Professional Documents
Culture Documents
Compressor Motor Protection Module 051
Compressor Motor Protection Module 051
INT69 TM®
for heavy start or high switching frequency
Application:
The INT69 VS, INT69 V and developed for motors with high
INT69 TM motor protection starting load or drives with high
modules have been especially switching frequency.
Hysteresis
14 11 12 1...3K Note :
on off
Due to the displacement of the perature) of the PTC sensors
trip-point to approx. 12.5k must, therefore be 10K below
Product Group A
14 11 12 RPTC the trip temperature is approx. the required trip temperature.
10K above the nominal re-
2,5k 4,5k sponse temperature of the PTC. Example:
INT69 V When the INT69 VS is used, the NAT=150°C (insulation class F)
NAT (nominal response tem- NAT=150°C minus 10K=140°C
relay
14 11 12 Hysteresis
approx.10K
on off
INT69 TM Motor Protection
Module:
RPTC The INT69 TM motor protection down period. As with to the
14 11 12
2,4k 12,5k module has also been desig- standard control modules, the
Edition: 690.00051.0
ned for motors with high starting trip point is 4.5k and thus cor-
INT69 VS
load and/or high switching fre- responds to the nominal re-
1...3K + 5min quency. The extended cool- sponse temperature of the PTC
relay 5min 1...3K down period of the INT69 VS thermistors. As soon as the
protection module is achieved PTC resistance deeps to 2.5k
Hysteresis increasing the switching hyster- the internal timer of the INT69 TM
14 11 12
1...3K esis, whereas the INT69 TM is is activated and after approx.
on off equipped with an additional time 5min the output relay pulls in
function for extended cool- again.
14 11 12 RPTC
2,5k 4,5k
INT69 TM
CMP Coproration • P.O. Box 15199 • Oklahoma City, OK 73155 • Phone: (405) 672-4544 • Fax: (405) 672-4547 • USA Toll Free: (800) 654-4786 • Mexico Toll Free: (800) 777-4786
www.cmpcorp.com • email: kriwan@cmpcorp.com
INT69 V®, INT69 VS®, INT69 TM®
for heavy start or high switching frequency
Technical data general
Supply voltage AC 50Hz 230V ±10% 3VA
Ambient temperature range -20...+60°C
Relay AC 250V, max. 5A, 300VA ind.
L N 1 2 12 14 11 B1 B2 Mechanical service life approx. 1 mio. switching cycles
Protection class acc. to with terminal cover: IP20
*) EN 60529 without terminal cover: IP00
mains Housing PA6 GF30
* ) with jumper: locked trip-out Mounting on 35mm standard rail acc. to
without jumper: unlocked trip-out EN 50022 or base mounted
Connection Diagram
INT69 VS, INT69 V
Technical data INT69 V
Measuring circuit
40 - type PTC, acc. to DIN 44081/082
6
4,5 - number of sensors 1...9 in series
- R25 total < 1,8k
Switching hysteresis 1...3K
Weight approx. 200g
72
87