SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of
heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training.
Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury.
When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are
attached to the equipment.
WARNING
Proper Field Wiring and Grounding Required!
Failure to follow code could result in death or serious injury.
All field wiring MUST be performed by qualified personnel. Improperly installed and
grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards,
you MUST follow requirements for field wiring installation and grounding as described in
NEC and your local/state/national electrical codes.
WARNING
Personal Protective Equipment (PPE) Required!
Failure to wear proper PPE for the job being undertaken could result in death or serious
injury.
Technicians, in order to protect themselves from potential electrical, mechanical, and
chemical hazards, MUST follow precautions in this manual and on the tags, stickers, and
labels, as well as the instructions below:
• Before installing/servicing this unit, technicians M UST put on all PPE required for
the work being undertaken (Examples; cut resistant gloves/sleeves, butyl gloves,
safety glasses, hard hat/bump cap, fall protection, electrical PPE and arc flash
clothing). ALWAYS refer to appropriate Safety Data Sheets (SDS) and OSHA
guidelines for proper PPE.
• When working with or around hazardous chemicals, ALWAYS refer to the
appropriate SDS and OSHA/GHS (Global Harmonized System of Classification and
Labelling of Chemicals) guidelines for information on allowable personal exposure
levels, proper respiratory protection and handling instructions.
• If there is a risk of energized electrical contact, arc, or flash, technicians MUST put
on all PPE in accordance with OSHA, NFPA 70E, or other country-specific
requirements for arc flash protection, PRIOR to servicing the unit. NEVER PERFORM
ANY SWITCHING, DISCONNECTING, OR VOLTAGE TESTING WITHOUT PROPER
ELECTRICAL PPE AND ARC FLASH CLOTHING. ENSURE ELECTRICAL METERS AND
EQUIPMENT ARE PROPERLY RATED FOR INTENDED VOLTAGE.
WARNING
Follow EHS Policies!
Failure to follow instructions below could result in death or serious injury.
• All Trane personnel must follow the company’s Environmental, Health and Safety
(EHS) policies when performing work such as hot work, electrical, fall protection,
lockout/tagout, refrigerant handling, etc. Where local regulations are more
stringent than these policies, those regulations supersede these policies.
• Non-Trane personnel should always follow local regulations.
Trane Copyright
This document and the information in it are the property of Trane, and may not be used or
reproduced in whole or in part without written permission. Trane reserves the right to revise this
publication at any time, and to make changes to its content without obligation to notify any
person of such revision or change.
Trademarks
All trademarks referenced in this document are the trademarks of their respective owners.
Revision History
• Added new variables to CenTraVac BACnet/Modbus Equivalents and Duplex CenTraVac
BACnet/Modbus Equivalents tables in Equivalent Data Points: CenTraVac, Duplex,
AdaptiView chapter.
• Added new object names and property values to CenTraVac Read-only Values and CenTraVac
Diagnostics tables in CenTraVac Object Data Points and Configurations chapter.
• Added new object names and property values to Duplex Read-only Values and Duplex
Diagnostics tables in Duplex CenTraVac Object Data Points and Configurations chapter.
• Updated register values of refrigerant type to Modbus CenTraVac Read-only table in Modbus
CenTraVac Data Points Descriptions and Configurations.
• Added new register object names to Modbus Duplex Read-only table in Modbus Duplex Data
Points Descriptions and Configurations.
BAS-SVP01Q-EN 3
Table of Contents
Protocols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
BACnet Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
BACnet Testing Laboratory (BTL) Certification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Modbus Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
UC800 Rotary Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Communication Interfaces. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Rotary Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Equivalent Data Points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
CenTraVac Chillers for BACnet/Modbus RTU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Duplex CenTraVac Chillers for BACnet/Modbus RTU . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Tracer AdaptiView Panel Upgrade for BACnet/Modbus RTU . . . . . . . . . . . . . . . . . . . . 17
BACnet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
BACnet Protocol Implementation Conformance Statement (PICS). . . . . . . . . . . . . . . 20
Standardized Device Profile (Annex L) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Interoperability Building Blocks (Annex K). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Object Types for CTV and AdaptiView . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Baud Rate, Device ID, and Supported Character Sets. . . . . . . . . . . . . . . . . . . . . . . . . . . 23
4 BAS-SVP01Q-EN
Table of Contents
BAS-SVP01Q-EN 5
Protocols
BACnet Protocol
The Building Automation and Control Network (BACnet®) protocol is ANSI/ASHRAE Standard
135. This standard allows building automation systems or components from different
manufacturers to share information and control functions. BACnet® provides building owners
the capability to connect various types of building control systems or subsystems together for
many uses. Multiple vendors can use this protocol to share information for monitoring and
supervisory control between systems and devices in a multi-vendor interconnected system. The
BACnet® protocol defines standard objects (data points) called BACnet® objects. Each object has
a defined list of properties that provide context information about that object. In addition,
BACnet® defines a number of application services that are used to interact with objects in a
BACnet® device.
Modbus Protocol
Modicon Communication Bus (Modbus®) is a layer-messaging protocol application which, like
BACnet®, provides client/server communication between devices over a variety of networks.
During communications on a Modbus® RTU network, the protocol determines how each
controller knows its device address, recognizes a message addressed to its device, determines
what action to take, and extracts any data or other information contained in the message.
Controllers communicate using a master/slave technique, whereby, only one device (master) can
initiate transactions (queries). Other devices (slaves) respond by supplying the requested data to
the master or by taking the action requested in the query. The master can address individual
slaves or it can initiate a broadcast message to all slaves. In turn, the slaves respond to queries
that are addressed to them individually or broadcasted. The Modbus® RTU protocol establishes
the format for the master query by placing into it the device address, a function code defining the
requested action, any data to be sent, and an error-checking field.
6 BAS-SVP01Q-EN
UC800 Rotary Switches
Communication Interfaces
The UC800 supports the communication interfaces listed below. There is one set of terminations
(link) for BACnet® and Modbus®. LonTalk™ and Comm 4 communication interfaces connect to
the IPC3 bus which is the MBUS connection.
• BACnet® MS/TP
• Modbus® Slave
• LonTalk™ using LCI-C (from the IPC3 bus)
• Comm 4 using TCI (from the IPC3 bus)
Rotary Switches
There are three (3) rotary switches on the front of the UC800 (shown below) used to define a
three-digit address when the UC800 is installed in a BACnet® or Modbus® RTU system (for
example, 107, 127, and so on). Valid MAC addresses are 001 to 127 for BACnet® and 001 to 247
for Modbus® RTU. For additional information about setting higher addresses, refer to the
section, Device ID.
2 3
2 3
7 8
7 8
7 8
x100 x10 x1
USB
• Marquee LED
– Shows solid green when the UC800 is powered and operating normally.
– Shows solid red when the UC800 is powered, but represents low power or a malfunction.
– Blinks red when an alarm exists.
• LINK, Machine Bus (MBUS), IMC
– The TX LED blinks green at the data transfer rate when the UC800 transfers data to other
devices on the link.
– The RX LED blinks yellow at the data transfer rate when the UC800 receives data from
other devices on the link.
• Ethernet Link
– The LINK LED shows solid green if the Ethernet link is connected and communicating.
– The ACT LED blinks yellow at the data transfer rate when data flow is active on the link.
• Service
– Shows solid green when pressed. For more details, refer to CVHE-SVX02*-EN
(Installation, Operation, and Maintenance: CVHE, CVHF, and CVHG Water-cooled
CenTraVac Chillers with Tracer AdaptiView Control).
–
BAS-SVP01Q-EN 7
Equivalent Data Points
CenTraVac Chillers for BACnet/Modbus RTU
The following table provides a quick reference to equivalent data point objects names for
CenTraVac™ chillers when using either BACnet® or Modbus® RTU communications.
N o t e : The table is sorted alphabetically by data point names.
Table 1. CenTraVac chiller BACnet/Modbus equivalents
Data Point Object Name BACnet Object Modbus RTU Register
Active Base Loading Setpoint AI3 30006
Active Base Loading Setpoint Source MI7 30031
Active Chilled Water Setpoint Source MI4 30029
Active Cool/Heat Setpoint Temperature AI7 30010
Active Current Limit Setpoint AI2 30005
Active Current Limit Setpoint Source MI5 30030
Active Hot Water Setpoint Source MI6 30032
AFD % RLA Ripple AI98 30129
AFD Average Input Current AI71 30112
AFD Average Motor Voltage AI76 30113
AFD Calculated Input Voltage AI111 30092
AFD DC Bus Voltage AI91 30130
AFD Input Current L1 AI72 30114
AFD Input Current L2 AI73 30115
AFD Input Current L3 AI74 30116
AFD Input Frequency AI75 30111
AFD Inverter Base Temperature AI78 30118
AFD Inverter Module Temp U AI99 30126
AFD Inverter Module Temp V AI100 30127
AFD Inverter Module Temp W AI101 30128
AFD Last Diagnostic Code (decimal) AI18 Not applicable
AFD Motor Current U AI84 30094
AFD Motor Current U % RLA AI81 30098
AFD Motor Current V AI85 30095
AFD Motor Current V % RLA AI82 30099
AFD Motor Current W AI86 30096
AFD Motor Current W % RLA AI83 30100
AFD Motor Voltage UV AI87 30123
AFD Motor Voltage VW AI88 30124
AFD Motor Voltage WU AI89 30125
AFD Output Power AI80 30120
AFD Output Voltage AI76 30113
AFD Rectifier Base Temperature AI79 30119
AFD Transistor Temp AI70 30110
Alarm Present BI10 30047
Approx Cond Water Flow AI14 30021
Approx Evap Water Flow AI12 30017
Approx Unit Heating Power Not applicable 30009
Average Line Current AI61 30004
Average Line Current Amps AI57 30097
8 BAS-SVP01Q-EN
Equivalent Data Points
BAS-SVP01Q-EN 9
Equivalent Data Points
10 BAS-SVP01Q-EN
Equivalent Data Points
BAS-SVP01Q-EN 11
Equivalent Data Points
12 BAS-SVP01Q-EN
Equivalent Data Points
BAS-SVP01Q-EN 13
Equivalent Data Points
14 BAS-SVP01Q-EN
Equivalent Data Points
BAS-SVP01Q-EN 15
Equivalent Data Points
16 BAS-SVP01Q-EN
Equivalent Data Points
BAS-SVP01Q-EN 17
Equivalent Data Points
18 BAS-SVP01Q-EN
Equivalent Data Points
BAS-SVP01Q-EN 19
BACnet
The Tracer® UC800 controller is an equipment unit controller that provides the equipment
system sequences and performs closed-loop control. In addition, the UC800 integrates with other
BACnet® systems and devices using BACnet® MS/TP.
20 BAS-SVP01Q-EN
BACnet
• Object_Identifier
• Object_Name
• Object_Type • Object_Name
• Priority_Array
• Present_Value • Present_Value
Analog Value • Relinquish_Default None None
• Status_Flags • Out_Of_Service
• Reliability
• Event_State • Relinquish_Default
• Out_Of_Service
• Units
• Inactive_Text
• Active_Text
• Object_Identifier
• Time_Delay
• Object_Name
• Notification_Class
• Object_Type • Object_Name
• Alarm_Value
• Present_Value • Out_Of_Service
Binary Input None None
• Event_Enable
• Status_Flags • Inactive_Text
• Acked_Transitions
• Event_State • Active_Text
• Notify_Type
• Out_Of_Service
• Event_Time_
• Polarity
Stamps
• Reliability
• Object_Identifier
• Object_Name
• Object_Type • Object_Name
• Present_Value • Present_Value
• Inactive_Text
• Status_Flags • Out_Of_Service
Binary Output • Active_Text None None
• Event_State • Relinquish_Default
• Reliability
• Out_Of_Service • Inactive_Text
• Polarity • Active_Text
• Priority_Array
• Relinquish_Default
BAS-SVP01Q-EN 21
BACnet
• Object_Identifier
• Object_Name
• Object_Type
• System_Status
• Vendor_Name
• Vendor_Identifier
• Max_Segments_
• Model_Name Accepted
• Firmware_Revision • APDU_Segment_
Timeout
• Application_Software_Version
• Max_Master
• Protocol_Version
Device Object_Name • Max_Info_Frames None None
• Protocol_Revision
• Local_Time
• Protocol_Services_Supported
• Local_Date
• Protocol_Object_Types_
Supported • UTC_Offset
• Object_List • Daylight_Savings_
Status
• Max_APDU_Length_Accepted
• Segmentation_Supported
• APDU_Timeout
• Number_Of_APDU_Retries
• Device_Address_Binding
• Database_Revision
• Object_Identifier
• Object_Name
• Object_Type
• Present_Value • Object_Name • State_Text
Multistate Input None None
• Status_Flags • State_Text • Reliability
• Event_State
• Out_Of_Service
• Number_Of_States
• Object_Identifier
• Object_Name
• Object_Type
• Present_Value • Object_Name
• Status_Flags • Present_Value • State_Text
Multistate Output None None
• Event_State • Relinquish_Default • Reliability
• Out_Of_Service • State_Text
• Number_Of_States
• Priority_Array
• Relinquish_Default
22 BAS-SVP01Q-EN
BACnet
• Object_Identifier
• Object_Name
• Object_Type
• Object_Name
Notification Class • Notification_Class None None None
• Recipient_List
• Priority
• Ack_Required
• Recipient_List
BAS-SVP01Q-EN 23
BACnet
24 BAS-SVP01Q-EN
BACnet CenTraVac Object Data Points and
Configurations
Device Object
Object Name Instance Property Values
UC800 (Dev Instance) Configurable Non-applicable
BAS-SVP01Q-EN 25
BACnet CenTraVac Object Data Points and Configurations
26 BAS-SVP01Q-EN
BACnet CenTraVac Object Data Points and Configurations
BAS-SVP01Q-EN 27
BACnet CenTraVac Object Data Points and Configurations
28 BAS-SVP01Q-EN
BACnet CenTraVac Object Data Points and Configurations
BAS-SVP01Q-EN 29
BACnet CenTraVac Object Data Points and Configurations
30 BAS-SVP01Q-EN
BACnet CenTraVac Object Data Points and Configurations
BAS-SVP01Q-EN 31
BACnet CenTraVac Object Data Points and Configurations
32 BAS-SVP01Q-EN
BACnet CenTraVac Object Data Points and Configurations
BAS-SVP01Q-EN 33
BACnet CenTraVac Object Data Points and Configurations
34 BAS-SVP01Q-EN
BACnet CenTraVac Object Data Points and Configurations
BAS-SVP01Q-EN 35
BACnet CenTraVac Object Data Points and Configurations
36 BAS-SVP01Q-EN
BACnet CenTraVac Object Data Points and Configurations
BAS-SVP01Q-EN 37
BACnet CenTraVac Object Data Points and Configurations
38 BAS-SVP01Q-EN
Duplex CenTraVac Object Data Points and
Configurations
Device Object
Object Name Instance Property Values
UC800 (Dev Instance) Configurable Non-applicable
BAS-SVP01Q-EN 39
Duplex CenTraVac Object Data Points and Configurations
40 BAS-SVP01Q-EN
Duplex CenTraVac Object Data Points and Configurations
BAS-SVP01Q-EN 41
Duplex CenTraVac Object Data Points and Configurations
42 BAS-SVP01Q-EN
Duplex CenTraVac Object Data Points and Configurations
BAS-SVP01Q-EN 43
Duplex CenTraVac Object Data Points and Configurations
44 BAS-SVP01Q-EN
Duplex CenTraVac Object Data Points and Configurations
BAS-SVP01Q-EN 45
Duplex CenTraVac Object Data Points and Configurations
46 BAS-SVP01Q-EN
Duplex CenTraVac Object Data Points and Configurations
BAS-SVP01Q-EN 47
Duplex CenTraVac Object Data Points and Configurations
48 BAS-SVP01Q-EN
Duplex CenTraVac Object Data Points and Configurations
BAS-SVP01Q-EN 49
Duplex CenTraVac Object Data Points and Configurations
50 BAS-SVP01Q-EN
Duplex CenTraVac Object Data Points and Configurations
BAS-SVP01Q-EN 51
Duplex CenTraVac Object Data Points and Configurations
52 BAS-SVP01Q-EN
Duplex CenTraVac Object Data Points and Configurations
BAS-SVP01Q-EN 53
Duplex CenTraVac Object Data Points and Configurations
54 BAS-SVP01Q-EN
Tracer AdaptiView Panel Upgrade Object Data Points
and Configurations
Device Object
Object Name Instance Property Values
UC800 (Dev Instance) Configurable Non-applicable
BAS-SVP01Q-EN 55
Tracer AdaptiView Panel Upgrade Object Data Points and Configurations
56 BAS-SVP01Q-EN
Tracer AdaptiView Panel Upgrade Object Data Points and Configurations
BAS-SVP01Q-EN 57
Tracer AdaptiView Panel Upgrade Object Data Points and Configurations
58 BAS-SVP01Q-EN
Tracer AdaptiView Panel Upgrade Object Data Points and Configurations
BAS-SVP01Q-EN 59
Tracer AdaptiView Panel Upgrade Object Data Points and Configurations
60 BAS-SVP01Q-EN
Tracer AdaptiView Panel Upgrade Object Data Points and Configurations
BAS-SVP01Q-EN 61
Tracer AdaptiView Panel Upgrade Object Data Points and Configurations
62 BAS-SVP01Q-EN
Tracer AdaptiView Panel Upgrade Object Data Points and Configurations
BAS-SVP01Q-EN 63
Tracer AdaptiView Panel Upgrade Object Data Points and Configurations
64 BAS-SVP01Q-EN
Tracer AdaptiView Panel Upgrade Object Data Points and Configurations
BAS-SVP01Q-EN 65
Modbus
The Tracer® UC800 controller is an equipment unit controller which provides the equipment
system sequences and performs closed-loop control. In addition, the UC800 integrates with
Modbus® systems and devices using Modbus® RTU protocol.
66 BAS-SVP01Q-EN
Modbus CenTraVac Chiller Data Points Descriptions and
Configurations
Holding Registers; Read/Write (Sorted by Register)
This function code is used to read the contents of a contiguous block of holding registers in a
remote device.
Table 14. Modbus CenTraVac chiller read/write
Register Register
Register Object Name Register Valid Range
Type Value
0 = Stop
BAS Chiller Auto Stop Command 40001 Binary 0,1
1 = Auto
0= Cool
1= Heat
BAS Chiller Mode Command 40002 Enumeration 0 to 3
2= Ice
3= Free Cool
0°F to 86°F
BAS Chilled Water Setpoint 40003 Temperature depending on installed options
(-17.78°C to 30.0°C)
BAS Current Limit Setpoint 40004 Percent 0–100
80°F to 140°F
BAS Hot Water Setpoint 40005 Temperature
(26.7°C to 60°C)
BAS Base Loading Setpoint 40006 Percent 0–100
0 = Disable
BAS Base Loading Enable 40007 Binary 0,1
1 = Enable
0 = False
BAS Diagnostic Reset 40008 Binary 0,1
1 = True
Evaporator Pump Override 40009 Binary 0,1
Condenser Pump Override 40010 Binary 0,1
BAS-SVP01Q-EN 67
Modbus CenTraVac Chiller Data Points Descriptions and Configurations
68 BAS-SVP01Q-EN
Modbus CenTraVac Chiller Data Points Descriptions and Configurations
BAS-SVP01Q-EN 69
Modbus CenTraVac Chiller Data Points Descriptions and Configurations
70 BAS-SVP01Q-EN
Modbus CenTraVac Chiller Data Points Descriptions and Configurations
Temperature s16
0.01 °C (100 = 1 °C);
Time Interval u32 Seconds
Voltage u16 Volts
None u16 Not applicable
BAS-SVP01Q-EN 71
Modbus Duplex CenTraVac Chiller Data Points
Descriptions and Configurations
Holding Registers; Read/Write (Sorted by Register)
This function code is used to read the contents of a contiguous block of holding registers in a
remote device.
Table 17. Modbus Duplex CenTraVac chiller read/write
Register Register
Register Object Name Register Valid Range
Type Value
BAS Chiller Auto Stop Command 40001 Binary 0,1
0= Cool
1= Heat
BAS Chiller Mode Command 40002 Enumeration 0 to 3
2= Ice
3= Free Cool
0°F to 75°F
BAS Chilled Water Setpoint 40003 Temperature (depending on installed options)
(-17.78°C to 23.9°C)
BAS Current Limit Setpoint 40004 Percent 0–100
80°F to 140°F
BAS Hot Water Setpoint 40005 Temperature
(26.7°C to 60°C)
BAS Base Loading Setpoint 40006 Percent 0–100
BAS Base Loading Enable 40007 Binary 0,1
BAS Diagnostic Reset 40008 Binary 0,1
Evaporator Pump Override 40009 Binary 0,1
Condenser Pump Override 40010 Binary 0,1
0= Auto
Circuit Lockout Ckt1 40011 Binary 0,1
1= Locked
0= Auto
Circuit Lockout Ckt2 40012 Binary 0,1
1= Locked
72 BAS-SVP01Q-EN
Modbus Duplex CenTraVac Chiller Data Points Descriptions and Configurations
BAS-SVP01Q-EN 73
Modbus Duplex CenTraVac Chiller Data Points Descriptions and Configurations
74 BAS-SVP01Q-EN
Modbus Duplex CenTraVac Chiller Data Points Descriptions and Configurations
BAS-SVP01Q-EN 75
Modbus Duplex CenTraVac Chiller Data Points Descriptions and Configurations
76 BAS-SVP01Q-EN
Modbus Duplex CenTraVac Chiller Data Points Descriptions and Configurations
BAS-SVP01Q-EN 77
Modbus Duplex CenTraVac Chiller Data Points Descriptions and Configurations
Temperature s16
0.01 °C (100 = 1 °C);
Time Interval u32 Seconds
Voltage u16 Volts
None u16 Not applicable
78 BAS-SVP01Q-EN
Modbus Tracer AdaptiView Data Points Descriptions
and Configurations
Holding Registers; Read/Write (Sorted by Register)
This function code is used to read the contents of a contiguous block of holding registers in a
remote device.
Table 20. Modbus Tracer AdaptiView read/write
Register Register
Register Object Name Register Valid Range
Type Value
BAS Chiller Auto Stop Command 40001 Binary 0,1
0 = Cool
1 = Heat
BAS Chiller Mode Command 40002 Enumeration 0 to 3
2 = Ice
3 = Free Cool
0°F to 75°F
BAS Chilled Water Setpoint 40003 Temperature (depending on installed options)
(-17.78°C to 23.9°C)
BAS Current Limit Setpoint 40004 Percent 0–100
80°F to 140°F
BAS Hot Water Setpoint 40005 Temperature
(26.7°C to 60°C)
BAS Base Loading Setpoint 40006 Percent 0–100
BAS Base Loading Enable 40007 Binary 0,1
BAS Diagnostic Reset 40008 Binary 0,1
BAS-SVP01Q-EN 79
Modbus Tracer AdaptiView Data Points Descriptions and Configurations
80 BAS-SVP01Q-EN
Modbus Tracer AdaptiView Data Points Descriptions and Configurations
BAS-SVP01Q-EN 81
Modbus Tracer AdaptiView Data Points Descriptions and Configurations
Temperature s16
0.01 °C (100 = 1 °C);
82 BAS-SVP01Q-EN
Modbus Tracer AdaptiView Data Points Descriptions and Configurations
BAS-SVP01Q-EN 83
3DC (Hex)/3DC (Dec) Listings with Software Part
Number
CenTraVac Chillers
Table 23. CenTraVac chiller software
3 DC (Hex) 3 DC (Dec) Diagnostic Name
Many of the codes in this listing are the same. Refer to the local display for more detail.
87 135 External Chilled/Hot Water Setpoint
89 137 External Current Limit Setpoint
08E 142 Evaporator Entering Water Temp Sensor
08F 143 Condenser Saturated Refrigerant Temp Sensor
09A 154 Condenser Entering Water Temp Sensor
09B 155 Condenser Leaving Water Temp Sensor
0A1 161 Outdoor Air Temp Sensor
0A4 164 Motor Winding Temperature 1 Sensor
0A7 167 Motor Winding Temperature 2 Sensor
0A8 168 Motor Winding Temperature 3 Sensor
0A9 169 Oil Tank Temperature Sensor
0AB 171 Evaporator Leaving Water Temp Sensor
0AC 172 Condenser Refrigerant Pressure Xdcr
0AD 173 Evap Saturated Refrigerant Temp Sensor
0AF 175 Inboard Bearing Temperature Sensor
0B0 176 Outboard Bearing Temperature Sensor
0C5 197 Low Evap Leaving Water Temp: Unit Off
0C6 198 Low Evap Leaving Water Temp: Unit On
0CA 202 EM Starter Contactor Interrupt Failure
0CA 202 SS Starter Contactor Interrupt Failure
0D7 215 Over Voltage
0D8 216 Under Voltage
0D9 217 EM Power Loss
0D9 217 MP: Reset Has Occurred
0D9 217 SS Power Loss
0DA 218 Extended Compressor Surge
0DA 218 Extended Compressor Surge
0DC 220 Condenser Water Flow Overdue
0E2 226 EM Momentary Power Loss
0E2 226 SS Momentary Power Loss
0E4 228 AFD Output Phase Loss
0E4 228 EM Phase Loss
0E4 228 SS Phase Loss
0E5 229 EM Phase Reversal
0E5 229 SS Phase Reversal
0E8 232 Unexpected Differential Oil Pressure
0EA 234 High Inboard Bearing Temperature
0EB 235 High Outboard Bearing Temperature
0EC 236 AFD Motor Current Overload
0EC 236 EM Motor Current Overload
0EC 236 SS Motor Current Overload
84 BAS-SVP01Q-EN
3DC (Hex)/3DC (Dec) Listings with Software Part Number
BAS-SVP01Q-EN 85
3DC (Hex)/3DC (Dec) Listings with Software Part Number
86 BAS-SVP01Q-EN
3DC (Hex)/3DC (Dec) Listings with Software Part Number
BAS-SVP01Q-EN 87
3DC (Hex)/3DC (Dec) Listings with Software Part Number
88 BAS-SVP01Q-EN
3DC (Hex)/3DC (Dec) Listings with Software Part Number
BAS-SVP01Q-EN 89
3DC (Hex)/3DC (Dec) Listings with Software Part Number
CenTraVac/Duplex Chillers
Table 24. CenTraVac/Duplex chiller software
3 DC (Hex) 3 DC (Dec) Diagnostic Name
Many of the codes in this listing are the same. Refer to the local display for more detail.
87 135 External Chilled/Hot Water Setpoint
89 137 External Current Limit Setpoint
08F 143 Condenser Saturated Refrigerant Temp Sensor
09A 154 Condenser Entering Water Temp Sensor
09B 155 Condenser Leaving Water Temp Sensor
0A1 161 Outdoor Air Temp Sensor
0A4 164 Motor Winding Temperature 1 Sensor
0A7 167 Motor Winding Temperature 2 Sensor
0A8 168 Motor Winding Temperature 3 Sensor
0A9 169 Oil Tank Temperature Sensor
0AB 171 Evaporator Leaving Water Temp Sensor
0AC 172 Condenser Refrigerant Pressure Xdcr
0AD 173 Evap Saturated Refrigerant Temp Sensor
0AF 175 Inboard Bearing Temp Sensor
0B0 176 Outboard Bearing Temp Sensor
0C5 197 Low Evap Leaving Water Temp: Unit Off
0C6 198 Low Evap Leaving Water Temp: Unit On
0CA 202 Starter Contactor Interrupt Failure
0D7 215 Over Voltage
0D8 216 Under Voltage
0D9 217 MP: Reset Has Occurred
0D9 217 Power Loss
0DA 218 Extended Compressor Surge
0DC 220 Condenser Water Flow Overdue
0E2 226 Momentary Power Loss
0E4 228 Current L1 Loss
0E4 228 Current L2 Loss
0E4 228 Current L3 Loss
0E4 228 Phase Loss
0E5 229 Phase Reversal
0EA 234 High Inboard Bearing Temperature
0EB 235 High Outboard Bearing Temp
0EC 236 Motor Current Overload
0ED 237 Evaporator Water Flow Lost
0EE 238 Compressor did Accelerate: Shutdown
0F0 240 Starter Did Not Transition
0F2 242 Low Differential Oil Pressure
0F4 244 High Oil Temperature
0F5 245 Condenser High Pressure Cutout
0F7 247 Condenser Water Flow Lost
0FB 251 Low Evaporator Refrigerant Temperature
0FD 253 Emergency Stop
188 392 Starter Dry Run Test
189 393 Solid State Starter Fault
18B 395 High Motor Winding Temperature 1
90 BAS-SVP01Q-EN
3DC (Hex)/3DC (Dec) Listings with Software Part Number
BAS-SVP01Q-EN 91
3DC (Hex)/3DC (Dec) Listings with Software Part Number
92 BAS-SVP01Q-EN
3DC (Hex)/3DC (Dec) Listings with Software Part Number
BAS-SVP01Q-EN 93
3DC (Hex)/3DC (Dec) Listings with Software Part Number
94 BAS-SVP01Q-EN
3DC (Hex)/3DC (Dec) Listings with Software Part Number
BAS-SVP01Q-EN 95
3DC (Hex)/3DC (Dec) Listings with Software Part Number
96 BAS-SVP01Q-EN
3DC (Hex)/3DC (Dec) Listings with Software Part Number
BAS-SVP01Q-EN 97
3DC (Hex)/3DC (Dec) Listings with Software Part Number
98 BAS-SVP01Q-EN
3DC (Hex)/3DC (Dec) Listings with Software Part Number
BAS-SVP01Q-EN 99
3DC (Hex)/3DC (Dec) Listings with Software Part Number
100 BAS-SVP01Q-EN
3DC (Hex)/3DC (Dec) Listings with Software Part Number
BAS-SVP01Q-EN 101
Resources
• Installation, Operation, and Maintenance: CVHE, CVHF, and CVHG Water-cooled CenTraVac
Chillers with Tracer AdaptiView Control (CVHE-SVX02*-EN)
• Diagnostics Manual: Diagnostic Descriptions, Troubleshooting Tables, and Control
Component Overview Diagnostics Manual for Water-cooled CenTraVac Chillers with Tracer
AdaptiView Control (CTV-SVD03*-EN)
• Hardware and Software Installation Guide: LonTalk Communication Interface for Trane
Chillers with Tracer AdaptiView Control (ACC-SVN100*-EN)
• Tracer TU Online Help
• Getting Started Guide: Tracer TU Service Tool (TTU-SVN02*-EN)
• Programming Guide: Tracer TU Service Tool for Water-cooled CenTraVac Chillers with Tracer
AdaptiView Control (CTV-SVP02*-EN)
N o t e : For further assistance, contact your local Trane sales office.
102 BAS-SVP01Q-EN
Notes
BAS-SVP01Q-EN 103
Trane - by Trane Technologies (NYSE: TT), a global climate innovator - creates comfortable, energy
efficient indoor environments for commercial and residential applications. For more information,
please visit trane.com or tranetechnologies.com.
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without
notice. We are committed to using environmentally conscious print practices.