eQUEST MODEL ANALYSIS

BUILDING TYPE: MUSEUM

AYUSH SONKESHARIYA
HINDUJA
SONIYA PATHARE
Energy consumption = 1558800 kWh

EPI = 129.9 kWh/sq m

Maximum Cooling load = 1387.542 = 115.62tons

129166.93sq ft/ 115.62 tons = 1117.16 sqft/ton


As per PV Watt Calculator, for the Delhi 10sq m. area will produce 1.5 kW DC.
Therefore 1 sq m. will produce 0.15 kW DC.

Terrace area of museum = 2700 sq m.


Let say 75% of the area can be used for pv panels = 2025 sq m.
Therefore area of 2025 will produce 303.75 kW DC

So, if we use a DC system of 303.75 kW,


It can produce an energy of 541,779 kWh/yr