INSTALLATION GUIDE

2.4 Inch TFT Terminal


Time Attendance & Access Control
1 2

Optional accessories Safety Precautions


The following precautions are to keep user s safe and prevent any damage.
Please read carefully before installation

Do not install the device in a place subject to direct sun


light, humidity, dust or soot.

Do not place a magnet near the product. Magnetic objects


such as magnet, CRT, TV, monitor or speaker may damage
Wiegand Card Reader Prox Card
the device.

Do not place the device next to heating equipment.

Be careful not to let liquid like water, drinks or chemicals


leak inside the device.

Do not let children touch the device without supervision.


FR1200 FP Reader K1-1 Exit Button
Do not drop or damage the device.

Do not disassemble, repair or alter the device.

Do not use the device for any other purpose than speci ed.

Door Lock Door Sensor


Clean the device often to remove dust on it. In cleaning, do
not splash water on the device but wipe it out with smooth
cloth or towel.

Contact your supplier in case of a problem.

2.4 Inch TFT Time Attendance & Access Control Terminal INSTALLATION GUIDE 2.4 Inch TFT Time Attendance & Access Control Terminal INSTALLATION GUIDE
3 4

Product PIN Diagram

RS485
8 pin Cable connectors
RS232
Wiegand Out
Camera
4 pin Cable connectors Ethernet (TCP/IP)
2.4-Inch Beep, LED
7 pin Cable connectors
TFT LCD Wiegand In
Power Out

RS485
}

Alarm
} AL+ } 485B } BEEP RJ45-6

Output

Ethernet
AL- 485A GLED RJ45-3
} NC1 } GND RLED RJ45-2

RS232 Wiegand Output

Wiegand In Power Out


Lock
COM1 TXD } IWD1 RJ45-1
NO1 RXD IWD0

2 pin Cable connectors Power In

Button Sensor Bell Auxiliary In


}
}
BUT
GND
} GND
WD1
} GND
+12V
SEN WD0

USB Storage
} BELL+
BELL-

Power In
} GND } GND
AUX +12V

Keypad Device Port Alarm


Reset Button Lock
12pin Cable connectors Exit Button
Doorbell & Door Sensor
LED Indicator Doorbell
Auxiliary In
Fingerprint
Sensor & Tamper alarm button
Card Reader

Speaker

RS485
AL+ }
Alarm
} } 485B } BEEP RJ45-6

Output

Ethernet
AL- 485A GLED RJ45-3
} NC1 } GND RLED RJ45-2

RS232 Wiegand Output

Wiegand In Power Out


Lock
COM1 TXD } IWD1 RJ45-1
NO1 RXD IWD0
Button Sensor Bell Auxiliary In

}
}
BUT
GND
} GND
WD1
} GND
+12V
Security Screw holes (for securing SEN WD0

the device onto the back plate) } BELL+


BELL-

Power In
} GND } GND
AUX +12V

2.4 Inch TFT Time Attendance & Access Control Terminal INSTALLATION GUIDE 2.4 Inch TFT Time Attendance & Access Control Terminal INSTALLATION GUIDE
5 6

Product Dimension Cables and Connectors


Digital input and Relay output
PIN DESCRIPTION WIRE
1 1 AL+ Red
2 AL- Black
3 NC1 Gray Alarm
4 COM1 Black Lock
5 NO1 White Exit Button
6 BUT Blue Door Sensor
7.34in
8.07in (186.5mm) 7 GND Red Doorbell
(205mm) 8 SEN Yellow Auxiliary In
9 BELL+ Orange
10 BELL- Green
11 GND Purble
12 12 Aux Brown

Wiegand output and RS485


PIN DESCRIPTION WIRE
3.39in 1.78in 3.0in 1 1 485B Yellow
(86mm) (45.1mm) (76.1mm) 2 485A Blue
3 GND Black
RS485
4 TXD Purple
RS232
5 RXD Gray
Wiegand Out
6 GND Black
7 WD1 White
8 8 WD0 Green

Wiegand input and Power out PIN DESCRIPTION WIRE


1 1 BEEP Brown
2 GLED Gray Beep
3 RLED Blue
LED
4 IWD1 Green
Wiegand Input
5 IWD0 White
Power Out
6 GND Black
7 7 +12V Red

Ethernet
8 PIN DESCRIPTION WIRE
1 7
1 RJ45-6 Black
6
5 2 RJ45-3 Red
4
3 RJ 45 3 RJ45-2 Green
TCP/IP
4 2
1 4 RJ45-1 Yellow

Power
PIN DESCRIPTION WIRE
1 1 GND Black
2 Power In
2 +12V Red

2.4 Inch TFT Time Attendance & Access Control Terminal INSTALLATION GUIDE 2.4 Inch TFT Time Attendance & Access Control Terminal INSTALLATION GUIDE
7 8

Mounting the device onto the Wall Power Connection


Fix the back plate onto the wall using wall mounting screws Without UPS

We recommend drilling the mounting plate screws

RS485
}

Alarm
} AL+ } 485B } BEEP RJ45-6

Output

Ethernet
AL- 485A GLED RJ45-3
} NC1 } GND RLED RJ45-2

RS232 Wiegand Output

Wiegand In Power Out


Lock
COM1 TXD } IWD1 RJ45-1
NO1 RXD IWD0

GND

Button Sensor Bell Auxiliary In


}
}
BUT
GND
} GND
WD1
} GND
+12V
SEN WD0

into solid wood (i.e. stud/beam). If a stud/beam


} BELL+
BELL-

Power In
} GND } GND
AUX +12V

cannot be found, then use the supplied drywall 2


plastic mollies (anchors). 12V DC
12V DC Adaptor

With UPS (Optional)

RS485
}

Alarm
} AL+ } 485B } BEEP RJ45-6

Output

Ethernet
AL- 485A GLED RJ45-3
} NC1 } GND RLED RJ45-2

RS232 Wiegand Output

Wiegand In Power Out


Lock
COM1 TXD } IWD1 RJ45-1

1
NO1 RXD IWD0

GND

Button Sensor Bell Auxiliary In


}
}
BUT
GND
} GND
WD1
} GND
+12V
SEN WD0
} BELL+
BELL-

Power In
} GND } GND
AUX +12V

2
12V DC

12V DC Adaptor

Recommended power supply


Inserting the device to backplate Use security screws to fasten the device to back plate 12V ± 10%, at least 500mA.
To share the power with other devices, use a power supply with higher
current ratings

2.4 Inch TFT Time Attendance & Access Control Terminal INSTALLATION GUIDE 2.4 Inch TFT Time Attendance & Access Control Terminal INSTALLATION GUIDE
9 10

Ethernet Connection
LAN Connection Direct Connection
1 1

4 4

RS485
}

Alarm
RS485

} } AL+ } 485B } BEEP


Alarm

} AL+ } 485B } BEEP RJ45-6 RJ45-6

Output
Output

Ethernet
RJ45-3
Ethernet

AL- 485A GLED RJ45-3 AL- 485A GLED


} NC1 } GND RLED RJ45-2 } NC1 } GND RLED RJ45-2

RS232 Wiegand Output


RS232 Wiegand Output

Wiegand In Power Out


Lock
Wiegand In Power Out
Lock

COM1 TXD } IWD1 RJ45-1 COM1 TXD } IWD1 RJ45-1

NO1 RXD IWD0 NO1 RXD IWD0

Button Sensor Bell Auxiliary In


Button Sensor Bell Auxiliary In

}
}
BUT
GND
} GND
WD1
} GND
+12V
}
}
BUT
GND
} GND
WD1
} GND
+12V

SEN WD0 SEN WD0


} BELL+
} BELL+
BELL- BELL-

Power In
Power In

} GND } GND } GND } GND


AUX +12V AUX +12V

Network Cable Adaptor Network Cable Adaptor

1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8

RJ 45
RJ 45

Ethernet Cable Ethernet Cable

PIN DESCRIPTION WIRE PIN DESCRIPTION WIRE


1 RJ45-6 Black 1 RJ45-6 Black
ZKBiosecurity 3.0 ZKBiosecurity 3.0
2 RJ45-3 Red 2 RJ45-3 Red
3 RJ45-2 Green 3 RJ45-2 Green
4 RJ45-1 Yellow 4 RJ45-1 Yellow

2.4 Inch TFT Time Attendance & Access Control Terminal INSTALLATION GUIDE 2.4 Inch TFT Time Attendance & Access Control Terminal INSTALLATION GUIDE
11 12

RS485 Connection
PC Connection

1 RS485 B
RS485 A
ZKBiosecurity 3.0 GND
RS485

}
Alarm

} AL+ } 485B } BEEP RJ45-6


Output

Ethernet

AL- 485A GLED RJ45-3


} NC1 } GND RLED RJ45-2
RS232 Wiegand Output

Wiegand In Power Out


Lock

COM1 TXD } IWD1 RJ45-1


NO1 RXD IWD0
Button Sensor Bell Auxiliary In

}
}
BUT
GND
} GND
WD1
} GND
+12V
SEN WD0
} BELL+
BELL-
Power In

} GND } GND
AUX +12V

PIN DESCRIPTION WIRE


1 485B Yellow
2 485A Blue
RS 485
3 GND Black
TXD Purple #1 BioPro SA30 #2 BioPro SA30 #63 BioPro SA30
4
5 RXD Gray
6 GND Black
7 WD1 White
8 WD0 Green

Do not use Incorrect RS 485 connections

x
RS485 B

485A

485A

485A
485B

485B

485B
GND

GND

GND
RS485 A PC PC
GND

Important Notes: RS 485

#1 BioPro SA30 #2 BioPro SA30 #63 BioPro SA30


1. RS485 communication wires should be a shielded and twisted pair cable.
2. RS485 communication wires should be connected in a bus cascade instead
of a star form, to achieve a better shielding e ect by reducing signal re ec-
tion during communications. x
RS485 B

485A

485A

485A
3. Adjust the communication speed as needed. The signal quality vary depend-

485B

485B

485B
GND

GND

GND
RS485 A PC PC PC
ing on wiring conditions, and it maybe necessary to lower the baudrates. GND

4. The GND Signal may be omitted if and only if the GND potential di erence
is less than ±5V RS 485

#1 BioPro SA30 #2 BioPro SA30 #63 BioPro SA30

2.4 Inch TFT Time Attendance & Access Control Terminal INSTALLATION GUIDE 2.4 Inch TFT Time Attendance & Access Control Terminal INSTALLATION GUIDE
13 14

RS485 Connection
FR1200 Connection System Settings
PIN DESCRIPTION WIRE PIN DESCRIPTION WIRE
1 BEEP Brown 1 485B Yellow
2 GLED Gray 2 485A Blue
3 RLED Blue 3 GND Black
4 IWD1 Green 4 TXD Purple
Do not use
5 IWD0 White 5 RXD Gray
6 GND Black 6 GND Black
7 +12V Red 7 WD1 White
8 WD0 Green

Select > Comm Select > Serial Comm


1

1
RS485

}
Alarm

} AL+ } 485B } BEEP RJ45-6


Output

Ethernet

AL- 485A GLED RJ45-3


} NC1 } GND RLED RJ45-2
RS232 Wiegand Output

Wiegand In Power Out


Lock

COM1 TXD } IWD1 RJ45-1


NO1 RXD IWD0
Button Sensor Bell Auxiliary In

}
}
BUT
GND
} GND
WD1
} GND
+12V
SEN WD0
} BELL+
BELL-
Power In

} GND } GND
AUX +12V

Select > RS232/485 Change > RS485 to (master unit)

DIP Settings
1. There are six DIP switches on the back of FR1200, switches 1-4 is for
RS485 address, switch 5 is reserved, switch 6 is for reducing noise on
long RS485 cable.
2. If FR1200 is powered from ProCapture terminal, the length of wire
should be less than 100 meters or 330 ft.
2008 FC R0HS
3. If the cable length is more than 200 meters or 600 ft., the number 6
switch should be ON as below

ON ON
Distance: More than 200 meters
1 2 3 4 5 6 1 2 3 4 5 6
FR1200

2.4 Inch TFT Time Attendance & Access Control Terminal INSTALLATION GUIDE 2.4 Inch TFT Time Attendance & Access Control Terminal INSTALLATION GUIDE
15 16

Lock Relay Connection


Device does not Share Power With The Lock Device Shares Power With The Lock

1 1
1

COM1 12V DC COM1 12V DC

GND
RS485

}
Alarm

} AL+ } 485B } BEEP RJ45-6

RS485
}

Alarm
AL+ 485B } BEEP
Output

} } RJ45-6

Output
Ethernet

AL- 485A GLED RJ45-3

Ethernet
AL- 485A GLED RJ45-3
} NC1 } GND RLED RJ45-2 } NC1 } RJ45-2
GND RLED

12V DC Adaptor
RS232 Wiegand Output

RS232 Wiegand Output


Wiegand In Power Out
Lock

Wiegand In Power Out


} RJ45-1

Lock
COM1 TXD IWD1 COM1 TXD } IWD1 RJ45-1
NO1 RXD IWD0 NO1 RXD IWD0
Button Sensor Bell Auxiliary In

Button Sensor Bell Auxiliary In


} BUT GND } GND } } GND GND
BUT }
} GND WD1 +12V } GND WD1 +12V
SEN WD0 WD0
SEN
} BELL+ } BELL+
BELL- BELL-
Power In

} GND } GND

Power In
} GND } GND
AUX +12V AUX +12V

12 12

PIN DESCRIPTION WIRE PIN DESCRIPTION WIRE


Sensor GND NC1
1 AL+ Red 1 AL+ Red
2 AL- Black 2 AL- Black
3 NC1 Gray 3 NC1 Gray
4 COM1 Black 4 COM1 Black
5 NO1 White 5 NO1 White
6 BUT Blue - 6 BUT Blue
+ Sensor GND NC1
7 GND Red 7 GND Red
8 SEN Yellow FR107 8 SEN Yellow
Diode
9 BELL+ Orange 9 BELL+ Orange
10 BELL- Green 10 BELL- Green
11 GND Purble 11 GND Purble -
+
12 Aux Brown 12 Aux Brown
FR107
Do not use Do not use Diode

Normally Closed Lock

Notes:
1. The system supports NO LOCK and NC LOCK. For example the NO LOCK (normally open
at power on) is connected with 'NO1' and 'COM1' terminals, and the NC LOCK (normally close Normally Closed Lock
at power on) is connected with 'NC1'and 'COM1' terminals.
2. When electrical lock is connected to the Access Control System, you must parallel one FR107
diode (equipped in the package) to prevent the self-inductance EMF a ecting the system.

! Do not reverse the polarities.

2.4 Inch TFT Time Attendance & Access Control Terminal INSTALLATION GUIDE 2.4 Inch TFT Time Attendance & Access Control Terminal INSTALLATION GUIDE
17 18

Wiegand Output Connection Standalone Installation

1
ZKBiosecurity 3.0 ZKBiosecurity 3.0
RS485

}
Alarm

} AL+ } 485B } BEEP RJ45-6


Output

Ethernet

AL- 485A GLED RJ45-3


} NC1 } GND RLED RJ45-2
RS232 Wiegand Output

Wiegand In Power Out


Lock

COM1 TXD } IWD1 RJ45-1

8
NO1 RXD IWD0
Button Sensor Bell Auxiliary In

}
}
BUT
GND
} GND
WD1
} GND
+12V
SEN WD0
} BELL+
BELL-
Power In

} GND } GND
AUX +12V

IN

PIN DESCRIPTION WIRE RS232/485


1 485B Yellow Converter RS485 Ethernet
2 485A Blue
3 GND Black
4 TXD Purple
5 RXD Gray
6 GND Black
7 WD1 White ALARM
8 WD0 Green WD0 WD1 GND
Do not use

PWR Sensor
2

GRD
RS485

No Touch
EXT

IN
GND EXIT
AUX 1

IN
Best Security Solution for the World
LAN

GND

BEEP
Lock
AUX 2 AUX 3

IN
GND

IN

GLED
Exit Button
GND
SWITCH

AUX4

IN
GND

+12V
GND
WD1
EXT

485-
485+ 485+
PC

485-
SGND
PWR
WD0
AUXOUT1

NO
2
STATE

COM RUN
ACT

GND
NC


GRD
RS485
AUXOUT2

NO
EXT

COM IN

NC GND

+12V
AUXOUT3

NO BEEP
COM GLED
NC WD1
WD0
AUXOUT4

NO GND
COM +12V
NC
RS485

IN
PC

SEN GND
GND
LOCK1

NO BEEP
COM GLED
GND
READER 2

NC WD1
WD0
SEN GND
GND
LOCK2

+12V
NO
BUTTON 3
CARD

COM IN
Advanced Access Control

NC GND

BEEP
SEN

Doorbell
GLED
READER 3

GND
LOCK3

NO WD1

COM WD0

NC GND
+12V
SEN
BUTTON 4
RUN

GND IN
LOCK4

NO GND
COM BEEP
NC GLED
READER 4
LOCK POWER

V+ WD1
READER 2

V- WD0
GND
+12V
+12V
GND
POWER

BUTTON 3
CARD

2.4 Inch TFT Time Attendance & Access Control Terminal INSTALLATION GUIDE 2.4 Inch TFT Time Attendance & Access Control Terminal INSTALLATION GUIDE
READER 3
BU
R
19 20

Third Party Controller How Does BioPro SA30 work


Wiegand Output Connection Fingerprint must be registered rst
by any nger print reader
ZKBiosecurity 3.0

Fingerprint Database

Identi cation

Finger Registration

Ethernet
GLED

GLED

GLED

GLED
BEEP

BEEP

BEEP

BEEP
+12V

485+
GND

GND

GND

GND

GND

+12V

+12V

+12V

+12V
PWR

GRD

GND

WD1
WD0
GND

GND

WD1
WD0
GND

GND

WD1
WD0
GND

GND

WD1
WD0
GND
485-

RUN
ACT
IN

IN

IN

IN

IN

IN

IN

IN

AUX 1 AUX 2 AUX 3 AUX4 EXT STATE BUTTON 1 READER 1 BUTTON


2 READER 2 BUTTON 3 READER 3 BUTTON 4 READER 4

Event Log Stored

EXT
RS485
PC
RS485
CARD RUN POWER
Veri cation failed
Best Security Solution for the World

Advanced Access Control Please try


again !
Veri cation
LAN SWITCH PC AUXOUT1 AUXOUT2 AUXOUT3 AUXOUT4 LOCK1 LOCK2 LOCK3 LOCK4 LOCK POWER
SGND

+12V
COM

COM

COM

COM

COM

COM

COM

COM
485+

GND

GND

GND

GND

GND
SEN

SEN

SEN

SEN
485-

NO

NO

NO

NO

NO

NO

NO

NO
NC

NC

NC

NC

NC

NC

NC

NC

V+
V-

Granted
Wiegand Wiegand Wiegand Wiegand Thank You
Output Output Output Output

Door Opens
READER 2

Outside Inside Lock Lock Inside Outside


BUTTON 3
CARD

2.4 Inch TFT Time Attendance & Access Control Terminal INSTALLATION GUIDE 2.4 Inch TFT Time Attendance & Access Control Terminal INSTALLATION GUIDE
READER 3
BU
R
21 22

How to Place a Finger on Scanner


ZKTeco s ngerprint readers will give optimal results for ngerprint matching DO NOT place the nger in the following positions
if the following recommendations and suggestions are followed.
If a nger is placed
as shown on the left,
Select a nger to enroll only a small area of
It is recommended to use an index nger or a nger is captured.
a middle nger. So it is recommended
Thumb, ring or little nger are relatively to place a nger as
di cult to place in the correct position shown on page 21.
Upright Skewed

How to place a nger on a sensor Sideways Partial

Place a nger such that it completely covers Tips for di erent ngerprint conditions
the sensor area with maximum contact. ZKTecos ngerprint products are designed to verify ngerprints with highest
Place core of the ngerprint at the center of security irrespective of the conditions of the skin of the nger. However, in case
the sensor. The core of a ngerprint is a center a ngerprint is not read on the sensor, please refer to the followings tips.
where the spiral of ridges is dense. (Usually core  If a nger is stained with sweat or water, scan after wiping moisture o .
of ngerprint is the opposite side of the lower part
of a nail.)  If a nger is covered with dust or impurities, scan after wiping them o .
Place a nger such that the bottom end of a nail is  If a nger is too dry, please blow some warm air from your mouth on the
located at the center of a sensor. nger tip.
Tips for ngerprint enrollment
In ngerprint recognition, enrollment process is very important. When enroll-
ing a ngerprint, please try to place the nger correctly with utmost care.
In case of low acceptance ratio, the following actions are recommended.
 Delete the enrolled ngerprint and re-enroll the nger.
 Try another nger if a nger is not easy to enroll due to scar or cuts.
In case of an enrolled ngerprint cannot be used due to injury or if the hand is
full, it is recommended to enroll more than two ngers per user.

2.4 Inch TFT Time Attendance & Access Control Terminal INSTALLATION GUIDE 2.4 Inch TFT Time Attendance & Access Control Terminal INSTALLATION GUIDE
23

Troubleshooting
1. Fingerprint can not be read or it takes too long.
 Check whether a nger or ngerprint sensor is stained with sweat, water, or dust
 Retry after wiping o nger and ngerprint sensor with dry paper tissue or a mildly
wet cloth.
 If a ngerprint is too dry, blow on the nger and retry.
2. Fingerprint is veri ed but authorization keeps failing.
 Check whether the user is restricted by group or time zone.
 Check with administrator whether the enrolled ngerprint has been deleted from the
device for some reason.
3. Authorized but door does not open.
 Check whether the lock open duration is set to appropriate time, which opens the lock.
 Check whether anti-passback mode is in use. In anti-passback mode, only the person
who has entered through that door can exit.
4. Why device display system broken and the alarm is ringing.
 Check whether the device and back plate are securely connected to each other. If not,
a tamper switch is activated which triggers the alarm and keeps it ringing.
5. How to set ProCapture used as ngerprint reader on inBio access controller.
 Reeference the Wiegand Output Connection on page 17.
 Enroll personnel s PIN in inBio panel as a card

2.4 Inch TFT Time Attendance & Access Control Terminal INSTALLATION GUIDE 2.4 Inch TFT Time Attendance & Access Control Terminal INSTALLATION GUIDE