU BD. A11P5
16
J3 (LOGIC BD.)
1
2
3
4
5
6
7
8
9
A1P3 A16P1
AY51-019-2
1
2
3
4
1
1
BLACK/RED 30VDC 2
2
AY10-005 ODYSSEY
WHT/BLK 30VDC RTN 3
3
4
SEE NOTE 5 4
PCB DOOR GROUND STUD 5
AY51-018-XX 5
AY51-012 6
6
BLK (16AWG) 7
7
WHT (16AWG) 8
8
GREEN/YELLOW (16AWG) FILAMENT BOARD GROUND 9
9
MAIN GROUND
STUD
GREEN/YELLOW (10AWG) GROUND TO HV TANK GREEN/YELLOW (10AWG)
WHT
BLK AY40-010T J5
ROTOR CABLE
1
RED A19,A1P5 A3,A IGBT DRIVE BD. ANODE 2
BLUE AY40-010T J5 1 3
AY51-058 X2 A3,B IGBT DRIVE BD. CATHODE
J9
J8
J7
J6
J4
J3
J2
J1
AY51-007 2 C13 4
+
F1 3.15A SB 440VAC 3 X-RAY
C9 TUBE (SEE TUBE
J9
J8
J7
J6
J4
J3
J2
J1
4
AY51-080
A18,A1P5
+
L1 R3 A,B 50 ROTOR
N/C
F2 3.15A SB 440VAC OHM 50W C14 CHART
AY51-080
LINE
LINE
SEE NOTE 6
C10 FOR
+
WHT
L2 R4 A,B 50 ROTOR
G2
E1
E2
G1
G2
E1
BLK
BLK
G1
AY51-023
E2
AY51-079
WHT
AY25-001
CB1
+
LOAD
TB1 C15 3
+ +3
LOAD
G2
E1
N/C
E2
G1
G2
E1
G1
E2
AY51-079
4
AY51-066
AY51-127 3 AY51-073 (2X) ~
+
C11 3
6 + +3 + A18C1 A18C2
(4X) A+ C-
AY51-066
AY51-088 5 ~
+
AY51-127 (4X) 8
+ A19C1 A19C2 C16 2
- - 2
(2X)
7
+
C12 2 2 ~ A18QB A18QA
10 - -
BLU
K2 A18R1
BRN 9
+
~ A19QB A19QA SEE NOTE 1 1 1 X-RAY TUBE ROTOR CONNECTION CHART
9
1 A19R1 ~
K1 2 SEE NOTE 1 1 1 AY51-065 TOSHIBA VARIAN DUNLEE
AY20-147 R5, R6 -
SEE NOTE 2
3.3/50WALUM.
AY51-128 (4X)
~ AY51-065 AY20-047 POWER MODULE 1- COMM. 5- COMM. OUTER- COMM.
- DB1
A18
10
2
1
BRN
BLU
1N4005
DB2 ANODE AY51-128 (4X) C7 C4 2- MAIN 4- MAIN CENTER- MAIN
D1
CATHODE
D2 1N4005
AY51-073
5- T.S. 1- T.S. T.S.-1
AY51-073
AY51-075 (3X)
TO THE NEAREST
1
K3 A9P7 J7 220VAC BROWN (16 AWG) 220VAC ROTOR MAIN BLK
INCOMING LINE
1 1 1
AY51-016 2 60 VAV 2 RED (16 AWG) 2 60 VAV ROTOR PHASE 2 RED PC1 PC2 PA1 PA2
3
T1 BLACK/RED
GREY/WHITE
3 0 VAC
J3
3 ORANGE (16AWG) 3 0 VAC ROTOR COMMON
4
WHT NOTES:
10
4 4 AY51-010 4
2
1
3 0VAC BLK (16AWG) 0VAC TO COLLIMATOR 10 3. C1 VALUE COULD CHANGE DEPENDING ON TUBE
1 16VAC BLK (16AWG)
2
TB2 J4 A10P4
SEE NOTE 4 9 MANUFACTURER OR MODEL. (SEE TUBE DATA
16VAC
AY51-079 X4
3
4 0VAC BLK (16AWG) 0VAC 24 VDC 1 6
2 0VAC 4 SHEET)
YELLOW
CATH. FDBK
3 380VAC 6 0VAC AY51-043 2
RED
CATH. RTN
16
14
7 28VAC 1 3 CONNECT MAS METER TO THESE WIRES. (WARNING
0VAC BLK (16AWG) 15V RTN 5 3
4 415VAC 8 0VAC 2 4
A17P1-9 AND 10 MUST BE CONNECTED TO GROUND OR
MAFDBK
7 28VAC BLK (16AWG) 15VDC 6 TO TUBE STAND 4
15
MARTN
9 28VAC 3 5
ANODE FDBK
ANODE RTN
15 0VAC BLK (16AWG) GROUND 7
5 0VAC
8
10 6 MAS METER)
280VAC
SHIELD 7
11 7VAC 7
A17P1
WHT FIL.COMMON
FIL. LARGE
FIL. SMALL
BLK (16AWG) 0VAC AY40-013T A17 1.5KE68CA
6 480VAC 9 120 3
12
TB3 ROTOR DRIVE BD.
8
AY20-031 5. AY51-019-2 IS USED FOR AEC OPTION ONLY.
7VAC
0VAC
9
115 VAC 1
10 HV MODULE NON AEC GENERATORS USE AY51-019-1
220
220V
4 6 A9P4 J4 BUCKY T. ON 2
FIL. SHIELD
60V
TB2 19 115 VAC RTN 3 J3 6. 40 AND 32 KW SYSTEMS CB1 MUST BE 50 AMP/3 POLES
AY51-012
AY51-023
AY51-015
LINE 20 220 VAC IN 4 C1 25 KW SYSTEMS CB1 MUST BE 30AMP/ 3 POLES
RED
1
BLK
LOAD 220 VAC IN GROUND 5
30UF/440VAC
1
2
3
4
5
6
7
8
9
2
17 60VAC ROTOR 6
GRN/YEL (16AWG)
3 (SEE NOTE 3)
GND 18 4 0 VAC ROTOR 7 TO TABLE
A10P3
AY51-017
LOAD
11 5 BUCKY READY 8
ORANGE
A2P1
YELLOW
BROWN
6
VIOLET
LINE AY51-017 GRN/YEL (16AWG)
WHITE
GREEN
GREY
BLUE
AY51-009-3P
BLACK (16AWG)
RED
EMI
YELLOW/WHT
1
2
3
4
5
6
BLK (16AWG) 115 VAC 1 A5P1
AY51-021
BRN/YEL
ORN/BLK
MARTN
BLK (16AWG) 115 VAC RTN 3
MASENSE
ANODE RTN
J1
ANODE FDBK
CATHODE RTN
1
2
3
4
5
6
7
8
CATHODE FDBK
BLK (16AWG) 1 220 VAC OUT T2 4 A1P8 SHIELD
1
2
3
4
5
6
7
8
9
A8P6 BLK (16AWG) 2 0 VAC OUT T2 GROUND 5
GROUND
24 VDC RTN
48VDC
BLK (16AWG) 120 VAC 6 J8 J1
48VDCRTN
WHT, C
RED, S
3
BLK (16AWG) 0VAC 24 VDC 7 TO WALLSTAND 1 J11 1 AY51-013
4 1 1
1
2
3
4
BLK,
A8P3 BUCKY READY 8 2 2 BRN
5 2 2 1 1
J6 3 RS 232 3 A2P7 RED
6 3 3 2 2
J3 4 SLAVE RS 232 4 J7 ORN
3 4 4 3 3
A6P1 A9P2 J2 5 PORT MASTER 5 +18 VDC YEL
10 AY51-005 6
5 5
6
1 4
GRN
4
2 AY40-005T J1 TB5 X - RAY ON 6 PORT 6 2 GROUND 5 5
A6, POWER SUPPLY BD. 32VAC 1 WHITE (16AWG) 1 X-RAY IN USE 1 7 7 OUTPUT A BLU
4 1 1 7 7 3 6 6
32VAC RTN 2 BLACK (16AWG) 2 X-RAY IN USE RTN 2 8 8 OUTPUT B VIO
5 2 2 8 8 4 7 7
15VAC 3 VIOLET 3 9 J10 9 GRY
AY51-022-3P
6 3 3 9 9 8 8
15VAC RTN 4 BLUE 4 A1P10 WHT AY40-007T
7 4 4 9 9
11VAC 5 RED 5 TB6 DOOR INTERLOCK A1P9 BLK A5, FILAMENT
8 5 5 10 10
BLACK(20AWG)
WHITE(20AWG)
9 6 6 1 CONTROL BD.
BLUE(20AWG)
AY51-012
3 1 4 5 5 9 1 5
30VDC 5 VIOLET BUCKY WALL
4 2 5 6 6 10 2 15VDC 6 AY51-019-2
VA - 30VDC 6 WHITE PREP
5 3 6 7 7 3 15VDC RTN 7
-15VDC RTN
7
15VDC RTN
15VDC RTN
24VDC RTN
24VDC RTN
A11P4
7 5 30VDCRTN 8 9 YELLOW/WHITE 9 BKY T. READY OCP ON 1 5 -15VDC 9
-15VDC
24VDC
24VDC
8 6 9 10 10 RS-485 2 6 10
WHT (16AWG)
10 3
BLK (16AWG)
12 12 4 8 12
1
2
3
4
5
6
7
8
9
10
12
13
14
15
16
11
J2 J3 A6P3 GREY TABLE RDY 5 24VDC RTN
11 9 13 13 PREP 5 9 13
AY51-004
12 10 14 14 28VDC 6 10 14
J4 BROWN EXPOSE 7
15 15 GND 7
8
15 J4 1 SC50-047T REV. E
10
16 16 28VDC 8 16 1
RED RED/GREEN 0VAC 9 2
BLUE(20AWG)
17 17 9 2
ORANGE/BLACK 7.5VAC GND J4 A2P4 3
18 18 J5 3
AY40-023T BROWN/YELLOW 15VDC GRN/YEL AY40-031S 4
AEC WALL 1
19 19 1 1 4
A9, INTERFACE BD. GREEN/ORANGE 15VDC RTN J1 A1P1 A11, AEC BD. 5
20 20 2 2 5
A8P4 (OPTIONAL) 6
BLUE
1 3 3 6
A1P2 J2 7
2 4 4 7
BROWN (22AWG) V SENSE A 8
1 1 3 5 5 8
R1A, R1B RED (22AWG) V SENSE C 9
AY51-018-XX
2 2 4 6 6 9
R2A, R2B 3 ORANGE (22AWG) 3 GROUND 5 7 7
1.2K/50W 4 YELLOW (22AWG) 4 24VDC 6 8 8 A11P3
AEC WALL 2
9 9 11 13 13 4
5
GRN/YEL (10AWG)
1
2
3
4
1
2
3
4
5
6
7
8
9
2
AY51-018-XX
3
3
BLACK/RED 30VDC A11P5 4
1
2
3
4
5
6
7
8
9
4
WHT/BLK 30VDC RTN 5
5
6
ODYSSEY.
(SEE NOTE 5) 6
AY51-019-2 7
7
AY51-012 8
8
PCB DOOR GROUND BLK (16AWG) 9
9
STUD WHT (16AWG)
GREEN/YELLOW (16AWG) FILAMENT BOARD GROUND
GREEN/YELLOW (10AWG)
BLACK (20AWG)
WHT (20AWG)
BLUE (20AWG)
RED (20AWG) A3,A J5 1
AY51-132 X2 BLK (10AWG) AY40-010T IGBT DRIVE BD 2
AY51-127 (2X) 4 RED(10AWG) RED(10AWG) 3
J9
J8
J7
J6
J4
J3
J2
J1
+ + + + + + + + 3 SEE NOTE 4
6 RED(10AWG) A3,B J5 1 1
AY51-015
5
+
AY40-010T IGBT DRIVE BD A18,A1P5
C-
2
_ _ _ _ _ _ _ _ 8 BLK(10AWG) C9 3 C11
J9
J8
J7
J6
J4
J3
J2
J1
7
GREEN/YELLOW (10AWG)
+ 4 A18
ROTOR CHART
10BLK(10AWG)
+ + + + + + +
CONNECTION)
9 AY51-133 (2X) C10 A19.A1P5 C12
FOR ROTOR
X-RAY TUBE
G1
G2
G2
E2
E1
E1
G1
E2
AY51-023
(SEE TUBE
1
+
SEE
2
AY51-128 (4X)
_ _ _ _ _ _ _ _
D1 SEE NOTE A19 3 + + 3 NOTES
+ + + + + + + K1 1 AY51-076 A18C1 A18C2 2-3
G1
G2
G2
+
E2
E1
E2
E1
G1
C3
AY51-076 3 + + 3 2 - - 2
A+
_ _ _ _ _ _ _ _
A19C1 A19C2 SEE AY51-077 A18QB A18QA
AY51-128 (4X)
+ + + + + + A18R1
BLACK (10AWG)
GREY/WHITE
NOTES
BLACK/RED
2 - - 2 1 1
RED (10AWG)
2-3
30A SB
ORANGE
C6
BROWN
VIOLET
A19R1 AY20-047 ANODE POWER MODULE C4
GREY
AY51-016
1 1
1
500VAC
ROTOR CABLE
AY20-044 GRN/YEL 2 C7 TOSHIBA VARIAN DUNLEE
AY20-047 CATHODE POWER MODULE
A9P7 PA1
BLACK 3 BLACK (10AWG) 1- COMM. 5- COMM. OUTER- COMM.
1
2
3
4
PC2
GREEN/YELLOW (10AWG) AY51-085 J7 220VAC 1 BROWN (16 AWG) AY51-010 1 220VAC ROTOR MAIN 1 BLK PA2 2- MAIN 4- MAIN CENTER- MAIN
60 VAV 2 RED (16 AWG) 2 60 VAC ROTOR PHASE 2 RED PC1
0 VAC 3 ORANGE (16AWG) 3 0 VAC ROTOR COMMON 3 WHT
C 3- PHASE 3- PHASE INNER- PHASE
ORANGE J3 4 4
4
BROWN A9P3 5 5- T.S. 1- T.S. T.S.-1
GREY A10P1 J1 CHASSIS GND 6 T.S.
VIOLET TB1 TEMP. FAULT 7 T.S. A 6- T.S. 2- T.S. T.S.-2
GROUND TO HV TANK
CATH. FDBK
ORANGE
VIOLET
1
WHITE
BLACK
CATH. RTN
110/220 VAC DOOR INTERLOCK 24 VDC 1 TO TUBE STAND 15VDC 3 3. C4,C7 .5UF 1500V
GREY
RED
BUE
MA RTN
16
14
2
MA FDBK
TB6 24 VDC RTN 2 15VDC RTN 4
15
3
ANODE FDBK
LINE
LINE
ANODE RTN
4
A17P1
GRN 2 DOOR COLL. READY 4 -15VDC 1.5KE68CA MANUFACTURER OR MODEL. (SEE TUBE DATA SHEET)
FIL.COMMON
EL70-004
SHIELD 7
10 AMP
FIL. LARGE
FIL. SMALL
22 5 -15VDC RTN
CB1
RTN 1 6
TO THE NEAREST X - RAY ON +15VDC 6 24VDC A17 AY20-031 5. DISCONNECT A17P1-9 AND10 FROM GROUND AND CONNECT
2 7
A9P1 J1 GROUND 7 24VDC HV MODULE MAS METER TO THESE WIRES (WARNING A17P1-9 AND 10
LOAD
INCOMING AC LINE
LOAD
3 8
23 24VDC RTN 9 BE CONNECTED TO GROUND OR TO THE MAS METER.)
FIL. SHIELD
0VAC BLK (16AWG) 1 0VAC J3 24VDC RTN 10
10 32VAC BLK (16AWG) 32VAC TB3 6. AY51-019-2 IS USED FOR AEC OPTION ONLY.
RED
WHT
2
WHT
BLK
C1, 30UF/440VAC
BLK
0VAC BLK (16AWG) 0VAC 115 VAC 1 NON AEC GENERATORS USE AY51-019-1.
1
2
3
4
5
6
7
8
9
3
AY51-017
16VAC BLK (16AWG) 16VAC BUCKY T. ON 2 A10P3
4
AY51-015
AY51-017
11 0VAC BLK (16AWG) 0VAC 115 VAC RTN 3 TO TABLE GRN/YEL (16AWG)
A2P1
EL99-001
EMI FLT
5
LINE
AY51-012
LINE
8
GREEN/YELLOW (10AWG)
4
TB1 T1 11VAC BLK (16AWG) 11VAC WHT (16AWG)
LOAD
GND
LOAD
AY51-021
12 0VAC BLK (16AWG) 0VAC 5 BLK (16AWG)
BROWN
ORANGE
YELLOW
7
WHITE
VIOLET
28VAC BLK (16AWG) 28VAC GROUND A5P1
GREY
6
RED
BLUE
GREEN
1 8
1
2
3
4
5
6
-10VAC 1 0VAC BLK (16AWG) 0VAC 7
9
0VAC 2 13 28VAC BLK (16AWG) 28VAC BUCKY READY 8 EL28-002 J1 A2P6 AY51-013
(16AWG)
2 10
1
2
3
4
5
6
8
7
60VAV 3 BLK (16AWG) 0VAC (SEE NOTE 4)
11
MA RTN
SHIELD
SHIELD
110VAC
MA SENSE
ANODE RTN
4 8 BLK (16AWG) 7VAC BRN
ANODE FDBK
A1P8 A1P8 J6
CATHODE RTN
0VAC
L
3
MAIN GROUND
CATHODE FDBK
12 1 1
1
2
3
4
5
6
7
8
9
J1
GROUND
RED
48VDC
7VAC
48VDCRTN
2 2
WHT, C
RED, S
A9P4 J4 TB4 1 J11 J8 ORN
4 1 3 3
BLK,
130VAC 2 1
GRN/YEL
5 9 115 VAC 1
2 RS 232 1 4 YEL 4
STUD
CONTROL BD.
YELLOW (20AWG/600V)
5 7 6 2 9 9
240VAC 8 7
BROWN (20AWG/600V)
AY51-023
6 8 7 3 10 10
9 8
RED (20AWG/600V)
19 A9P5 J5 A1P4 J4
R3A, R3B
23
21
22
20
1
A9P6 AY51-008
A8P4 50/50W
J6 A1P9 A2P8 J8
A8P7
J9 2
2 1 RED 1 24VDC 1 GROUND 3 AY51-019-2
A11P4
BLK (16AWG) 4 0 VAC 2 GREEN/YELLOW 2 24VDC RTN 15VDC 1 2 +18 VDC 4
BLK (16AWG) 110 VAC BLACK 28VDC 15VDC OUTPUT A
BLK (16AWG)
BLK (16AWG)
BLK (16AWG)
BLK (16AWG)
3 3 3 2 3 5
1 4 GREEN/YELLOW 4 GROUND 15VDCRTN 3 4 OUTPUT B 6
5 5 BLUE 5 BUCKY TABLE 15VDCRTN 4 5 7
1
2
3
4
5
6
7
8
9
10
12
13
14
15
16
11
1
15VDC AY40-005T 6 6 VIOLET 6 BUCKY WALL -15VDC 5 8
8
2
7
4
3
5
1
6
9
10
2
15VDC A6, POWER J1 7 WHITE 7 PREP -15VDCRTN 6 9 A11P2
1
2
3
0VAC SW.
0VAC
2 2 5 1 1 10 10 9 1 12 2
3 3 6
-15VDCRTN 32VACRTN 2 BLACK 2 32VACRTN 11 GREY/WHITE 11 DOOR 24VDCRTN 10 2 15VDC 13 3
3
24VDC
110/220
AEC WALL 1
110/220VAC SW.
AY51-012
5 5 8 4 4 13 13 4 15 5
6 6 9
24VDCRTN 11VAC 5 RED 5 11VAC 14 GREEN/BROWN 14 K2, 24VDC 5 -15VDC 16 6
6
48VDCRTN
48VDCRTN
30VDCRTN
30VDCRTN
15VDCRTN
7 220VAC 7 10
24VDCRTN 11VACRTN 6 BRN/YEL 6 11VACRTN 15 BROWN 15 EXPOSE OCP ON 1
1
6 -15VDC RTN A11P1 7
7
28VAC BLU/YEL 28VAC GREEN PREP RDY 2 24VDC A2P4 8
RS-485
48VDC
48VDC
30VDC
15VDC
8 8 7 7 16 16 2 7 8
30VDC
3 GND 7
8
5 5 1
2
VIO BATT + C A8P6 J4
RED
9
1.2K/ A J6 AY51-011 A1P2 J2
28VDC 8
9
6 6 2
3 SC50-048T REV. H
AEC WALL 2
10 9 7 7 3
BLU 1.2K/ C BROWN (22 AWG) V SENSE A GND AY40-003S 4
11 1 1 J5 8 8 4
RED (22 AWG) V SENSE C GRN/YEL A2, KVP BD. 5
4 2 2 9 9 5
MONITOR/CHARGER
14 7 7 4 14 14 AEC TABLE
AY51-018-XX
GREY (20 AWG) 24VDC MAG. RTN
9
8
7
6
5
4
3
2
1
15 9 9 6
GRN/YEL 8 RTN 10 BLACK (22 AWG) 10 FAULT RESET 7
BD.
9
8
7
6
5
4
3
2
1
J8 J2 12 WHT/BRN (22 AWG) 12 NOT USED 9 A11P5
A8P8 10
1
2
3
AY51-039-SE A1P3 J3
11 A16P1 1
GRN/YEL (10AWG)
A8P2
GRN/YEL (20AWG)
GRN/YEL (20AWG)
AY51-004 12 1
R1A,R1B 1.2K/50W
2
AY51-012
AY10-005 ODYSSEY
WHT/BLK WHT/BLK 33VDC RTN 3
2 14 AY51-19-2 SEE NOTE 6 3
4
R2A, R2B
3 15 4
5
50/50W
4 16 5
6
6
7
PCB DOOR 7
BLK (16AWG) 8
GROUND 8
WHT (16AWG) 9
9
STUD GREEN/YELLOW (16AWG) FILAMENT BD. GROUND AY51-018-XX
GREEN/YELLOW (10AWG)
BLK (20AWG)
WHT (20AWG)
BLU (20AWG) BLK (6AWG)
RED (20AWG) A3,A J5 1
C12
+
AY51-132 X2 AY40-010T IGBT DRIVE BD 2
4 RED(6AWG) RED(6AWG) 3
J9
J8
J7
J6
J4
J3
J2
J1
3
+ + + + + + + + + + + + + + + + 6 BLK(6AWG) C13 4
A3,B J5 1
AY51-015
5
+
AY40-010T IGBT DRIVE BD 2 A18,A1P5
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 8 RED(6AWG) C8
C-
3
J9
J8
J7
J6
J4
J3
J2
J1
GREEN/YELLOW (10AWG)
7
+ + BLK(6AWG)
10
4 A18
+ + + + + + + + + + + + + +
ROTOR CHART
CONNECTION)
9 AY51-133 (2X) A19,A1P5
G1
G2
G2
C14
E2
E1
E1
G1
E2
AY51-023
C9
FOR ROTOR
1
X-RAY TUBE
+
(SEE TUBE
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ K1 2
A19 3 + + 3
AY51-128 (4X)
SEE
+ + + + + + + + + + + + + + A18C1 A18C2 NOTE 5
G1
+
G2
G2
E2
E1
E1
G1
+
E2
D1 C15
C3
+
AY51-076 3 + + 3 2 - - 2
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
A+
C10
+
SEE A19C1 A19C2 AY51-076 A18QB A18QA
BLACK (6AWG)
BLACK (6AWG)
+ + + + + + + + + + + + NOTE SEE SEE A18R1
C4 X-RAY TUBE ROTOR CONNECTION CHART
RED (6AWG)
RED (6AWG)
AY51-128 (4X)
2 - - 2 1 1
BLACK/RED
GREY/WHITE
1 C11 NOTE 5 NOTE
30A SB
30A SB
+
TOSHIBA VARIAN DUNLEE
_ _ _ _ _ _ _ _ _ _ _ _ A19QB A19QA 1
ORANGE
C6
VIOLET
AY20-047
AY51-016
BROWN
A19R1 C4A 1- COMM. 5- COMM. OUTER- COMM.
ANODE POWER MODULE
GREY
AY51-085 1 1
AY51-077
AY51-085
1 1 2- MAIN 4- MAIN CENTER- MAIN
500VAC
A21
500VAC
A20 RED RED C7 AY51-077
F1,F2
F1, F2
ROTOR CABLE
RED
AY20-044 AY20-044 3- PHASE 3- PHASE INNER- PHASE
GRN/YEL 2 GRN/YEL 2 AY20-047
A9P7 CATHODE POWER MODULE C7A PA1 5- T.S. 1- T.S. T.S.-1
BLACK 3 BLACK 3
1
2
3
4
PC2 6- T.S. 2- T.S. T.S.-2
J7 220VAC BROWN (16 AWG) AY51-010 220VAC ROTOR MAIN 1 BLK PA2
1 1
GREEN/YELLOW (10AWG) BLK (10AWG) 60 VAV RED (16 AWG) 60 VAC ROTOR PHASE 2 RED PC1 NOTES:
GREEN/YELLOW (10AWG) 0 VAC
2
3 ORANGE (16AWG)
2
3 0 VAC ROTOR COMMON 3 WHT C
J3 4 1. C8 THRU C15, 2400 UF/ 450VDC
4 4
A9P3 5
TB1
A10P1 J1 CHASSIS GND
TEMP. FAULT
6
7
T.S.
T.S.
A 2. C1 VALUE COULD CHANGE DEPENDING ON TUBE
MANUFACTURER OR MODEL. (SEE TUBE DATA SHEET)
GROUND TO HV TANK
CATH. FDBK
TO GROUND OR TO THE MAS METER.)
VIOLET
1
WHITE
BLACK
CATH. RTN
GREY
110/220 VAC DOOR INTERLOCK 24 VDC 1 TO TUBE STAND 15VDC 3 4. AY51-019-2 AND AY51-020 ARE USED FOR AEC
RED
BLUE
MA RTN
16
14
2
MA FDBK
TB6 24 VDC RTN 2 15VDC RTN 4 OPTION ONLY.
15
3
ANODE FDBK
LOAD CB1 LINE
LINE
ANODE RTN
4 NON AEC GENERATORS AY51-020 IS NOT INSTALLED
A17P1
GRN 2 DOOR COLL. READY 4 -15VDC 1.5KE68CA
FIL.COMMON
EL70-004
SHIELD 7
10 AMP
FIL. LARGE
FIL. SMALL
22 RTN 5
1 -15VDC RTN 6
X - RAY ON +15VDC 6
2 24VDC 7 A17 AY20-031 5. CAPACITORS VALUES: C3,C4,C4A,C6,C7,C7A
A9P1 J1 GROUND 7 AY51-043 24VDC HV MODULE
LOAD
8 FIL. SHIELD
0VAC BLK (16AWG) 1 0VAC J3 24VDC RTN 10 SE
10 32VAC BLK (16AWG) 32VAC TB3 C3 C4 C4A C6 C7 C7A
RED
INCOMING AC LINE
WHT
2
WHT
BLK
GEN.
BLK
C1, 30UF/440VAC
0VAC BLK (16AWG) 0VAC 115 VAC 1
1
2
3
4
5
6
7
8
9
3
AY51-017
T1 16VAC BLK (16AWG) 16VAC BUCKY T. ON 2 A10P3
AY51-015
4 AY51-017
11 0VAC BLK (16AWG) 0VAC 115 VAC RTN 3 TO TABLE GRN/YEL (16AWG) 32KW 1uF 0.5uF 1uF 0.5uF
EL99-001
A2P1
EMI FLT
AY51-012
5
LINE
LINE
WHT (16AWG)
GREEN/YELLOW (10AWG)
GREEN/YELLOW (10AWG)
LOAD
6
BLK (16AWG)
BROWN
12 0VAC BLK (16AWG) 0VAC 5
AY51-021
ORANGE
YELLOW
7 A5P1
WHITE
GREEN
VIOLET
GREY
28VAC BLK (16AWG) 28VAC GROUND 6 40KW 1uF 1uF 1uF 1uF
BLUE
1 8
1
2
3
4
5
6
RED
-10VAC 1 0VAC BLK (16AWG) 0VAC 7
9
0VAC 2 13 28VAC BLK (16AWG) 28VAC BUCKY READY 8 EL28-002 J1 A2P6 AY51-013
(16AWG)
2 10
1
2
3
4
5
6
8
7
3 BLK (16AWG) 11 0VAC (SEE NOTE 2) 50KW 1uF 1uF 0.25uF 1uF 1uF 0.25uF
MA RTN
MA SENSE
ANODE RTN
SHIELD
SHIELD
110VAC
ANODE FDBK
4 8 BLK (16AWG) 7VAC A1P8 A1P8 J6 BRN
CATHODE RTN
0VAC
CATHODE FDBK
MAIN GROUND
L
3
GROUND
12 1 1 J1
1
2
3
4
5
6
7
8
9
RED
48VDC
7VAC
WHT, C
RED, S
2 2
48VDCRTN
A9P4 J4 1 ORN
TB4 J11 J8
BLK,
4 130VAC 5 2
1
1
3 3
GRN/YEL
2 1 4 4
BROWN (20AWG/600V)
STUD
5 1
4
3 2
3
5 5
RED (20AWG/600V)
AY51-023
6 8 7 3 10 10
BUCKY READY 8 9
9 (LOGIC BD.) 8
8
4 OUTPUT B J2 CONTROL BD.
J10 9 J3 A2P3 A5P2
9
60VAV
AY51-022-SE
23
21
22
20
19 A9P5 J5 A1P4 J4
R3A, R3B
1
A9P6 AY51-008
A8P4 50/50W
J6 J9 A1P9 A2P8 J8 2
RED 24VDC GROUND AY51-019-2
A8P7
2 1 1 1 3
A11P4
BLK (16AWG) 4 0 VAC 2 GREEN/YELLOW 2 24VDC RTN 15VDC 1 2 +18 VDC 4
BLK (16AWG) 110 VAC BLACK 28VDC 15VDC OUTPUT A
BLK (16AWG)
BLK (16AWG)
BLK (16AWG)
BLK (16AWG)
3 3 3 2 3 5
1 4 GREEN/YELLOW 4 GROUND 15VDCRTN 3 4 OUTPUT B 6
5 5 BLUE 5 BUCKY TABLE 15VDCRTN 4 5 7
1
2
3
4
5
6
7
8
9
10
12
13
14
15
16
11
1 15VDC AY40-005T 6 6 VIOLET 6 BUCKY WALL -15VDC 5 8
8
2
7
4
3
5
1
6
9
10
-15VDC
0VAC SW.
0VAC
2 2 5 1 1 10 10 9 1 12 2
32VACRTN BLACK 32VACRTN GREY/WHITE DOOR 3
3 3 6 -15VDCRTN 2 2 11 11 24VDCRTN 10 2 15VDC 13 3
110/220
4
110/220VAC SW.
AEC WALL 1
0VAC 15VAC VIOLET 15VAC BLUE/YELLOW SPARE 15VDC RTN
AY51-012
4 4 7 24VDC 3 3 12 12 3 14 4
5
5 220VAC 5 8 24VDC 15VACRTN 4 BLUE 4 15VACRTN 13 GREY 13 TABLE RDY A1P5 4 15VDC RTN 15 5
6
6 6 9 24VDCRTN 11VAC 5 RED 5 11VAC 14 GREEN/BROWN 14 K2, 24VDC 5 -15VDC 16 6
48VDCRTN
48VDCRTN
30VDCRTN
30VDCRTN
15VDCRTN
15VDC
3 GND 7
8
5 5 1
2
VIO 9 BATT + C A8P6 8 J4 6 6 2
J6 AY51-011 A1P2 28VDC 9 3
RED 1.2K/ A J2
AEC WALL 2
10 9 7 7 3
BLU 1.2K/ C BROWN (22 AWG) V SENSE A GND AY40-003S 4
11 1 1 J5 8 8 4
RED (22 AWG) V SENSE C GRN/YEL A2, KVP BD. 5
MONITOR/CHARGER
4 2 2 9 9 5
ORANGE (22 AWG) GROUND A1P1 6
12 3 3 10 10 6
BRN BATT- A YELLOW (22 AWG) 24VDC 7
5 4 4 1 11 11 7
GRY BATT- C GREEN (22 AWG) AUTO SHUT OFF J1 8
6 5 5 2 12 12 8
WHT VA- BLUE (22 AWG) SYSTEM ON 9
13 6 6 3 13 13 9
BLK VC- VIOLET (20 AWG) 24VDC MAG. J5
AY40-028T
AY51-018-XX
GREY (20 AWG) 24VDC MAG. RTN
A8, LINE
7 8 8 5
RED
BLU
9
8
7
6
5
4
3
2
1
15 9 9 6
GRN/YEL RTN BLACK (22 AWG) FAULT RESET
BD.
8 10 10 7 SEE NOTE 4
GRN/YEL 16 RTN 11 BLK/ORN (22 AWG) 11 NOT USED 8 A11P5
9
8
7
6
5
4
3
2
1
J8 J2 12 WHT/BRN (22 AWG) 12 NOT USED 9
A8P8 10
3
2
1
AY51-039-SE A1P3 J3
11
GRN/YEL (10AWG)
GRN/YEL (20AWG)
GRN/YEL (20AWG)
A8P2
12
AY10-005 ODYSSEY
A16P1
R1A,R1B 1.2K/50W
AY51-012
AY51-004
3 15 3
4
50/50W
4 16 4
5
5
AY51-018-XX 6
PCB DOOR 7
6
BLK (16AWG) 7
GROUND STUD WHT (16AWG) 8
8
GREEN/YELLOW (16AWG) FILAMENT BD. GROUND 9
9
J9
J8
J7
J6
J4
J3
J2
J1
WHT16AWG
F2 3.15A SB 440VAC R4 A,B 50 OHM C9 C13
BLK16AWG
3 4
CHART FOR
LINE
LINE
LINE
J9
J8
J7
J6
J4
J3
J2
J1
+
+
B L2
BLK16AWG
SEE NOTE 6
50W 4
A19,A1P5 A18,A1P5 ROTOR
AY51-079
C L3 CONNECTION)
AY51-079
AY51-080
AY51-080
AY51-073 AY20-047
CB1
WHT
AY25-001 C10 C14
GRN/YEL (10AWG)
GRN/YEL (16AWG)
AY51-073 AY20-047
N N (2X)
LOAD
LOAD
LOAD
4 (2X)
+
3
~ +
~ + A+ C-
G2
G2
G1
E2
E2
E1
E1
G1
6
AY51-068 (3X)
G2
G2
G1
E2
E2
E1
E1
G1
NEUTRAL 5 3 + 3
C11 ~ C15 +
0 1 8 3 + 3
7
~ +
+
A18C1 A18C2
ROTOR CABLE
T1 PHASE A
220 2 10 A19C1 A19C2 ~ -
ORN
BLU
BRN
9
K2 285 1
~ - C16 - 2 - 2
3 K1 C12 - 2 - 2
DB2
AY20-146 R8 R9 R10
9
AY51-065
2
+
A18QB A18QA
AY51-127 (4X) DB2
AY51-065
380
+
4 A19QB A19QA A18R1
AY51-066
SEE NOTE 3 1 1
3.3/50W ALUM.
AY51-066
D2 415 5 SEE NOTE 3 1 1
10
2
1
BRN
ORN
1N4005
BLU
1N4005
440 6 A19R1 SEE NOTE
D3
A19 POWER MODULE CATHODE A18 POWER MODULE ANODE 1 AND 2
480 7
C7 C4
0 1 AY51-128 AY51-128 (4X)
K3 BLK (10AWG) C6 C3
(4X)
AY51-069 (3X)
9
T1 PHASE B
BLK (10AWG)
285 3 A9P7 A9P3
D1 J7 220VAC BROWN (16 AWG) 220VAC
10
1 1
2
1
1
0VAC BLK (16AWG) 0VAC SEE NOTE 4 10 9
2 0 1 16VAC BLK (16AWG)
2
16VAC TB2 J4 A10P4 2- MAIN 4- MAIN CENTER- MAIN
3
220
AY51-023
2 8 11VAC BLK (16AWG) 5 11VAC 24 VDC RTN 2 A10P5 J5 15VDC 1 5 3- PHASE 3- PHASE INNER- PHASE
T1 PHASE C
14
CATH. FDBK
4
YELLOW (20AWG)
6 2
AY51-043
285
CATH. RTN
3 28VAC BLK (16AWG) 28VAC COLL. READY 4 15VDC RTN 1 5- T.S. 1- T.S. T.S.-1
16
7 1 3
MA FDBK
5 0VAC BLK (16AWG) 0VAC 5 15VDC RTN 3
MA RTN
RED (20AWG)
8 2 4
380 4 28VAC BLK (16AWG) 28VAC +15VDC 6 -15VDC 4 6- T.S. 2- T.S. T.S.-2
15
9 3 5
ANODE FDBK
15 0VAC BLK (16AWG) 0VAC GROUND 7 -15VDCRTN
ANODE RTN
6 10 6
BLK(16AWG)
BLK(16AWG)
7
415 5 0 1 7 7VAC BLK (16AWG) 7VAC 24VDC 1.5KE68CA
FIL.COMMON
11 7
8
FIL. LARGE
FIL. SMALL
60 2 0VAC BLK (16AWG) 0VAC 24VDC NOTES:
7 12 8
SHIELD
440 6 120 3 TB3 24VDC RTN A17
9
8 115 VAC 1 AY40-013T 24VDC RTN 10 AY20-031 HV MODULE 1. C3, C4 ,C6 AND C7 1UF/1500VAC
480 7 4 6 BUCKY T. ON 2
19 A9P4 J4 115 VAC RTN 3 TO TABLE A10 ROTOR DRIVE BD. J3 2. C5 AND C8 ARE NOT INSTALLED.
9
220
20 4 A10P3
WHT
WHT
FIL. SHIELD
BLK
220 VAC IN GROUND 5 3. C9 THRU C16, 2400UF/450VDC
10
1
2
3
4
5
6
7
8
9
EMI FLT 1
17 2 220 VAC IN 6
AY51-017
LOAD 18 60VAC ROTOR 7 4. DISCONNECT A17P1-9 AND 10 FROM GROUND AND
11 11
3
0 VAC ROTOR BUCKY READY 8 C1, 30UF/440VAC CONNECT THE MAS METER TO THESE WIRES.
LINE 4 AY51-017
ORANGE
(SEE NOTE 5) GREEN/YELLOW (16AWG) (WARNING A17P1-9 AND 10 MUST
YELLOW
AY51-012
A2P1
12 5
AY51-021
VIOLET
BROWN
BLK (16AWG) BE CONNECTED TO GROUND OR MAS METER.)
GREY
GREEN
BLUE
6
WHITE
LINE WHT (16AWG)
RED
TB2 LOAD 10 TB4 A5P1 5. C1 VALUE COULD CHANGE DEPENDING ON
1
2
3
4
5
6
GRN/YEL (16AWG) 115 VAC 1
AY51-013 TUBE MANUFACTURER OR MODEL (SEE TUBE
1
2
3
4
5
6
7
8
GND
BLK (16AWG) BUCKY W. ON 2
J1
1
2
3
4
5
6
7
8
9
BLK (16AWG) A9P5 J5 115 VAC RTN 3 TO WALLSTAND BRN J1 DATA BASE)
GROUND
WHT, C
1 1
RED, S
BLK, L
MA RTN
RED
MA SENSE
ANODE RTN
BLK (16AWG) 4 A1P8
ANODE FDBK
48VDC
48VDCRTN
CATHODE RTN
CATHODE FDBK
2 2
1
2
3
4
5
6
7
8
9
1
2
3
4
5
6
7
8
9
BLK (16AWG) 220 VAC OUT GROUND 5 ORN 6. 32.5 AND 40KW GENERATORS CB1 MUST BE 30 AMP.
INCOM. LINE
INCOM. LINE
1 3 3
BLK (16AWG) 0 VAC OUT 24 VDC 6 J11 J8 1 YEL 50KW GENERATORS CB1 MUST BE 50 AMP.
2 1 4 4
BLK (16AWG) 120 VAC 24 VDC RTN 7 2 GRN
3 2 5 5
RS 232
A8P3 BLK (16AWG) 0VAC BUCKY READY 8 3 BLU 7. AY51-019-2 IS USED FOR AEC OPTION ONLY.
PORT
SLAVE
4 3 6 6
J3 4 VIO NON AEC GENERATORS USE AY51-019-1.
8 5 4 7 7
PHASE C,IN RS 232 5 GRY AY40-007T
3 1 6 5 8 8
PHASE A,IN PHASE A BLK A6P1 J2 J6 A9P6 A1P4 J4 MASTER 6 WHT A5, FILAMENT
10 2 6 9 9
AY40-005T J1 AY51-005 A9P2 AY51-008 PORT 7 BLK
CONTROL BD.
YELLOW/WHITE
5 3 7 10 10
PHASE B BLK A6, POWER 32VAC 1 WHITE (16AWG) 1 32VAC RED 24VDC 8
1 4 1 1 1 1 8
PHASE N. BLK 32VAC RTN 2 BLACK (16AWG) 2 32VAC RTN GREEN/YELLOW 24VDC RTN 9 J6 A1P6 A5P2 J2
RED/GREEN
6 5 SUPPLY BD. 2
3 3
2 2 2 9
15VAC VIOLET 15VAC BLACK 28VDC
ORN/BLK
BRN/YEL
7 6 3 3 3 3 A1P3
PHASE C BLK 15VAC RTN 4 BLUE 4 15VAC RTN GREEN/YELLOW GROUND J10 A1P10 A2P8 J8 J3
2 7 4 4 4 4 1
11VAC 5 RED 5 11VAC BLUE BUCKY TABLE +18 VDC
4 8 5 5 5 5 1 2
BLACK(20AWG)
WHITE(20AWG)
AY51-012
9 6 6 6 6 1 2 3
BLUE(20AWG)
7 7 7 7 2 3 4
8 8
A11P4
A8P6 J6 28VAC RTN 8 BLACK/RED 8
28VAC RTN 8
WHITE/BLACK 8
COLLIMATOR READY 15VDC RTN 3 4 OUTPUT B 5
4 24VRTN K2 9 YELLOW/WHITE 9 BUCKY T. READY 15VDC RTN 4 5 6
24V K2 15VDC AY51-004 DOOR BLACK/RED BUCKY W. READY -15VDC
AY51-015
3 1 10 10 5 7
1
2 24VRTN K3 15VDC 2 48VDC 1 INTERLOCK TB6 11 GREY/WHITE 11 DOOR INTERLOCK -15VDC RTN 6 8
1
2
3
4
5
6
7
8
9
10
12
13
14
15
16
11
24V K3 15VDC RTN 48VDC 2 1 DOOR BLUE/YELLOW SPARE 24VDC
1 3 2 12 12 7 9
48VDCRTN 3 DOOR RTN GREY TABLE RDY A2P7 J7 A11P2
15VDC RTN 4 3
2
13 13 24VDC 8 10
A8P1 48VDCRTN 4 GREEN/BROWN K2, 24VDC +18 VDC J4
-15VDC 5 4 14 14 24VDC RTN 9 1 11
VA+/2.4K 30VDC 5 BROWN EXPOSE GROUND J2 1
1 -15VDC RTN 6 5 15 15 24VDC RTN 10 2 12 1
30VDC 6 X - RAY ON GREEN PREP RDY 2
2 24VDC 7 6 TB5 16 16 J9 A1P9 3 OUTPUT A 13 2
-15VDC RTN
7 3
15VDC RTN
15VDC RTN
24VDC RTN
24VDC RTN
AEC WALL 1
4 9 8 18 18 15 4
-15VDC
24VDC
24VDC
WHT (16AWG)
5 10 9 19 19 1 16 5
BLK (16AWG)
7 3 1 7
VC+/2.4K A6P3 A9, INTERFACE BD. 4 8
8 J2 EXP. 4 2 15VDC 1 1 8
A1P3 J3 5 9
9 AY40-022T-2 PREP 5 3 15VDC RTN 2 2 9
2.4K A8, LINE AY40-006S 6
15VDC RTN
RED(20AWG)
RED(20AWG)
10 28VDC 6 4 3 3
A6P2 BLACK/RED 33VDC A1, CPU BD. 7 -15VDC A11P3
10
1
2
3
4
5
6
7
8
9
11 MONITOR 1 GND 7 5 4 4
BLUE(20AWG)
VC- 8
12 WHT/BLK 33VDC RTN 2 (LOGIC BD.) 28VDC 8 6 -15VDC RTN 5 5 J3
BLUE(20AWG)
BD. 9 24VDC 1
3 9 7 6 6 1
J1 GND 24VDC 2
4 J5 8 7 7 2
A1P1 24VDC RTN 3
9 8 8 3
J4 A8P4 AY51-012 A1P2 J2 J1 24VDC RTN 4
1 10 9 9 4
AY51-011
AEC WALL 2
5
2 10 10 5
AY51-018-XX
BROWN (22 AWG) V SENSE A A2P5 J5 6
1 1 3 11 11 6
RED (22 AWG) V SENSE C AY40-003S 7
2 2 4 12 12 7
R1A, R1B ORANGE (22 AWG) GROUND A2, KVP BD. 8
3 3 5 13 13 8
R2A, R2B YELLOW (22 AWG) 24VDC 9
4 4 6 J4 14 14 9
1.2K/50W GREEN (22 AWG) AUTO SHUT OFF J1 J5
5
BLUE (22 AWG)
5
SYSTEM ON
7
A11P1
AEC TABLE
6 6 8 A2P4
VIOLET (20 AWG) 24VDC MAG.
9
8
7
6
5
4
3
2
1
7 7 9
8 GREY (20 AWG) 8 24VDC MAG. RTN 10
9 WHITE (22 AWG) 9
MISSING PHASE 11
A11P5
9
8
7
6
5
4
3
2
1
10 BLACK (22 AWG) 10 FAULT RESET 12
11 BLACK/ORANGE (22 AWG) 11 NOT USED 13 A16P1
WHITE/BROWN (22 AWG) NOT USED 1
12 12 14 1
2 TO OCP ASSEMBLY
15 2
3
16
4
3 AY10-004 QUEST
(SEE NOTE 7) 4 AY10-005 ODYSSEY
AY51-019-2 5
5
DOOR GROUND 6
6
7
7
8
8
GREEN/YELLOW (16AWG) FILAMENT BD. GROUND 9
9
AY51-018-XX
MAIN GROUND
STUD
GROUND TO HV TANK GREEN/YELLOW (10AWG)
WHT
BLK
BLUE
RED
AY51-058 (3X) AY51-007 F1 3.15A SB 440VAC IGBT DRIVE J5 1 IGBT DRIVE J5 1
R3 A,B 50 OHM BD,CATHODE 2 C13 BD, ANODE 2
A L1 TB1 50W C9 3 3
BLK16AWG
J9
J8
J7
J6
J4
J3
J2
J1
J9
J8
J7
J6
J4
J3
J2
J1
WHT16AWG
F2 3.15A SB 440VAC R4 A,B 50 OHM 4 4 X-RAY TUBE
LINE
LINE
LINE
+
B L2
BLK16AWG
A19,A1P5
AY51-080
50W (SEE TUBE
A18,A1P5
AY51-072
50 AMP/3P
WHT
C L3 AY25-001 ROTOR CHART
CB1
AY51-080
AY20-047 AY20-047
AY51-072 (2X) C10 (2X) C14
GRN/YEL (10AWG)
GRN/YEL (16AWG)
AY51-066
FOR ROTOR
N L4 4
LOAD
AY51-066
LOAD
LOAD
3 CONNECTION)
+
6
~
~
G2
G2
G1
G2
G2
G1
E2
E2
E2
E2
E1
E1
E1
G1
E1
G1
5 C15
AY51-088 (3X) 8
+
NEUTRAL + C11 + 3 + 3
+ 3 + 3
ROTOR CABLE
0 1 7
~ A+ C-
AY51-066
AY51-066
10
+
~ A19C1 A19C2 A18C1 A18C2
YELLOW
T1 PHASE A
198 2 9
-
RED
AY20-146 R8 R9 R10
1
ORN
K2 K1 - C12 - 2 - 2
- 2 - 2
BRN
BLU
208 2
3 ~ C16
9
AY51-065
3.3/50W ALUM. AY51-127 (4X) ~ A19QB A19QA A18QB A18QA
AY51-065
220
+
4 DB1 A18R1
220 5 DB2 1 1 1 1
D2
1N4005
220 5A
10
2
1
ORN
BLU
1N4005 6 A19R1
D3
SEE NOTE
280
A19 POWER MODULE CATHODE A18 POWER MODULE ANODE 1 AND 2
7
C7 C4 X-RAY TUBE ROTOR CONNECTION CHART
0 1 AY51-128(4X)
AY51-128(4X) C6 C3
K3 2 BLK (10AWG) TOSHIBA VARIAN DUNLEE
AY51-075 (3X)
9
2 BLK (10AWG)
T1 PHASE B
198 2 2 BLK (10AWG) 1- COMM. 5- COMM. OUTER- COMM.
A9P7 A9P3 AY51-010
208 3 J7 220VAC BROWN (16 AWG) 220VAC 2- MAIN 4- MAIN CENTER- MAIN
10
1 1
2
1
D1 1
1 60 VAV 2 RED (16 AWG) 2 60 VAC ROTOR MAIN 1 BLK
1N4005 220 4 2 0 VAC ORANGE (16AWG) 0 VAC ROTOR PHASE 2 RED 3- PHASE 3- PHASE INNER- PHASE
AY51-016 2 3 3
5 BLACK/RED 3 J3 ROTOR COMMON 3 WHT PC1 PC2 PA1 PA2
3 4 4
5A GREY/WHITE 4 4 5- T.S. 1- T.S. T.S.-1
4
6 TB1 A10P1 J1 5
6 T.S.
24 VAC COLL. 1 TO COLLIMATOR CHASSIS GRN C 6- T.S. 2- T.S. T.S.-2
220
220
240
280
AY51-023
198 2 8 11VAC BLK (16AWG) 5 11VAC 24 VDC RTN 2 A10P5 J5 15VDC 1
5 3. C9 THRU C16, 2400UF/450VDC
AY51-078 X3
CATH. FDBK
14
4 6
AY51-043 2
CATH. RTN
208 3 28VAC BLK (16AWG) 28VAC COLL. READY 4 15VDC RTN 1 4. DISCONNECT A17P1-9 AND 10 FROM GROUND AND
WHT FIL.COMMON 16
7 1 3
MA FDBK
0VAC BLK (16AWG) 0VAC 5 15VDC RTN 3 CONNECT THE MAS METER TO THESE WIRES.
5
MA RTN
8 2 4
220 4 28VAC BLK (16AWG) 28VAC +15VDC 6 -15VDC 4 (WARNING A17P1-9 AND 10 MUST CONNECTED TO
ANODE FDBK
5 15 0VAC BLK (16AWG) 0VAC GROUND 7 -15VDCRTN GROUND OR MAS METER.)
8
15
ANODE RTN
6 10 6
BLK(16AWG)
BLK(16AWG)
7
5A 0 1 7 7VAC BLK (16AWG) 7VAC 24VDC 1.5KE68CA
YELLOW
11 7
6 2 0VAC BLK (16AWG) 0VAC 24VDC 5. C1 VALUE COULD CHANGE DEPENDING ON
BLK FIL. L.
7 12 8
SHIELD
3 TB3 24VDC RTN
FIL. SHLD
A17
RED
7
115 VAC 1 AY40-013T 24VDC RTN AY20-031
8
220
10
4 6 BUCKY T. ON 2 DATA BASE)
280 19 A9P4 J4 115 VAC RTN 3 TO TABLE A10 ROTOR DRIVE BD. J3 HV MODULE 6. AY51-019-2 IS USED FOR AEC OPTION ONLY.
9 20 4 NON AEC GENERATORS USE AY51-019-1.
60
220
120
1
2
3
4
5
6
7
8
9
10 17
1
220 VAC IN 6 A10P3
EMI FLT 2
GRN/YEL (16AWG)
18 60VAC ROTOR 7
A2P1
AY51-017
11 LOAD 11
3
0 VAC ROTOR BUCKY READY 8 AY51-017 BLK (16AWG)
4
LINE WHT (16AWG)
ORANGE
BROWN
YELLOW
AY51-021
AY51-012
12 5
VIOLET
GREEN
WHITE
C1, 30UF/440VAC
GREY
BLUE
6
RED
1
2
3
4
5
6
LINE (SEE NOTE 5) A5P1
LOAD 10 TB4 J1 AY51-013
1
2
3
4
5
6
7
8
GRN/YEL (16AWG) 115 VAC 1
GND
MA RTN
MA SENSE
BRN
ANODE RTN
2
ANODE FDBK
BLK (16AWG) BUCKY W. ON A1P8
CATHODE RTN
CATHODE FDBK
WHT, C
1 1
RED, S
BLK, L
1
2
3
4
5
6
7
8
9
GROUND
BLK (16AWG) A9P5 J5 115 VAC RTN 3 TO WALLSTAND RED J1
48VDC
48VDCRTN
2 2
BLK (16AWG) 4 ORN
3 3
1
2
3
4
5
6
7
8
9
1
2
3
4
5
6
7
8
9
BLK (16AWG) 220 VAC OUT 5 YEL
INCOM. LINE
INCOM. LINE
1 GROUND 1
4
GRN
4
BLK (16AWG) 2 0 VAC OUT 24 VDC
6 J11 J8 1 5 5
BLK (16AWG) 120 VAC 7 2 BLU
3 24 VDC RTN 2 6 6
RS 232
BLK (16AWG) 0VAC 8 J10 3 VIO
PORT
SLAVE
4 BUCKY READY 3 7 7
J3 PHASE N. BLK 4 GRY
8 5 5 4 8 8
PHASE C,IN PHASE A BLK RS 232 5 WHT
3 2 6 5 9 9
10 PHASE A,IN 3 A6P1 AY51-005 J2 J6 A9P6 A1P4 J4 MASTER 6
6
10
BLK
10
PHASE B BLK A9P2 AY51-008 PORT 7
YELLOW/WHITE
5 4 7
32VAC 1 WHITE (16AWG) 1 32VAC RED 24VDC 8 J6 A1P6 A5P2 J2
1 1 1 1 1 1 8
AY40-005T 32VAC RTN 2 BLACK (16AWG) 2 32VAC RTN GREEN/YELLOW 24VDC RTN 9 AY40-007T
RED/GREEN
6 6 2 2 2 2 9 A1P3
PHASE C BLK A6, POWER 15VAC 3 VIOLET 3 15VAC BLACK 28VDC A1P10 J3 A5, FILAMENT
ORN/BLK
BRN/YEL
AY51-022-3P
7 7 3 3 3 3 1
15VAC RTN 4 BLUE 4 15VAC RTN GREEN/YELLOW GROUND A2P8 J8
2 8 SUPPLY BD. 4
5 5
4 4 4 2 CONTROL BD.
4 11VAC 5 RED 5 11VAC 5 BLUE 5 BUCKY TABLE J9 A1P9 1 +18 VDC 3
J5 A8P5 11VAC RTN 6 BROWN/YELLOW 6 11VAC RTN VIOLET BUCKY WALL GROUND
15VDC
AY51-012
9 6 6 6 6 1 2 4
BLACK(20AWG)
WHITE(20AWG)
7 7 7 7 2 3 5
BLUE(20AWG)
A8P6 J6 28VAC RTN 8 BLACK/RED 8 28VAC RTN WHITE/BLACK COLLIMATOR READY OUTPUT B
8 8 8 8 15VDC RTN 3 4 6
4 24VRTN K2 J1 9 YELLOW/WHITE 9 BUCKY T. READY 15VDC RTN 4 5 7 AY51-019-2
3 24V K2 15VDC 1 DOOR 10 BLACK/RED 10 BUCKY W. READY -15VDC 5 8
AY51-015
24VRTN K3 48VDC 1 GRAY/WHITE DOOR INTERLOCK
15VDC TB6 -15VDC RTN
A11P4
2 2 1 INTERLOCK 11 11 6 9
24V K3 48VDC 2 DOOR BLUE/YELLOW SPARE
1 15VDC RTN 3 2
1
12 12 24VDC 7 10
15VDC RTN 48VDCRTN 3 2 DOOR RTN GREY TABLE RDY 24VDC A2P7 J7
AY51-009-3P 4 3 13 13 8 11
-15VDC 48VDCRTN 4 GREEN/BROWN K2, 24VDC 24VDC RTN +18 VDC
5 4 14 14 9 1 12
1
2
3
4
5
6
7
8
9
10
12
13
14
15
16
11
-15VDC RTN 30VDC 5 BROWN EXPOSE 24VDC RTN GROUND
6 5 15 15 10 2 13
24VDC 30VDC 6 X - RAY ON TB5 GREEN PREP RDY OUTPUT A A11P2
7 6 16 16 3 14
-15VDC RTN
7
15VDC RTN
15VDC RTN
24VDC RTN
24VDC RTN
24VDC 8 30VDCRTN 7
1 X-RAY ON RTN 17 RED/GREEN 17 0VAC GRN/YEL 4 OUTPUT B 15 J4
WHT (16AWG)
BLK (16AWG)
9 8 18 18 16 1
-15VDC
OCP ON
15VDC
15VDC
24VDC
24VDC
10 9 19 19 1 2
J2 15VDCRTN 10 GREEN/ORANGE GROUND 2 3
10 20 20 RS-485 2 3
A8P1 A8P2 AY40-023T 3 4
J3 RS-485 3 1 15VDC 1 1 AY40-031S 4
AEC WALL 1
VA+/2.4K A6P3 A9, INTERFACE BD. 4 5
1 J2 EXP. 4 2 15VDC 2 2 A11, AEC BD. 5 SC50-050T REV. K
A1P3 J3 5 6
2 PREP 5 3 15VDC RTN 3 3 (OPTIONAL) 6
2.4K AY40-006S 6 7
3 28VDC 6 4 15VDC RTN 4 4 7
BLACK/RED 33VDC 7 8
10
4 1 GND 7 5 5 5 8
VA - AY51-004 WHT/BLK 33VDC RTN 8 -15VDC RTN 9
5 2 (LOGIC BD.) 28VDC 8
9
6 6 6 9
6 3 9 7 24VDC J4 7 7
AY51-018
A6P2 GND 24VDC A11P3
7 4 J5 8 8 8
8 VC+/2.4K A1P1 9 24VDC RTN 9 9 J3
J4 A8P4 AY51-012 A1P2 J2 J1 24VDC RTN 1
9 1 10 10 10 1
2.4K AY51-011 2
RED(20AWG)
RED(20AWG)
10 2 11 11 2
BLUE(20AWG)
AEC WALL 2
12 2 2 4 13 13 4
BLUE(20AWG)
AY51-020
BLUE (22 AWG) SYSTEM ON/OFF 8
6 6 8 8
VIOLET (20 AWG) 24VDC MAG. 9
7 7 9 9
AY40-022T-3 8 GREY (20 AWG) 8 24VDC MAG. RTN 10 J5
A8, LINE WHITE (22 AWG) MISSING PHASE AEC TABLE
9 9 11
R1A, R1B BLACK (22 AWG) FAULT RESET
1
2
3
4
5
6
7
8
9
MONITOR 10 10 12
R2A, R2B 11 BLK/ORN (22 AWG) 11 NOT USED 13
1.2K/50W BD. WHT/BRN (22 AWG) NOT USED A11P5 A16P1
AY10-005 ODYSSEY.
12 12 14
1
2
3
4
5
6
7
8
9
1
15 1
DOOR GROUND 2
16 2
3
AY51-019-2 (SEE NOTE 6) 3
4
4
5
5
6
6
7
7
GREEN/YELLOW (16AWG) FILAMENT BD. GROUND 8
8
9
9
AY51-018-XX
MAIN GROUND
STUD
GROUND TO HV TANK GREEN/YELLOW (10AWG)
WHT
BLK
BLUE
RED
AY51-074 X3 F1 3.15A SB 440VAC IGBT DRIVE J5 1 IGBT DRIVE J5 1
TB1 AY51-007 R3 A,B 50 OHM BD,CATHODE BD, ANODE
2 2
A L1 50W C9 3 C13 3
J9
J8
J7
J6
J4
J3
J2
J1
J9
J8
J7
J6
J4
J3
J2
J1
WHT 16AWG
F2 3.15A SB 440VAC R4 A,B 50 OHM
BLK 16AWG
4 4
BLK16AWG
LINE
LINE
LINE
+
B L2 50W A19,A1P5
AY51-080
A18,A1P5
C-
AY51-080
AMP/3P
WHT
AY25-001 AY51-073 (2X) AY51-073
C L3 AY20-047
CB1
AY20-047
C10
GRN/YEL (10AWG)
GRN/YEL (16AWG)
(2X)
50
4 C14
LOAD
LOAD
LOAD
N L4
ROTOR CHART
3
CONNECTION)
6 AY51-079 ~ AY51-079
FOR ROTOR
+
+
~
X-RAY TUBE
G2
G2
G1
G2
G2
G1
E2
E2
E2
E2
E1
E1
E1
G1
E1
G1
(SEE TUBE
5
8 +
AY51-068(3X)
0
NEUTRAL
1 7 + C11
3 + +3 3 + +3
~
AY51-066
AY51-066
ORN
10 A19C1 A19C2 C15 A18C1 A18C2
BLU
BRN
220 ~
T1 PHASE A
9
K2 2
-
A+
9
+
2 - 2 2 - - 2
-
AY20-146 R8,R9,R10 285 3 AY51-127 (4X) 2
- ~
~ A19QB A19QA A18QB A18QA
AY51-065
D2 3.3/50W ALUM. 380 4 K1 A18R1
10
DB1
2
1
BRN
ORN
415 DB2
1N4005
5
AY51-065
+
D3
440
A19R1 X-RAY TUBE ROTOR CONNECTION CHART
6
SEE NOTE 3 A19 POWER MODULE CATHODE A18 POWER MODULE ANODE TOSHIBA VARIAN DUNLEE
480 7
SEE NOTE 3
ROTOR CABLE
K3 1- COMM. 5- COMM. OUTER- COMM.
9
0 1 SEE
AY51-069 (3X)
285 3 A9P7 C4
1N4005
J7 220VAC 1 C6 5- T.S. 1- T.S. T.S.-1
T1 PHASE B
380 4 1 60 VAV 2 A9J8 A9P8 C3
AY51-016 2 0 VAC 3 1 1 BRN 6- T.S. 2- T.S. T.S.-2
415 5 BLACK/RED 3 J3 4 TO 2 2
GREY/WHITE 4 COLL. 3 3
440 6 TB1 4 YEL
24 VAC COLL. 5
4 NOTES:
T.S.
T.S.
1 PC1 PC2 PA1 PA2
H9 WHT
5
H8 RED
H7 BLK
480 7 A9P1 J1 24 VAC RTN 2 6 BLU BRN 5
6 9 1 1
GROUND 3 7 VIO ORN C3, C4, C6 AND C7 1UF/1500VAC C5 AND C8, .5 UF/1500VAC.
TB2 T2 7 2 2 1.
1 0 1 9 32VAC BLK (16AWG) 1 32VAC
TO TUBE
8 8 GRY
C
AY51-071 X3
0VAC BLK (16AWG) 2 0VAC 9 9 WHT 2. DO NOT INSTALL C5 AND C8 IN 50KW GENERATORS.
STAND BLK 1 1 2 3
2 220 2 16VAC BLK (16AWG) 3 16VAC TB2 AY51-089
A 1
TS2
T1 PHASE C
COMM
285 3 8 11VAC BLK (16AWG) 11VAC 24 VDC RTN 2 TB3 TO SEE NOTE 4 10 9 GRN 6
PHASE
MAIN
3 5
AY51-023
3
AY51-015
16 0VAC BLK (16AWG) 0VAC PREP 1 9 TB1 DISCONNECT A17P1-9 AND 10 AND CONNECT THE MAS METER TO THESE
6
3 1
DIGITAL 4
4.
380 4 28VAC BLK (16AWG) 28VAC COLL. READY 4 PREP 2 2 6
4 0VAC BLK (16AWG)
7
0VAC 5 RECP. RDY 3 RECEPTOR 5
WIRES. (WARNING A17P1-9 AND 10 MUST BE CONNECTED TO GROUND OR
8 TO MAS METER.)
415 5 28VAC BLK (16AWG) 28VAC +15VDC 6 PREP RDY 1 4 TABLE 2 RED 4 P/O
14
5 9 7 L1
CATH. FDBK
15 0VAC BLK (16AWG) 0VAC GROUND 7 PREP RDY 2 5 1 9 200VAC 5. 50 KW GENERATOR STANDARD HV MODULE IS AY30-031 125 KV
16
10 TB2
CATH. RTN
440 6 0 1 7 7VAC BLK (16AWG) 7VAC TO EXPOSE 1 6 3 8
TO
YELLOW
6 11
MA FDBK
L2
MA RTN
60 2 0VAC BLK (16AWG) 0VAC EXPOSE 2 7 4 6. AY51-019-2 IS USED FOR AEC OPTION ONLY, NON AEC GENERATORS USE
15
12 TABLE 240VAC
480 7 120 3 TB3 DR RDY RAD 8 AID ROTOR CONTROLLER AY51-019-1
ANODE FDBK
RED
ANODE RTN
115 VAC HV ON 1
SHIELD 7
1 9 MODEL LC102
FIL. SMALL
WHT FIL.COMMON
AY51-089
8
220 4 6 BUCKY W. ON 2 HV ON 2 10
A17 7. DIGITAL GENERATOR, AY40-023T IS REPLACED WITH AY40-034T.
AY51-033
FLT 1
FIL. SHIELD
17 220V IN GND 6 TB7 SEE NOTE 5
10 LOAD 18
2
60V ROTOR 7 PREP 1 1 TO GREEN/YELLOW (16AWG)
RED
3
11 0V ROTOR BUCKY READY 8 PREP 2 2 BLK (16AWG)
11 LINE 4 DIGITAL
RECP. RDY 3 WHT (16AWG)
5 AY51-017
TO PREP RDY 1 4 RECEPTOR AY51-017 A2P1 A5P1
12 LINE
6
PREP RDY 2 5 WALL
WALL
LOAD 10 TB4 EXPOSE 1 6
1
2
3
4
5
6
1
2
3
4
5
6
7
8
GRN/YEL (16AWG) BLK (16AWG) 115 VAC 1 BUCKY EXPOSE 2 7 AY51-013
9 WHT
GRN
8 GRY
BRN
BLU
SHLD
7 VIO
GND
ORN
BRN
GRN
BLK (16AWG) A9P5 J5 BUCKY W. ON 2 DR RDY RAD 8 J1
RED
BRN
BLK
1 1
L
J1
WHT, C
RED, S
RED
GROUND
BLK (16AWG) 115 VAC RTN 3 HV ON 1 9 A1P8
48VDC
48VDCRTN
2 2
MA RTN
1
2
3
4
5
6
ORN
MA SENSE
ANODE RTN
CATH RTN
4 10
ANODE FDBK
BLK (16AWG) 220V OUT HV ON 2
CATH FDBK
BLK,
1 3 3
BLK (16AWG) 0 VAC OUT GROUND 5 24VDC 11 YEL
INCOM. LINE
INCOM. LINE
2 4 4
1
2
3
4
5
6
7
8
9
1
2
3
4
5
6
7
8
9
BLK (16AWG) 120 VAC 24 VDC RTN 6 24VDC RTN 12 GRN
3 5 5
BLK (16AWG) 0VAC 24 VDC 7 J10 J8 1 BLU
4 1 6 6
2 SHIELD VIO
MASTER
A8P3 J3 5 BUCKY READY 8 AY40-034 D.R. 2 7 7
RS 232
PHASE N. BLK 3 GRY
PORT
8 5 6 CONFIGURATION SEE NOTE 7 3
4 SHIELD
8
WHT
8
3 PHASE C,IN PHASE A 2 BLK RS 232 4 9 9
PHASE A,IN A6P1 A9P2 J2 J6 A9P6 J4 SLAVE 5 BLK AY40-007T
10 3 5 10 10
PHASE B BLK AY40-005T J1 AY51-005 AY51-008 A1P4 PORT 6 A5, FILAMENT
YELLOW/WHITE
5 4 6
A6, POWER 32VAC 1 WHITE (16AWG) 1 32VAC RED 24VDC 7 J6 A2P6 A5P2 J2
1 1 1
2 2
1 1 1 7
8 CONTROL BD.
32VAC RTN BLACK (16AWG) 32VAC RTN GREEN/YELLOW 24VDC RTN
RED/GREEN
SUPPLY BD.
BLK
6 6 2 2 2 2 8 A2P3
3 3 9
AY51-022-3P
7 7 3 3 3 3 9 1
15VAC RTN 4 BLUE 4 15VAC RTN GREEN/YELLOW GROUND A1P10 A2P7 J7
2 8 4 4 4 4 2 AY51-019-2
11VAC 5 RED 5 11VAC BLUE BUCKY TABLE GROUND
4 5 5 5 5 1 3
J5 A8P5 11VAC RTN 6 BROWN/YELLOW 6 11VAC RTN VIOLET BUCKY WALL 15VDC +18 VDC
9 6 6 6 6 1 2 4
7 7
A11P4
BLACK(20AWG)
7 7 7 7 2 3 5
BLUE(20AWG)
28VAC RTN 8 BLACK/RED 8 28VAC RTN WHITE/BLACK COLLIMATOR READY 15VDC RTN OUTPUT B
RED(20AWG)
8 8 8 8 3 4 6
4 24VRTN K2 9 YELLOW/WHITE 9 BUCKY T. READY 15VDC RTN 4 7
24V K2 15VDC AY51-004 DOOR BLACK/RED BUCKY W. READY -15VDC
3 1 10 10 5 8
1
2
3
4
5
6
7
8
9
10
12
13
14
15
16
11
24VRTN K3 48VDC 1 GRAY/WHITE DOOR INTERLOCK
2 15VDC 2 1 INTERLOCK TB6 11 11 -15VDC RTN 6 9
24V K3 15VDC RTN 48VDC 2 1 DOOR BLUE/YELLOW SPARE 24VDC
1 3 2 12 12 7 10
48VDCRTN 3 2 DOOR RTN GREY TABLE RDY A2P8 J8 J4 A11P2
15VDC RTN 24VDC
AY51-012
AY51-009-3P 4 3 13 13 8 11
A8P6 J6 -15VDC 48VDCRTN 4 GREEN/BROWN K2, 24VDC 24VDC RTN GROUND
5 4 14 14 9 1 12
-15VDC RTN 30VDC 5 BROWN EXPOSE 24VDC RTN +18 VDC J2 1
6 5 15 15 10 2 13 1
24VDC 30VDC 6 X - RAY ON TB5 GREEN PREP RDY J9 A1P9 OUTPUT A AY40-031S 2
7 6 16 16 3 14 2
-15VDC RTN
24VDC 7 GRN/YEL 3
15VDC RTN
15VDC RTN
24VDC RTN
24VDC RTN
8 30VDCRTN 7
1 X-RAY ON RTN 17 RED/GREEN 17 0VAC 4 OUTPUT B 15 A11, AEC BD. 3
30VDCRTN 8 2 X-RAY ON A1P5 (OPTIONAL) 4
AY51-007 24VDC RTN ORANGE/BLACK 7.5VAC
AEC WALL 1
9 8 18 18 5 16 4
-15VDC
24VDC
24VDC
WHT (16AWG)
10 9 19 19 1 5
SC50-054T REV. S
BLK (16AWG)
1 3 1 1 1 7
J2 A6P3 A9, INTERFACE BD. 4 15VDC 8
2 EXP. 4 2 2 2 8
2.4K 5 15VDC RTN 9
3 PREP 5 3 3 3 9
6 15VDC RTN
4 28VDC 6 4 4 4
VA - BLACK/RED 30VDC AY40-006S 7 A11P3
10
-15VDC
1
2
3
4
5
6
7
8
9
5 1 GND 7
8
5 5 5
6 WHT/BLK 30VDC RTN 2 J3 A1, CPU BD. 8 6 -15VDC RTN 6 6 J3
28VDC 9 1
A6P2 24VDC J4
7 3 (LOGIC BD.) GND 9 7 7 7 1
2
8 VC+/2.4K A1P3 4 J5 8 24VDC 8 8 2
A1P1 24VDC RTN 3
RED(20AWG)
9 9 9 9 3
AEC WALL 2
2.4K J4 A8P4 J1 24VDC RTN 4
RED(20AWG)
10 1 10 10 10 4
AY51-011
AY51-018-XX
5
11 2 11 11 5
BLUE(20AWG)
AY51-020
A8, LINE 6 BLUE (22 AWG) 6 SYSTEM ON 8 J5
VIOLET (20 AWG) 24VDC MAG. AEC TABLE
MONITOR 7 7 9
GREY (20 AWG) 24VDC MAG. RTN
1
2
3
4
5
6
7
8
9
8 8 10
R1A, R1B BD. 9 WHITE (22 AWG) 9 MISSING PHASE 11
R2A, R2B 10 BLACK (22 AWG) 10 FAULT RESET 12 A11P5
1
2
3
4
5
6
7
8
9
1.2K/50W 11 BLACK/ORANGE (22 AWG) 11 NOT USED 13 A16P1
WHITE/BROWN (22 AWG) NOT USED 1
12 12 14 1
2 TO OCP ASSEMBLY
15 2
A1P2 J2 3
16
4
3 AY10-004 QUEST
DOOR
AY51-012 AY51-019-2 (SEE NOTE 6) 5
4
AY10-005 ODYSSEY
GROUND 5
6
6
7
7
8
8
GREEN/YELLOW (16AWG) FILAMENT BD. GROUND 9
9
AY51-018-XX
MAIN GROUND
STUD
GROUND TO HV TANK GREEN/YELLOW (10AWG)
WHT
BLK
BLUE
RED
AY51-074 (3X) F1 3.15A SB 440VAC IGBT DRIVE J5 1 IGBT DRIVE J5 1
A L1 AY51-007 R3 A,B 50 OHM BD,CATHODE 2 C13 BD, ANODE 2
C9
WHT16AWG
50W 3 3
BLK16AWG
J9
J8
J7
J6
J4
J3
J2
J1
J9
J8
J7
J6
J4
J3
J2
J1
+
B L2 TB1 F2 3.15A SB 440VAC R4 A,B 50 OHM 4 4
BLK16AWG
LINE
LINE
LINE
+
50W A19,A1P5
A18,A1P5 X-RAY TUBE
C L3
AY51-080
AMP/3P
AY25-001 AY51-073
CB1
WHT
AY51-080
AY20-047 AY20-047 (SEE TUBE
AY51-073 (2X) C10 C14
GRN/YEL (10AWG)
GRN/YEL (16AWG)
LOAD
LOAD
LOAD
3
~ + AY51-079
+
FOR ROTOR
6
~ + AY51-079
G2
G2
G1
G2
G2
G1
E2
E2
E2
E2
E1
E1
E1
G1
E1
G1
AY51-068 (3X) 5 CONNECTION)
NEUTRAL 8
X-RAY TUBE ROTOR CONNECTION CHART
3 + + 3 3 + +3
0 7
ORN
1 ~ C15 TOSHIBA VARIAN DUNLEE
BLU
AY51-066
AY51-066
BRN
10
K2 220
~ C11 A19C1 A19C2 A18C1 A18C2
T1 PHASE A
9
+
2 A+ C- 1- COMM. 5- COMM. OUTER- COMM.
ROTOR CABLE
AY20-146 R8 R9 R10
YELLOW
+
2 - 2 2 - - 2
285 3 AY51-127 (4X) 2 - 2- MAIN 4- MAIN CENTER- MAIN
~ -
RED
DB1
2
1
BRN
ORN
AY51-065
BLU
DB2 C12 1 1 1 1
AY51-065
D2 415
1N4005
+
5 5- T.S. 1- T.S. T.S.-1
+
D3
ANODE
440 6 CATHODE POWER MODULE 6- T.S. 2- T.S. T.S.-2
1N4005 SEE NOTE 3 A19 POWER MODULE SEE NOTE 3 A18
480 7 AY51-128(8X)
K3 C7 NOTES:
AY51-069 (3X)
9
0 1 SEE C4
BLK (10AWG) C6 NOTE 1 1. C3, C4, C6 AND C7 1UF/1500VAC, C5 AND C8 ARE NOT USED
220 2 BLK (10AWG) C3
BLK (10AWG) 2. C1 VALUE COULD CHANGE DEPENDING ON TUBE MODEL (SEE TUBE DATA SHEET)
10
D1
2
1
T1 PHASE B
4 1 60 VAV 2 RED (16AWG) 2 60 VAV ROTOR MAIN 1 BLK PC1 PC2
AY51-016 2 0 VAC 3 ORANGE (16AWG) 3 0 VAC ROTOR PHASE 2 RED 4. DISCONNECT A17P1-9 AND 10 AND CONNECT THE MAS METER TO THESE WIRES.
415 5 BLACK/RED J3 ROTOR COMMON 3 WHT PA1 PA2 (WARNING A17P1-9 AND 10 MUST BE CONNECTED
3 4 4
GREY/WHITE TO 1 BRN A10P1 4 TO GROUND OR TO MAS METER.)
4 1
440 6 TB1 2 J1 5
24 VAC COLL. 1
COLL.
3
2
3 CHASSIS GRD 6 T.S. C 5. DIGITAL GENERATOR, AY40-023T IS REPLACED WITH AY40-034T.
480 2 7 T.S.
TB2 7 T2 A9P1 J1 24 VAC RTN 4 4 YEL TEMP. FAULT
A
AY51-071 X3
0VAC BLK (16AWG) 0VAC 24 VDC 1 9 WHT 15VDC 6 7. GENERATOR WITHOUT DIGITAL RECEPTOR OPTION AY51-090 IS
3 285 3 8 11VAC BLK (16AWG)
4
11VAC 24 VDC RTN 2
9
AY51-090 15VDC RTN
2
5
AY51-023
5 3 REPLACED WITH AY51-048.
AY51-015
16 0VAC BLK (16AWG) 0VAC 3 A9J8 A9P8 15VDC RTN 2
14
4 380 4 28VAC BLK (16AWG)
6
28VAC COLL. READY 4 TB3 TO -15VDC
4
1
16
7 5
0VAC BLK (16AWG) 0VAC 5 PREP 1 1 -15VDC RTN 3
5 415 5 28VAC BLK (16AWG)
8
28VAC +15VDC 6 PREP 2 2
DIGITAL
24VDC
6
4
15
9 7
15 0VAC BLK (16AWG) 0VAC GROUND 7 RECP. RDY 3 RECEPTOR 24VDC
ANODE FDBK
AY51-043
6 10 8 1.5KE68CA
CATH. FDBK
440 6 0 1 7 7VAC BLK (16AWG) 7VAC TO PREP RDY 1 4 TABLE 24VDC RTN
ANODE RTN
FIL. SMALL
WHT FIL.COMMON
SHIELD 7
11 9
YELLOW
CATH. RTN
60 2 0VAC BLK (16AWG) 0VAC PREP RDY 2 J5 J3 24VDC RTN
FIL. LARGE
5
A17
MA FDBK
8
7 12 TABLE 10
MA RTN
480 7 120 3 TB3 EXPOSE 1 6
RED
1
2
3
1
2
3
4
5
6
7
8
9
HV MODULE
A10P3
220
A10P5
4 6 BUCKY W. ON 2 DR RDY RAD 8
19 A9P4 J4 115 VAC RTN 3 HV ON 1 9
FIL. SHIELD
9
AY51-012
20 4 HV ON 2 10 SHLD
RED
220V IN CH. GND 5 24VDC 11 C1, 30 UF
BLK
EMI FLT
10 1
AY51-021
17 220V IN GND 6 24VDC RTN 12 (SEE
SHLD
2 AY51-017
LOAD 18 60V ROTOR 7
11 3 NOTE
AY51-017
LINE 11 4 0V ROTOR BUCKY READY 8 TB7
TO PREP 1 1 TO 2) AY51-090
12 5
AY51-017
A11P10
A11P8
PREP 2 2
WALL DIGITAL
A2P1
6
RECP. RDY 3
ORANGE
YELLOW
LINE
BUCKY RECEPTOR
VIOLET
10 TB4 PREP RDY 1 4
GREY
BROWN
BLUE
GREEN
LOAD
WHITE
1
2
3
4
5
6
1
2
3
4
5
6
7
8
9
1
2
3
4
5
6
7
8
9
GRN/YEL (16AWG) BLK (16AWG) 115 VAC 1 PREP RDY 2 5 WALL
8 GRY
BRN
RED
BLU
9 WHT
GND
YEL
VIO
BLK (16AWG) A9P5 J5 BUCKY W. ON 2 EXPOSE 1 6
J1
AY51-020
1
2
3
4
5
6
7
8
9
1
2
3
4
5
6
7
8
9
A11P11
BLK (16AWG) 115 VAC RTN 3 EXPOSE 2 7
1 GND A11P12
MA RTN
1
2
3
4
5
6
7
MA SENSE
ANODE RTN
A1P8
CATH RTN
BLK (16AWG) 220V OUT 4 DR RDY RAD 8 18VDC J10 J8 AEC J12
ANODE FDBK
CATH FDBK
INCOM. LINE
INCOM. LINE
1 2 1 1
BLK (16AWG) 0 VAC OUT GROUND 5 HV ON 1 9 A AEC TABLE 1
2 3 2 2 WALL 1 1
1
2
3
4
5
6
7
8
9
1
2
3
4
5
6
7
8
9
BLK (16AWG) 120 VAC 24 VDC RTN 6 HV ON 2 10 B 2
3 4 3 3 2
A8P3 BLK (16AWG) 0VAC 24 VDC 7 24VDC 11 J10 J8 1 AEC 3
4 1 4 4 3
PORT
J3 PHASE N. BLK BUCKY READY 8 24VDC RTN 12 2 A2P7 J7 4
SLAVE
8 5 5 2 5 5 WALL 4
RS 232
PHASE C,IN PHASE A BLK 3 5
3 2 6 3 6 6 5
PHASE A,IN AY40-034 D.R. RS 232 4 2 6
10 3 4 7 7 6
PHASE B BLK A6P1 A9P2 J2 J6 J4 SLAVE 5 A2P8 J8 7
5 4
AY51-005 CONFIGURATION SEE NOTE 5 5
6
8 8 7
8
AY40-005T J1 A9P6 PORT GROUND
YELLOW/WHITE
1 1 6 1 9 9 8
1 1 7 9
BLK
PHASE C 32VAC RTN 2 BLACK (16AWG) 2 32VAC RTN RED 24VDC RTN 8 OUTPUT A
RED/GREEN
7 7 SUPPLY BD. 2
3 3
2 1 1 8
9
3 11 11 A11P13
15VAC VIOLET 15VAC GREEN/YELLOW 28VDC OUTPUT B
ORN/BLK
BRN/YEL
2 8 3 3 2 2 9 4 12 12
15VAC RTN 4 BLUE 4 15VAC RTN BLACK GROUND J11 J13 1
4 4 4 3 3 5 13 13 1
11VAC 5 RED 5 11VAC GREEN/YELLOW BUCKY TABLE 2
9 5 5 4 4 14 14 2
11VAC RTN 6 BROWN/YELLOW 6 11VAC RTN BLUE BUCKY WALL 15VDC J4 A2P4 J11 3
6 6 5 5 1 3
BLACK(20AWG)
WHITE(20AWG)
7 7 6 6 2 1 4
BLUE(20AWG)
A8P6 J6 A8P5 28VAC RTN 8 BLACK/RED 8 28VAC RTN WHITE COLLIMATOR READY 15VDC RTN 15VDC J3 A2P3 5
8 8 7 7 3 2 1 1 5
24VRTN K2 DOOR WHITE/BLACK BUCKY T. READY 15VDC RTN 15VDC RTN 6
4 8 8 4 3 2 2 6
7
3 24V K2 15VDC 1 INTERLOCK 9 YELLOW/WHITE 9 BUCKY W. READY -15VDC 5 4 15VDC RTN 3 3 7
24VRTN K3 15VDC 48VDC 1 TB6 BLACK/RED DOOR INTERLOCK -15VDC 8
2 2 1 10 10 -15VDC RTN 6 5 4 4 8
2 1 9
1 24V K3 15VDC RTN 3 48VDC 2 DOOR 11 GREY/WHITE 11 SPARE 24VDC 7 6 -15VDC RTN 5 5 9
3 2
AY51-009-3P 15VDC RTN 4 48VDCRTN 3 DOOR RTN 12 BLUE/YELLOW 12 TABLE RDY 24VDC 8 7 24VDC 6 6
-15VDC 48VDCRTN 4 GREY K2, 24VDC 24VDC RTN 24VDC A11TB10
AY51-007 5 4
5
13 13 9 8 7 7
1
1 VA+/2.4K -15VDC RTN 6 30VDC 5 X - RAY ON 14 GREEN/BROWN 14 EXPOSE 24VDC RTN 10 9 24VDC RTN 8 8 TB10 24VDC
24VDC 30VDC 6 TB5 BROWN PREP RDY J9 A1P9 24VDC RTN AY40-027S 2 PREP
2 7 6 15 15 10 9 9
SC50-053T REV. E
-15VDC RTN
7
15VDC RTN
15VDC RTN
24VDC RTN
24VDC RTN
2.4K 24VDC 30VDCRTN 1 X-RAY ON RTN GREEN 0VAC GRN/YEL A11, UNIVERSAL 3 EXPOSE
3 8 7 16 16 10 10
24VDC RTN 30VDCRTN 8 2 X-RAY ON RED/GREEN 7.5VAC A1P5 A2P5 J5 TOMO 4 BUCKY RDY
4 9 8 17 17 11 11 AEC BD.
-15VDC
24VDC
24VDC
TABLE
WHT (16AWG)
5 10 9 18 18 1 12 12
WHT (20AWG)
BLK (16AWG)
10 2
BLK (20AWG)
6 10 19 19 RS-485 2 13 13
A8P2 AY40-023T SEE NOTE 5 GREEN/ORANGE 3 A2, KVP BD. 7 24VDC RTN
WHT/BLK
7 J3 20 20 RS-485 3 14 14
VC+/2.4K A6P3 A9, INTERFACE BD. 4 8 GROUND
8 J2 EXP. 4 15 15
AY51-062 A1P3 J3 5 J6
9 PREP 5 16 16
RED(20AWG)
2.4K 6 A11TB12
RED(20AWG)
10 28VDC 6
7
10
11 1 GND 7
BLUE(20AWG)
10
VC- WHT/BLK 33VDC RTN A1, CPU BD. 2 PREP
A2P6
1
2
3
4
5
6
7
8
9
12 2 28VDC 8
9 WALL 3 EXPOSE
BLUE(20AWG)
WHT
AY51-019-2
RED
ORN
GRN
GRY
BRN
BLU
BLK
VIO
AY51-013
YEL
J4 A8P4 A1P2 J2 J1 2 TB1 6 GROUND
1
AY51-011 3 300VDC
A5P2
2
BROWN (22 AWG) V SENSE A 4
1 1 3
1
2
3
4
5
6
7
8
9
10
RED (22 AWG) V SENSE C TB11 A11TB11
2 2 4
R1A, R1B 3 ORANGE (22 AWG) 3 GROUND 5
1 .4S
R2A, R2B YELLOW (22 AWG) 24VDC J2 A11P7 J7 2 .6S
4 4 6 1
1.2K/50W GREEN (22 AWG) AUTO SHUT OFF AY40-007T TOMO 3 .8S
5 5 7 2
BLUE (22 AWG) SYSTEM ON A5 FILAMENT BD. 4 1.2S
6 6 8 3 SWEEP 5
DOOR GROUND 7 VIOLET (20 AWG) 7 24VDC MAG. 9 4 2S
8 GREY (20 AWG) 8 24VDC MAG. RTN 10 5
TIME 6 A16P1
AY40-022T-2 WHITE (22 AWG) MISSING PHASE 7 1
9 9 11 6 1
A8, LINE BLACK (22 AWG) FAULT RESET 8 2
10 10 12 2
48VDCRTN
BLACK/ORANGE (22 AWG) NOT USED A11P1 9 3
GROUND
MONITOR 11 11 13
J1
3
C WHT
WHITE/BROWN (22 AWG) NOT USED 10 GROUND 4 TO OCP ASSEMBLY
S RED
L BLK
12 12 14 1 4
48VDC
BD. 5
15 2 5 AY10-004 QUEST
J12 J1 J6 J5 6
16 3 6 AY10-005 ODYSSEY
7
7
8
1
2
3
4
5
6
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
9
8
A1P12 A5P1 9
9
1
2
3
4
5
6
7
8
9
A11P6
A11P5
AY51-049
GREEN/YELLOW (16AWG) FILAMENT BD. GROUND GREEN/YELLOW (16AWG)
BLK (16AWG) AY51-062
WHT (16AWG) AY51-090 OR
AY51-048
AY51-048
BLACK (20AWG) SEE NOTE 7
WHITE (20AWG)
AY51-018-XX
BLACK
YELLOW/GREEN
WHITE
BROWN
BLACK/RED
YELLOW/WHITE
AY51-012
MAIN GROUND
STUD GROUND TO HV TANK GREEN/YELLOW (10AWG)
WHT
BLK
BLUE
RED
F1 3.15A SB 440VAC IGBT DRIVE J5 1 IGBT DRIVE J5 1
AY51-074 X3 AY51-007 R3 A,B 50 OHM BD,CATHODE 2 C13 BD, ANODE 2
A L1 TB1 50W C9 X-RAY TUBE ROTOR CONNECTION CHART
WHT16AWG
BLK16AWG
3 3
J9
J8
J7
J6
J4
J3
J2
J1
J9
J8
J7
J6
J4
J3
J2
J1
+
F2 3.15A SB 440VAC R4 A,B 50 OHM 4 4
BLK16AWG
LINE
LINE
LINE
AY51-080
+
B L2 50W A3,B P5 TOSHIBA VARIAN DUNLEE
C-
A3,A P5
AY51-080
AY51-079
AY25-001 1- COMM. 5- COMM. OUTER- COMM.
WHT
C L3 AY20-047 AY51-073 X2
CB1
AY20-047
C10 C14
CONNECTIONS.)
4
50
LOAD
LOAD
N L4 3
+
~ +
FOR ROTOR
6 AY51-079
+
~ + 3- PHASE 3- PHASE INNER- PHASE
G2
G2
G1
G2
G2
G1
E2
E2
E2
E2
E1
E1
E1
E1
G1
G1
5
AY51-068 X3 NEUTRAL 8 3 + + 3 3 + +3 5- T.S. 1- T.S. T.S.-1
0 1 7 C11 ~
AY51-066
AY51-066
RED 10 A19C1 A19C2 A18C1 A18C2 6- T.S. 2- T.S. T.S.-2
~
A+
220 9
T1 PHASE A
+
ORN 2 C15
BLU
BRN
AY51-073 X2
+
3
~ -
YELLOW
AY20-146 R8,R9,
9
1N4005
DB2 1 1 1 1 1. C3, C4, C6 AND C7 1UF/1500VAC, C5 AND C8 .5 UF/1500VAC
AY51-065
AY51-065
(SEE NOTE 3)
415
+
D3
D2 5 C16
10
2
1
BRN
ORN
440
+
6 SEE NOTE 3
A19 POWER MODULE CATHODE A18 POWER MODULE ANODE 3. C9 THRU C16, 2400UF/450VDC
480 7
4. DISCONNECT A17P1-9 AND 10 AND CONNECT THE MAS METER TO THESE WIRES
ROTOR CABLE
AY51-069 X3 0 1 SEE (WARNING A17P1-9 AND 10 MUST BE CONNECTED
BLK (10AWG) C8 NOTE 1 TO GROUND OR TO MAS METER.)
9
1
2
1
380
T1 PHASE B
1N4005 4 1 60 VAV 2 A9J8 A9P8 C3
AY51-016 2 0 VAC 3 1 1 BRN
415 5 BLACK/RED J3 2 7. GENERATORS WITH TOMO OPTION, AY40-006S MUST BE REV F OR HIGHER
3 4 2
GREY/WHITE 4 TO 3 3
440 6 TB1 4 YEL 8.
T.S.
T.S.
COLL. 4 GENERATOR WITH UNIVERSAL AEC AND DIGITAL RECEPTOR AY51-048
24 VAC COLL. 1 5 PC1 PC2 PA1 PA2
H9 WHT
H8 RED
IS REPLACED WITH AY51-090
H7 BLK
5
480 5
7 T2 A9P1 J1 24 VAC RTN 2 6 6 BLU BRN
9
1 1
TB2 GROUND 3 7 7 VIO ORN 2 2
1 0 1 9 32VAC
0VAC
BLK (16AWG)
BLK (16AWG)
1
2
32VAC
0VAC TO TUBE
8
9
8
9
GRY
WHT
C
1 2 3
2 220 2 16VAC BLK (16AWG) 3 16VAC TB2 STAND AY51-090 A BLK 1
9 1
TS2
T1 PHASE C
COMM
8 11VAC 10 9 6 2
MAIN
AY51-071 X3
AY51-023
PHASE
SEE NOTE 4
3 5 3 TB1
AY51-015
16 0VAC BLK (16AWG) 0VAC 3 PREP 1 1 9
6 DIGITAL 4
380 4 28VAC BLK (16AWG) 28VAC COLL. READY 4 PREP 2 2 6
4 0VAC BLK (16AWG)
7
0VAC 5 RECP. RDY 3 RECEPTOR 5
8
415 5 28VAC BLK (16AWG) 28VAC +15VDC 6 PREP RDY 1 4 2 RED 4 P/O
TABLE
14
5 15 0VAC BLK (16AWG)
9
0VAC GROUND 7 PREP RDY 2 5 1 9 7 L1
200VAC
16
10 8 TB2
440 6 0 1 7 7VAC BLK (16AWG) 7VAC TO EXPOSE 1 6 3
6 11 TO
YELLOW
60 0VAC L2
2 BLK (16AWG) 0VAC EXPOSE 2 7 4 AID ROTOR CONTROLLER
15
12 TABLE 240VAC
480 7 120 3 TB3 DR RDY RAD 8 MODEL LC102 GND
ANODE FDBK
RED
7 1.5KE68CA
CATH. FDBK
BUCKY
ANODE RTN
1 9
SHIELD 7
115 VAC HV ON 1
FIL. SMALL
WHT FIL.COMMON
CATH. RTN
220 4 6 BUCKY W. ON 2 HV ON 2 10
MA FDBK
8
A17
MA RTN
19 A9P4 J4 115 VAC RTN 3 24VDC 11
EMI 20 4 24VDC RTN 12 AY30-032 SHLD
9 HV MODULE
AY51-033
FILTER 1 220V IN CH. GND 5
FIL. SHIELD
17 220V IN GND 6 TB7 SEE NOTE 5
10 LOAD 18
2
60V ROTOR 7 PREP 1 1 TO SHLD
AY51-017
RED
3
11 0V ROTOR BUCKY READY 8 PREP 2 2 AY51-017
11 LINE 4 DIGITAL
RECP. RDY 3
A2P1
5
A11P10
RECEPTOR
A11P8
TO PREP RDY 1 4
12 6
PREP RDY 2 5 WALL
LINE WALL
LOAD 10 TB4 EXPOSE 1 6
1
2
3
4
5
6
BUCKY
1
2
3
4
5
6
7
8
9
1
2
3
4
5
6
7
8
9
GRN/YEL (16AWG)
GRY
BLK (16AWG) 115 VAC 1 EXPOSE 2 7
WHT
BRN
YEL
BLU
SHLD
GRD
VIO
ORN
GRN
BLK (16AWG) A9P5 J5 BUCKY W. ON 2 DR RDY RAD 8
RED
BRN
BLK
J1
1
2
3
4
5
6
7
8
9
1
2
3
4
5
6
7
8
9
BLK (16AWG) 115 VAC RTN 3 HV ON 1 9 A1P8 1 GRD A11P12
MA RTN
1
2
3
4
5
6
7
8
9
MA SENSE
ANODE RTN
BLK (16AWG) 220V OUT 4 HV ON 2 10 18VDC J10 J8 AEC J12
CATH RTN
ANODE FDBK
CATH FDBK
1 2 1 1
BLK (16AWG) 0 VAC OUT GROUND 5 24VDC 11 A AEC TABLE 1
INCOM. LINE
INCOM. LINE
2 3 2 2 WALL 1 1
1
2
3
4
5
6
7
8
9
1
2
3
4
5
6
7
8
9
BLK (16AWG) 120 VAC 24 VDC RTN 6 24VDC RTN 12 B 2
3 4 3 3 2
AY51-090
BLK (16AWG) 0VAC 24 VDC 7 J10 J8 1 AEC 3
4 1 4 4 3
2 4
MASTER
A8P3 BUCKY READY 8 AY40-034 D.R. A2P7 J7
AY51-020
5 2 5 5 WALL 4
RS 232
J3 PHASE N. BLK 3 5
PORT
8 5 6 CONFIGURATION SEE NOTE 6 3
4
6 6 5
6
3 PHASE C,IN PHASE A 2 BLK RS 232 4 7 7 2 6
PHASE A,IN A6P1 A9P2 J2 J6 A9P6 A1P4 J4 SLAVE 5 A2P8 J8 7
10 3 5 8 8 7
PHASE B BLK AY40-005T J1 AY51-005 AY51-062 PORT 6 GROUND 8
5 4 6 1 9 9 8
YELLOW/WHITE
7 7 3 3 3 3 9 4 12 12
15VAC RTN 4 BLUE 4 15VAC RTN GREEN/YELLOW GROUND J11 J13 1
2 8 4 4 4 4 5 13 13 1
11VAC 5 RED 5 11VAC BLUE BUCKY TABLE 2
4 5 5 5 5 14 14 2
9 11VAC RTN 6
6 BROWN/YELLOW 6
6 11VAC RTN 6 VIOLET 6 BUCKY WALL 15VDC 1 J4 A2P4 A11P11 J11 3
3
BLACK(20AWG)
WHITE(20AWG)
7 7 7 7 2 1 4
BLUE(20AWG)
A8P6 J6 J5 A8P5 28VAC RTN 8 BLACK/RED 8 28VAC RTN WHITE/BLACK COLLIMATOR READY 15VDC RTN 15VDC J3 A2P3 5
8 8 8 8 3 2 1 1 5
24VRTN K2 DOOR YELLOW/WHITE BUCKY T. READY 15VDC RTN 15VDC RTN 6
4 9 9 4 3 2 2 6
24V K2 15VDC BLACK/RED BUCKY W. READY -15VDC 15VDC RTN 7
3 1 INTERLOCK 10 10 5 4 3 3 7
24VRTN K3 15VDC 48VDC 1 TB6 GRAY/WHITE DOOR INTERLOCK -15VDC 8
2 2 1 11 11 -15VDC RTN 6 5 4 4 8
24V K3 48VDC 2 1 DOOR BLUE/YELLOW SPARE 9
1 15VDC RTN 3 2 12 12 24VDC 7 6 -15VDC RTN 5 5 9
AY51-009-3P 15VDC RTN 48VDCRTN 3 2 DOOR RTN GREY TABLE RDY 24VDC 24VDC
4 3 13 13 8 7 6 6 A11TB10
-15VDC 48VDCRTN 4 GREEN/BROWN K2, 24VDC 24VDC RTN 24VDC
5 4 14 14 9 8 7 7
-15VDC RTN 30VDC 5 X - RAY ON BROWN EXPOSE 24VDC RTN 24VDC RTN TB10 1 24VDC
6 5 15 15 10 9 8 8
24VDC 7 30VDC 6
6 TB5 16 GREEN 16 PREP RDY J9 A1P9 10 24VDC RTN 9 9 AY40-027S 2 PREP
-15VDC RTN
24VDC 30VDCRTN 7 1 X-RAY ON RTN RED/GREEN 0VAC GRN/YEL A11, UNIVERSAL 3 EXPOSE
15VDC RTN
15VDC RTN
24VDC RTN
24VDC RTN
8 7 17 17 10 10
VA+/2.4K 24VDC RTN 30VDCRTN 8 2 X-RAY ON ORANGE/BLACK 7.5VAC A1P5 A2P5 J5 TOMO 4 BUCKY READY
1 9 8 18 18 11 11 AEC BD.
-15VDC
24VDC
24VDC
2 10 9 TABLE
WHT (16AWG)
19 19 1 12 12
WHT (20AWG)
BLK (16AWG)
10 2
BLK (20AWG)
3 J2 10 20 20 2
3
13 13
A8P2 J3 AY40-023T SEE NOTE 6 A2, KVP BD. 7 24VDC RTN
WHT/BLK
4 3 14 14
VA - J2 A6P3 A9, INTERFACE BD. 4 8 GROUND
5 4 15 15
A1P3 J3 5 J6
6 5 16 16
6 A11TB12
7 6
VC+/2.4K BLACK/RED 30VDC AY40-006S 7 A11P9 J9 TB12 1 24VDC
10
1
2
3
4
5
6
7
8
9
8 1 7
WHT/BLK 30VDC RTN A1, CPU BD. 8 2 PREP
10
RED(20AWG)
A2P6
1
2
3
4
5
6
7
8
9
9 2 8
A6P2 9 WALL 3 EXPOSE
2.4K
SC50-055T REV. F
RED(20AWG)
AY51-019-2
11 4
SEE NOTE 7 A1P1 STAND
VC- AY51-047 1 5 24VDC RTN
BLUE(20AWG)
WHT
ORN
GRN
GRY
BRN
RED
BLU
12
BLK
AY51-013
YEL
VIO
BLUE(20AWG)
A5P2
2
BROWN (22 AWG) V SENSE A 4
1 1 3
1
2
3
4
5
6
7
8
9
10
RED (22 AWG) V SENSE C TB11 A11TB11
2 2 4
3 ORANGE (22 AWG) 3 GROUND 5
1 .4S
YELLOW (22 AWG) 24VDC J2 A11P7 J7 2 .6S
4 4 6 1
5 GREEN (22 AWG) 5 AUTO SHUT OFF 7 AY40-007T 2 TOMO 3 .8S
R1A, R1B BLUE (22 AWG) SYSTEM ON A5 FILAMENT.BD. 4 1.2S
6 6 8 3 SWEEP
R2A, R2B 7 VIOLET (20 AWG) 7 24VDC MAG. 9 4
5 2S
1.2K/50W 8 GREY (20 AWG) 8 24VDC MAG. RTN 10 5
TIME 6
AY40-022T-2 9 WHITE (22 AWG) 9 MISSING PHASE 11 6
7
A8, LINE 10 BLACK (22 AWG) 10 FAULT RESET 12
8
1
48VDCRTN
BLACK/ORANGE (22 AWG) NOT USED A11P1 9 1
GROUND
MONITOR 11 11 13
J1 2 TO OCP ASSEMBLY
C WHT
WHITE/BROWN (22 AWG) NOT USED 10 GROUND 2
S RED
L BLK
12 12 14 1 3
48VDC
BD. 15 2 3 AY10-004 QUEST
4
J12 16 J1 3 J6 J5 5
4 AY10-005 ODYSSEY.
5
6
6
1
2
3
4
5
6
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
9
DOOR GROUND A1P12 A5P1
7
7
8
STUD 8
1
2
3
4
5
6
7
8
9
9
A11P6
A11P5
9
AY51-049
AY51-062
A16P1
GREEN/YELLOW (16AWG) FILAMENT BD. GROUND GREEN/YELLOW (16AWG)
BLK (16AWG)
WHT (16AWG) AY51-048 OR AY51-090
SEE NOTE 8
BLACK (20AWG)
WHITE (20AWG)
AY51-018-XX
BLACK
YELLOW/GREEN
WHITE
BROWN
BLACK/RED
YELLOW/WHITE
AY51-012
MAIN GROUND
STUD
GROUND TO HV TANK GREEN/YELLOW (10AWG)
WHT
BLK
BLUE
RED A18,A1P5
F1 3.15A SB 440VAC IGBT DRIVE J5 1 IGBT DRIVE J5 1
AY51-058 (3X) AY51-007 R3 A,B 50 OHM BD,CATHODE 2 BD, ANODE 2
A L1 TB1 50W 3 3
WHT16AWG
BLK16AWG
J9
J8
J7
J6
J4
J3
J2
J1
J9
J8
J7
J6
J4
J3
J2
J1
F2 3.15A SB 440VAC R4 A,B 50 OHM 4 C13 4
LINE
LINE
LINE
+
BLK16AWG
B L2 50W C9 A19,A1P5
AY51-080
AY51-080
WHT
C L3 AY25-001 AY51-072 AY20-047 AY51-072
AY51-079
CB1
AY20-047
AY51-079
AMP/3P
C14 X-RAY TUBE
GRN/YEL (10AWG)
GRN/YEL (16AWG)
LOAD
LOAD
N L4 (SEE TUBE
50
+
6 ROTOR CHART
+
~ + ~ X-RAY TUBE ROTOR CONNECTION CHART
G2
G2
G1
G2
G2
G1
E2
E2
E2
E2
E1
E1
E1
E1
G1
G1
AY51-088 (3X) 5 +
8
FOR ROTOR D
NEUTRAL 3 + + 3 C15 3 + +3 TOSHIBA VARIAN DUNLEE
ROTOR CABLE
0 1 7
~ C11 ~ CONNECTION)
AY51-066
AY51-066
10 A19C1 A19C2 A18C1 A18C2 1- COMM. 5- COMM. OUTER- COMM.
9
- -
+
198 2
ORN
1 2
K2 BLU ~ - - 2 ~ 2 - - 2 2- MAIN 4- MAIN CENTER- MAIN
BRN
208 3 2
K1 A+ C-
YELLOW
AY20-146 R8 R9 R10
9
T1 PHASE A
DB2 C12 A19QB A19QA DB1 C16 A18QB A18QA 3- PHASE 3- PHASE INNER- PHASE
AY51-065
220 4 AY51-127 (4X) A19R1 A18R1
RED
AY51-065
+
+
3.3/50W ALUM. 220 5 1 1 1 1 5- T.S. 1- T.S. T.S.-1
D2
1N4005
220 5A
10
2
1
BRN
ORN
BLU
D3
240 6
A19 POWER MODULE CATHODE A18 POWER MODULE ANODE C7
280 7 AY51-128 (4X) SEE C4 AY51-128 (4X)
C6 NOTES:
NOTE C3
0 1 1. C3, C4, C6 AND C7 1UF/1500VAC,
1
K3 BLK (10AWG) C5 AND C8 ARE NOT USED
AY51-075 (3X)
9
T1 PHASE B
1 1
2
1
D1 220 4 1 60 VAV 2 RED (16AWG) 2 60 VAV ROTOR MAIN 1 BLK 3. C9 THRU C16, 2400UF/450VDC
1N4005 5 AY51-016 0 VAC ORANGE (16AWG) 0 VAC ROTOR PHASE 2 RED
2 3 3
5A BLACK/RED 3 J3 4 A9J8 A9P8 4 ROTOR COMMON 3 WHT C 4. DISCONNECT A17P1-9 AND 10 AND CONNECT
220
220
TB2
6
24 VAC COLL.
TB1
1
COLL. 2
3
2
3 CHASSIS GRND
5
6 T.S. A (WARNING A17P1-9 AND 10 MUST BE CONNECTED
TO GROUND OR TO MAS METER.)
240
10
280
14
STAND
3 3 8 1
T1 PHASE C
16
4 9 2 REV F OR HIGHER
AY51-078 X3
AY51-023
4 5 3
AY51-090
AY51-015
3 16 0VAC BLK (16AWG) 0VAC 3 15VDC RTN 4 7. GENERATOR WITH UNIVERSAL AEC AND DIGITAL
15
6 4
208
WHT FIL.COMMON
RED FIL. SMALL
0VAC
28VAC BLK (16AWG) 28VAC COLL. READY 4 TB3 TO -15VDC
ANODE FDBK
8
5 7 5 1.5KE68CA RECEPTOR, AY51-048 IS REPLACED WITH AY51-090.
CATH. FDBK
4 BLK (16AWG) 0VAC 5 PREP 1 1
ANODE RTN
SHIELD 7
8 DIGITAL -15VDC RTN 6
CATH. RTN
220 5 28VAC BLK (16AWG) 28VAC +15VDC 6 PREP 2 2 24VDC A17
MA FDBK
BLK FIL. L.
6 9 7
MA RTN
15 0VAC BLK (16AWG) 0VAC GROUND 7 RECP. RDY 3 RECEPTOR 24VDC
AY51-043
FIL. SHLD
10 8
5A 0 1 7 7VAC BLK (16AWG) 7VAC TO PREP RDY 1 4 TABLE 24VDC RTN AY30-031
YELLOW
AY51-012
280 7 115 VAC 1 BUCKY EXPOSE 2 7
1
2
3
1
2
3
4
5
6
7
8
9
220
A10P5
4 6 BUCKY W. ON 2 DR RDY RAD 8
9 19 A9P4 J4 115 VAC RTN 3 HV ON 1 9
20 4 HV ON 2 10 SHLD
10
AY51-021
220V IN CH. GND 5 24VDC 11 C1, 30 UF
EMI FLT 1
17 220V IN GND 6 24VDC RTN 12 (SEE
11 LOAD 18
2
60V ROTOR 7
AY51-017
AY51-017
3 NOTE
LINE 11 0V ROTOR BUCKY READY 8 TB7 SHLD
12 4
PREP 1 1 TO 2) AY51-090
A2P1
5
A11P10
A11P8
6 TO PREP 2 2
DIGITAL
RECP. RDY 3
WHITE
ORANGE
LINE
YELLOW
GRAY
WALL RECEPTOR
VIOLET
10 TB4 PREP RDY 1 4
BROWN
BLUE
GREEN
LOAD
AY51-020
1
2
3
4
5
6
1 BUCKY
1
2
3
4
5
6
7
8
9
1
2
3
4
5
6
7
8
9
GRN/YEL (16AWG) BLK (16AWG) 115 VAC PREP RDY 2 5 WALL
GRY
RED
BLU
9 WHT
BRN
YEL
GND
VIO
BLK (16AWG) A9P5 J5 BUCKY W. ON 2 EXPOSE 1 6
J1
A11P11
1
2
3
4
5
6
7
8
9
1
2
3
4
5
6
7
8
9
BLK (16AWG) 115 VAC RTN 3 EXPOSE 2 7
1 GRD A11P12
MA RTN
1
2
3
4
5
6
7
8
MA SENSE
ANODE RTN
A1P8
CATH RTN
4 8
ANODE FDBK
BLK (16AWG) 220V OUT DR RDY RAD 18VDC J10 J8 AEC J12
CATH FDBK
1 2 1 1
BLK (16AWG) 0 VAC OUT GROUND 5 HV ON 1 9 A AEC TABLE 1
INCOM. LINE
INCOM. LINE
2 3 2 2 WALL 1 1
1
2
3
4
5
6
7
8
9
1
2
3
4
5
6
7
8
9
BLK (16AWG) 120 VAC 24 VDC RTN 6 HV ON 2 10 B 2
3 4 3 3 2
BLK (16AWG) 0VAC 24 VDC 7 24VDC 11 J10 J8 1 AEC 3
4 1 4 4 3
2 4
MASTER
A8P3 5 BUCKY READY 8 24VDC RTN 12
2 A2P7 J7 5 5 4
WALL
RS 232
J3 PHASE N. BLK 3 5
PORT
8 5 6 3 6 6 5
PHASE C,IN PHASE A BLK AY40-034 D.R. RS 232 4 2 6
3 2 4 7 7 6
PHASE A,IN A6P1 A9P2 J2 J6 A9P6 J4 SLAVE 5 A2P8 J8 7
10 3
AY51-005 CONFIGURATION SEE NOTE 5 5
6
8 8 7
8
PHASE B BLK AY40-005T J1 PORT GROUND
YELLOW/WHITE
5 4 6 1 9 9 8
A6, POWER 32VAC 1 WHITE (16AWG) 1 32VAC RED 24VDC 7 18 VDC 9
1 1 1 1 1 1 7 2 10 10 9
32VAC RTN 2 BLACK (16AWG) 2 32VAC RTN GREEN/YELLOW 24VDC RTN 8 OUTPUT A
RED/GREEN
SUPPLY BD.
BLK
6 6 2 2 2 2 8 3 11 11 A11P13
AY51-022-3P
7 7 3 3 3 3 9 4 12 12
15VAC RTN 4 BLUE 4 15VAC RTN GREEN/YELLOW GROUND J11 J13 1
2 8 4 4 4 4 5 13 13 1
11VAC 5 RED 5 11VAC BLUE BUCKY TABLE 2
4 5 5 5 5 14 14 2
9 11VAC RTN 6 BROWN/YELLOW 6 11VAC RTN VIOLET BUCKY WALL 15VDC J4 A2P4 J11 3
6 6 6 6 1 3
BLACK(20AWG)
WHITE(20AWG)
7 7 7 7 2 1 4
BLUE(20AWG)
A8P6 J6 J5 A8P5 28VAC RTN 8 BLACK/RED 8 28VAC RTN WHITE/BLACK COLLIMATOR READY 15VDC RTN 15VDC J3 A2P3 5
8 8 8 8 3 2 1 1 5
24VRTN K2 DOOR YELLOW/WHITE BUCKY T. READY 15VDC RTN 15VDC RTN 6
4 9 9 4 3 2 2 6
24V K2 15VDC BLACK/RED BUCKY W. READY -15VDC 15VDC RTN 7
3 1 INTERLOCK 10 10 5 4 3 3 7
24VRTN K3 15VDC 48VDC 1 TB6 GREY/WHITE DOOR INTERLOCK -15VDC 8
2 2 1 11 11 -15VDC RTN 6 5 4 4 8
24V K3 15VDC RTN 48VDC 2 1 DOOR BLUE/YELLOW SPARE 24VDC -15VDC RTN 9
1 3 2 12 12 7 6 5 5 9
15VDC RTN 48VDCRTN 3 2 DOOR RTN GREY TABLE RDY 24VDC 24VDC
4 3 13 13 8 7 6 6 A11TB10
AY51-009-3P -15VDC 48VDCRTN 4 GREEN/BROWN K2, 24VDC 24VDC RTN 24VDC
5 4 14 14 9 8 7 7
VA+/2.4K -15VDC RTN 30VDC 5 X - RAY ON BROWN EXPOSE 24VDC RTN 24VDC RTN TB10 1 24VDC
1 6 5 15 15 10 9 8 8
24VDC 30VDC 6 TB5 GREEN PREP RDY J9 A1P9 24VDC RTN AY40-027S 2 PREP
2 7 6 16 16 10 9 9
-15VDC RTN
7
15VDC RTN
15VDC RTN
24VDC RTN
24VDC RTN
24VDC
24VDC
WHT (16AWG)
5 10 9 19 19 1 12 12 TABLE
WHT (20AWG)
BLK (16AWG)
10 2
BLK (20AWG)
6 10 20 20 RS-485 2 13 13
3
WHT/BLK
RED(20AWG)
10 28VDC 6
7
10
11 1 GND 7
BLUE(20AWG)
10
VC- WHT/BLK 33VDC RTN A1, CPU BD. 2 PREP
A2P6
1
2
3
4
5
6
7
8
9
12 2 28VDC 8
BLUE(20AWG)
AY51-019-2
4
SEE NOTE 6 J5 A1P1 STAND
24VDC RTN
RED
1 5
WHT
ORN
GRN
BLU
GRY
BRN
BLK
AY51-013
YEL
VIO
J4 A8P4 J1 2 TB1 6 GROUND 1
A1P2 J2 1 1
AY51-011 3 300VDC 2
A5P2
2 2
BROWN (22 AWG) V SENSE A 4 3 TO OCP ASSEMBLY
1 1 3 3
1
2
3
4
5
6
7
8
9
10
RED (22 AWG) V SENSE C TB11 A11TB11 4
2 2 4 4 AY10-004 QUEST
R1A, R1B ORANGE (22 AWG) GROUND 1 .4S 5
3 3 5 A11P7 5 AY10-005 ODYSSEY
R2A, R2B YELLOW (22 AWG) 24VDC J2 J7 2 .6S 6
4 4 6 1 6
1.2K/50W GREEN (22 AWG) AUTO SHUT OFF AY40-007T TOMO 3 .8S 7
5 5 7 2 7
BLUE (22 AWG) SYSTEM ON A5 FILAMENT.BD. 4 1.2S 8
6 6 8 3 SWEEP 9
8
DOOR GROUND 7 VIOLET (20 AWG) 7 24VDC MAG. 9 4
5 2S 9
8 GREY (20 AWG) 8 24VDC MAG. RTN 10 5
TIME 6 A16P1
AY40-022T-3 WHITE (22 AWG) MISSING PHASE 7
9 9 11 6
A8, LINE 10 BLACK (22 AWG) 10 FAULT RESET 12
8
48VDCRTN
BLACK/ORANGE (22 AWG) NOT USED A11P1 9
GROUND
MONITOR 11 11 13
J1
C WHT
WHITE/BROWN (22 AWG) NOT USED 10 GROUND
S RED
L BLK
12 12 14 1
48VDC
BD. 15 2
J12 16 J1 3 J6 J5
AY51-018-XX
1
2
3
4
5
6
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
9
A1P12 A5P1
1
2
3
4
5
6
7
8
9
A11P6
A11P5
AY51-049
GREEN/YELLOW (16AWG) FILAMENT BD. GROUND GREEN/YELLOW (16AWG)
BLK (16AWG) AY51-062
WHT (16AWG) AY51-048 0R
AY51-048
BLACK (20AWG)
AY51-090 SC50-051T REV. E
WHITE (20AWG) SEE NOTE 7
BLACK
YELLOW/GREEN
WHITE
BROWN
BLACK/RED
YELLOW/WHITE
AY51-012
5 380V BLK
STUD SEE TUBE
4 220V BLK
TOSHIBA VARIAN DUNLEE
3 120V BLK
GROUND TO HV TANK GREEN/YELLOW (10AWG) CHART #1
2A 80V BLK
WHITE 1- COMM. 5- COMM. OUTER- COMM.
2 60V BLK
FOR ROTOR
ROTOR CABLE
BLACK
1 0V BLK
BLUE CONNECTION 2- MAIN 4- MAIN CENTER- MAIN
RED IGBT DRIVE J5 1
AY51-058 (3X) F1 3.15A SB 440VAC BD,CATHODE 2 IGBT DRIVE J5 1
3- PHASE 3- PHASE INNER- PHASE
AY51-007 R3 A,B 50 OHM 3 BD, ANODE 2 C- A+
J9
J8
J7
J6
J4
J3
J2
J1
A L1 50W 5- T.S. 1- T.S. T.S.-1
TB1
4 3
LINE
LINE
LINE
J9
J8
J7
J6
J4
J3
J2
J1
WHT16AWG
F2 3.15A SB 440VAC R4 A,B 50 OHM A19,A1P5 C13
BLK16AWG
50 AMP/3P
4
6- T.S. 2- T.S. T.S.-2
CB1
B L2 50W C9 AY51-088 (2X)
SEE NOTE 1
AY20-047
AY25-001
A18,A1P5
AY51-080
WHT
+
C L3
BLK
AY20-047
SEE NOTE 1
AY51-080
LOAD
ORANGE
4 AY51-088
LOAD
LOAD
C14
A20,A2TB4
GRN/YEL (10AWG)
GRN/YEL (16AWG)
GRN/YEL (16AWG)
WHITE
BLACK
BLACK
3 C10
N L4 0 (2X)
RED
1 6
+
~ +
G2
G2
G1
E2
E1
G1
E2
E1
AY51-088(3X) 5 AY51-079 AY51-079 SEE MANUAL
+
~ +
G2
G2
G1
E2
G1
E2
E1
E1
198 2 8 3 + +3 C15
PHASE A
7
6
5
4
3
2
1
1
2
3
4
5
6
1
2
7 C11
208 3 10
~ 3 + +3
+
~ A19C1 A19C2 A20,A2TB1 A20,A2TB2
AY51-066
ORN
9
+
A18C1 A18C2
BRN
BLU
K2 220 4 1 2 AY51-065 C16 NOTES:
- - 2 ~ - TB1 TB2 TB4
COMM.
9
PHASE
TEMP.
TEMP.
220 5 AY51-065
MAIN
AY51-127 2 C12 2 2
~ - - -
+
A19QB A19QA DB1
(4X)
T1
AY20-146 R8, R9
240 6
+
K1 DB2 A18QB A18QA
J3 3
AY51-066
D3 1 1 WHT/BLK 2. C3, C6 1uF/1500V, C4,C7 .5uF/1500V
10
2
2
1
D2 ORN 285 7
BLU
5 220
BLK (10AWG) BLK (10AWG) 4
K3 AY51-141(2X) (2X) 4. DISCONNECT A17P1-9,-10 AND CONNECT
9
1 J4 5
J1 J2
AY51-069
PHASE B
A2TB3
SEE CONNECTED TO GROUND OR TO MAS METER)
10
12
13
14
11
10
(6X)
1
2
3
4
5
1
2
3
4
5
6
7
8
9
1
2
3
4
5
6
2
1
D1 C2A
A20
208 3 A9P8 C4
1N4005 A9P7 C6 NOTE 5. AY40-062T INTERFACE BOARD IS USED ON
J7 J3 J8 1 1 BRN 12uF
220 4 220VAC 2 2 C3 Q-HSS DIGITAL GENERATOR ONLY, Q-HSS
1 1 2
AY51-146
440V
WHT/ORN
WHT/BRN
WHT/RED
AY51-016
WHT/YEL
3
ORANGE
ORANGE
YELLOW
NON DIGITAL GENERATOR USE AY40-061T.
BLACK
2 2 3
YELLOW
AY51-130
AY51-131
BROWN
BROWN
GREEN
220
GREEN
VIOLET
5A BLACK/RED 0VAC 4 YEL
BLACK
RED
WHITE
3 3 4
GREY
BLUE
T1 GREY/WHITE TO 5
RED
RED
TB2
BLK
4 5
240 6 TB1 6 BLU 6. AY51-019-2 IS USED FOR AEC OPTION
COLL. 6
1 T2
9 24 VAC COLL. 1 7 7 VIO PC1 PC2 PA1 PA2 ONLY, NON AEC GENERATORS USE
7 A9P1 J1 24 VAC RTN 2 8 GRY
2 8 AY51-019-1.
285
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
9
1
2
3
4
5
6
10
12
13
14
11
GROUND 3 9 9 WHT A20,A1P3 A20,A1P4 A20,A1P5
3
0
8
32VAC BLK (16AWG) 1 32VAC TO C 7. USE CABLE AY51-151 CABLE FOR
1 32VAC RTN BLK (16AWG) 2 0VAC TUBE TB3 TO J3 J4 J5
16 BLK (16AWG) PREP 1 INTERFACING TO RS-580 SYSTEM:
4 2
16VAC
16VAC RTN BLK (16AWG)
3
4
16VAC
0VAC 24 VDC
TB2
1 STAND PREP 2
1
2
DIGITAL A C2B - CONNECT WIRES FROM P81-7,-8 TO P2-1
RECEPTOR 10
AY51-134 (3X)
PHASE C
11VAC BLK (16AWG) 11VAC 24 VDC RTN 2 RECP. RDY 3 9 - CONNECT WIRES FROM P81-4,-5 TO P2-2
AY51-023
SEE NOTE 4
AY51-015
12uF
198
5
5 3 BLK (16AWG) 6 0VAC 3 PREP RDY 1 4 TABLE - CONNECT WIRE FROM P81-4 TO GND
15 BLK (16AWG) 24VAC COLL. READY 4 PREP RDY 2 5 6 J1 1.5KE68CA 440V
6 208 0 1
7
EXPOSE 1 - CONNECT WIRE FROM P81-1 INTERFACE
BLK (16AWG) 0VAC 5 6 5 AY40-035S HSS
YELLOW (20AWG)
8 BOARD A9TB1-2
(20AWG)
BLU FDBK
CONTROL BD.
14
9
7 220 2A DR RDY RAD - CONNECT WIRE FROM P81-2 TO INTERFACE
GRN RTN
RED FDBK
5 80 BLK (16AWG) 0VAC GROUND 7 8 1 A20 Q-HSS
WHT FIL.COM. 16
10
220 5A BLK (16AWG) HV ON 1 A20, A1 BOARD A9TB1-1
BRN RTN
7VAC TO 9 3
T1
11VAC RTN
11
8 240 120 3 HV ON 2 AY20-177
ORN RTN
6 BLK (16AWG) 0VAC 10 4 J1 J2 - CONNECT WIRE FROM P81-3 TO INTERFACE
15
12 TABLE
RED FIL.SMALL
24VAC RTN
24VAC RTN
TB3 24VDC 11
8
BOARD A9TB1-3
YEL FDBK
9
SHLD 7
220 4 BUCKY 24VDC RTN
RED
BLK FIL.L.
7VAC RTN
FOR SYSTEMS OTHER THAN RS-580 CONSULT
24VAC
24VAC
285 BUCKY W. ON 2
A17
10
7VAC
1
2
3
4
5
6
7
8
9
1
2
3
4
5
6
7
8
9
AY51-089
10
FIL.SHLD
380 5 6 115 VAC RTN 3 TB4 RESPECTIVE MANUALS
19 4 PREP 1 1 TO AY20-031
11 HV MODULE
WHT
ORN
RED
PREP 2
GRY
BRN
BLU
20
GRN
CH. GND 5 2
YEL
VIO
EMI DIGITAL AY51-012-1
GND 6 RECP. RDY 3
INCOM. LINE
INCOM. LINE
LOAD
LINE
WHT
GRN
GRY
BRN
WHT
ORN
GRN
BLU
RED
GRY
YEL
BRN
VIO
BLU
VIO
BLK (16AWG) 115 VAC RTN 3 24VDC RTN 12 A1P8 SHIELD
1
2
3
4
5
6
1
2
3
1
BLK (16AWG) 1 220V OUT 4 A11P5
BLK (16AWG) 2 0 VAC OUT GROUND 5 X - RAY ON J1 J5
1
2
1
3
4
5
6
7
8
9
1
1 1
1
2
3
4
5
6
7
8
9
BLK (16AWG) 3 115 VAC 24 VDC RTN 6 TB5 1
MA RTN
BLK
ANODE FDBK
MA SENSE
2 2
ANODE RTN
P1-N
CATH RTN
P1-L
CATH FDBK
A8P3 BLK (16AWG) 4 0VAC 24 VDC 7 X-RAY ON RTN 2 J10 RS 232 J8 1 3 3 3
J3 BUCKY READY 8 X-RAY ON 3 MASTER 2 4
AY51-020
4 4
PHASE N. BLK PORT
AEC TABLE
8 5 3 5 5 5
3 PHASE C,IN PHASE A 2
BLK AY40-062T D.R. RS 232 4 6 6 6
10 PHASE A,IN 3 A6P1 A9P2 J2 J6 A9P6
CONFIGURATION SEE NOTE 5 SLAVE 5 A2P7 J7 7 7 7
PHASE B AY40-005T J1 AY51-005 PORT 6 GROUND 8
YELLOW/WHITE
5 4 1 8 8
1 1 A6, POWER 32VAC 1 WHITE (16AWG) 1 32VAC 1 RED 1 24VDC 7 2 +18 VDC 9 9 9
BLK
32VAC RTN BLACK (16AWG) 32VAC RTN GREEN/YELLOW 24VDC RTN 8 OUTPUT A EL68-007
RED/GREEN
AY51-022-3P
6 6 SUPPLY BD. 2 2 2 2 3 10 10
PHASE C 15VAC BLUE 15VAC BLACK 28VDC OUTPUT B A11P2
ORN/BLK
9
BRN/YEL
7 7 3 3 3 3 4 11 11 OPTIONAL POWER
2 8 15VAC RTN 4 VIOLET 4 15VAC RTN 4 GREEN/YELLOW 4 GROUND J11 12 12
4 11VAC 5 RED 5 11VAC 5 BLUE 5 BUCKY TABLE AY40-003S 13 13 J2 1 SUPPLY (28VDC/8
9 J5 A8P5 11VAC RTN 6 BROWN/YELLOW 6 11VAC RTN 6 VIOLET 6 BUCKY WALL 15VDC 1 A2, KVP BD. 14 14 2 AMP)
BLACK(20AWG)
WHITE(20AWG)
AY51-012-1
24VAC BLUE/YELLOW 24VAC WHITE PREP 15VDC J4 A2P4 A11P1 J1
BLUE(20AWG)
7 7 7 7 2 3
RED(20AWG)
A8P6 J6 24VAC RTN BLACK/RED 24VAC RTN WHITE/BLACK COLLIMATOR READY 15VDC RTN A2P8 J8 4
AEC WALL 1
8 8 8 8 3
4 24VRTN K2 9 YELLOW/WHITE 9 BUCKY T. READY 15VDC RTN 4 1 GROUND J3 A1P3 A11P4
J4 5
24V K2 15VDC DOOR BLACK/RED BUCKY W. READY -15VDC +18 VDC
3 1 10 10 5 2 1 1 6
2 24VRTN K3 15VDC 2 48VDC 1 INTERLOCK TB6 11 GREY/WHITE 11 DOOR INTERLOCK -15VDC RTN 6 3 OUTPUT A 2 2 7
1 24V K3 15VDC RTN 3 48VDC 2
1 DOOR 12 BLUE/YELLOW 12 SPARE 24VDC 7 4 OUTPUT B 3 3 8
AY51-009-3P 15VDC RTN 4 48VDCRTN 3
2 DOOR RTN 13 GREY 13 TABLE RDY 24VDC 8 5 4 4 9
-15VDC 5 48VDCRTN 4 14 GREEN/BROWN 14 K1, 24VDC 24VDC RTN 9 5 5
-15VDC RTN 28VDC X- BROWN EXPOSE 24VDC RTN A2P5 J5
6 5 15 15 10 6 6 A11P3
24VDC 7 28VDC 6 RAY ON TB5 16 GREEN 16 PREP RDY J9 A1P9 1 15VDC 7 7 J3
-15VDC RTN
GRN/YEL
15VDC RTN
15VDC RTN
24VDC RTN
24VDC RTN
(OPTIONAL)
2
BLK (20AWG)
BLACK/RED
AY40-031S
3
15VDC
15VDC
24VDC
24VDC
10 9 19 19 1 4 10 10
AEC WALL 2
15VDCRTN GREEN/ORANGE GROUND RS-485 2 -15VDC
WHT/BLK
AY51-007 4
WHT/BLK
1
10 20 20 2 5 11 11
VA+/2.4K J2 A8P2 J3 AY40-061T SEE NOTE 5 AY51-008 RS-485 3 -15VDC RTN +
1 J4 3 6 12 12 5
J2 A6P3 A9, INTERFACE BD. A1P4 EXP. 4 24VDC _
2 4 7 13 13 6
RED 2.4K PREP 5 24VDC
RED
3
J3 5 8 14 14 7
28VDC 6 24VDC RTN
4 A1P3 6 9 15 15 8
VA - A6P2 BLACK/RED 28VDC GND 7 24VDC RTN J6 SEE NOTE 7
10
9
1
2
3
4
5
6
7
8
9
5 1 7 10 16 16
WHT/BLK 28VDC RTN 28VDC 8
6 2 8
GND 9
7 3 AY40-006S 9
VC+/2.4K AY51-047-1 J5
10
A1P6
A1, CPU BD.
1
2
3
4
5
6
7
8
9
8 4
SEE NOTE 6
9
A1P1
AY51-013
2.4K J4 A8P4 (LOGIC BD.) J1
WHT
RED
ORN
GRN
GRY
BRN
10 1
BLU
YEL
BLK
AY51-011
VIO
A1P2 J2
AY51-018-XX
11 2
VC- BROWN (22 AWG) V SENSE A
A5P2
12 1 1 3
1
2
3
4
5
6
7
8
9
10
A8P1 J1 ORANGE (22 AWG) GROUND
BLUE
4 4 6
AY40-053S3 5 GREEN (22 AWG) 5 AUTO SHUT OFF 7 1 BLK L
A8, LINE BLUE (22 AWG) SYSTEM ON RED S
AY51-019-2
6 6 8 2
CONTROL BD.
A5, FILAMENT
7 VIOLET (20 AWG) 7 28VDC MAG. 9 3 WHT C
MONITOR BD. GREY (20 AWG) 28VDC MAG. RTN GROUND
AY40-007T
8 8 10 4
R1A, R1B 9 WHITE (22 AWG) 9 MISSING PHASE 11 5 A16P1
R2A, R2B BLACK (22 AWG) FAULT RESET 1
10 10 12 6 1
1.2K/50W BLACK/ORANGE (22 AWG) NOT USED 2
11 11 13 7 48VDC 2
WHITE/BROWN (22 AWG) NOT USED 3
12 12 14 8 48VDCRTN 3
4
15 4
5
DOOR GROUND 16 5
AY51-018-XX 6
6
AY51-012-1 7
7
BLK (16AWG) 8
8
WHT (16AWG) 9
9
GREEN/YELLOW (16AWG) FILAMENT BD. GROUND GRN/YEL (16AWG)
GREEN/YELLOW (16AWG)
1
NOT USED, TIE
SC50-071T REV. B
2
3 BACK
2A 80V BLK
3 120V BLK
4 220V BLK
5 380V BLK
ROTOR CABLE
2 60V BLK
BLACK
1 0V BLK
BLUE CONNECTION 3- PHASE 3- PHASE INNER- PHASE
RED IGBT DRIVE J5 1 5- T.S. 1- T.S. T.S.-1
AY51-058 (3X) TB1 BD,CATHODE 2 C- A+
AY51-007 F1 3.15A SB 440VAC IGBT DRIVE J5
R3 A,B 50 3 1 6- T.S. 2- T.S. T.S.-2
A L1 C13
J9
J8
J7
J6
J4
J3
J2
J1
4 BD, ANODE 2
OHM 50W C9
LINE
LINE
LINE
A19,A1P5 3
WHT16AWG
BLK16AWG
+
F2
J9
J8
J7
J6
J4
J3
J2
J1
B L2 R4 A,B 50
SEE NOTE 1
4
SEE NOTE 1
50 AMP/3P
+
AY20-047
GREEN/YELLOW (16AWG)
BLK16AWG
OHM 50W
A20,A2TB4
ORANGE
A18,A1P5
C L3
CB1
GREEN
WHITE
BLACK
AY51-080
AY51-080
3.15A SB C10
LOAD
LOAD
LOAD
440VAC AY20-047
RED
4 AY51-088 (2X) C14
WHT
N L4
GRN/YEL (10AWG)
GRN/YEL (16AWG)
G1
G2
NOTES:
G2
G1
E2
E1
E2
E1
0 1 6 AY51-079
+
AY51-088
AY51-079
7
6
5
4
3
2
1
1
2
3
4
5
6
1
2
5
+
(3X) 3 + +3 ~ +
G2
E1
G1
E2
1. C9 THRU C16, 2400uF/450VDC.
G2
E1
G1
E2
198 2 8
~ + A20,A2TB1 A20,A2TB2
PHASE A
AY51-066
7 A19C1 A19C2 3
208 3 10
+ +3 2. C3, C6 1uF/1500V, C4,C7 .5uF/1500V
~ C15 TB1 TB2 TB4 C5 AND C8 ARE NOT INSTALLED
AY51-066
C0MM.
PHASE
TEMP.
TEMP.
9
MAIN
YELLOW
ORN
K2 BRN ~ C11 2
- - 2 A18C1 A18C2
BLU
4 1 A20,A2P3
+
3. C1 COULD CHANGE DEPENDING ON TUBE
RED
5 2
+
K1 A19QB A19QA ~ - 2 - - 2 3
WHT/BLK MODEL AND MANUFACTURER. (SEE TUBE DATA
3.3/50W ALUM.
~ - A19R1
5
5A
J3 2
T1
C12 1 1 DB1 A18QB A18QA AY40-036S HSS BLACK/RED BASE)
10
1
2
1
AY51-127
240 6 C16 A18R1
D2 DB2 DRIVER BD. C1 25uF/440V
(4X)
AY51-065
AY51-065
1N4005
BRN
ORN
+
1 1
BLU
1N4005 7 A20, A2 1 SEE NOTE 3 4. DISCONNECT A17P1-9 AND -10 AND CONNECT
+
A19 TB3
D3
AY51-088 POWER MODULE CATHODE THE MAS METER TO THESE WIRES.
285 2
(X2) (WARNING A17P1-9 AND -10 MUST BE
220
220
BLK (10AWG) A18 POWER MODULE ANODE 3
BLK (10AWG) 4 CONNECTED TO GROUND OR TO MAS METER.)
BLK (10AWG) J1 J4 5
J2 5. AY40-062T INTERFACE BOARD IS USED ON
5 220
0
K3
285
AY51-069
9
A2TB3
AY51-141 AY51-128 (4X)
10
12
13
14
11
NON DIGITAL GENERATOR USE AY40-061T.
(6X)
1
2
3
4
5
1
2
3
4
5
6
7
8
9
1
2
3
4
5
6
C2A
A20
198 2 (2X) C7 SEE NOTE 2 AY51-141
PHASE B
A9J8 A9P8 12uF
10
208 3 1 BRN C6 C4
1 440V
AY51-146
WHT/ORN
1N4005 A9P7
WHT/BRN
WHT/RED
AY51-062 IS REPLACED WITH AY51-008 AND
WHT/YEL
J7 J3 2
ORANGE
ORANGE
C3
YELLOW
YELLOW
BLACK
2
AY51-130
AY51-131
BROWN
220 4
BROWN
VIOLET
GREEN
3
GREEN
220VAC
WHITE
BLACK
AY51-090 IS REPLACED WITH AY51-089.
RED
1 1 3
GREY
BLUE
4 YEL
RED
RED
5A
BLK
2 2 4 NON DIGITAL GENERATOR WITH TOMO OPTION
BLACK/RED 3 0VAC 3 5 5
6 GREY/WHITE 6 BLU AY51-090 IS REPLACED WITH AY51-048.
T1
T2 4
TB1 TO COLL. 7
6
VIO
240
220
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
9
1
2
3
4
5
6
10
12
13
14
11
9 AY51-016 24 VAC COLL. 1 8 8 GRY PC1 PC2 PA1 PA2 A20,A1P3 A20,A1P4 A20,A1P5
1 7 A9P1 J1 24 VAC RTN 2 9 9 WHT 7. USE CABLE AY51-151 CABLE FOR
GROUND 3 J4 J5 INTERFACING TO RS-580 SYSTEM:
J3
2 0 1 32VAC BLK (16AWG) 1 32VAC TB3 TO C - CONNECT WIRES FROM P81-7,-8 TO P2-1
8 0VAC BLK (16AWG) 0VAC TO TUBE PREP 1 1 C2B - CONNECT WIRES FROM P81-4,-5 TO P2-2
3 2 DIGITAL
2 16 16VAC BLK (16AWG) 3 16VAC TB2 STAND PREP 2 2
RECEPTOR A 12uF - CONNECT WIRE FROM P81-4 TO GND
PHASE C
AY51-023
AY51-015
5 BOARD A9TB1-2
0VAC BLK (16AWG) 6 0VAC 3 PREP RDY 2 5
CONTROL BD.
5 220 4 15 24VAC BLK (16AWG) 24VAC COLL. READY 4 EXPOSE 1 6 6 - CONNECT WIRE FROM P81-2 TO INTERFACE
GRN RTN
220 5A 60 2 BLK (16AWG) 24VAC +15VDC 6 DR RDY RAD 8 2 A20 Q-HSS - CONNECT WIRE FROM P81-3 TO INTERFACE
BLU FDBK
14
9
2A
RED FDBK
80 BLK (16AWG) 0VAC GROUND 7 HV ON 1 9 1
T1
BOARD A9TB1-3
16
10
7 6 AY20-177
BRN RTN
240 BLK (16AWG) 7VAC TO HV ON 2 10 3 J1 J2
YELLOW
ORN RTN
120 4
24VAC
3 BLK (16AWG) 0VAC 24VDC 11
0VAC
0VAC
TABLE
15
12
8 7 TB3 24VDC RTN 12 A20,A1P1 A20,A1P2 RESPECTIVE MANUALS
8
RED
7
1.5KE68CA
YEL FDBK
AY51-134
BUCKY
10
7VAC
0VAC
1
2
3
4
5
6
7
8
9
1
2
3
4
5
6
7
8
9
9
WHT FIL.COM.
BUCKY W. ON 2 TB4 A17
SHLD
BLK FIL. L.
380 5 6 115 VAC RTN 3 PREP 1 1 TO
FIL. SHLD
RED
ORN
10 AY20-031
WHT
BRN
GRN
GRY
YEL
19
BLU
4 PREP 2 2
VIO
EMI DIGITAL
20 CH. GND 5 RECP. RDY 3 HV MODULE AY51-012-1
INCOM. LINE
INCOM. LINE
LOAD
LINE
A11P8
TB2 WALL HV ON 1 9
A11P10
GRN/YEL (16AWG) TB4 HV ON 2 10
1 BUCKY
A2P1
10 SHLD
GRY
115 VAC 24VDC 11 AY51-021
WHT
BRN
YEL
BLU
A1P10
VIO
BLK (16AWG) A9TB8 TB8 BUCKY W. ON 2 24VDC RTN 12
WHT
BRN
RED
ORN
1
2
1
2
GRN
BLU
GRY
3
4
5
6
7
8
9
3
4
5
6
7
8
9
YEL
VIO
1
2
3
4
5
6
1
2
3
1
BLK (16AWG) 115 VAC RTN 3 A1P8 A11P12
1
2
3
4
5
6
7
8
9
BLK (16AWG) 1 220V OUT 4 X - RAY ON GND J10 J8 AEC J12
1
1 1 1
BLK (16AWG) 2 0 VAC OUT GROUND 5 TB5 1
2 18VDC 2 2 AEC TABLE 1
WALL
P1-N
1
2
3
4
5
6
7
8
9
1
2
3
4
5
6
7
8
9
P1-L
BLK (16AWG) 3 115 VAC 24 VDC RTN 6 X-RAY ON RTN 2 A
MA RTN
MA SENSE
ANODE RTN
2
CATH RTN
ANODE FDBK
3 3 3
CATH FDBK
BLK (16AWG) 4 0VAC 24 VDC 7 X-RAY ON 3 J10 RS 232 J8 1 B 1 AEC
BLK
BLK
A8P3 1 4 4 4 3
J1
J3 BUCKY READY 8 MASTER 2
2 5 5 WALL 4
AY51-020
PHASE N. BLK AY40-062T D. R. PORT 3 A2P7 J7
8 5 3 6 6 5
PHASE C,IN PHASE A BLK RS 232 4 2
3 2 CONFIGURATION SEE NOTE 5 4 7 7 6
PHASE A,IN A6P1 A9P2 J2 J6 A9P6 SLAVE 5
10 3 AY51-005 5
A2P8 8 8 7
5 PHASE B 4 AY40-005T J1 PORT 6
6 J8 9 9 8 EL68-007
YELLOW/WHITE
6 6 2 2 2 2 8 2 11 11 A11P13
AY51-022-3P
7 7 3 3 3 3 9 3 12 12
BRN/YEL
4 BLUE 4 YELLOW/GREEN
AY51-009-3P
8 BLACK/RED 8 WHITE/BLACK
BLUE(20AWG)
A8P6 J6 24VAC RTN 8 8 24VAC RTN 8 8 COLLIMATOR READY 15VDC RTN 3 1 15VDC J3 1 1 5
24VRTN K2 DOOR YELLOW/WHITE BUCKY T. READY 15VDC RTN 15VDC
4 9 9 4 2 2 2 6
24V K2 15VDC BLACK/RED BUCKY W. READY -15VDC 15VDC RTN
3 1 INTERLOCK 10 10 5 3 3 3 7
24VRTN K3 15VDC 48VDC TB6 GREY/WHITE DOOR INTERLOCK -15VDC RTN 15VDC RTN
2 2 1 11 11 6 4 4 4 8
24V K3 15VDC RTN 48VDC 1 DOOR BLUE/YELLOW SPARE 24VDC -15VDC
1 3 2 12 12 7 5 5 5 9
15VDC RTN 48VDCRTN 2 DOOR RTN GREY TABLE RDY 24VDC -15VDC RTN
4 3 13 13 8 6 6 6 A11TB10
-15VDC 48VDCRTN GREEN/BROWN K1, 24VDC 24VDC RTN 24VDC
AY51-007 -15VDC RTN
5 4 14
BROWN
14 9 7 7 7 P2-1 P2-2
1 VA+/2.4K 6 28VDC 5 X - RAY ON 15 15 EXPOSE 24VDC RTN 10 8 24VDC 8 8 TB10 1 24VDC
24VDC 28VDC TB5 GREEN PREP RDY J9 A1P9 24VDC RTN AY40-027S 2 PREP
1
2 7 6 16 16 9 9 9
RED 2.4K 24VDC 28VDCRTN 1 X-RAY ON RTN RED/GREEN 0VAC GRN/YEL 24VDC RTN A11, UNIVERSAL 3 EXPOSE +
-15VDC RTN
15VDC RTN
15VDC RTN
24VDC RTN
24VDC RTN
3 8 7 17 17 10 10 10
24VDC RTN 28VDCRTN 2 X-RAY ON ORANGE/BLACK 7.5VAC A1P5 TOMO 4 BUCKY RDY _
4 9 8 18
BROWN/YELLOW
18
1
11 11 AEC BD.
VA - 24VDC RTN 15VDC 15VDC A2P5 J5 5
-15VDC
5 10 9 19 19 OCP ON 1 12 12 TABLE
(OPTIONAL)
15VDC
15VDC
24VDC
24VDC
WHT (16AWG)
GREEN/ORANGE 2
WHT (20AWG)
15VDCRTN GROUND 6
BLK (20AWG)
6 10 20 20 2 13 13
BLACK/RED
BLACK/RED
7
J2 A8P2 J3 AY40-061T SEE NOTE 5 AY51-062 RS-485 3
3 AY40-003S 14 14
7 24VDCRTN
A1P4 J4 4
VC+/2.4K J2 A6P3 A9, INTERFACE BD. A2, KVP BD. 8 GROUND
WHT/BLK
WHT/BLK