Professional Documents
Culture Documents
6, DECEMBER 2022
Response of a Surge Arrester With a Series Gap for 6.6-kV Distribution Lines to
Steep-Front Transients
Ryota Mori , Member, IEEE, and Akiyoshi Tatematsu , Senior Member, IEEE
Authorized licensed use limited to: University of Craiova. Downloaded on January 10,2024 at 07:55:26 UTC from IEEE Xplore. Restrictions apply.
IEEE TRANSACTIONS ON ELECTROMAGNETIC COMPATIBILITY, VOL. 64, NO. 6, DECEMBER 2022 2297
Fig. 3. Measured output current of PCI in short circuit. (a) Time frame of
Fig. 2. Surge arrester with a series gap [14]. −0.5–2.5 µs. (b) Time frame of −10–50 ns.
TABLE I
SPECIFICATIONS OF SURGE ARRESTER WITH A SERIES GAP
Fig. 4. Measured current through surge arrester and voltage across it when the
surge arrester was not activated.
TABLE II
SPECIFICATIONS OF MEASURING EQUIPMENT
Authorized licensed use limited to: University of Craiova. Downloaded on January 10,2024 at 07:55:26 UTC from IEEE Xplore. Restrictions apply.
2298 IEEE TRANSACTIONS ON ELECTROMAGNETIC COMPATIBILITY, VOL. 64, NO. 6, DECEMBER 2022
Fig. 5. Comparison between the measured current through surge arrester and
that calculated using (1).
Fig. 7. Evaluation of time to sparkover.
lines between 0.9 Vpeak and 0.3 Vpeak and between 0.9 Ipeak
Fig. 6. Capacitance and conductance measured using an impedance analyzer. (Ipeak : peak value of the current) and 0.3 Ipeak , respectively.
(a) Frequency characteristics of capacitance. (b) Frequency characteristics of
conductance.
III. MEASURED RESULTS
A. Discharge Characteristics of 6.6-kV Surge Arrester With
which were obtained using the following expressions: Internal Series Gap
N
N
Fig. 8 shows the measured voltage–time characteristics of the
C= s n Cn / sn (2) internal series gap of the surge arrester obtained, as explained in
n=1 n=1
Section II-B. In Fig. 8, in addition to the measured results, we
N
N
also give the fitting curve of the measured voltage–time charac-
G= s n Gn / s n (3) teristics, which was expressed using the following approximate
n=1 n=1 expression [17]:
where N, sn, and s n are the number of samples of the Fourier
transform, the spectrum of the derivative of the measured voltage 1 t − tf
V = V0 1 + exp − (4)
at the nth frequency, and the spectrum of the measured voltage at 2 ts
the nth frequency, respectively. The capacitance Cn and conduc-
tance Gn at the nth frequency were measured by an impedance where V0 is the minimum sparkover voltage and tf and ts are the
analyzer (HP, 4294A), as shown in Fig. 6. parameters to simulate the effect of the discharge delay, which
As shown in Fig. 5, the rise time and shape of the calculated were estimated from the measured results (N: number of data)
current agree well with the measured waveform before the by the least squares method. In the above measured results, the
occurrence of the sparkover across the series gap, and it was maximum sparkover voltage was 49.5 kV at 9.0 ns, which is
confirmed that this current occurred mainly because of the effect about 1.5 times larger than that for the steep lightning impulse
of the capacitance of the surge arrester. Taking this phenomenon voltage with a rise time of 0.5 µs given in the manufacturer’s
into account, to evaluate the discharge characteristics (voltage– specifications. On the other hand, the voltage–time character-
time characteristics) from the measured voltage and current, istics at around 30–40 ns later appear flat, and the minimum
we defined that the voltage V is the peak value of the voltage sparkover voltage V0 was 33.3 kV, which was almost the same
waveform Vpeak , and the time to sparkover t (see Fig. 7). As as that for the lightning impulse voltage specified in the data
shown in Fig. 7, tV and tI are zero crossing times of the straight sheet provided by the manufacturer.
Authorized licensed use limited to: University of Craiova. Downloaded on January 10,2024 at 07:55:26 UTC from IEEE Xplore. Restrictions apply.
IEEE TRANSACTIONS ON ELECTROMAGNETIC COMPATIBILITY, VOL. 64, NO. 6, DECEMBER 2022 2299
IV. CONCLUSION
In this letter, using a PCI system, we measured the discharge
characteristics (voltage–time characteristics) and residual volt-
age of the 6.6-kV surge arrester with a series gap, which is
commonly installed in 6.6-kV distribution lines as countermea-
sures against lightning overvoltage in Japan. From the measured
results, we found the following points:
1) The sparkover across the series gap occurred at 49.5 kV to
operate the surge arrester even at 9.0 ns in the voltage–time
characteristics for the steep-front transients. This voltage
is about 1.5 times larger than the sparkover voltage for
the steep lightning impulse voltage, which is given in
the specifications from the manufacturer. In addition, the
sparkover voltage of the series gap around 30–40 ns later
is similar to that for the steep lightning impulse voltage
with a rise time of 0.5 µs within a difference of 5%.
2) The voltage across the surge arrester converges to a resid-
ual voltage after the occurrence of the sparkover across the
series gap. Even when the time of the occurrence of the
sparkover was 9.0 ns, the maximum residual voltage of
Fig. 9. Measured current through surge arrester and voltage across it. the surge arrester was 34.9 kV, which is about 1.5 times
(a) Sparkover time of 9.0 ns. (b) Sparkover time of 40.1 ns.
larger than that for the lightning impulse voltage specified
in the data sheet of the manufacturer. The residual voltage
of the surge arrester when the sparkover occurred at around
B. Residual Voltage of 6.6-kV Surge Arrester With Internal
40 ns later is almost identical to that for the lightning
Series Gap
impulse voltage.
As an example of the measured waveforms of the voltage and The above measured results can be used to model the surge
current, Fig. 9(a) and (b) shows the measured currents flowing arresters with a series gap and evaluate voltages induced on
through the surge arrester and the voltages across it, where the distribution lines and overvoltages entering transformers and
sparkover occurred across the internal series gap in the wavefront other equipment through electromagnetic transient simulations.
and wave tail of the applied voltage, respectively. In Fig. 9(a)
and (b), the times of the occurrence of the sparkover are 9.0 ns
and 40.1 ns, respectively. From these results, we found that the REFERENCES
current starts to flow immediately after the occurrence of the [1] S. Yokoyama, K. Michishita, T. Sato, H. Sugimoto, and Y. Morooka,
sparkover across the series gap, and then the voltage across “Review of lightning observation on overhead distribution lines in Japan,”
in Proc. 11th Asia-Pacific Int. Conf. Lightning, 2019, pp. 1–6.
the surge arrester converges to an almost constant residual [2] North American Electric Reliability Corporation and the U.S.
voltage after the sparkover of the series gap. In Fig. 9(a), the Department of Energy, “High-impact, low-frequency event risk to
peak value of the voltage after the occurrence of the sparkover the North American bulk power system,” Jun. 2010. [Online]. Available:
https://www.energy.gov/ceser/downloads/high-impact-low-frequency-
is 34.9 kV, which is 1.5 times larger than the residual voltage risk-north-american-bulk-power-system-june-2010
of 24 kV for the lightning impulse current (8/20 µs, 2500 A) [3] Electromagnetic Compatibility (EMC)—Part 1-3: General—The Effects
specified in the data sheet of the manufacturer. In Fig. 9(a), the of High-Altitude EMP (HEMP) on Civil Equipment and Systems, IEC/TR
61000-1-3, 2002.
voltage shows a tendency to decrease after around 30 ns for [4] Electromagnetic Compatibility (EMC)—Part 2-10: Environment—
the increasing current. The main reason for this is presumed to Description of HEMP Environment—Conducted Disturbance, IEC 61000-
be the effect of the frequency characteristics of the MOV, which 2-10, 2021.
[5] V. J. Kruse, T. K. Liu, F. M. Tesche, and P. R. Barnes, “Flashover vulnerabil-
indicates that it will be necessary to evaluate the voltage–current ity of transmission and distribution lines to high-altitude electromagnetic
relationship of the MOV itself for steep-front transients. On the pulse (HEMP),” IEEE Trans. Power Del., vol. 5, no. 2, pp. 1164–1169,
other hand, in Fig. 9(b), the peak voltage is 22.5 kV, which is Apr. 1990.
[6] V. J. Kruse, D. J. Nickel, E. R. Taylor, J. J. Bonk, and P. R. Barnes,
closer to the specified residual voltage of 24 kV for the lightning “Impacts of a nominal nuclear electromagnetic pulse on electric power
impulse current. Although the current for the steep-front tran- systems: A probabilistic approach,” IEEE Trans. Power Del., vol. 6, no. 3,
sient is 60.9 A in this case, in case of HEMP events, the peak pp. 1251–1263, Jul. 1991.
[7] J. S. Foster Jr. et al., “Report of the commission to assess the threat
values of currents flowing through surge arresters in distribution to the United States from electromagnetic pulse (EMP) attack,” Criti-
lines are much smaller than those due to lightning strikes, and cal National Infrastructures, Apr. 2008. [Online]. Available: http://www.
the residual voltage of the surge arrester does not change so empcommission.org/docs/A2473-EMP_Commission-7MB.pdf
Authorized licensed use limited to: University of Craiova. Downloaded on January 10,2024 at 07:55:26 UTC from IEEE Xplore. Restrictions apply.
2300 IEEE TRANSACTIONS ON ELECTROMAGNETIC COMPATIBILITY, VOL. 64, NO. 6, DECEMBER 2022
[8] Electromagnetic Compatibility (EMC)—Part 2: Environment—Section 9: [13] High-Altitude Electromagnetic Pulse (HEMP) Protection for Ground-
Description of HEMP Environment—Radiated Disturbance, IEC 61000- Based C4I Facilities Performing Critical Time-Urgent Missions, Part 1:
255 2-9, 1996. Fixed Facilities, MIL-STD-188-125-1, 1998.
[9] R. Hoad and W. A. Radasky, “Progress in high-altitude electromag- [14] Y. Koga, Y. Yoneda, T. Sato, S. Yokoyama, and S. Matsumoto, “Degra-
netic pulse (HEMP) standardization,” IEEE Trans. Electromagn. Compat., dation characteristics on MOV of surge arrester used for 6.6 kV power
vol. 55, no. 3, pp. 532–538, Jun. 2013. distribution line,” in Proc. 33rd Int. Conf. Lightning Protection, 2016,
[10] E. Savage, J. Gilbert, and W. Radasky, “The early-time (E1) high-altitude pp. 1–5.
electromagnetic pulse (HEMP) and its impact on the U.S. power grid,” [15] T. Sakoda, H. Horie, A. Takei, K. Kubo, M. Mizutani, and T. Fukano,
Metatech Corporation, Meta-R-320, Jan. 2010. [Online]. Available: http: “Study on discharge time lag phenomenon for a surge arrester with a spark
//large.stanford.edu/courses/2019/ph241/rogers1/docs/meta-r-320.pdf gap,” IEEJ Trans. Fundam. Mater., vol. 138, no. 9, pp. 457–462, 2019.
[11] F. Heidler, Z. Flisowski, W. Zischaank, C. Bouquegneau, and C. Mazzetti, [16] L. Fu-Cheng, L. Jin-Song, and T. Xiao-Xue, “Simulation study on leakage
“Parameters of lightning current given in IEC 62305_background, expe- current of metal zinc oxide arrester,” in Proc. Chin. Control Decis. Conf.,
rience and outlook,” in Proc. 29th Int. Conf. Lightning Protection, 2008, 2018, pp. 5705–5709.
pp. 1–22. [17] S. Matsumoto, T. Sato, H. Honda, and S. Yokoyama, “Approximate
[12] Y. Zhou, Y.-Z. Xie, D.-Z. Zhang, N. Dong, Y.-H. Chen, and Y. Jing, formula for surface V-t characteristics of 6.6-kV distribution insulator,”
“Response of 10-kV metal-oxide surge arresters excited by nanosecond- in Proc. Int. Conf. Lightning Protection, 2012, pp. 1–5.
level transient electromagnetic disturbances,” IEEE Trans. Electromagn.
Compat., vol. 63, no. 2, pp. 614–621, Apr. 2021.
Authorized licensed use limited to: University of Craiova. Downloaded on January 10,2024 at 07:55:26 UTC from IEEE Xplore. Restrictions apply.