You are on page 1of 7

GENFOCU

SITE ACCEPTANCE TEST REPORT FOR SUB MAIN DISTRIBUTION BOARD


PROJECT: SEA WORLD ABUDHABI SOLAR PV PROJECT
CLIENT M/S. MIRAL/SEA WORLD DATE: 16-03-2024
DEVLOPER M/S. EMERGE/MASDAR PAGE: 1 of 7
SOLAR EPC M/S. GOLDEN FALCON EQUIPMENT LV PANEL(A0-SMDB-SOLAR-1)
TESTING AGENCY M/S. GENFOCUS SUBSTATION / LOCATION UTILITY LV ROOM

1. BREAKER NAME PLATE DETAILS:

MAKE ABB CURRENT RATING 2000 A


TYPE SACE E2.2N SL.NO CD31176957
MAIN INCOMER 2000A TP ACB
VOLTAGE RATING 690V ASSET DETAIL
(A0-SMDB-SOLAR-1)

2. GENERAL CHECKS:

S No Description Result
1 Check visual inspection of LV PANEL, ACB, MCCB, and other equipment. OK
2 Check any damages, painting and identification label, etc. OK
3 Check the tightness of Cable and Equipment. OK
4 Check tag name of cable. NA
5 Check ACB Cable tightness. OK
6 Verify ACB Rating and panel details as per load schedule. OK
7 Check visual inspection of CT wiring. OK
8 Check the healthiness of the auxiliary fuse. OK
9 Check secondary injection ACB trip test. OK
10 Check torque tightness of Busbar & ACB. OK

3. BREAKER INSULATION RESISTANCE TEST:

ACB Condition Phase Applied Voltage (V) IR Value(GΩ) Remarks


R - R’ >100 OK
OFF Y - Y’ >100 OK
B - B’ >100 OK
500V DC for 1 Min
R-(Y+B+E) >100 OK
ON Y-(R+B+E) >100 OK
B-(R+Y+E) >100 OK

4. ACB CONTACT RESISTANCE TEST:

Tested by Witness by/Approved By Witness by/Approved By


Company GENFOCUS GOLDEN FALCON SEA WORLD
Name ABHILASH CHANDRAN
Signature
Date 16-03-2024
GENFOCU
S

SITE ACCEPTANCE TEST REPORT FOR SUB MAIN DISTRIBUTION BOARD


PROJECT: SEA WORLD ABUDHABI SOLAR PV PROJECT
CLIENT M/S. MIRAL/SEA WORLD DATE: 16-03-2024
DEVLOPER M/S. EMERGE/MASDAR PAGE: 2 of 7
SOLAR EPC M/S. GOLDEN FALCON EQUIPMENT LV PANEL(A0-SMDB-SOLAR-1)
TESTING AGENCY M/S. GENFOCUS SUBSTATION / LOCATION UTILITY LV ROOM

S No Phase Ref. Measured Value [µΩ] REMARKS


1 R-ɸ 18 OK
2 Y- ɸ 16 OK
3 B-ɸ 15 OK

5. BREAKER TRIP TEST REPORT: Note:(Ekip Trip Test File Attached)

6. FINAL PROTECTION SETTING:


Protection curve Protection Setting Delay time Test trip
Long time (L) 1.0 x In 144 Sec -

Short time (S) OFF 0.1 Sec -


Instantaneous (I) 4.0 x In - -

TESTING OF CURRENT TRANSFORMER

1. Name Plate Detail

Tested by Witness by/Approved By Witness by/Approved By


Company GENFOCUS GOLDEN FALCON SEA WORLD
Name ABHILASH CHANDRAN
Signature
Date 16-03-2024
GENFOCU
S

SITE ACCEPTANCE TEST REPORT FOR SUB MAIN DISTRIBUTION BOARD


PROJECT: SEA WORLD ABUDHABI SOLAR PV PROJECT
CLIENT M/S. MIRAL/SEA WORLD DATE: 16-03-2024
DEVLOPER M/S. EMERGE/MASDAR PAGE: 3 of 7
SOLAR EPC M/S. GOLDEN FALCON EQUIPMENT LV PANEL(A0-SMDB-SOLAR-1)
TESTING AGENCY M/S. GENFOCUS SUBSTATION / LOCATION UTILITY LV ROOM

Feeder / CT Ref. Q0-MAIN INCOMER 1(A0-SMDB-SOLAR-1)


Type/Make ZIEGLER
Purpose Metering
Ratio (A) 2000/5
Class 0.2s FS10
Burden (VA) 15 VA
Serial No. R-ɸ G230342421 Y-ɸ G230342403 B-ɸ G230342425

2. Visual Inspection Tests:


Description R-ɸ Y-ɸ B-ɸ
Check Visual Inspection for damage, proper installation and Name Plate Detail   
Tightness Check at CT Sec. TB – LV Compartment   

3. Insulation Resistance Tests: Duration: 1 Min


Insulation Resistance Value (GΩ)
Reference Applied Voltage (V)
R-ɸ Y-ɸ B-ɸ
Secondary – Earth 500 36 31 41
4. Polarity Test:
NOTE: Refer the Attached Omicron CT Analyzer Test Report

5. Winding Resistance Measurement Test (Secondary):


NOTE: Refer the Attached Omicron CT Analyzer Test Report

6. Magnetization Characteristic Test (Knee Point):


NOTE: Refer the Attached Omicron CT Analyzer Test Report

1. EARTH LEAKAGE RELAY

RELAY MAKE ELMEX


AUX VOLTAGE 230V

Tested by Witness by/Approved By Witness by/Approved By


Company GENFOCUS GOLDEN FALCON SEA WORLD
Name ABHILASH CHANDRAN
Signature
Date 16-03-2024
GENFOCU
S

SITE ACCEPTANCE TEST REPORT FOR SUB MAIN DISTRIBUTION BOARD


PROJECT: SEA WORLD ABUDHABI SOLAR PV PROJECT
CLIENT M/S. MIRAL/SEA WORLD DATE: 16-03-2024
DEVLOPER M/S. EMERGE/MASDAR PAGE: 4 of 7
SOLAR EPC M/S. GOLDEN FALCON EQUIPMENT LV PANEL(A0-SMDB-SOLAR-1)
TESTING AGENCY M/S. GENFOCUS SUBSTATION / LOCATION UTILITY LV ROOM

CURRENT SETTING RANGE 0.03-30 A


TIME SETTING RANGE 0-10 Sec
SERIAL NO Not Visible

2. EARTH LEAKAGE RELAY PRIMARY INJECTION TRIP TEST:

Current setting(A) Time setting (Sec) Pickup current in(A) Trip time in(sec)

SECONDARY INJECTION TEST OF VOLTMETER

1. Name Plate Detail:


Make ELMEX Type EVM72X72
Serial No. 2305251156 Full Scale Reading 0-500V
Accuracy Class 1.5

2. Secondary Injection:
Injected Primary Actual Voltage in
Reading
Voltage (V) Voltmeter (V)
25% 125 127
50% 250 251
75% 375 375
100% 500 500
% Error = [(Actual Reading – Expected Reading) / Expected Reading] * 100

Acceptance Criteria: Error should be ± 1.5%.

SECONDARY INJECTION TEST OF AMMETER

1.Name Plate Detail:

Make ELMEX
Type EPM72X72
Accuracy Class 1.5
Tested by Witness by/Approved By Witness by/Approved By
Company GENFOCUS GOLDEN FALCON SEA WORLD
Name ABHILASH CHANDRAN
Signature
Date 16-03-2024
GENFOCU
S

SITE ACCEPTANCE TEST REPORT FOR SUB MAIN DISTRIBUTION BOARD


PROJECT: SEA WORLD ABUDHABI SOLAR PV PROJECT
CLIENT M/S. MIRAL/SEA WORLD DATE: 16-03-2024
DEVLOPER M/S. EMERGE/MASDAR PAGE: 5 of 7
SOLAR EPC M/S. GOLDEN FALCON EQUIPMENT LV PANEL(A0-SMDB-SOLAR-1)
TESTING AGENCY M/S. GENFOCUS SUBSTATION / LOCATION UTILITY LV ROOM

CT Ratio 2000/5A
Full Scale Reading 0-4000A
Serial No. R-ɸ 2305250423 Y-ɸ 2305250424 B-ɸ 2305250460

2. Secondary Injection:
Injected Secondary Expected Primary Measured Primary Current in
Reading
Current in (A) Current in (A) Ammeter (A)
R 1.25 500 504
25% 1.25
Y 500 504
B 1.25 500 505
R 2.50 1000 1005
50% 2.50
Y 1000 1005
B 2.50 1000 1004
R 3.75 1500 1500
75% 3.75
Y 1500 1500
B 3.75 1500 1500
R 5.0 2000 2000
100% 5.0 2000
Y 2000
B 5.0 2000 2000
% Error = [(Actual Reading – Expected Reading) / Expected Reading] * 100

Acceptance Criteria: Error should be ± 1.5%.

CALIBRATON OF MULTI FUNCTION METER

1. Name Plate Detail:

MAKE SCHNEIDER ELECTRIC TYPE Easy Logic PM2100


Meter Serial No 540220079122 CT RATIO 2000/5 A
VT RATIO 500 V

2. AMMETER CALIBRATION:
Tested by Witness by/Approved By Witness by/Approved By
Company GENFOCUS GOLDEN FALCON SEA WORLD
Name ABHILASH CHANDRAN
Signature
Date 16-03-2024
GENFOCU
S

SITE ACCEPTANCE TEST REPORT FOR SUB MAIN DISTRIBUTION BOARD


PROJECT: SEA WORLD ABUDHABI SOLAR PV PROJECT
CLIENT M/S. MIRAL/SEA WORLD DATE: 16-03-2024
DEVLOPER M/S. EMERGE/MASDAR PAGE: 6 of 7
SOLAR EPC M/S. GOLDEN FALCON EQUIPMENT LV PANEL(A0-SMDB-SOLAR-1)
TESTING AGENCY M/S. GENFOCUS SUBSTATION / LOCATION UTILITY LV ROOM

MEASURED DISPLAY CURRENT (A)


INJECTED CURREN (A) EXPECTED CURRENT(A)
R Y B

3. VOLTMETER CALIBRATION

Measured Display Voltage (V)


Voltage Applied (V) Expected Voltage (V)
RN YN BN RY YB BR

1. REMARK: NIL

2. EQUIPMENT DETAILS:

SL.NO INSTRUMENT NAME MAKE/MODEL SERIAL NO CALIBRATION VALID


1 IR Tester Megger / MIT515 101283345 08-06-2024
3 Digital Multimeter Fluke / 87V 38030052 31-01-2025
4 MOM Programma / MOM200A 1603262 31-01-2025
5 Secondary Injection Megger /Sverker 900 2001745 14-02-2025
6 CT Analyzer Omicron / CT Analyzer LF541J 14-04-2024
Tested by Witness by/Approved By Witness by/Approved By
Company GENFOCUS GOLDEN FALCON SEA WORLD
Name ABHILASH CHANDRAN
Signature
Date 16-03-2024
GENFOCU
S

SITE ACCEPTANCE TEST REPORT FOR SUB MAIN DISTRIBUTION BOARD


PROJECT: SEA WORLD ABUDHABI SOLAR PV PROJECT
CLIENT M/S. MIRAL/SEA WORLD DATE: 16-03-2024
DEVLOPER M/S. EMERGE/MASDAR PAGE: 7 of 7
SOLAR EPC M/S. GOLDEN FALCON EQUIPMENT LV PANEL(A0-SMDB-SOLAR-1)
TESTING AGENCY M/S. GENFOCUS SUBSTATION / LOCATION UTILITY LV ROOM

7 Secondary Injection EKIP TT D29000220740W041 27-09-2024

Tested by Witness by/Approved By Witness by/Approved By


Company GENFOCUS GOLDEN FALCON SEA WORLD
Name ABHILASH CHANDRAN
Signature
Date 16-03-2024

You might also like