You are on page 1of 5

2296 IEEE TRANSACTIONS ON ELECTROMAGNETIC COMPATIBILITY, VOL. 64, NO.

6, DECEMBER 2022

Response of a Surge Arrester With a Series Gap for 6.6-kV Distribution Lines to
Steep-Front Transients
Ryota Mori , Member, IEEE, and Akiyoshi Tatematsu , Senior Member, IEEE

Abstract—Surge arresters with a series gap are commonly in-


stalled in distribution lines to effectively protect insulators, trans-
formers, and other equipment from lightning threats in Japan.
On the other hand, it has been well known that the high-altitude
electromagnetic pulse (HEMP) at an early stage, called E1 HEMP,
may extensively cause overvoltage on distribution lines, and the
rise time of the E1 HEMP is as short as a few nanoseconds, which
is much shorter than that of lightning electromagnetic pulses. To
evaluate the effectiveness of surge arresters with a series gap against
overvoltage induced by the E1 HEMP, it is necessary to evaluate the
effect of a discharge delay due to the series gap on the protection
level of surge arresters for steep-front transients. In this work, using Fig. 1. Schematic diagram of an experimental setup.
a pulse current injection system, we apply a high voltage to a surge
arrester with a series gap widely used for 6.6-kV distribution lines in
Japan and measure the response of the surge arrester to steep-front
transients. From the measured results, we obtain the voltage–time the surge arresters installed in a wide area may be useful to
characteristics of the surge arrester with a series gap and residual protect distribution lines from the HEMP threat. In [12], the
voltages, which are compared with the results for lightning impulse responses of metal–oxide surge arresters, which are used in
voltage.
10-kV distribution lines, to steep-front transients with a rise time
Index Terms—Distribution lines, high-altitude electromagnetic of 5–100 ns were studied using a pulse current injection (PCI)
pulse (HEMP), lightning electromagnetic pulse (LEMP), pulse system [13], and it was found that the peak values of the residual
current injection (PCI), surge arresters with a series gap.
voltage of the surge arresters are about 50%–60% higher than
those under lightning impulse voltages. On the other hand, most
I. INTRODUCTION of the surge arresters used for protecting 6.6-kV distribution
lines in Japan have an internal series gap [14] to prevent faults
N GENERAL, the causes of lightning faults in 6.6-kV dis-
I tribution lines are classified into indirect and direct lightning
strikes. In 6.6-kV distribution lines in Japan, power distribution
caused by increased leakage current or temporary overvoltage
in distribution systems. In [15], it was presented that the internal
series gap of a surge arrester used in 6.6-kV distribution lines
equipment (e.g., insulators, pole-mounted transformers, and increases the sparkover voltage of the series gap owing to a
automatic switches) are rarely damaged due to lightning over- discharge delay for lightning impulse voltages with a rise time
voltage induced by lightning electromagnetic pulses (LEMPs) of 1–10 µs.
arising from indirect lightning strikes because the distribution In this work, using a PCI system, we apply a high voltage
lines are well protected by surge arresters installed at short to a surge arrester with a series gap, which is widely installed
intervals [1]. On the other hand, it has been well known that in 6.6-kV distribution lines in Japan, and study the response of
the high-altitude electromagnetic pulse (HEMP) at an early the surge arrester to the steep-front transient with a rise time of
stage, called E1 HEMP, may extensively cause overvoltage on several nanoseconds to evaluate the effect of a discharge delay
distribution lines [2], [3], [4], [5], [6], [7], whereas the rise time due to its internal series gap on the protection level of the surge
of the E1 HEMP is as short as a few nanoseconds [8], [9], [10], arrester. To the best of our knowledge, this is the first study on
which is much shorter than that of LEMPs [11]. As mentioned the transient response of the 6.6-kV surge arrester with a series
earlier, in 6.6-kV distribution lines in Japan, many surge arresters gap to impulse voltages with a rise time of several nanoseconds.
are closely installed to protect against lightning overvoltage, and
II. EXPERIMENTAL SETUP
Manuscript received 1 March 2022; revised 23 July 2022; accepted 22
August 2022. Date of publication 9 September 2022; date of current version A. Overview of Experimental Setup
14 December 2022. (Corresponding author: Ryota Mori.)
The authors are with the Central Research Institute of Electric Power Fig. 1 shows the experimental setup used to measure the
Industry, Kanagawa 240-0196, Japan (e-mail: ryota-m@criepi.denken.or.jp; response of a 6.6-kV surge arrester with an internal series gap,
akiyoshi@criepi.denken.or.jp). an overview, and the specifications of which are given in Fig. 2
Color versions of one or more figures in this article are available at
https://doi.org/10.1109/TEMC.2022.3202155. and Table I, respectively. As shown in Fig. 1, the surge arrester
Digital Object Identifier 10.1109/TEMC.2022.3202155 was mounted on a large copper plate, and using a PCI system,
0018-9375 © 2022 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.
See https://www.ieee.org/publications/rights/index.html for more information.

Authorized licensed use limited to: University of Craiova. Downloaded on January 10,2024 at 07:55:26 UTC from IEEE Xplore. Restrictions apply.
IEEE TRANSACTIONS ON ELECTROMAGNETIC COMPATIBILITY, VOL. 64, NO. 6, DECEMBER 2022 2297

Fig. 3. Measured output current of PCI in short circuit. (a) Time frame of
Fig. 2. Surge arrester with a series gap [14]. −0.5–2.5 µs. (b) Time frame of −10–50 ns.

TABLE I
SPECIFICATIONS OF SURGE ARRESTER WITH A SERIES GAP

Fig. 4. Measured current through surge arrester and voltage across it when the
surge arrester was not activated.
TABLE II
SPECIFICATIONS OF MEASURING EQUIPMENT

upper terminal of the surge arrester and the bottom terminal of


the surge arrester to the copper plate, as short as possible.

B. Evaluation of Discharge Characteristics


Fig. 4 shows the measured waveforms of the voltage across
the surge arrester and the current flowing through it when the
surge arrester was not activated, that is, the applied voltage was
not sufficiently high to short the series gap through sparkover.
we applied a steep-front high voltage to the surge arrester while
Here, to evaluate the discharge characteristics (voltage–time
changing the charged voltage of the PCI system (maximum peak
characteristics) of the internal series gap that may delay the
current in a short circuit, 1.2 kA; maximum peak voltage in an
operation of the surge arrester, it is necessary to obtain the
open circuit, 80 kV). Using the aforementioned experimental
time to sparkover at the series gap t, that is, the time difference
setup, we measured the transient response of the surge arrester.
between the start time of applying the voltage and the time of
From the measured waveforms of the voltage across the surge
the occurrence of the sparkover to short the series gap. However,
arrester and the current flowing through it, we obtained the
as shown in Fig. 4, the pulsed current, the peak value of which
discharge characteristics, that is, voltage–time characteristics of
was around 23.9 A, flowed through the surge arrester even when
the internal series gap, that cause the delay of the operation of
the series gap was not short through sparkover. This current is
the surge arrester. Table II summarizes the specifications of the
assumed to be the effect of a leakage current, and the leakage
measuring equipment used in this letter.
current Il of a surge arrester with a series gap can be expressed
Before performing the test, we measured the output current
as follows [16]:
of the PCI system, where its output terminal was treated as short
circuit. Fig. 3 shows the measured current waveform at the output dV (t)
terminal. The rise time (time between 10% and 90% of the I l = iC + i G , iC = C · , iG = G · V (t) (1)
dt
peak value on the wavefront) and pulsewidth (50% duration)
of the current were 6.8 ns and 549 ns, respectively, and we where iC , iG , and V denote the leakage current due to the
confirmed that the current waveform in the short circuit satisfied capacitance C of the surge arrester, the leakage current due to
the limits specified in MIL-STD-188-125-1 [13]. Note that, as the conductance G of the surge arrester, and the voltage across
shown in Fig. 3, the injected current had a steep front, and in the surge arrester, respectively.
the experimental setup, to minimize the unintended effect of the Fig. 5 shows the measured current flowing through the surge
inductance of wires, we kept the length of the wires, which were arrester and the current calculated using (1). The capacitance C
used to connect the output terminal of the PCI system to the and conductance G were set to 4.87 pF and 6.19 µS, respectively,

Authorized licensed use limited to: University of Craiova. Downloaded on January 10,2024 at 07:55:26 UTC from IEEE Xplore. Restrictions apply.
2298 IEEE TRANSACTIONS ON ELECTROMAGNETIC COMPATIBILITY, VOL. 64, NO. 6, DECEMBER 2022

Fig. 5. Comparison between the measured current through surge arrester and
that calculated using (1).
Fig. 7. Evaluation of time to sparkover.

Fig. 8. Measured voltage–time characteristics of surge arrester.

lines between 0.9 Vpeak and 0.3 Vpeak and between 0.9 Ipeak
Fig. 6. Capacitance and conductance measured using an impedance analyzer. (Ipeak : peak value of the current) and 0.3 Ipeak , respectively.
(a) Frequency characteristics of capacitance. (b) Frequency characteristics of
conductance.
III. MEASURED RESULTS
A. Discharge Characteristics of 6.6-kV Surge Arrester With
which were obtained using the following expressions: Internal Series Gap
N
 N
 Fig. 8 shows the measured voltage–time characteristics of the
C= s n Cn / sn (2) internal series gap of the surge arrester obtained, as explained in
n=1 n=1
Section II-B. In Fig. 8, in addition to the measured results, we
N
 N
 also give the fitting curve of the measured voltage–time charac-
G= s n Gn / s n (3) teristics, which was expressed using the following approximate
n=1 n=1 expression [17]:
where N, sn, and s n are the number of samples of the Fourier   
transform, the spectrum of the derivative of the measured voltage 1 t − tf
V = V0 1 + exp − (4)
at the nth frequency, and the spectrum of the measured voltage at 2 ts
the nth frequency, respectively. The capacitance Cn and conduc-
tance Gn at the nth frequency were measured by an impedance where V0 is the minimum sparkover voltage and tf and ts are the
analyzer (HP, 4294A), as shown in Fig. 6. parameters to simulate the effect of the discharge delay, which
As shown in Fig. 5, the rise time and shape of the calculated were estimated from the measured results (N: number of data)
current agree well with the measured waveform before the by the least squares method. In the above measured results, the
occurrence of the sparkover across the series gap, and it was maximum sparkover voltage was 49.5 kV at 9.0 ns, which is
confirmed that this current occurred mainly because of the effect about 1.5 times larger than that for the steep lightning impulse
of the capacitance of the surge arrester. Taking this phenomenon voltage with a rise time of 0.5 µs given in the manufacturer’s
into account, to evaluate the discharge characteristics (voltage– specifications. On the other hand, the voltage–time character-
time characteristics) from the measured voltage and current, istics at around 30–40 ns later appear flat, and the minimum
we defined that the voltage V is the peak value of the voltage sparkover voltage V0 was 33.3 kV, which was almost the same
waveform Vpeak , and the time to sparkover t (see Fig. 7). As as that for the lightning impulse voltage specified in the data
shown in Fig. 7, tV and tI are zero crossing times of the straight sheet provided by the manufacturer.

Authorized licensed use limited to: University of Craiova. Downloaded on January 10,2024 at 07:55:26 UTC from IEEE Xplore. Restrictions apply.
IEEE TRANSACTIONS ON ELECTROMAGNETIC COMPATIBILITY, VOL. 64, NO. 6, DECEMBER 2022 2299

significantly for currents of about 60 to some hundreds ampere


owing to its nonlinear behavior.

IV. CONCLUSION
In this letter, using a PCI system, we measured the discharge
characteristics (voltage–time characteristics) and residual volt-
age of the 6.6-kV surge arrester with a series gap, which is
commonly installed in 6.6-kV distribution lines as countermea-
sures against lightning overvoltage in Japan. From the measured
results, we found the following points:
1) The sparkover across the series gap occurred at 49.5 kV to
operate the surge arrester even at 9.0 ns in the voltage–time
characteristics for the steep-front transients. This voltage
is about 1.5 times larger than the sparkover voltage for
the steep lightning impulse voltage, which is given in
the specifications from the manufacturer. In addition, the
sparkover voltage of the series gap around 30–40 ns later
is similar to that for the steep lightning impulse voltage
with a rise time of 0.5 µs within a difference of 5%.
2) The voltage across the surge arrester converges to a resid-
ual voltage after the occurrence of the sparkover across the
series gap. Even when the time of the occurrence of the
sparkover was 9.0 ns, the maximum residual voltage of
Fig. 9. Measured current through surge arrester and voltage across it. the surge arrester was 34.9 kV, which is about 1.5 times
(a) Sparkover time of 9.0 ns. (b) Sparkover time of 40.1 ns.
larger than that for the lightning impulse voltage specified
in the data sheet of the manufacturer. The residual voltage
of the surge arrester when the sparkover occurred at around
B. Residual Voltage of 6.6-kV Surge Arrester With Internal
40 ns later is almost identical to that for the lightning
Series Gap
impulse voltage.
As an example of the measured waveforms of the voltage and The above measured results can be used to model the surge
current, Fig. 9(a) and (b) shows the measured currents flowing arresters with a series gap and evaluate voltages induced on
through the surge arrester and the voltages across it, where the distribution lines and overvoltages entering transformers and
sparkover occurred across the internal series gap in the wavefront other equipment through electromagnetic transient simulations.
and wave tail of the applied voltage, respectively. In Fig. 9(a)
and (b), the times of the occurrence of the sparkover are 9.0 ns
and 40.1 ns, respectively. From these results, we found that the REFERENCES
current starts to flow immediately after the occurrence of the [1] S. Yokoyama, K. Michishita, T. Sato, H. Sugimoto, and Y. Morooka,
sparkover across the series gap, and then the voltage across “Review of lightning observation on overhead distribution lines in Japan,”
in Proc. 11th Asia-Pacific Int. Conf. Lightning, 2019, pp. 1–6.
the surge arrester converges to an almost constant residual [2] North American Electric Reliability Corporation and the U.S.
voltage after the sparkover of the series gap. In Fig. 9(a), the Department of Energy, “High-impact, low-frequency event risk to
peak value of the voltage after the occurrence of the sparkover the North American bulk power system,” Jun. 2010. [Online]. Available:
https://www.energy.gov/ceser/downloads/high-impact-low-frequency-
is 34.9 kV, which is 1.5 times larger than the residual voltage risk-north-american-bulk-power-system-june-2010
of 24 kV for the lightning impulse current (8/20 µs, 2500 A) [3] Electromagnetic Compatibility (EMC)—Part 1-3: General—The Effects
specified in the data sheet of the manufacturer. In Fig. 9(a), the of High-Altitude EMP (HEMP) on Civil Equipment and Systems, IEC/TR
61000-1-3, 2002.
voltage shows a tendency to decrease after around 30 ns for [4] Electromagnetic Compatibility (EMC)—Part 2-10: Environment—
the increasing current. The main reason for this is presumed to Description of HEMP Environment—Conducted Disturbance, IEC 61000-
be the effect of the frequency characteristics of the MOV, which 2-10, 2021.
[5] V. J. Kruse, T. K. Liu, F. M. Tesche, and P. R. Barnes, “Flashover vulnerabil-
indicates that it will be necessary to evaluate the voltage–current ity of transmission and distribution lines to high-altitude electromagnetic
relationship of the MOV itself for steep-front transients. On the pulse (HEMP),” IEEE Trans. Power Del., vol. 5, no. 2, pp. 1164–1169,
other hand, in Fig. 9(b), the peak voltage is 22.5 kV, which is Apr. 1990.
[6] V. J. Kruse, D. J. Nickel, E. R. Taylor, J. J. Bonk, and P. R. Barnes,
closer to the specified residual voltage of 24 kV for the lightning “Impacts of a nominal nuclear electromagnetic pulse on electric power
impulse current. Although the current for the steep-front tran- systems: A probabilistic approach,” IEEE Trans. Power Del., vol. 6, no. 3,
sient is 60.9 A in this case, in case of HEMP events, the peak pp. 1251–1263, Jul. 1991.
[7] J. S. Foster Jr. et al., “Report of the commission to assess the threat
values of currents flowing through surge arresters in distribution to the United States from electromagnetic pulse (EMP) attack,” Criti-
lines are much smaller than those due to lightning strikes, and cal National Infrastructures, Apr. 2008. [Online]. Available: http://www.
the residual voltage of the surge arrester does not change so empcommission.org/docs/A2473-EMP_Commission-7MB.pdf

Authorized licensed use limited to: University of Craiova. Downloaded on January 10,2024 at 07:55:26 UTC from IEEE Xplore. Restrictions apply.
2300 IEEE TRANSACTIONS ON ELECTROMAGNETIC COMPATIBILITY, VOL. 64, NO. 6, DECEMBER 2022

[8] Electromagnetic Compatibility (EMC)—Part 2: Environment—Section 9: [13] High-Altitude Electromagnetic Pulse (HEMP) Protection for Ground-
Description of HEMP Environment—Radiated Disturbance, IEC 61000- Based C4I Facilities Performing Critical Time-Urgent Missions, Part 1:
255 2-9, 1996. Fixed Facilities, MIL-STD-188-125-1, 1998.
[9] R. Hoad and W. A. Radasky, “Progress in high-altitude electromag- [14] Y. Koga, Y. Yoneda, T. Sato, S. Yokoyama, and S. Matsumoto, “Degra-
netic pulse (HEMP) standardization,” IEEE Trans. Electromagn. Compat., dation characteristics on MOV of surge arrester used for 6.6 kV power
vol. 55, no. 3, pp. 532–538, Jun. 2013. distribution line,” in Proc. 33rd Int. Conf. Lightning Protection, 2016,
[10] E. Savage, J. Gilbert, and W. Radasky, “The early-time (E1) high-altitude pp. 1–5.
electromagnetic pulse (HEMP) and its impact on the U.S. power grid,” [15] T. Sakoda, H. Horie, A. Takei, K. Kubo, M. Mizutani, and T. Fukano,
Metatech Corporation, Meta-R-320, Jan. 2010. [Online]. Available: http: “Study on discharge time lag phenomenon for a surge arrester with a spark
//large.stanford.edu/courses/2019/ph241/rogers1/docs/meta-r-320.pdf gap,” IEEJ Trans. Fundam. Mater., vol. 138, no. 9, pp. 457–462, 2019.
[11] F. Heidler, Z. Flisowski, W. Zischaank, C. Bouquegneau, and C. Mazzetti, [16] L. Fu-Cheng, L. Jin-Song, and T. Xiao-Xue, “Simulation study on leakage
“Parameters of lightning current given in IEC 62305_background, expe- current of metal zinc oxide arrester,” in Proc. Chin. Control Decis. Conf.,
rience and outlook,” in Proc. 29th Int. Conf. Lightning Protection, 2008, 2018, pp. 5705–5709.
pp. 1–22. [17] S. Matsumoto, T. Sato, H. Honda, and S. Yokoyama, “Approximate
[12] Y. Zhou, Y.-Z. Xie, D.-Z. Zhang, N. Dong, Y.-H. Chen, and Y. Jing, formula for surface V-t characteristics of 6.6-kV distribution insulator,”
“Response of 10-kV metal-oxide surge arresters excited by nanosecond- in Proc. Int. Conf. Lightning Protection, 2012, pp. 1–5.
level transient electromagnetic disturbances,” IEEE Trans. Electromagn.
Compat., vol. 63, no. 2, pp. 614–621, Apr. 2021.

Authorized licensed use limited to: University of Craiova. Downloaded on January 10,2024 at 07:55:26 UTC from IEEE Xplore. Restrictions apply.

You might also like