Damper - rectangular DJP


Dimensions
1
A 105 110
20 20
20 2

3
B
4

50 100
20 5

Motor overview
6
Description Type Motor Motor
DJP is a rectangular control and shut-off damper. 0 3
DJP-RU NM24A-V NF24A-MF
7
DJP has opposing aerodynamic damper blades that are DJP-RP NM24A-MF NF24A-MF
rotated via a lever device. The damper is supplied with an DJP-SU NM24A-SR NF24A-SR
LS connection system for rectangular ducts. The damper DJP-SP NM24A-MF NF24A-MF 8
can be used for pressure or volume flow regulation with
external control options (open, closed, min., max.) depend- RU Used only with PR (and FRU) and is preset to a VAV
ing on the form of control/regulation. input signal: 6 ± 4 V.
9
DJP is available with a spring return motor, so the damper RP Has a programmable motor, is used together with PR
can be used as a smoke damper. The damper can be con- and is preprogrammed for a VAV input signal: 6 ± 4 V.
trolled by an FRA (as a VRA) or a PR regulator, directly by a Has a modulating output signal indicating damper 10
temperature sensor or BMS system (2–10 V modulating) or position for mechanical control of a slave damper.
as a slave for another damper (mechanical slave operation
with the same damper position). SU Has a motor, which is controlled by a modulating 11
input signal (2-10 V).
When ordering, it is important to specify the form of control, Also has a modulating output signal indicating
and whether the damper motor must be programmable. All damper position.
DJP dampers have Belimo motors installed. 12
SP Has a programmable motor, which can be controlled
by an optional input signal (standard modulating).
Also has a modulating output signal indicating 13
damper position for mechanical control of a slave
damper.
Ordering example
14
Product DJP a AxB c d
Type

Standard 0
15
Spring return 3
Size
A (Width) 16
B (Height)
Form of control
R: Regulator-controlled 17
S: Slave or sensor-controlled
Programming
U: Without programming 18
P: Programmable

We reserve the right to make changes without prior notice 583


lindab | v av

Damper - rectangular DJP


Technical data
1
Frequency-related sound effect level

DJP-1m2 Sound power level [Lw] [dB]


3 Pressure dif- Centre frequency [Hz] [LWA (A)]
Duct velocity ference [Pa] [dB(A)]
125 250 500 1000 2000 4000 8000
2m/s 50 62 60 59 53 50 45 42 60
4
100 66 64 62 59 57 54 52 65

200 71 65 63 65 65 61 58 70
5 400 81 80 79 81 81 78 76 86

4m/s 50 65 63 62 56 53 48 45 63

6 100 69 67 65 62 60 57 54 68

200 74 68 67 68 68 64 60 73

7 400 84 83 82 84 84 81 79 89

6m/s 50 67 65 63 57 54 49 45 64

100 72 68 67 65 63 58 49 70
8
200 75 69 68 70 71 66 63 76

400 85 84 83 86 85 83 80 91
9 8m/s 50 68 66 63 59 56 51 48 65

100 74 73 71 67 65 59 56 73
10 200 80 80 79 75 75 70 65 82

400 87 86 85 87 87 84 81 92

11
Correction of sound effect level for other damper sizes

12 Area [m²] 0,1 0,2 0,4 0,6 0,8 1,0 1,5 2,0

dB correction -10 -7 -4 -2 -1 0 +2 +3

13

14

15

16

17

18

584 We reserve the right to make changes without prior notice


lindab | vav

Damper - rectangular DCT/DJP


Technical data
Dimensioning Example 1
When dimensioning the dampers inherent noise from the The example shows the working area for a Ø250 mm
dampers and their regulating properties (damper character- damper, which works between
istics) must be taken into consideration.
If excessively large dampers are used, the working area Vmax =1,236 m3/h; Δp = 50 Pa
2
(angle of rotation) at given Vmin and Vmax may be so limited
that regulation does not function satisfactorily. Efforts must and
be made to use damper dimensions that result in the largest 3
possible working areas (angles of rotation). Vmin =309 m3/h ; Δp = 100 Pa.
Due to regulation accuracy, working areas with damper
angles > 75° should be avoided. The diagram shows the The diagram shows damper positions 31° and 69°. 4
damper position at given pressure losses and volume flows.

Correction of sound effect level for other damper sizes 5

Pressure drop Pa DCT Cirkular damper 6


1000

700

500
7
400
300

200
8
0
α 10
150
25
α1
100
α 1 60 9
00
70 α2
50
50 α2
15
40 α3 10
00
30 α4
00
α5
20 l/s
15 20 30 40 50 70 100 150 200 300 500 700 1000
m 3/h
0 10 20 30 40 50 60 70 80 90 11
50 70 100 150 200 300 500 700 1000 2000 3000 5000

Air volume Turning angle

Pressure drop Pa Louvre damper DJP


12
1000

700
13
500
400
300
14
2
m
05
0,

200
2
m

150
10
0,

100
15
2
m
25

70
0,
2
m

50
16
50
0,

40
2
m

30
00
1,

20
150 200 300 400 500 700 1000 2000 3000 5000 10000
l/s
0 10 20 30 40 50 60 70 80 90
17
m 3/h
500 700 1000 2000 3000 5000 10000 20000 50000

Air volume Turning angle


18