Professional Documents
Culture Documents
7
1.2 Scope ............................................................................................................................. 7
1.3 Smaller airports............................................................................................................... 7
1.4 Staff responsibilities and inspection requirements.............................................................. 8
1.5 Stock control .................................................................................................................. 8
10.1 General........................................................................................................................54
10.2 Fuelling personnel ........................................................................................................54
10.3 Driving and positioning of vehicles.................................................................................54
10.4 Bonding aircraft and fuelling equipment ......................................................................56
10.5 Fuelling procedures ......................................................................................................56
10.6 Fuelling with passengers on board or embarking or disembarking ...................................65
10.7 Fuelling while aircraft mounted Auxiliary Power Units (APUs) are in operation ..................65
10.8 Fuelling while Ground Power Units (GPUs) are in operation .............................................66
A3.1 Monthly inspection all airport depot and fuelling equipment hoses hoses................................79
A3.2 Pressure testing fuelling equipment hoses...................................................................79
................................
A3.3 Damaged hoses ...........................................................................................................80
................................
A3.4 Flexible joints...............................................................................................................80
................................
A11.1 Introduction...............................................................................................................97
A11.2 Application of soak testing ..........................................................................................97
ASTM D2276/IP 216 Standard Test Method for Particulate Contaminant in Aviation Turbine Fuel by Line Sampling
ASTM D2624 or IP274 Standard Test Methods for Electrical Conductivity of Aviation and Distillate Fuels
ASTM D3241 Jet Fuel Thermal Oxidation Test
ASTM D6469 Standard Guide for Microbial Contamination in Fuels and Fuel Systems
ASTM D6986 Standard Test Method for Free Water, Particulate, and Other Contamination in Aviation Fuels (Visual Inspection Procedures)
ASTM D4176 Standard Test Method for Free Water and Particulate Contamination in Distillate Fuels
ASTM D4057 Standard Practice for Manual Sampling of Petroleum and Petroleum Products
ASTM D4306 Standard Practice for Aviation Fuel Sample Containers for Tests affected by Trace Contamination
ASTM D7566 Standard Specification for Aviation Turbine Fuel Containing Synthesized Hydrocarbons
EN 12312-5 Aircraft Ground Support Equipment-Specific Requirements - Part 5 Aircraft Fuelling Equipment
BS EN 14015:2004 Specification for the design and manufacture of site built, vertical, cylindrical, flat-bottomed, above ground, welded, steel tanks for the
storage of liquids at ambient temperature and above
BS 3492 Specification for road and rail tanker hoses and hose assemblies for petroleum products, including aviation fuels
BS 5842 Specification for thermoplastic hose assemblies for dock, road and tanker use
ISO 1825 (EI1529) Rubber hoses and hose assemblies for aircraft ground fuelling and defuelling
ISO 3170 (IP 475) Methods of Test for Petroleum and its Products. BS 2000 475: Petroleum Liquids. Manual Sampling)
ISO 6789 Assembly tools for screws and nuts hand torque tools requirements and test methods for design conformance testing and recalibration
procedure
ISO/IEC Guide 43-1:1997 Proficiency testing by interlaboratory comparisons
AS 1852 Nozzles and Ports Gravity Fuelling Interface Standard for Civil Aircraft
ARP 5789 Aviation Fuel Facilities
ARP 5818 Design & Operation of Aircraft Refuelling Tanker Vehicles
AS 5877 Detailed Specification for Aircraft Pressure Refuelling Nozzle
The following chapters in this document detail standards that can be used for the design of
airport storage and handling systems, where relevant to quality control considerations, for
the design and maintenance of fuelling equipment, and for the operating and quality
control procedures to be used.
in section 1.3 and may also be used as a reference for general aviation and other small
airfield operations. Procedures applicable to other airport locations may be found in the
following separate documents:
(a) Aviation Fuel Quality Control and Operating Standards for Into-Plane Fuelling Services
(JIG 1).
(b) Aviation Fuel Quality Control and Operating Standards for Airport Depots and Hydrants
(JIG 2).
smaller a
(a) Aviation fuel is supplied to the location by road or rail transport, and
(b) Fuelling equipment has a maximum flow rate of 1,000 litres/min per delivery hose, and
(c) The total number of fuelling operations per year is less than 10,000 and throughput is
less than 10 million litres, and
(d) If a hydrant is used for fuelling, it has a diameter of 150
At locations where there are no mobile fuellers, and fuelling is from fixed fuelling cabinets,
the limits shown in (c) are not applicable.
There shall be a process to ensure that the location is inspected at least once per
year by suitably qualified personnel. The designated person shall accommodate
and be involved in inspections by the aviation fuel supplying com company, IATA
airlines and civil aviation authorities. As a minimum, the designated person shall
attend the close
close-out meetings at the conclusion of inspection visits.
Where inspection reports are required to be recorded in the JIG Inspection
Tracking System the designated person shall ensure that the status of
recommendations is regularly updated.
The quantities of each grade of fuel received, stored and delivered shall be accurately
measured, recorded and monitored. Effective stock control can assist in detecting fuel leaks
and in detecting fraudulent activity.
It is the responsibility of the designated person to ensure that accurate stock records are
maintained and that stock losses are monitored. Further guidance may be requested from
the fuel supplier.
The quantity of fuel in stock should be measured on a daily basis, although this may be
relaxed to a weekly check at low activity locations.
All personnel should attend fire drills at least once per year.
year Personnel should be
trained in the use of fire extinguishers and be famfamiliar with the location of fuel
emergency stop buttons.
Smoking is only permitted in designated safe areas.
Apron speed limits shall be observed by fuel service vehicles and correct fuelling
procedures followed at all times. Where no speed limits exist, a maximum of
25km/hour shall be observed.
Working from height, even as little as one metre, is hazardous and a slip or fall
can easily cause a sprain or a broken bone. When climbing up or down ladders
three points of contact shall be maintained at all times (i.e. one hand, two feet or
two hands and one foot) - nothing should be hand-held. Damaged or unstable
ladders and steps shall not be used and care shall be taken not to over-reach or
lean away from the ladder/steps. Care shall also be taken when using low level
fuelling steps and portable work platforms.
Facilities for first aid treatment shall be available and staff should be familiar with
the location of the first aid kit. Procedures shall ensure that appropriate medical
aid and ambulance services can be obtained at short notice.
Adequate washing facilities shall be available and instruction given on the care to
be exercised when handling products to avoid contact with the skin. Portable eye
wash equipment shall be provided and a suitably located emergency shower
should also be available. Clothing soaked with fuel shall be removed under a
shower without delay and a shower or bath taken.
To reduce health hazards in handling aviation products, safe handling precautions
(extracted from aviation fuel supplier Material Safety Data Sheets) shall be
available and should be displayed.
Mobile phones shall not be taken into the fuel storage area unless intrinsically safe
for use in the applicable hazardous area/zone and approval is given, and shall not
be used while performing tasks such as tank draining and fuel sampling. Mobile
phones
es shall not be used by operators during fuelling operations.
New personnel shall be thoroughly trained in all operations and procedures which they will
be called upon to perform in the course of their duties, and in all actions to be taken in the
event of an emergency. Existing personnel called upon to undertake new tasks shall be
similarly trained before undertaking the new task without supervision.
An employee training record shall be maintained for employee which indicates for
which tasks training has been given and the date of such training.
Follow-up job observation (with refresher training if it is found to be necessary) is to be
undertaken by supervisory or training staff at a frequency determined by the designated
person, based on his/her assessment of ongoing operator performance. The dates and
results of these follow-
Training is to cover routine standard tasks such as sampling, tank and filter draining, etc.,
and tasks which are specific to a location, such as fuel receipts, tank management, etc. The
latter tasks shall be the subject of specific written procedures which also form the basis of
the training given. Where appropriate, some of these written procedures should be
displayed at the work location.
Airport facilities shall be secured to prevent the access of unauthorised people, theft of fuel
and equipment, contamination of fuel and the use of equipment for illegal activities. Keys
should be removed from unattended vehicles. Security measures to be considered include
the use of contract guards, perimeter fencing, alarm systems and the locking of valves.
Spillage and leakage shall be avoided at all times. Any uncontrolled release of product
represents a fire hazard as well as an environmental pollutant. Even the smallest of drips
from a leaking valve or flange may eventually result in environmental damage unless
appropriate action is taken to stop the leak and clean up the affected area. Any testing
activity involving the handling of fuel is a potential source of spillage and it is important that
care is taken during all product handling procedures to avoid spilling any product.
Procedures shall be established to assess all changes for potential hazards and take
appropriate action to manage any changes that may affect the operation.
Changes to the following should be evaluated for potential HSSE impacts:
Plant and facilities
Equipment
Hardware or software
Operating procedures
Design and construction
onstruction
Maintenance procedures
dures
Organisational structures
tructures and responsibilities
Personnel training
raining or competency requirements
Legislative and regulatory requirements
(a) Samples shall be drawn from a gauge hatch or other suitable opening giving
direct and unrestricted access to the bulk of the liquid.
(b) Containers shall be as specified in Section 3
3.2
(c) Before sampling, the apparatus and the container shall be flushed and rinsed
thoroughly at least three times with the product to be sampled and allowed
to drain before use.
(d) No sample container shall be completely filled with liquid. Approximately 5%
ullage shall always be left to allow for expansion.
(e) Containers shall be sealed and labelled immediately after filling. The label
attached to the sealed container should bear the following relevant
information where applicable:
Sample no.:
Date and time:
Taken by:
Place:
Type of sample:
Tank no./vehicle compartment no./or location:
Batch no.:
Grade or specification:
Test required/performed:
Clear, clean glass jars of at least 1 litre capacity, with wide necks and screw caps, or closed
, shall be used for product examination in
connection with the Appearance Check and Visual Check procedure (see 3.4). Buckets used
for flushing shall be manufactured from good quality stainless steel or lined with white
enamel
dissipate. Buckets shall be equipped ed with an effective bonding cable and clip. Sample
equipment fabricated from copper or its alloys shall not be used.
When samples are taken for laboratory testing, suitable containers shall be provided by the
laboratory or the fuel supplier. These shall bee carefully rinsed with the fu
fuel at least three
times before preparing the sample. Laboratory testing is required following an aircraft
incident, after significant work on storage tanks such as internal lining and where fuel stock
is static (see 6.1.6).
A sample obtained from the middle depth of the upper third of the tank contents.
A sample obtained by blending Upper, Middle and Lower samples. For a vertical tank of
uniform cross-section, the blend consists of equal parts of the three samples. For horizontal
tanks where the liquid height is less than three metres, a Middle Sample is an acceptable
alternative.
A sample obtained from the material on the bottom surface of the tank or container at its
lowest point.
A sample obtained from the water draw-off or drain point of a storage or vehicle tank or
filter body.
A sample obtained from a line sampling point, drawn while the product is flowing.
This document contains the results of the Recertification Test (see 3.4.2 (b)) and confirms
that the product is satisfactory. It shall be dated and signed by an authorised signatory.
This document contains the results of the Periodic Test (see 3.4.2 (c)) and confirms that
the product is satisfactory. It shall be dated and signed by an authorised signatory.
This document supports any transfer of product, confirming compliance with the relevant
fuel specification and, for Jet A-1, the requirements of the JIG Aviation Fuel Quality
Requirements for Jointly Operated Systems (AFQRJOS) Check List, and contains at least the
following information:
date and time of loading or transfer
grade of fuel
batch number and batch density (at 15oC) of the product in the tank from which it
originated
If required by the fuel supplying company, the density and the temperature of the product
after loading should also be recorded.
This test covers all tests required by the relevant fuel specification and, for
Jet A-1, the latest
atest issue of the JIG Aviation Fuel Quality Requirements for
Jointly Operated Systems (AFQRJOS) Check List.
List.
Unless FAME (Fatty Acid Methyl Ester) can be controlled to limit the exposure
in Jet fuel
uel to less than 5 mg/kg in accordance with JIG Bulletin 75, then in
markets and supply chains where FAME is present in multiproduct systems,
FAME concentration shall be tested by an approved method, wherever Jet
fuel has been transported in multi-product
multi transport systems that also carry
gas oil/diesel fuel or non-dedicated
dedicated storage that may have contained gas oil/
diesel fuel.
Sample quantity required:
Jet A-1 2 litres minimum
Aviation gasoline (Avgas) 25 litres
An approved sample container as specified in section 3.2 shall be used.
This test is carried out to verify that the quality of the aviation fuel
concerned has not changed and remains within the specification limits after
transportation in ocean tankers or multi-product pipelines, etc.
The results of all Recertification Tests shall be checked to confirm that:
the specification limits are met
no significant changes have occurred in any of the properties.
This check should be made by comparing the recertification results with the
corresponding values shown on the last previous analysis made on the fuel
(e.g. with a Refinery Certificate of Quality or previous Certificate of Analysis
or previous Recertification Test Certificate). It is important to check that the
determined properties have not changed. It is the only way to be reasonably
sure that the remaining unchecked specification properties have also not
changed significantly and remain satisfactory.
The check shall be carried out by recording all relevant details on forms of
the type shown in Appendix A8/A9. Acceptable differences are given on the
forms. If one or more of the results exceeds these values then the product
shall not be released until an adequate explanation is found, or until it is
Appearance/colour X X
Saybolt colour X
Distillation X X
Flash point X
Density @ 15oC X X
Reid vapour
apour pressure
ressure X
Freezing point X
Corrosion (copper) X X
Existent gum X X
Lead content (1) X
Knock rating (Motor Method) Lean X
Conductivity and temperature (2)
MSEP X
Thermal stability JFTOT (3)
FAME (4)
This test is carried out to certify that product which has been static in
storage for more than 6 months conforms to the relevant specifications and
that the quality of the product has not changed since the last tests were
carried out.
Samples for periodic tests should be taken from each tank which has
contained product and which has had no product receipts for 6 months.
Samples should also be taken from each tank in which less than half of the
product has been replaced during the 6-month
month period.
Drummed stock shall be subjected
ubjected to a Periodic Test after 12 months from
filling date.. See also section 6.3 and Appendix A12 for more information
about drums.
The results of all periodic tests should be checked carefully against previous
analysis reports to confirm that no signif
significant changes have occurred, taking
note
ote of the comments under section 3.4.2 (b) above in respect of
recertification tests.
Test requirements are shown in the table below.
Appearance/colour
Appearance/ X X
Saybolt colour X
Distillation X X
Flash point X
Density @ 15oC X X
Reid vapour pressure X
Corrosion (copper) X X
Existent gum X X
Lead content X
Knock rating (Motor Method) Lean X
Conductivity and temperature (1)
MSEP X
Thermal stability JFTOT X
Sample quantity required:
Jet A-1: 2 litres minimum
Avgas: 4 litres
An approved container as specified in sub-section 3.2 shall be used.
(1) To be carried out on bulk stock in storage or immediately after taking a
sample from bulk storage.
Appearance/colour X X
Particulate contaminant (visual) X X
Water visual X X
A Visual Check is an Appearance Check for Jet fuel with the addition of a
chemical water check (see 3.4.2 (h)). Use an IATA recommended chemical
water detector.
Samples for a Visual Check shall be drawn into scrupulously clean, clear
sampling containers).
The primary field check for suitability of aviation fuel is the Appearance
Check. This may be confirmed by the use of a chemical water detector test
for Jet fuel to indicate the presence of free water in the sample. A chemical
water detector test is mandatory for samples that can be considered
representative of into-plane fuel quality, although it may also be used in
other sampling applications where it is considered appropriate to have a
verification of free water status. (See 3.4.2 (e) for permitted chemical water
detectors.)
Operation
primary containment.
Tank overfill containment is provided (the volume and extent of overfill
containment shall be assessed against the environmental risk, but will typically
be based on flow rate and time).
Horizontal double-skinned tanks have all pipework entries above the maximum
liquid level, but discharge shall be at low level inside the tank.
The second skin containment volume meets national regulations (110% rule
may not apply).
Semi-buried or buried tanks may not require a bund; however, the overfill
containment shall be provided as above.
The number and size of tanks should be sufficient to provide adequate working
capacity, taking into account peak period airport requirements, supply
replenishment arrangements and emergency stock coverage. Allowance should
also be made for settling, testing and tank cleaning requirements.
A single filter for both receipt and fueller loading may be u used, but the preferred
option is separate inlet and outlet filter vessels. At locations where a single filter is
used for both receipt and fueller loading, a filter water separator qualified to the
latest edition of EI 1581
581 is the preferred option for both Jet fuel and Avgas.
Additional quality assurance checks shall be considered in the case of a single
inlet/outlet filter
filter.
For locations where receipts occur less than mo monthly, a 100 mesh strainer may be
used as an alternative to a receipt filter. Increased settling times shall be observed
and delivery/fueller loading shall be via a filter vessel meeting the above
requirements for Jet Fuel and Avgas.
Filtration used for delivery to aircraft shall not be used for any other purpose.
All filtration and water separation equipment shall be maintained and checked
regularly, as detailed in Appendix A1.
The operation of small low-pressure aviation fuel hydrant systems with pipework of 150mm
( ) diameter or less is covered in Appendix A7 of this document. Recommended design
features for other hydrant systems are contained in the Aviation Fuel Quality Control and
Operating Standards for Airport Depots and Hydrants (JIG 2).
Road bridging vehicles and rail tank cars supplying airport depots should be dedicated to
one grade of aviation product and be provided with grade selective couplings. Where
equipment is fitted with more than one size/design of discharge coupling, the unused one
should be sealed or, preferably, removed. Adaptors that change the size/design of outlet
couplings when connected to vehicle or rail tank car outlets should not be used.
Where it is necessary to switch vehicles or rail tank cars between grades, it is the
responsibility of the aviation fuel supplying company to ensure that effective cleaning and
change of grade procedures (draining, flushing and testing) are followed and recorded and
that equipment outlet couplings and grade markings are changed. The receipt location shall
ensure that their suppliers provide documentation, including cleaning certification, for all
grade changes.
The switching of road or rail tank cars between gas oil/diesel and aviation fuel is strongly
discouraged. FAME (Fatty Acid Methyl Ester) concentration shall be tested by an approved
method, wherever Jet fuel has been transported in non non-dedicated vehicles that may have
carried gas oil/diesel fuel and the cha
change of use procedure shall be validated to ensure that
the permitted FAME level in Jet fuel has not been exceeded. Note that FAME may be
present due to carryover or cross-contamination within the common unsegregated
distribution system for fuels. Therefore, this limit shall be checked following transportation
and/or storage in multi-product distribution systems known to present a risk of FAME
contamination (see Annex G of Defence Standard 91-91 for further guidance).
The receipt location shall be notified in advance of every change of service between diesel
and aviation fuel.
On arrival at the depot the vehicle or rail tank cars should be checked to ensure
that the required seals (where secured to manlids, outlet, filling and drain points)
are intact and that the grade markings on the sides and at the outlets are correct.
If it is necessary to work at height to carry out these checks, a risk assessment
shall be carried out and appropriate measures put in place (such as fall protection
equipment) to minimise risk. The documents shall correctly identify the equipment,
and the quantity and grade of product. A copy of the Release Certificate and,
where equipment is not grade-dedicated, details of the previous load carried and
the most recent change of grade procedure shall be available and be checked
before receipt of the product.
At some locations the offloading of road tank cars and the quality control checks
before discharge may be performed by the delivery driver. However, driver
controlled deliveries
eliveries shall only be made where the vehicles are dedicated, bottom
loaded, fitted with grade selective systems and where approved by the aviation
fuel supplying company.
The location management and the supplying company shall also introduce
additional procedures and equipment to avoid the possibility of a spillage or of
receiving contaminated product. The following contr
controls are required:
To ensure that the driver is in constant attendance, the normal journey time
from the supplying location and the airport shall be less than 4 hours and the
vehicle shall not be parked overnight.
The offloading facility shall be equipped with a deadman of a type that
requires periodic action by the driver to maintain the flow; and
Receiving tanks shall be fitted with a high-level alarm system that shuts down
the fuel flow (see section 4.2.3).
Electronic densitometers meeting IP 559 that convert density readings to density
at standard temperature are recommended because of their ease of use and
accuracy.
The scope of the additional tasks to be performed by the drivers at the receiving
location shall be clearly identified and specific written procedures prepared. All
drivers authorised to perform driver controlled deliveries shall receive training in
the additional tasks to be performed and the training shall be recorded. The
receiving location shall maintain records of the training provided and shall only
allow access to those drivers who have been trained.
After fuel has been received into storage tanks the inlet and outlet valves shall be
closed. A system to indicate the status of the product in the tank shall be used.
et valve or by
the use of a control system to ensure that the valves remain closed until product
release.
Provided that free water and sediment can be consistently maintained at low levels
by means of approved filtration (see section 4.4) and that tanks meet the design
requirements of section 4.2 (including floating suctions for all Jet fuel tanks),
minimum fuel settling times before release are:
Horizontal tanks: 1 hour
Vertical tanks:
tanks 2 hours
In any other case, minimum settling times are:
Jet fuel:
uel: 3 hours per metre depth of fuel or 24 hours, whichever is less.
Avgas: 45 minutes per metre depth of fuel.
The product in the tank shall be given a local batch number before tank release (Release
Certificate - see 3.4 (e)). After settling, the tank sump/low point shall be checked for the
presence of water and sediment by flushing. Following the recording of a satisfactory
Control Check, where the density is compared against the calculated expected density, and
including a Visual Check, the tank may be released into service.
Fuel System Icing Inhibitor (FSII) additive may be required at some locations. Where
applicable, guidance on dosing and handling precautions for FSII should be provided by the
aviation fuel supplier and strictly enforced. Where the use of aerosol containers of FSII is
containers of FSII.
Other specification-approved additives may only be used in accordance with guidance from
the aviation fuel supplier. Unapproved additives are not to be used under any
circumstances.
All checks shall be recorded in daily/periodic record documents (see Chapter 11).
Jet fuel tanks shall be internally inspected and cleaned if necessary within
12 months of commissioning and subsequently in accordance with the table below,
taking account of the safety precautions outlined in section 2.1. Internal inspection
and cleaning is subject to a maximum frequency of 5 years, provided it is allowed
by local regulatory requirements and the necessary conditions have been met (see
c below).
Airport storage tank cleaning intervals may be extended to a maximum of 10 years
from the date of last cleaning by approved variance from year 5 and if supported
by acceptable documented PQ history, annual visual al inspection without entry, and
annual microbial growth test with acceptable results since the last internal
cleaning.
Given that tank entry and cleaning is a higher risk activity, opportunities to clean
tanks in conjunction with other work should be take taken, e.g. a tank has been
drained down and gas freed for mechanical inspection or repair.
Notes:
shown.
Necessary conditions:
Historic tank cleaning and inspection records show that only small amounts
of contamination have been found.
For internal visual inspection without entry, the tank internal surfaces can
be adequately inspected (i.e. views of the floor and sump are not
obstructed by internal baffles, floating decks or blankets, etc.)*.
Full internal epoxy lining.
* Where the visual inspection without entry does not afford clear
unobstructed views
iews of the internal surfaces, and provided the tank
design meets the minimum requirements of section 4.2, then annua
annual
microbial growth tests with results within permissible levels is an
acceptable alternative.
No chemicals or cleaning materials that could adversely affect the aviation fuel to
be stored in the tanks shall be used unless required for decontamination of the
tank. If it was found necessary to use a cleaning chemical or if repairs were
carried
d out, a Composite Sample shall be taken for a Periodic Test before product
release.
Tank cleaning shall be carried out by an approved contractor, experienced in
confined entry procedures. Detailed records of the types and quantity of sediment
found, and of the condition of the tank interior fittings and coatings, shall be
maintained. A suitable form is shown as Appendix A2. Tank inspection and
cleaning records shall be retained. The dates of the most recent tank cleaning
should be marked on the tank shell.
Where no chemicals or cleaning materials have been used and no repairs to the
tank internal components have been carried out, the product release procedures
shown in section 5.5 are applicable after refilling.
Product recovery tanks shall be inspected, without entry, quarterly for cleanliness
and condition. An IATA-endorsed microbial growth test (see section 3.4.2 (g)) on a
sump sample after flushing may be carried out as an alternative to quarterly visual
inspection. Cleaning and repairs to internal lining shall be carried out where there
is cause.
Tank internal surfaces are dirty, i.e. the inspection reveals microbial growth or
build-up of sediment exceeding approximately 20% of the tank bottom
surface.
Presence of microbiological contamination, excessive dirt, rust or other debris
in water drain samples. Fuel quality downstream indicates excessive
contamination, e.g. short filter life.
Tank-side fast flush tanks shall be kept clean and empty when not in use for
draining and sampling.
pressure control valves. Establish maximum flow into storage and then slowly
close the return line valve over 10-15 seconds. The pressure at zero flow
represents the maximum pump outlet pressure.
All fuelling vehicles and trailers shall carry at least two 9kg (unless a different size
is specified by local legislation) dry chemical type fire extinguishers in quick
release housings consistent with local regulations. At least one extinguisher shall
be readily accessible from either side of the vehicle. For small capacity trailers
(less than 500 litres) and fixed fuelling cabinets, a single 9kg extinguisher is
Fuelling equipment shalll be designed for use with petroleum products and
constructed to acceptable safety standards, incorporating satisfactory tank venting
arrangements, appropriate pressure relief valves, hydrostatically tested pumping
circuits, electrical components appropriate
te for the area classification of the location
in question, air braking safeguards, externally mounted emergency stop buttons,
etc. All new fuelling vehicles should be powered by diesel engines or electric
motors. All new fuelling equipment and compatible replacement components for
existing equipment shall meet the current requirements of the relevant
specifications.
Further information may be found in EN 12312 12312-5 Aircraft Ground Support
Equipment Part 5: Aircraft Fuelling Equipment.
All fuelling vehicles
vehicles shall carry only one grade of product and the grade
identification (see
see EI 1542) shall be displayed prominently on each side, at the
control panel and at all fill points.
All motorised/self
motorised/self-propelled fuelling vehicles shall be fitted with an interlock system
to prevent drive
drive-away, roll-away and jet blast blow-away during fuelling of aircraft.
This system shall be activated whenever the vehicle pump or Power Take Off
(PTO) is engaged and/or when any of the following components are removed from
their normally stowed positions:
delivery hose pressure couplings
overwing fuelling nozzles
fuelling cabinet doors
fueller tank-top hand rails
movable fuelling platforms
hydrant inlet couplers.
Interlock switches shall also be fitted to fueller bottom-loading connections and
should be fitted at vehicle bonding cable clip stowage. Seat interlocks should not
be fitted to driver seats.
The interlock system shall be designed:
to fail safe (i.e. air operated interlocks apply vehicle brakes if air pressure
drops)
The interlock override allows a vehicle to be moved away from the aircraft in the
event of interlock
terlock failure. The override switch shall be safety wired and sealed in
the interlock operating position. The sealing wire shall be easy to break in an
emergency.
The following lights (recommended 50mm diameter) shall be fitted in a promin prominent
position in the vehicle cab and the emitted light shall be clearly visible to the driver
when seated in the normal driving position
position:
n interlock status warning light - amber in colour - which is alight whenever
an
an interlock protected component is remo
removed from its stowed position
n emergency override status warning light - red in colour - which is alight
an
whenever the override mechanism is moved from its normal operating
position..
position
The use of LEDs (Light Emitting Diodes) as an alternative to conventional warning
lights should be considered because of their reliability and long service life.
Audible alarms associated with the above warning lights should be considered. For
light
is on and a louder external alarm to indicate that the interlock system is
overridden.
An audible alarm that is activated if the cab door is opened when the handbrake is
not engaged should be considered.
Externally mounted emergency engine stop controls (red coloured), one on each
side of the vehicle, shall be provided on all fuelling vehicles, clearly identified with
a label explaining their purpose, and shall be accessible from the ground at all
times. An additional engine stop control shall be fitted to elevating fuelling
platforms.
Operating the engine stop on a mobile fueller should also stop the fuel flow. If the
cargo pump is powered by an independent source such as an electric motor or
separate diesel engine, a separate fuel emergency stop control shall be fitted.
Deadman systems may include an override feature that allows the operator to
complete a fuelling operation in the event of a deadman failure. Where fitted, the
preferred override is a push button type that requires the operator to push and
hold the button in the depressed position to maintain the flow. If not of the push
button type, the override switch shall be sealed.
The fuelling system shall be designed so that all fuel which passes through the
delivery meter and filter is delivered to the aircraft and cannot be diverted
elsewhere. This is particularly relevant to fuellers if they are designed to defuel.
For new builds (from January 2014) a meter by-pass line is not an acceptable
design. Any non-compliant vehicles produced pre-2014 shall have been modified
to include a double valve arrangement with a means of positive confirmation (e.g.
drain valve between the valves) that no fuel is being diverted to the defuel circuit
during normal fuelling. Alternatively, the vehicle shall have the defuel circuit
drained and permanently disconnected.
Tanks shall be constructed of mild steel internally coated with a light coloured
epoxy material, approved as being compatible with aviation fuels, or of aluminium
alloy or stainless steel.
The tank shall drain to a low point sump, provided with a drain line and valve. All
drain and sample lines should have self-closing valves (e.g. spring loaded valves).
Single compartment tanks are preferred, but if multi-compartment tanks are used,
then each compartment shall have separate drain lines not manifolded together.
All drain lines shall have a constant downward slope.
Tanks shall be fitted with suitably sized vents based on maximum loading and
delivery flow rates.
Where fixed fuelling cabinets are used for underwing pressure fuelling, a deadman system
or spring-loaded valve shall be included in the design to ensure that fuellings are
continuously attended.
Engine/pump stop controls shall be easily accessible and clearly identified.
Grade identification (EI 1542) shall be displayed clearly.
For additional fuelling cabinet and trailer design requirements including filters see section
7.1.
Buckets and metal containers used for fuel draining shall be bonded to the vehicle
or tank pipework before and during the draining operation and to the receiving
vessel/tank
essel/tank when decanting. Plastic
P or galvanised containers shall not be used.
All electrical bonding wires, clips and reels shall be checked daily for firm
attachment and general condition, and weekly for electrical continuity (there
should be less than 25 ohms resistance). Where applicable, continuity shall be
checked over several revolutions of the reel while unreeling or reeling in the
bonding wire slowly.
In the case of towable platforms and mobile fuelling steps with integral hoses, the
continuity shall be tested between the bonding wire clip and the designated
bonding point on the towable platform for the fuelling vehicle bonding clip.
Permissive bonding systems that require a bonding circuit to allow pump start
have a self-check function and (usually) indicator lights. These types of systems
shall be checked daily for general condition and maintained in accordance with the
All critical gauges (i.e. gauges whose function and accuracy are necessary for safe
operations, including fuelling vehicle/cabinet,
vehicle/cabinet filter and test rig pressure gauges and hose
pressure testing gauges) shall
sha be regularly checked for accuracy and free movement and
adjusted, repaired or replaced as necessary, as follows
follows.
Direct reading gauges (e.g. indicating pump delivery pressures, etc.) shall be
checked 6-monthly
monthly against a suitable master gauge or de dead-weight tester.
Pressure gauges shall be accurate throughout the normal operating range to
within 5% of the maximum scale deflection.
Bourdon tube type differential pressure gauges (used on filtration equipment) shall
be tested similarly, 6-monthly.
Piston type differential pressure gauges (e.g. Haar or Gammon type) need only be
checked for free movement throughout the full piston travel and visually for
correct zeroing. This shall be done every month.
Non-critical gauges should be identifie
should be shown on critical gauges.
Requirements for testing, inspection and maintenance of these units are given in
Appendix A1.
All fueller loading hoses shall meet a recognised industry standard suitable for
aviation fuel. Hoses meeting the requirements of the latest issue of EI 1529
All electrical
lectrical equipment, both fixed and portable, and wiring shall be of a suitable type for
the Hazardous Area of Classification in which it is used and shall be checked and
maintained by a person(s) yearly. Hazardous area classified
electrical equipment (eg ATEX marked and certified) shall only be maintained by trained
personnel. Fixed facility earthing straps/rods shall be checked at least annually for
resistance where fitted to storage ta
tanks, pipework and filter vessels etc.
Emergency shutdown switches shall be tested monthly.
Deadman control
controls, where installed on bridger receipt or fueller loading facilities, shall be
performance tested at least monthly.
Fuelling equipment shall be maintained in sound condition at all times to ensure a reliable,
safe fuelling service. Maintenance work shall be scheduled so that all units receive thorough
instructions.
Defects shall be rectified without delay and equipment removed from service if necessary.
New or transferred fuelling equipment and equipment after major repair or overhaul shall
be thoroughly checked, flushed and tested to ensure that it is in proper operating condition
before being brought into service. All relevant routine equipment checks shall be performed
and the results recorded.
If fuelling equipment is out of service for a period in excess of one month it shall be
checked, flushed and tested to ensure that it is in proper operating condition before being
used. All relevant routine checks shall be performed and the tests recorded.
Functional testing shall be carried out at least weekly in accordance with written
procedures.
Once per week, the complete interlock system shall be tested by attempting to drive the
vehicle from standstill while each interlocked component is removed in turn. The interlock
override seal shall then be broken and the override function checked to ensure that the
vehicle can be moved with a hose coupler removed from stowage. Finally, the override
switch shall be reset, resealed and function tested by the removal of one interlocked
component. The correct function of the warning lights shall also be observed during the
test.
In addition to the complete weekly test, a daily check shall be performed and documented.
This daily check consists of removing at least one of the interlocked components (a
different one each day in rotation) and checking that the interlock switch and light are
working.. If testing identifies a faulty interlock function, the first action shall be to
quarantine the vehicle, to prevent use, and arrange
nge repair work.
The presence of intact interlock override seals shall be checked daily to ensure that the
system has not been overridden. The reason for breaking interlock override seals shall
always be recorded.
: Attempting to drive a heavy fueller from standstill while
whil performing the weekly check
can damage vehicle components. This check should to be performed carefully, particularly
for fuellers fitted with an automatic gearbox, where the power sent to the wheels cannot be
effectively controlled during
ring the test.
The function of the externally mounted emergency engine/fuelling stop system shall be
checked monthly.
The correct operation of pressure/surge control equipment shall be checked under dynamic
conditions at least every 6 months in accordance with procedures approved by the fuel
supplier.
The correct operation and performance of the deadman control system shall be checked at
least every month in accordance with procedures approved by the fuel supplier (see section
7.2.5 for operating requirements). This may be carried out during aircraft fuelling. An
annual check to confirm the setting of the intermittent timer device shall be conducted.
Where cordless deadman systems are in use, a check shall be conducted quarterly, to
confirm the correct function.
Each hose and flexible joints shall be given a permanent identification when first
Before use, new hoses shall be tested in accordance with the 6-monthly pressure
test procedure in Appendix A3.
Fuel that remains static in hoses may be subject to colou colour and thermal
degradation. The contents of all in-
in-service
in -service fuelling equipment delivery hoses shall
be delivered to aircraft, circulated or flushed to product recovery systems at the
following frequencies:
Overwing fuelling hose - weekly with at least twice the hose content.
Pressure fuelling hose - monthly with at least twice the hose content.
All hoses
hoses,, including those on fuelling steps, that may be subjected to pressure
shall be inspected and tested routinely in accordance with Appendix A3.
Hoses shall be kept under observation during fuelling operations and, if a
weakness or defect is observed, delivery through the defective hose shall be
stopped and the hose replaced. Hoses with soft spots, kinks, deformities, bulges or
blisters, abrasive wear or cracks that expose the carcass textile reinforcement, or
cuts in the hose which have damaged the carcass textile reinforcement, shall be
immediately taken out of service.
Damaged hoses may be shortened by removal of the damaged end section,
provided that the remainder of the hose is satisfactory. After rectification, by
shortening and refitting of couplings, the hose shall be subjected to the 6-monthly
test procedure (see Appendix A3.2) and the venturi re-adjusted if necessary,
before being returned to service.
Nozzles and couplings shall be checked for leaks during every fuelling operation and
and any observed leak shall
be reported and the nozzle/coupling removed from service. Leaking nozzles/couplings shall
be repaired in accordance with the m by a suitably qualified
Overwing nozzles shall be checked for general condition and leaks during every fuelling
operation and any observed leak shall be reported. Records of repairs and adjustments
shall be maintained.
Wire mesh strainers fitted to pressure couplings (underwing nozzles) and overwing nozzles
shall be removed and inspected. This check shall be performed at least monthly for
overwing nozzles and at least every 6 months hs for pressure couplings. Care shall be taken
when carrying out this procedure to ensure thatat any contaminant which may be present is
not dislodged from the strainer before examination. Where the hose
hose-end coupling has to be
disassembled to remove the strainer for inspection this shall be performed by competent
and trained personnel. The integrityy of the coupling shall be checked by pressurising the
hose to working pressure after reassembly.
Jet fuelling vehicle tanks shall be emptied and visually checked from inspection
hatches for internal cleanliness and condition. This check shall be performed at
least annually. Attention should be given to the condition of any internal linings,
tank seam welds and evidence of microbiological activity. Internal fittings such
as foot valves and high
hi level shut-off mechanisms shall be inspected at the
same time and overhauled if necessary.
If there are visible signs of contamination or damage, then the tank shall be
drained and tank entry for cleaning or repair may be necessary - see the cleaning
section
ction below. If more than 50% of the fueller tank cannot be observed from
the inspection hatches then internal inspection by borescope, dismantling or
manned entry shall be required. Appropriate safety precautions concerning the
entry of personnel into a tank shall be applied (confined space entry). Tank entry
shall only take place when all other options avoiding tank entry have been ruled
out.
Aviation gasoline fueller tanks shall not be checked internally by visual inspection
from the top hatch on a routine basis, due to the risks presented by concentrated
aviation gasoline vapours. An annual product quality review shall be performed of
the vehicle filtration and daily drains, and an Appearance Check carried out on a
sample taken from the vehicle to determine if there are any indications that the
fueller tank requires cleaning. The vehicle tank shall be cleaned if required
following this review.
Visual inspections of fueller tanks shall include a check on the condition of tank
vents and top hatch/manlid gaskets, ensuring correct controls are in place when
working at height (e.g. fall protection when working on vehicle tank tops).
This is a high risk activity and shall only take place by manned tank entry when all
other options have been ruled out.
Whenever possible fueller tank cleaning should take place via top hatches,
avoiding tank entry. Water or steam cleaning equipment should be used without
the use of chemical cleaning materials. Dirt, rust or other debris should be
removed via mopping. Fuellers shall be fully drained of cleaning water before
being returned to service.
Records of all inspections, cleaning and repairs shall be maintained.
Product recovery tanks used for recovery of samples taken from fuelling equipment shall be
emptied and visually inspected quarterly,
terly, without entry, for cleanliness and condition.
Cleaning and repairs to internal lining shall be carried out as necessary.
The correct function of emergency platform lowering systems and wand sensors fitted to
platform
m high points shall be checked monthly. The check on the wand sensors shall
simulate the failure mode by applying a downward pressure on the wand. The check shall
also confirm that the wand activates at least 30cm above the highest level of the platform
or any stowed equipment that projects beyond the platform.
In addition to the function check during each fueller loading, the correct operation of all
high level alarms and cut-off devices, including those fitted to vehicle sample tanks, shall be
function-tested at least every 6 months and the results of the tests shall be recorded. The
6-monthly check shall include the fueller loading deadman, the pre-set meter, the high level
cut-off and vehicle tank level gauge as appropriate. High-
All stepladders and towable platforms shall be visually inspected daily/before use when in
service, for any loose, cracked, damaged or missing parts and any spills/drips shall be
All monitoring and measurement devices which are critical to safe operations shall be
calibrated on a regular basis to ensure accuracy to within required tolerances. Each location
shall establish a list of such equipment and maintain records showing for each device. See
Appendix A13 for more details.
The correct operation and performance of the deadman control system, where installed for
bridger receipt or for fueller loading, shall be checked at least every month in accordance
with procedures approved by the fuel supplier.
B: One vehicle internal automatic overfill protection device connected to the foot
valve. There shall be an automatic cut-off device pre-check that shall be
activated shortly after the start of each loading operation. Additionally, there
shall be a loading meter (preferably pre-set type) to limit the loaded quantity
to a pre-calculated amount.
Sampling during fuelling operations is not routinely required (except for fuelling
ex-hydrant - see Appendix A7) provided that the fuelling equipment has been
thoroughly checked in accordance with section 9.2.1.
Fuelling operations shall be carried out by competent personnel trained in aircraft fuelling
procedures, the operation of fuelling equipment and the action to be taken in the event of
an emergency. Personnel shall be familiar with the location and operation of emergency
stop controls and switches on fuelling equipment and on the apron.
Vehicles shall not be driven at excessive speed for road conditions and weather,
weather
and speed limits imposed by the airport authorities
uthorities shall not be exceeded. Where
no regulations exist, a limit of 25 km/h shall be enforced
enforced on the apron. As soon as
practicable after leaving the vehicle parking stand, brakes shall be tested to ensure
satisfactory operation.
The use of a mobile phone or two-way -way
way communication device while driving a
fuelling vehicle is strictly prohibited. Calls shall not be made or received whil
while
driving.
Vehicles shall not approach aircraft until the aircraft anti
anti-collision lights have been
switched off.
The approach to an aircraft shall be such that in the event of vehicle brake failure
collision will be avoided. Vehicle brakes shall be safely tested on approach to the
aircraft parking stand (approx
(approximately 15m from the stand).
Vehicles should always move forward into the fuelling position, if possible. If a
vehicle has to be reversed into or out of the fuelling position, a competent guide
person shall direct the manoeuvre. Reversing speed shall not exceed slow walking
pace. Wherever possible, reversing should be performed in a straight line.
Fueller and (drawbar) trailer combinations shall not be reversed into position.
Reversing aids (e.g. rear-facing cameras with a screen inside the cab and
reversing sensors/proximity switches) may be used in addition to a guide person
(banksman). The use of mirrors and a guide person shall remain the primary
means of reversing guidance.
Vehicles shall be positioned safely, taking account of the following:
(a) Extreme care shall be taken to avoid the possibility of collision with any part of
the aircraft or ground servicing equipment while manoeuvring into (and away
from) the fuelling position.
(b) A clear exit path shall be maintained throughout the fuelling operation to
allow the fueller to be driven away quickly in the event of an emergency. If
the exit path becomes obstructed by vehicles or equipment then the fuelling
De-icing of aircraft shall not take place during fuelling operations and should be
performed after the fuelling operation whenever possible. If de-icing is required
when fuelling is taking place, the fuelling operation shall be suspended until the
de-icing is completed
De-icing fluid is a hazardous material and skin contact should be avoided.
Operators should take care to ensure that drips of de-icing fluid do not fall into
their eyes for example, from a recently treated aircraft wing. Any spillage of de-
icing fluid is likely to create a very slippery area on the apron. For these reasons,
fuelling vehicles shall not approach an aircraft if de-icing procedures are in
The aircraft, fuelling equipment and, where applicable, overwing nozzles shall be electrically
bonded together throughout the fuelling operation to ensure that no difference in electrical
potential exists between the units.
Bonding between fuelling equipment and aircraft shall be completed before any hoses are
connected or tank filler caps opened. Bonding shall be maintained until all hoses have been
disconnected or, for overwing fuelling, tank filler caps replaced.
For fuelling operations with towable fuelling platforms fitted with integral hoses, the
following bonding requirements shall be followed:
The towable fuelling platform shall be bonded directly to the aircraft using the bonding
cable on the platform. The fuelling vehicle shall be either separately bo
bonded directly to
the aircraft or bonded to the platform using the bonding cable on the vehicle.
When overwing fuelling, care should be taken to follow the correct procedure for bonding
and inserting the nozzle into the tank fill point. If the filler caps h
have been removed before
the fuelling operation, they should be replaced and vapour in the vicinity allowed to
disperse before starting the fuelling operation. The procedure may vary with aircraft type,
but the following is considered best practice:
Open the fill point cover flap where fitted.
Attach a nozzle bonding jack or clip to the bonding point or cover flap (if a suitable
bonding point or cover flap is available on the aircraft), with the filler cap still closed.
Open the filler cap.
Insert the fuelling
ng nozzle and keep the nozzle in contact with the neck of the filling point
throughout the fuelling operation
operation.
(a) Fuelling is not permitted during severe local electrical storms. Into-plane
fuelling services should work with the local airport authority to define the
procedure for suspension of all fuelling operations when electrical storms are
in the immediate vicinity.
Fuelling operations should not be performed during very high wind conditions.
The stability of fuelling platforms when fully extended may be affected by high
winds, so fuelling at height should not be permitted if wind speeds in excess of
40 knots are expected.
(b) ling
equipment.
(c) Ascertain fuelling requirements. In the case of overwing (trigger nozzle)
fuelling, the grade of fuel required shall be confirmed (see section 10.5.4).
(d) Fire extinguishers shall be readily available. They may remain on the fuelling
equipment provided they are carried in open housings or in racks with quick
opening fastenings.
(a) During fuelling, check the fuelling equipment for leaks. For underwing
pressure fuellings, record differential pressure (dP
(dP) and flow rate once during
the fuelling on the log sheet and compare to the reading on previous fuelling.
The differential pressure reading shall be recorded shortly after fuelling
begins, once the maximum flow rate for the fuelling is reached. If there is a
difference (positive or negative) in dP from the previous fuelling that cannot
be explained by the change in flow rate, fuelling shall be stopped and an
investigation shall be conducted, including taking samples from downstream
of the filter. (Note: this should be recorded on the log sheet or separate
record.)
For investigative purposes the following list, which is not exhaustive, should
be used by the into-plane operation:
What is the cause of the high dP? (Check fuel samples and condition of
monitor elements)
(b) The operator shall position himself/herself at a point where he/she has a clear
view of the fuelling equipment control panel and aircraft fuelling points.
Deadman controls (where fitted) shall always be used and shall be
wedged or blocked open. Whenever possible, the operator should control the
fuelling from ground level. Where access to the aircraft fuelling points is from
a vehicle platform, it shall not be raised or lowered while fuel is flowing.
Frequent observation of aircraft vents should also be carried out to ensure no
spill is occurring. Monitoring of the wing vents on the opposite side of the
aircraft and at the tail should take place to the extent possible, without the
operator leaving the fuelling area.
(c) No aircraft maintenance shall be conducted which could provide a source of
ignition for fuel vapours. General aircraft servicing such as baggage handling
and catering services etc. may be carried out during fuelling operations.
However, in n the event of obvious defects developing in equipment operating
within 6 metres of fuelling operations, the units shall be stopped and no
attempt made to restart them during
ing fuelling operations.
(d) Fuel spills are fire hazards and cause environmental damage. Aircraft engines
when hot can be a fire ignition source and extra care shall be taken to prevent
spillage of fuel during hot engine operations, particularly when fuel fuelling
equipment is in close proximity
ximity to the aircraft. If a spillage occurs, fuelling
operations shall be stopped and action shall be taken in accordance with local
airport regulations.
(e) Fuelling
uelling personnel shall not operate aircraft fuel system controls unless
training has been provided in accordance with the requirements of the fuel
supplier related to the provision of additional services
services. It is the responsibility
of the airline personnel/pilots to determine the volume of fuel to be loaded
and to instruc
instruct fuelling personnel accordingly.
responsibility to determine the density of the fuel being delivered and to mak
make
any associated calculations. Furthermore, it is their responsibility to
manipulate aircraft tank valves and switches, drip and dip sticks and to check
the security of tank fifill caps, covers and components.
(f) Using a mobile phone on the apron during fuelling operations is strictly
prohibited. Where for operational reasons it is necessary to use mobile
phones, they shall remain in the vehicle cab at all times and be contained in
tight-fitting covers to avoid the possibility of the battery falling out if dropped.
If it is necessary for the operator to respond to a call, the fuelling operation
shall be stopped.
(g) Before leaving the aircraft at the completion of the fuelling, the operator shall
make a final check
vehicle, to ensure that aircraft fuel caps have been re-fitted, that the fuelling
vehicle is properly disconnected from the aircraft and that all equipment is
stowed correctly. Fuelling vehicles shall be driven away from the aircraft
slowly in a forward direction.
In addition to the procedures in sections 10.5.1 and 10.5.2 the following shall be
applied:
In addition to the aircraft fuelling procedures detailed above, the following checks
and actions shall be taken:
(a) Immediately before connection of the fuelling vehicle delivery nozzle(s), the
aircraft fuel adaptor shall be checked visually to ensure that it appears to be in
good condition
condition, with no missing or damaged lugs, loose or missing securing
screws, cracks, excessive wear or other obvious damage or contamination.
Adaptors affected by any of the above shall be brought to the attention of the
airline staff for correction before the fuelling can begin. Fuelling staff shall not
attempt to tighten loose adaptors or other aircraft fuelling bay components
themselves.
No connection shall be made to an adaptor with a missing lug or any other
defect including excessive wear.
(b) After connection and before starting fuel flow, rotate the nozzle handle to the
locked position and open the poppet actuation lever. The aircraft adaptor shall
be checked that it is secure by attempting to remove the nozzle with the
nozzle handle in the locked position.
(c) On starting of fuel flow the nozzle to aircraft adaptor connections shall be
checked to ensure that there are no leaks. Fuelling shall not be carried out
from an adaptor to which the coupler does not connect securely, or which
leaks.
that aircraft fuel adaptors are in good condition and to take appropriate action
when damage is reported.
IN ACCORD ANCE TO YOUR INSTRUCTIONS AND THE FUEL GRADE AIRCRAFT REG ________
LABEL ON THE AIRCRAFT, YOUR AIRCRAFT __________ HAS
TIME _______
BEEN FUELLED WITH ________ LITRES OF
RECEIPT NO ___________
IN ACCORD ANCE TO YOUR INSTRUCTIONS AND THE FUEL GRADE AIRCRAFT REG ________
LABEL ON THE AIRCRAFT, YOUR AIRCRAFT __________ HAS
TIME _______
BEEN FUELLED WITH ________ LITRES OF
RECEIPT NO ___________
Delivery of aviation fuel direct from drums into aircraft shall be avoided wherever
possible. Where this is unavoidable then specific written procedures shall be
developed and followed, consistent with the overwing fuelling procedures in
section 10.5.4 including grade confirmation. These shall include the following:
Different grades of fuel shall be clearly segregated in storage to minimise the risk
of fuelling error.
There shall be a system which ensures that the batches are used in order of filling
date (first-in first-out system).
For more details concerning drum storage see Appendix A12.
The drum suction tube shall be constructed of aluminium or stainless steel and
shall be fitted with a leg or stand to prevent the tube from being closer than
40mm from the bottom m of the drum. When not in use the suction tube shall be
fully covered and fitted with an end cap to protect it from dust and debris. It shall
be inspected and cleaned as necessary before being inserted into the drum.
The pump may be either manual or powered. ed. Where the pump is powered it shall
be of a design suitable for use in hazardous areas. It shall also be fitted with a
cable of sufficient length to ensure that the power source is located outside the
hazardous areas of the aircraft and fuelling operati
operation.
Filtration shall be fitted and shall consist of a filter monitor qualified to EI 1583.
The filtration and pumping unit shall be fitted with bonding wires for bonding to
the drum and to the aircraft being refuelled.
A meter may also be installed in the delivery system if required.
The delivery hose shall be of an approved aviation hose of one continuous length.
The delivery nozzle shall be fitted with a 60 mesh or finer nozzle strainer.
Suitable fire extinguisher(s) shall be available or placed in the iimmediate vicinity of
the operation.
The drum shall be bonded to the aircraft. The order of bonding should be pump to
drum, then pump to aircraft. The bonding between the pump and drum shall not
be removed until:
The pump is removed.
All openings/bungs are replaced and closed.
Procedures should ensure that deliveries are only made from full drums. However,
where a partially full drum is left after a metered delivery and it is not possible to
downgrade the fuel to non-aviation use, the drum shall be re-sealed with the
original bungs (without Tri-sure cap) and marked , with an
indelible marker. The drum shall be stored so that the fuel level covers the bungs.
It shall be used first at subsequent fuellings and checked carefully for the presence
of water before use.
Fuelling of any Avgas aircraft while passengers are on board is not permitted.
Passengers shall not be allowed to remain on board helicopters during routine fuelling
operations.
Fuelling may be carried out provided:
Such fuelling is permitted by the airline and local airport regulations.
The
he airline accepts sole responsibility for ensuring that:
(a) The provisions of the local airport regulations
egulations relating to fuelling are carried
out.
(b) Instructions
nstructions are issued to its employees for the safety of all passengers during
fuelling and these instructions are strictly observed
(c) Passengers
assengers joining or leaving the aircraft are moved under the supervision of
a responsible person over a safe route.
route Passengers shall be kept at a safe
distance from the fuelling operation and other hazardous areas such as
shall
all be strictly enforced.
Before fuelling begins the fuelling operator shall be assured that fuelling with
passengers on board (including embarking/disembarking) can start.
Fuelling shall be stopped if a hazardous situation, such as spillage or fire
fire, arises, or
there is any infringement of these regulations which could lead to a dangerous
incident, and the captain/pilot of the aircraft or the airline representative/engineer
informed.
(a) The fuelling unit shall be located as far from the APU exhaust as practicable.
(b) The APU may be started and stopped during the fuelling operation without
notification.
(c) In the event of fuel spillage, the APU shall be stopped immediately and remain
stationary until spillage is removed and there is no danger from inflammable
vapours.
(a) The APU shall be started before the covers of the fuelling connections and
hydrant caps are removed or any fuelling connections made.
(b) If the APU is stopped during the fuelling operation, it shall not be started until
the flow of fuel has stopped.
Some aircraft are not equipped with a dedicated APU and use one of the nacelle
engines (known as
while
Note: Fuelling Zone: This is comprised of areas with a radius of at least 3 metres, or
more if specified by local authorities, from filling and venting
venting points on the aircraft,
fuelling vehicle and its hoses in use.
GPUs shall be positioned at least 6 metres away from fuelling vehicles and clear of
wing tank vents.
The enginene of the GPU shall be started and electrical connections
connection made before
fuelling begins. The unit shall not be disconnected or switches operated during
fuelling.
In the event of fuel spillage, the engines on the GPU shall be stopped immediately
immediately,
and should remain stationary until the spillage is removed and there is no danger
from inflammable vapours.
Fuelling operations may be carried out subject to the same conditions as those applicable to
general
al aircraft servicing, with the exception that in the event of fuel spillage the engine of
the unit shall be stopped. This is to prevent the possibility of flammable vapours being
passed into the aircraft passenger compartment.
Fuelling of an aircraft which has one propulsion engine running is a non-routine, emergency
operation and requires very strict safety precautions. The procedure should be used only
when an aircraft engine cannot be restarted because of inoperative ground aircraft starting
equipment.
The procedure outlined below applies specifically to underwing fuelling.
The designated person shall ensure that the fuelling operation with one engine running, as
requested by the customer, is within the scope of the current airport regulations.
Fuelling helicopters without engines and rotors running is a routine operation which, from
safety considerations, is similar to the fuelling of fixed wing aircraft.
Fuelling is not permitted during maintenance to landing gear under any circumstances.
(Maintenance to landing gear can introduce variables (such as metallic equipment) that
may create a spark and can also compromise safety requirements during
fuelling/defuelling.)
Daily product dips, tank contents and water checks, including date/time.
Release Certificates and details of incoming consignments with reference to
Release Certificates, quantities, dates and times.
Receipt tank details, settling and release checks.
Product deliveries and transfers, including the date/time when tanks are put in
service.
Recertification and Periodic Test Certificates.
Filter sump drains.
Fuelling equipment draining and sampling.
Filtration equipment differential pressure rrecord and graphs.
Where some maintenance tasks are performed by visiting contractors or mechanics, a copy
of their maintenance records should be retained at the location.
Storage tank inspection and cleaning records.
Microfilter, filter separator and monitor differential pressure graphs, inspection and
maintenance records (Appendix A1.4).
Hose inspection and testing (Appendix A3).
Details and dates of all maintenance work.
Mobile equipment serviceability checks.
Deadman controls and hose stowage/brake interlocks.
Emergency/Engine Stops
Pressure/surge control equipment checks.
Meter calibration test record.
Pressure and vacuum gauge test record.
Nozzle inspection and repair record.
Tank cleaning, annual filter inspection records and hose records shall be retained for the
lifetime of the equipment. Other maintenance records shall be retained for at least one
year, or longer if still relevant to the equipment condition (e.g. major repair work, filter
differential pressure, etc.). Records of accidents/incidents should be retained for at least 5
years.
All records related to the quality and quantity of fuel received, stored and delivered
(including receipt documentation and delivery tickets) should be retained for a minimum 7
years. Documents do not have to be retained on site and may be stored in an organised
archiving system.
maximum achievable flow rate shall be marked on the vessel or a suitable area close to the
vessel and noted in the filter records. IIf the rated flow is significantly greater than
maximum achievable flow then the possibility of de
de-rating the vessel shall be discussed with
the manufacturer.
Stacked elements are no longer acceptable. Where stacked elements are being used, the
stacked elements shall be replaced by full-length single elements at the next internal
inspection. This applies to all element types (monitors, coalescers, separators and
microfilters).
cool dry
place. Elements shall be used on a first-in first-
recommended maximum shelf life.
All filter water separators shall have similarity certificates in accordance with EI 1582,
confirming compliance of the installed elements and vessel to EI 1581.
Additional information on aviation filters can be found in EI 1550.
Daily, at the start of the morning shift, filter vessels shall be drained of any free
water, while under pressure. Details of any free water or sediment found shall be
at (or corrected to) the maximum achievable flow rate through the filter vessel
as currently installed. The maximum achievable flow rate will usually be less
than the design or rated flow of the vessel
if flow rate falls to unacceptably low levels
if unusual sediment is found downstream of the filter
if there is a sudden drop in differential pressure without any obvious cause
being found
after 3 years.
When new elements have been installed in fuellers and hydrant servicers,
approximately 4,500 litres of product shall be circulated through the unit,
preferably back to storage, at maximum flow to remove small fibres, etc., before
the unit is returned to service.
Where gauze strainers are required for fuel quality reasons they shall be fitted with a
sample point, drained weekly and inspected monthly.
Other strainers such as pump protection strainers shall be opened, checked for damage and
cleaned at least once per year unless they are installed such that they form a pipework low
point. All low points shall be drained at least monthly.
A pressure test, using a hydrostatic test pump, shall be carried out when
commissioning new hoses, whenever couplings are attached or re
re-attached to
hoses
es and routinely every 6 months.
Required test pressures are shown in Table A3.2.1 below.
The condition of flexible joints made of hose material shall be checked visually (under
normal use) 6-monthly. These joints shall not be painted.
Analysis of incident
Recommendations implemented
Risk based
Y Y Risk based Y Risk based Risk based Risk based
Risk
Y Y Y Risk based Y Risk based N
based
Y (outside Y (outside Y (outside
Y Y fuelling fuelling fuelling Y N Y
vehicle) vehicle) vehicle)
Y Y Risk Y Risk Risk
Risk based N
based based based
expected
b ry between sites. Each site should assess the
specific risks on site and specify minimum requirements appropriate to the activity and risk.
Hydrant servicer filters shall be checked for water and sediment at the start of the morning
shift.
Draining shall be carried out from filter separator and microfilter sumps and the inlet side of
filter monitors until the line
ne content has been displaced. A sample of at least 1 litre shall
then be taken for a Visual Check. Where it is not possible to obtain a 1-litre
1 sample under
pressure off-ramp,
ramp, this check shall be performed under pressure at the start of the first
fuelling of the day. If the sample does not provide a satisfactory Visual Check, additional
draining and sampling shall be performed until a sample providing a satisfactory Visual
Check is obtained.
The vehicle shall be withdrawn from service and an investigation shall be carried out
immediately to determine the source of the contamina
contamination if abnormal quantities of free
water or sediment are found, or if it is not possible to obtain a clear and bright sample
which provides a satisfactory Visual Check.
Where Jet fuel hydrant servicers are equipped with filter separators they should be fi
fitted
with an FWS water detection device in the sump. They should have the capability of being
function-tested
tested externally in accordance with the
To protect the fuelling operation from a sudden rise in dP, a dP switch shall be in installed on
all hydrant servicer
ervicer ffilter vessels fitted with filter monitor elements, to activate if a high dP
is reached.
The dP switch shall be connected to the dP gauge and linked in series with the deadman
and fuelling control system. The dP switch shall be set to 22 psi (1.5 bar) for filter monitors.
The system shall not be capable of being reset by the fuelling operator and it shall be
installed so that the deadman override does not reset and reactivate the system.
The system shall also be fitted with a mechanism (e.g. a key operated device) to reset the
dP switch after installing new filter elements or following dP gauge free movement tests.
The function of differential pressure switches fitted to filter monitor vessels on hydrant
servicer vehicles shall be checked to ensure that the fuelling operation will be stopped if the
activation pressure of 22psi (1.5bar) is reached. This check shall be performed and
recorded every 6 months.
Following any activation of a dP switch, the fuelling vehicle shall be removed from the
fuelling operation for investigation, and the fuelling operation management and the depot
operator shall be notified immediately. Other fuelling operations at the airport should be
notified by the depot/hydrant operation management.
For investigative purposes the following list, which is not exhaustive, should be used by the
into-plane operation:
What is the cause of the high dP? (Check fuel samples and condition of monitor
elements)
Is the dP switch circuit function correctly?
Are there other fuelling vehicles experiencing an increase in dP? (Particularly in the case
of hydrant servicers operating close to the affected servicer)
If a second vehicle is in use to complete the fuelling, is there any indication of
increasing dP?
Was the dP increase a sudden change from a low value, indicating a problem, rather
After the fuel contained in the vehicle delivery pipework and filter vessel has been
displaced, a 1-litre
litre sample shall be taken downstream
downstrea (outlet side) of the filter for
an Appearance (or Visual*) Check. If water is found in the sample, a second
sample shall be drawn immediately.
A 1-litre
litre sample shall be drawn from the filter separator sump (FWS) or inlet
(upstream)
eam) side of the monitor vessel under pressure immediately after each
fuelling for an Appearance (or Visual*) Check. If water is found in the sample or a
distinctive colour change is obtained with the chemical water detector, a second
sample shall be drawn immediately.
* A chemical water detector test shall be performed on at least one of (a) or (b)
above.
If a hydrant servicer is withdrawn from service or is reassigned to another aircraft before
the fuelling operation is completed, this procedure shall be followed before leaving the
aircraft.
If the presence of water or dirt is confirmed, the fuelling shall be stopped and the airline
representative and hydrant operating company informed immediately. No further delivery
shall be made until the reasons for the presence of water have been determined and
remedial action taken.
In addition to the procedures shown in Chapter 10 the following applies for underwing
fuelling by hydrant servicer. Each operation shall have one agreed sequence for connection
and disconnection. Either of the following options is acceptable.
Remove pit valve adapter cap and clean Attach lanyard, pull to ensure pit valve is closed
dirt/moisture from pit valve adapter and hydrant and extend lanyard on apron
coupler
Connect hydrant pit coupler and air line to pit valve Remove pit valve adapter cap and clean
and position pit marker dirt/moisture from pit valve adapter and hydrant
coupler
Open hydrant pit coupler Connect hydrant
ant pit coupler and air line to pit
valve and position pit marker
Connect delivery hose(s) to aircraft Open hydrant pit coupler
Get confirmation of fuel figure to start fuelling from Get confirmation of fuel figure to start fuelli
fuelling
airline representative from airline representative
Open pit valve (if manually operated) Open pit valve (if manually operated)
Open delivery valve and activate deadman control Open delivery valve and activate deadman
to start delivery control to start delivery
Check hydrant pit coupler for leakage Check hydrant pit coupler for leakage
Note: If the sequence of connection and disconnection is broken due to distraction the
operator shall begin the sequence again from the start.
For hydrant servicers, a clear exit path should also be maintained but this is not considered
mandatory, given the lower inherent risk in a servicer (with no large quantity of aviation
fuel on board) and that a servicer would not normally be driven away in the event of an
emergency during fuelling.
Hydrant servicer inlet hoses, inlet couplers and hydrant pit valves are vulnerable to damage
caused by other aircraft servicing vehicles. This has been demonstrated by a number of
major incidents in recent years, each of which could have had catastrophic effects including
fire and loss of life. Incidents have occurred in both good and poor weather conditions, in
daylight and during the hours of darkness.
To
o improve the visibility of the hydrant pit valve area at all times, a high vivisibility hazard
marker shall be displayed above the pit opening. A four-winged winged flag is preferred but
alternative designs/equipment providing a similar degree of all-round
all round visibility may be used.
During the hours of darkness the hydrant pit valve and inlet hose shall be illuminated. Red
or orange safety lamps or vehicle-mounted
mounted searchlights may be used for this purpose.
Additional methods of protecting and increasing the visibility of the hydrant pit and hydrant
servicer inlet hose should be considered. Examples
ples of such additional methods include the
use of high visibility road cones, inlet hose collars and warning signs. The area around
hydrant pit covers should be painted with a warning pattern to ensure apron vehicles or
aircraft avoid driving over or parking
ing on them.
Inlet coupler stowage shall be designed to minimise exposure of coupling to contamination
(e.g. surface dirt and water from the ground and vehicle tyres). NonNon-compliant existing
hydrant servicing vehicles shall be modified as appropriate where no protection is currently
in place.
Inlet couplers and hydrant pit valves shall be checked for wear at least annually, using the
Lanyards for hydrant pit valve operation shall be manufactured from fire-resistant material
of adequate strength to enable the valve to be operated remotely if an emergency occurs
during the fuelling operation and shall be of a highly visible colour, such as red. The
selected colour should be in line with any local regulations concerning the recommended
colours for emergency systems and shall be different from that of the fuelling vehicle
bonding cable. These colours shall be consistent across the site vehicle fleet.
The lanyards shall be a minimum of 5m (16 feet) in length.
There shall be no electrical connection between the fuelling vehicle and the hydrant pit. If
lanyards are attached to vehicle-mounted reels, the reels shall be electrically isolated from
the vehicle. Electrical isolation of the reels shall be checked weekly with an electrical
continuity meter.
Monthly static checks of the seals and annual dynamic checks shall be carried out (see
A7.10 for more details). The dynamic check shall be made on the correct operation of the
quick release valve as controlled by the lanyard valve closing time should be between 2
and 5 seconds. The performance checks of the valve shall be made under pressure at the
highest flow rate practicable and may be carried out during a fuelling operation. The results
shall be recorded.
With some existing (non API/IP type) hydrant pit valves, the valve closing time may exceed
5 seconds. In this situation, it is necessary to observe the overshoot, which should not
exceed 50 litres.
The fuel hydrant emergency stop buttons (ESBs) shall be clearly identified and easily
accessible. Clear access to these buttons should be maintained at all times. High visibility
identification signs should be located such that they remain visible at all times.
A monthly check of the hydrant emergency shut-down system shall be performed in
accordance with a detailed written test method. Procedures shall ensure that the function
A7.9.1 Hydrants that are fitted with a system to confirm their integrity (tightness control)
shall be checked on a regular basis (at least monthly),
monthly) in accordance with written
ons and taking into account
national and local regulations.
As a minimum, where no leak detection system exists, the system shall be
checked at least monthly at normal operating pressure
pressure, when no fuellings are in
progress, and the pressure decay over time (minimum 2 hours) recorded. The
pressure decay (typically less than 10 psi) shall be compared to previous results.
Any increase in pressure drop that cannot be attributed to changes in test
pressure or fuel temperature is an indication of a possible hydran
hydrant leak or isolation
valve failure and further investigation shall be cconducted to identify the cause.
In addition, for existing hydrants without leak detection systems, consideration
should be given to using a mobile leak detection system to check for leakage
leak at
least every 6 months.
Further information about the checking of hydrant system integrity is contained in
in:
EI 1540 Design, Construction, Commissioning, Maintenance and Testing of
Aviation Fuelling Facilities, latest edition (Automated Hydrant Integr
Integrity Testing)
EI 1560 Recommended practice for operation, inspection, maintenance and
commissioning of aviation fuel hydrant systems and hydrant system extensions
(Hydrant System Integrity Testing)
All buried fuel pipes and hydrant systems without an operational leak detection
system shall be pressure tested annually to Maximum Operating Pressure (MOP) to
confirm their leak tightness. MOP is defined as maximum pump output pressure at
maximum tank head. Where possible the pressure test should be of 8
duration (see API 570 and API 2611 for further information), but if test results
confirming the absence of leaks can be established positively this may be reduced
to a minimum of 1 hour. If test results suggest the possibility of a leak, a pressure
test at 110% of Maximum Allowable Operating Pressure (MAOP) should be
performed. Where the MAOP is not known, the test should be performed at 125%
of the maximum working pressure of the system. Testing shall be in accordance
with written procedures highlighting the fact that this normally requires the
isolation of pressure relief valves. See EI 1560 10.2.3 for further details on testing.
Hydrant pit valves shall be inspected and tested in accordance with the following schedule
to ensure that the performance of the equipment is within acceptable limits. There shall
also be a planned maintenance system in
recommendations.
(1) Ensure the pit box is clean and free from water, product and surface dirt/grit. Clean if
required.
(2) Examine the condition of the pit lining.
(3) Ensure the valve and components are free from product leaks.
(4) Examine the condition
ondition of jacking screws where fitted.
(5) Carry out a visual examination of the operating handle/linkage and lanyard
connections.
(6) Check the presence and condition of the dust cap and tether.
(7) Examine the pit
it lid condition, seal (if fitted), tether (if required), pit number and grade
marking if applicable.
Any defects shall be reported immediately.
This is done by depressing the equalising valve as described below. As a small amount of
fuel will be released, a protective shield/cover shall be used to contain any spray of fue
fuel and
to protect the operator. Alternatively, a test coupler equipped with a pressure gauge kit
supplied for the purpose by a manufacturer
manufacturer, with instructions for use, may be used. With
the main valve in the closed position, the test coupler is attached, thus opening the
equalising
qualising valve. A continued rise in pressure within the coupler indicates that the pit valve
needs to be repaired.
(1) Ensure that the operating mechanism is free from obstruction, is secure and that no
excessive free play is observed.
(2) With the valve operating mechanism in the closed position, and using the necessary
shield/cover, depress the equalising valve. After the initial release of fuel, a steady flow
will indicate a failure of the main seal and the valve shall be removed from service for
repair.
If only a few drops of fuel are observed following the initial release of fuel, the valve is
serviceable.
Close the hydrant pit valve from full flow rate, by pulling the lanyard. The valve closure
time shall be between 2 and 5 seconds. This test may be performed during aircraft fuelling.
Note: Certain older mechanically operated pit valves were not designed to meet the more
stringent performance requirements currently recognised within the industry, and
may not meet all the above requirements.
In this situation, and in conjunction with the manufacturer of the valves, accurate
performance criteria should be agreed and included in the written testing/operating
procedures, or a decision made to upgrade the valves.
The following procedure is considered best practice (use
e a stopwatch
stopwatch):
After repair or overhaul, the valve shall be fully tested, preferably on a test rig at the
maximum flow to which the valve will operate in service. Closure time by pulling the
lanyard shall be between 2 and 5 seconds.
Property Test Spec Previous New 1 New 2 New 3 Weighted Current Accept.
method* limits Recert RCQ/ RCQ/ RCQ/ average Recert. Diff.
(Heel) CoA CoA CoA
Appearance
Distillation D86
Initial boiling point 8
10% evaporated at ºC 4
6
6
6
End Point, ºC 10
Sum of 10+50% 10
evaporated
Recovery, % vol -
Loss, % vol -
Distillation D86
Initial boiling point Report -
10% Recovered, ºC 205 max 8
50% Recovered, ºC Report 8
90% Recovered, ºC Report 8
End Point ºC 300max 8
Residue, % vol 1.5 -
Loss, % Vol 1.5 -
Where minimum/maximum limits are given, the Acceptable Difference values do not apply to results below minimum or
above maximum.
* Test methods as per relevant specification.
**** FAME test limit, see JIG bulletin 75 for guidance on when FAME testing is required.
Site-specific
specific soak test plans should be reviewed and approved by the technical
representatives of the operation
ation before commissioning begins.
Soak testing shall be completed on the constructed facility rather than on
representative sections of pipe or individual pieces of equipment (e.g. tanks or
filter vessels) before installation. This ensures that the soak ttest identifies any
contamination caused by the fabrication of the equipment and resulting from on on-
site construction work.
For tie-ins,
ins, where in-situ
in situ soak testing may not be practicable, the relatively short
sections of pipe, fittings or valves involved may be soak-tested before installation,
provided that adequate precautions are taken to maintain the cleanliness of the
tie-in
in components until the new system is put into service.
Once the system has been filled with the correct grade of fuel, all components in
the system that contain moving parts in contact with the fuel should be exercised
New vehicles are sometimes delivered with the remains of product, used by the
supplier for performance testing, trapped in the fuel circuit together with small
amounts of debris. Vehicle manufacturers should use filtered kerosene for this
purpose but airport operators shall assume that any product remaining in the
vehicle is contaminated. It is important that pockets of test fuels are thoroughly
drained to the point that the internal surfaces contain no more than a wet film of
product. Ideally they should be completely dry before filling with the appropriate
grade of fuel for the soak test.
The requirement to soak test new vehicles can be eliminated if the manufacturer
provides evidence that the vehicle has successfully passed a soak test in line with
these requirements before delivery. However, if the condition of the vehicle upon
New aircraft fuelling hoses and fueller loading hoses meeting EI 1529 or ISO 1825
shall:
A: Be filled with product and left to soak for a minimum of eight hours at a
temperature of 15°C or higher. Longer soak times are required where product
temperatures are lower.
B: A sample shall be taken of the soaked product and subjected to an
appearance check. Product used for hose soaking shall not be used as aviation
fuel and shall be downgraded.
C: If the appearance check shows no evidence of manufacturing
manufactu residue or
discoloration then the hose shall be flushed with at least twice the hose
content followed by an inspection of the hose end strainer.
D: If the appearance check is unsatisfactory then steps A, B and C shall be
repeated.
Soak testing is not required for suction hoses and hose assemblies for road or
rail delivery.
sufficient fuel to cover the floating or fixed suction and the receipt nozzle to allow
for circulation through the piping system to flush out any contaminants without
pump cavitation.
The risk presented by the unlined surfaces is the potential contamination from
rolling oils and welding flux on bare metal surfaces. These materials can be
removed by high pressure water washing but some soak testing of the unlined
surfaces is then required to demonstrate the effectiveness of the cleaning.
At the end of the soak period representative samples shall be obtained from appropriate
locations as outlined below and submitted for laboratory
ratory testing.
A Bottom Sample from the low point shall be used for horizontal and vertical tanks. A
sample taken from this location represents the most severe case
case, as the fuel is in close
contact with the lining and any heavy contaminants are likely to be collected during
sampling.
Small piping configurations that can be circulated into a tank may be tested as part of the
tank soak test and not sampled/tested separately.
Larger supply piping networks shall have samples taken from e each major section (e.g.
receipt and delivery lines) for separate testing. Samples should be taken from more than
one point and combined into a single composite sample.
Hydrant piping networks shall have samples taken from each major section for separate
testing. Samples should be taken from more than one point (e.g. low point drains, high
point vents and hydrant pit valves) and combined into a single composite sample.
Samples should be taken from all vehicle low points and combined into a single composite
sample.
In all cases it is important to ensure that the sampling point is clean and flushed before
taking the sample. Any accumulated solid matter (particulate) and/or free water should be
removed until the fuel is clear and bright. Only approved sample containers shall be used
and the container shall be flushed and rinsed thoroughly with the product to be sampled
and allowed to drain before use. This is very important because sampling lines on tanks
may be forgotten in the commissioning.
Soak testing is applicable throughout the distribution system from refinery to airport.
Upstream facilities will require Recertif
Recertification testing or full specification testing before the
fuel can be released.
The following table and accompanying notes provide a summary of the soak test
requirements for storage tanks, piping, ancillary equipment and vehicles.
Applies to lining material meeting EI 1541 and covered by a 10 year joint material and
applications warranty from the manufacturer.
Newly installed ancillary equipment (e.g. pumps,
pumps, filter vessels, valves, pit valves, control
valves, meters, sense tubing, water drain lines, etc) should be soak
soak-tested during the system soak
test.
New vehicles delivered directly from the manufacturer or vehicles arriving at an airfield
location
tion without records or after repairs at a contractor facility or vehicles that have been out of
service for an extended period.
Keep empty drums totally segregated from full stock, and designate stacks as being so
segregated. Keep all bungs in empty drums.
Key:
JIG 4 * Visual check of the hose during use
**Unattended sites shall be weekly and before use