Installation and
operating instructions
File No: 94.81
Date: february 27, 2023
Supersedes: 94.81
Date: november 09, 2016
contents
1.0 Introduction 4 5 .3 Control keys 22
1.1 Instructions for safe use 4 5 . 4 Programming 23
1. 2 Temperature 4 5 . 4 .1 Parameter selection 23
1. 4 Vibration levels 5 5 . 4 . 2 Changing data 24
1.5 Storage 5 6.0 Sensorless operation 24
1.6 Uncrating 5 6.1 Default operating mode – 25
1.7 Handling Design Envelope Quadratic pressure control
430 0 & 438 0 units 5 6.1.1 Settings for quadratic
2 .0 Installation 6 (control curve) pressure
2 .1 Location 6 control 25
2 . 2 Installation 6 6. 2 Constant pressure control 25
2 .3 Pump piping – general 7 6. 2 .1 Settings for constant
2 . 4 Alignment 8 Pressure control 26
2 .5 Starting pump 8 6.3 Changing control modes 26
2 .6 General care 8 6.3 .1 Change to external
2 .7 Lubrication 9 sensor control 26
2 . 8 System cleanliness 9 6.3 . 2 Change to open loop
3 .1 Enclosure rating 13 (ba s) control 26
3 . 2 Ambient temperature 13 6.3 .3 Change to sensorless
4 .0 Electrical installation 13 control 26
4 .1 Ground leakage current 13 6. 4 Special Application Procedures 26
4 . 2 Start/stop of pump 13 6. 4 .1 2-way bypass valve
4 .3 Additional motor protection 13 control 26
4 . 4 Supply voltage 14 6. 4 . 2 Maximum flow control 28
4 .5 Supply fusing 14 6. 4 .3 Flow limit breach closes
4 .6 Grounding & it mains 14 a dry-contact relay 29
4 .7 Relay connections 15 6. 4 . 4 Minimum flow control 29
4 . 8 Electrical installation 6. 4 .5 Multiple sensor control 30
& control connections 15 6. 4 .6 Motor pre-heat
4 . 8 .1 Access to terminals 18 application 31
4 . 8 . 2 Control terminals 18 6. 4 .7 Start standby pump by
4 . 8 .3 Connection examples 19 falling sensor reading 33
4 . 8 . 4 Remote lcp keypad 6. 4 . 8 Start standby by system
wiring 20 contact opening 34
5 .0 Programming, monitoring 20 7.0 Warnings & alarms 36
& diagnotics 7.1 Fault messages 36
5 .1 glcp functions & operation 21 8 .0 Acoustic noise & vibration 39
5 . 2 Indicator lights (leds) 22 table 1 Alarm/warning code list 40
table 2 ivs 102 parameter settings 42
i nstall a ti o n & Design Envelope 4300 & 4380
o perat i ng i nstr uct i on s Vertical In-line Pumping Unit
This document contains specific information regarding the safe Install the Design Envelope unit with adequate access
installation, operating and maintenance of the Armstrong Design for routine maintenance. Adequate space, particularly
Envelope pumps should be read and understood by installing, at the fan inlet 2" (50 mm), is necessary to facilitate
operating and maintenance personnel. The equipment supplied airflow. Where several Design Envelope units are installed in close
has been designed and constructed to be safe and without risk to proximity, care must be taken to ensure that there is no re-circula-
health and safety when properly installed, operated and main- tion of exhausted warm air.
tained. The instructions following must be strictly adhered to. If
clarification is needed on any point please contact Armstrong Where under normal operating conditions the limit of 68°c/155°f
quoting the equipment serial number. (Restricted Zone) for normal touch, or 80°c/176°f (Unrestricted
Zone) for unintentional touch, may be experienced, steps should
be taken to minimize contact or warn operators/users that normal
1.1 instructions for safe use operating conditions will be exceeded. In certain cases where
the temperature of the pumped liquid exceeds the above stated
No installation of this equipment should take place temperature levels, pump casing temperatures may exceed
unless this document has been studied and understood. 100°c/212°f and not withstanding pump insulation techniques
Handling, transportation and installation of this equip- appropriate measures must be taken to minimize risk for
ment should only undertaken by trained personnel with proper use operating personnel. The ambient temperature for standard
of lifting equipment. See later diagrams for lifting advice. Refer to motors must be no greater than 40°c/104°f.
the pump nameplate for pump speed, pressure and temperature
limitations. The limits stated must not be exceeded without
written permission from Armstrong.
Typical Pumping Unit Sound Pressure Level, Decibels, A-Weighted, at 1 m (3 ft.) from unit.
0.28 7.11
0.24 a
6.10
0.20 5.08
0.16 4.06
x y
0.12 3.04
0.08 2.03
0.04 1.01
0 0
1 10 100 1000 0.75 7.5 75 750
Pumps not immediately placed into service, or removed from integrated controls, pump or motor. Never place cable slings
service and stored, must be properly prepared to prevent exces- around the pump shaft or integrated controls. The eye bolts or
sive rusting. Pump port protection plates must not be removed lifting lugs on the motor are intended for lifting only the motor and
until the pump is ready to connect to the piping. not the complete unit.
For Design Envelope 4300 units, remove the coupling guard and Electric motor driven pumps should not be located in damp or
insert lifting straps through the pump/motor pedestal on either dusty location without special protection.
side of the coupling. For Design Envelope 4380 units, remove
the motor eye-bolt and install a swivel hoist ring tied to a lifting Airflow into the motor and/or motor fan should not be obstructed.
strap. Place secondary lifting straps around the motor feet (and/
or spacers). As the lifting device is engaged (Using a spacer bar It is good practice to leave sufficient space around equipment for
if necessary) and the straps tighten ensure no part of the strap- maintenance and service needs. If the ivs102 controls are sup-
ping is touching any part of the control or motor fan cover. Lift the plied with integral disconnect switches, 36ins / 1 meter clearance
pumping unit carefully from the pallet in this manner and allow the may be required in front of the controls to meet local electrical
unit to stand upright on a flat surface and re-position the straps, if codes.
necessary, to ensure safe and damage-free transportation into the
pipe installation.
2 . 2 installation
2.2.3
In closed systems, where possible, the pumps should be installed
Should additional space saving be required the discharge spool
immediately downstream of the expansion tank /make-up connec-
piece may be replaced by a long-radius elbow.
tion. This is the point of zero pressure change and is necessary for
effective pump operation. Do not install more than one expansion
tank connection into any closed hydronic system.
Design Envelope 4300 & 4380 insta lla t io n &
Vertical In-line Pumping Unit oper ating in struct io n s
2.2.4 tors and the base isolated from the building structure on an inertia
Fig 2.4 illustrates a similar arrangement to Fig 2.2 with additional base. (Fig. 2.11 is generally acceptable when using plastic piping).
floor mounted pipe-stools isolated from the structure by ‘waffle’
style neoprene isolation pads under the Armstrong Suction Guide 2.2.12
and Flo-Trex valve. The motor and integrated control assembly can be rotated in
90° increments to meet installation spacing requirements.
2.2.5 Where applicable, remove the coupling guard to access the motor
Floor mounted saddle supports (Fig. 2.5) are typical for condenser bolts. Remove the motor bolts to rotate the motor and integrated
water pumps where cooling tower base is at the mechanical room control assembly by hand. Larger motors may need strapping and
elevation. slight lifting to break the contact with the pedestal. Care should
be taken that the controls are not damaged during lifting and
2.2.6 that the flushline, flushline accessories and the coupling guard
Where required, additional floor support may be used as shown removal/seal service window are not compromised following the
in Fig. 2.6. Note that the pump should not be rigidly attached to turn (Fig. 2.12). vil pumping units without integrated controls can
the column. Leave a small gap between pump and column or also be rotated in a similar manner to facilitate access to the the
install a ‘waffle’ isolation pad under the pump. It is critical that motor terminal box.
piping be installed in such a manner that the pump does not
become a pipe support. 2.2.13
For d1 and d2 chassis ivs102 units (150 hp–350 hp), ensure ad-
2.2.7 equate space is available for the access door to swing open.
Fig. 2.7 illustrates stanchion plates at the pump inlet and outlet (Fig. 2.13)
ports that may be supplied for installation convenience. Isolation
pads must be used under the legs and monitored as pipe hang-
ers are adjusted to ensure the pump flanges are not supporting important:
the piping. Bolting to the floor or housekeeping pad is not recom-
mended. If the stanchions are bolted down the bolts must be All Design Envelope 4300 pumps contain a tapped hole in the mo-
isolated from the stanchion or an inertia base and flexible pipe tor bracket above the discharge flange (see Fig. 2.14) for draining
connectors used. the well. Pipe this drain hole to a floor drain to avoid overflow of
the cavity caused by collecting chilled water condensate or from
2.2.8 seal failure.
Fig. 2.8 illustrates installations with stanchion plates for seismical-
ly active regions. Seismically rated isolation pads or snubbers with
bolts isolated from the stanchion plates are installed to restrain the 2.3 pump piping – gener al
pump during a seismic event. Pipe hangers carry the weight of the
equipment as seismic components are designed only to restrain Never connect a pump to piping, unless extra care is taken to
the equipment during a seismic event. measure and align the piping flanges well. Always start piping
from pump.
2.2.9
Use as few bends as possible and preferably long radius elbows.
Many Vertical In-Line pumps are piped successfully into grooved
piping systems. In-line pumps are supported well by grooved Do not use flexible connectors on the suction or discharge of a
piping however flange adapter locking devices or a welded flange vertical in-line pump, unless the pump is rigidly mounted to a
at the pump should be used to prevent the possibility of pipe foundation.
mounted pumps rotating in the piping. Armstrong offers grooved
Ensure piping exerts no strain on pump as this could distort
suction guides with cast-in outlet flanges and Flo-Trex valves with
the casing causing breakage or early failure due to pump
Armgrip™ fittings to prevent this possibility. (Fig. 2.9)
misalignment.
2.2.10 All conecting pipe flanges must be square to the pipework and
Do not support the unit by the motor eye bolts (Fig. 2.10) or by any parallel to the pump flanges.
other part of the motor.
Suction and discharge pipes may be increased or decreased at
pump nozzle to suit pump capacity and particular conditions of
2.2.11
installation. Use eccentric reducers on suction connection with flat
Connecting the pump to a permanent rigid base (Fig. 2.11) is not
side uppermost.
recommended unless isolated from the piping by flexible connec-
i nstall a ti o n & Design Envelope 4300 & 4380
o perat i ng i nstr uct i on s Vertical In-line Pumping Unit
Layout the suction line with a continual rise towards the pump Design Envelope 4380 units are fitted with seal flush/vent lines
without high points, thus eliminating possibility of air pockets that piped to the pump suction area. When these units operate, re-
may prevent the pump from operating effectively. sidual air is drawn out of the pump towards the suction piping.
Bump or energize the motor momentarily and check that
A strainer of three or four times the area of the suction pipe,
the rotation corresponds with the directional arrow on the
installed in the suction line, will prevent the entrance of foreign
pump casing (clockwise when viewed from drive end.).
materials into the pump. V" (3 mm) diameter perforations in the
strainer is typical.
Start the pump with the discharge valve closed and the suction
In open systems, test suction line for air leaks before starting; this valve open, then gradually open the discharge valve when the
becomes essential with long suction line or static lift. motor is at operating speed. The discharge valve may be “cracked”
or open slightly at start up to help eliminate trapped air.
Install, at the pump suction, a straight pipe of a length equivalent
to four or six times its diameter; this becomes essential when han-
When stopping the pump: Close the discharge valve and de-ener-
dling liquids above 120°f (49°c). Armstrong suction guides may be
gize the motor.
used in place of the straight pipe run and in-line strainer.
Install an isolation valve in both suction and discharge lines on Do not run the pump against a closed discharge valve for an
flooded suction application; these valves are used primarily to extended period of time (a few minutes maximum.)
isolate the pump for inspection or repair.
Should the pump be noisy or vibrate on start-up a common reason
Install a non-slam non-return check valve in discharge line
is overstated system head. Check this by calculating the pump
between pump and isolation valve to protect pump from excessive
operating head by deducting the suction pressure gauge value
back pressure and to prevent water running back through the
from the discharge gauge reading. Convert the result into the units
pump in case of driver failure on open systems.
of the pump head as stated on the pump nameplate and compare
the values. The system designer or operator should be made
aware of this soon as some adjustment may be required
2 . 4 alignment to the drive settings to make the pump suitable for the system
as installed.
Design Envelope 4300 units are accurately aligned at the factory
prior to being shipped and do not need re-aligning when installed. Check rotation arrow prior to operating the unit. The
Alignment on a Design Envelope 4300 unit may be verified by as- rotation of all Armstrong Vertical In-Line units is clock-
suring an equal and parallel gap between coupling halves on both wise when viewed from the drive end. (Looking from on
sides of the coupling. top of/behind the motor).
2 .5 starting pump Vertical In-Line pumps are built to operate without periodic
maintenance, other than motor lubrication on larger units. A
Ensure that the pump turns freely by hand, or with some systematic inspection made at regular intervals, will ensure years
gentle mechanical help such as a strap or Allen key in of trouble-free operation, giving special attention to the following:
coupling bolt.
• Keep unit clean
Ensure that all protective guarding is securely fixed in position.
• Provide the motor with correctly sized overload protection. Keep
moisture, refuse, dust or other loose particles away from the
The pump must be fully primed on start up. Fill the pump casing
pump and ventilating openings of the motor.
with liquid and rotate the shaft by hand to remove any air trapped
in the impeller. On Design Envelope 4300 any air trapped in the • Avoid operating the unit in overheated surroundings
casing as the system is filled must be removed by the manual air (Above 100°f/40°c).
vent in the seal flush line. Ensure entrained air is removed from
Design Envelope 4300 pumps, prior to starting, through the air
vent on the seal flush line. Open vent until clear of air.
Design Envelope 4300 & 4380 insta lla t io n &
Vertical In-line Pumping Unit oper ating in struct io n s
warning: The following Armstrong files are available for mechanical seal
replacement instructions:
Whenever any service work is to be performed on a • Series 4300: tc Motor Frame – File 43.88
pumping unit, disconnect the power source to the driver, • Series 4380: File 43.81
lock it off and tag with the reason. Any possibility of the
unit starting while being serviced must be eliminated.
If mechanical seal environmental accessories are installed, ensure
water is flowing through the sight flow indicator and that filter car- 2 .8 system cleanliness
tridges are replaced as recommended. (See Armstrong files 43.85
and 43.86 for seal environmental instructions). Before starting the pump the system must be thoroughly cleaned,
flushed and drained and replenished with clean liquid.
Welding slag and other foreign materials, Stop Leak and cleaning
2 .7 lubrication compounds and improper or excessive water treatment are all
detrimental to the pump internals and sealing arrangement.
Pump
Lubrication is not required. There are no bearings in the pump that Proper operation cannot be guaranteed if the above conditions are
need external lubrication service. not adhered to.
Large Design Envelope 4300 units are installed with a shaft bush- note:
ing located beneath the impeller that is lubricated from the pump Particular care must be taken to check the following before the
discharge. pump is put into operation:
The Design Envelope 4300 pump is flushed from the pump dis- fig. 2.1 Hanger supported pipe mounted
charge because the mechanical seal chamber is isolated from the
liquid in the pump by a throttle bushing. Because the seal chamber
is isolated, seal environmental controls such as filters and separa-
tors, when installed in the Design Envelope 4300 flush line are
very effective, as only the seal chamber needs cleansing, and will
prolong seal life in hvac systems.
Do not run the pump unless properly filled with water as the
mechanical seals need a film of liquid between the faces for proper
operation.
10
fig . 2 . 2 Pipe mounted supported at ceiling fig . 2 . 4 With additional pipe supports
Pipe support
2' or 3'
height above
2' or 3' Neoprene Drain connection finished floor
height above isolation pad
Drain connection
finished floor
Fig. 2.3 Discharge elbow for minimum footprint
Fig. 2.4 With additional pipe supports
fig . 2 .3 Discharge elbow for minimum footprint fig . 2 .5 Floor saddle support
Fig. 2.3 Discharge elbow for minimum footprint
Fig. 2.4 W
Hangers
Hangers support
support the
the weight
weight
of
of the
the filled
filled piping,
piping, pumps
pumps Pipe hanger (typ.)
and
and fittings
fittings See specification
for size and type
Split coupler
Flush line Flo-Trex valve
Recommended field Flo-Trex valve
pressure gauge piping
arrangement
Drain connection
Fig. 2.5 Floor saddle support
Fig. 2.3 Discharge elbow for minimum footprint
Fig. 2.4 With additional pipe supports Fig. 2.6 A
11
Stanchion plates
gap
Seismicallyrated
Seismically Rated Snubbers
snubbers or or
Padsand
andconcrete
Concrete Foundation
Fig. 2.7 With stanchion plates pads foundation
Recommended field
Seismically Rated Snubbers or Flush line
pressure gauge piping
Pads and Concrete Foundation arrangement Flo-Trex valve
Pet cock
(typ.)
Fig. 2.8 Seismic region installation Stanchion plates
Suction
guide
Isolation pads Drain connection
Fig. 2
Seismically Rated Snubbers or
Fig. 2.9 Mounting in grooved pipe
Pads and systems
Concrete Foundation
Fig. 2.7 With stanchion plates
Page 7 of 26
Fig. 2.8 Seismic region installation
Page 7 of 26
12
fig . 2 .10 Motor lifting hook supported fig . 2 .13 Clearance radius for d size chassis
15.7
15.7
(399)
(399)
≤105,0°
20.7
(526)
45°
15.70”
(399)
Design Envelope 4300 seal
leaks or condensate drain
hole. Plumb to drain for
≤105° area cleanliness.
45°
15.70”
(399)
≤105°
20.70”
2.14 Tapped collection well on Series 4300 (526)
13
integr ated controls The size of the leakage current to the ground depends on the fol-
lowing factors, in order of priority:
3 .1 enclosure r ating
1 Switching frequency
The standard enclosure rating for Design Envelope 4300 2 Motor grounded on site or not
and Design Envelope 4380 integrated controls is ul type
12 or ul type 4x for outdoor applications. If the pump is The leakage current is of importance to safety during handling/op-
to be installed in a wet or dusty environment then a higher enclo- eration of the Design Envelope pump if (by mistake) the on-board
sure rating may be required (contact Armstrong). inverter has not been grounded.
safety, risk of death If a higher number of starts/stops is required then the start/stop
digital input must be used (mains voltage directly connected).
Before removing the inverter cover, the system must This is the preferred method of starting and stopping Design
be disconnected from the mains supply. After switch- Envelope Pumps.
ing off, wait for at least 15 minutes for the capacitors to
discharge before opening the cover. The three phase mains must be isolated before performing
maintenance of the pump.
caution
4 .3 additional motor protection
High voltage testing (Megging) of the motor/inverter
may cause damage to the electronic components and With the exception of supply fuses / mcb’s to protect
therefore should not be carried out. the installation (for over-current and short-circuit
protection), no additional overload or over-temperature
protection is required (i.e. thermal overloads). Protection features
4 .1 ground leak age current include:
4 .5 supply fusing 95
Illustration : Terminals for mains and earthing.
fig . 3 Mains and2.grounding
Figure Terminals connections
for Mains andfor a5 units
Grounding
Branch circuit protection (20 0 -2 40V - 1.5hp 1ph/ 5hp and below 3ph,
In order to protect the installation against electrical and fire 38 0 -48 0V/ 5 25- 6 0 0V - 10hp and below)
hazard, all branch circuits in an installation, switch gear, machines
etc., must be short-circuit and over-current protected according
to the national/international regulations.
95
Short circuit protection
The inverter must be protected against short-circuit to avoid
electrical or fire hazard. Armstrong recommends using the fuses
detailed in the separate ivs102 Operating Instructions to protect
service personnel or other equipment in case of an internal failure
in the unit. The frequency converter provides full short circuit
protection in case of a short-circuit on the motor output.
Figure 3. Mains and Grounding Connections for A5 Units Figure 4b. Mai
(200-240V - 5HP and Below, 380-480V / 525-600V - 10HP units (200-240V
4 .6 grounding and it mains and Below) 600V - 60 to 12
NB!
Check the mains voltage corresponds to the mains volt-
age of the frequency conv erter name plate.
ween
15
ween
Figure 4c. Mains and Grounding Connections for D1 and D2 units (380-480V - 150 to 350HP, 525-600V - 150 to 350HP)
fig . 5 Relay contact details
Relay 1 - RUNNING
Terminal 01: Common
Terminal 02: Normal Open 240V AC
Terminal 03: Normal Closed 240V AC
Relay 2 - ALARM
Terminal 04: Common
Terminal 05: Normal Open 400V AC
Terminal 06: Normal Closed 240V AC
5 Units Figure 4b. Mains and Grounding Connections for C1 and C2
- 10HP units (200-240V - 25 to 60HP, 380-480V - 50 to 125HP, 525-
600V
fig - 60Mains
. 4c to 125HP)
and grounding connections for d1
and d2 units ( 38 0 -48 0v – 150 to 350hp, 5 25- 6 0 0v
Figure 5. Relay Contact Details
– 150 to 350hp)
Page 10 of 26
Page 11 of 26
95
Figure 4c. Mains and Grounding Connections for D1 and D2 units (380-480V - 150 to 350HP, 525-600V - 150 to 350HP)
16
The following illustrations identify the location of the relays within fig
Figure 6. .Relay
8 Relay connection
Connection Terminals forterminals
A5, B1 and for Figure
c 1 and c 2 Connection
7. Relay units Terminals for C1 and C2 Units
B2 Units
specific inverter sizes:
The following illustrations identify the location of the relays within spec ific inverter sizes:
fig . 6 Relay connection: terminals for a5 , b1
and b2 units in figures 6, 7 and 8 identify the locati
The illustrations on of the relays within specific inverter sizes:
AUX RELAY
01 02 03
04 05 06
Figure 6. Relay Connection Terminals for A5, B1 and Figure 7. Relay Connection Terminals for C1 and C2 Units
f the relays within spec ific inverter sizes:
B2 Units
fig . 7 Relay connection terminals for c 1 and c 2 units
locati on of the relays within specific inverter sizes:
AUX RELAY
01 02 03
04 05 06
17
3-Phase
Power input
(1-ph power:
No 92 (l2)
connection)
18
1,2,3 4, 5, 61
Relay RelayRunning
2 Alarm
4,5,6 Relay
12 2 Alarm
Supply +24v dc
12 13
Supply Supply
+24V DC +24v dc
13 18
Supply Digital Input
+24V DC Start
19 Digital Input Pump Operating
18 Digital Input Start
Mode
19 Digital Input Control terminal
Pump Operating Mode
4.8.1 ACCESS TO TERMINALS 20 Common 0vsettings are as follows:
functions and factory
20 Common
27 Terminal No.0V Type / Description
Digital Input Factory Setting
Low Water Interlock
1,2,3 Relay 1 Running
ACCESS TO TERMINALS Control terminal functions and 27 29 Input
factory settings are as Digital
follows: 4,5,6
Digital
LowInput
Water InterlockNo
Relay 2
Operation
Alarm
19
3 (R1 N/C)
3 (R1 N/C)
Running Output 2 (R1 N/O)
Running Output 2 (R1 N/O) iii. CONSTANT CURVE MODE - POTENTIOMETER
1 (R1 COM) iii. CONSTANT
CONTROLCURVE MODE - POTENTIOMETER
1 (R1 COM)
CONTROL
To control the pump based on a 0-10v potentiometer sig-
6 (R2 N/C) To nal
control pump basedbelow.
use the connections on a 0-10v potentiometer sig-
6 (R2 N/C) nal use the connections below.
Alarm Output 5 (R2 N/O)
Alarm Output 5 (R2 N/O)
4 (R2 COM)
4 (R2 COM)
i nstall a ti o n & Design Envelope 4300 & 4380
o perat i ng i nstr uct i on s Vertical In-line Pumping Unit
20
iii constant curve mode – potentiometer iv.i constant curve mode - bms signal
12 (+24v)
iv.i CONSTANT CURVE MODE - BMS SIGNAL
To control the pump based on a 0-10v potentiometer
20 (0v)
signal It may be required to run the pump at full speed without automatic
It may be required to run the pump at full speed without
use the connections below.
Start Signal 18 (D12
IN)(+24v) speed control
iv.i speed
automatic CONSTANT (eg(egduring
control CURVE
during system
MODE
system commissioning).
- BMS SIGNAL This can be
commissioning).
This can be achieved
achieved without without programming changes
programming by
19 (D20
IN)(0v)
It may be required
making the connections below. to run the pump atby
changes fullmaking the connec-
speed without
27 (D18
IN)(D IN)
Start Signal12 (+24v) iv.i CONSTANT CURVE MODE tions -below.
automatic
BMS SIGNALspeed control (eg during system commissioning).
29 (D IN)
20 (0v)
19 (D IN) It may be required to run the pump This can
at full be achieved
speed without without programming changes by
32 (D IN)
Start Signal 18 (D IN)
27 (D IN)
automatic speed control (eg during making the connections below.
system commissioning). 12 (+24v)
19 (D IN) 33 (D IN) This can be achieved without programming changes by 20 (0v)
27 (D IN) 29 (D IN) making the connections below.
Start Signal 18 (D IN)
29 (D IN) 50 (10V)
32 (D IN)
0-10V Derived from 1k 19 (D IN) 12 (+24v)
32into
(D(+24v)
IN) 53 (Ain)
Potentiometer 12 33 (D IN) 12 (+24v)
iv.i CONSTANT CURVE MODE - BMS SIGNAL 27 (D IN)
Input T53 (common
3320
(D(0v)
IN) 54 (Ain) 20 (0v)
55 (0 v)
It may be required to run the pump at full 20 (0v) without
speed 29 (D IN)
18 (D IN)
Start Signal 18 (D IN) automatic speed control (eg during system
Start Signal (D IN)Start Signal
18commissioning).
50 (10V) 32 (D IN)
5019
(10V)
(D IN) This can be achieved without programming changes by 19 (D IN)
0-10V Derived from 1k0-10V Derived from 1k 19 (D IN) 33 (D IN)
Output Frequency
5327
(Ain) 42 (Aout)
53 (Ain) making the connections below.
Potentiometer into Potentiometer into(D IN)
4-20mA Analogue
Input T53 (common Input T53 (common 5429
(Ain) 39 (Aout) 27 (D IN) 27 (D IN)
(D IN) 54 (Ain)
29 (D IN) 50 (10V)
5532
(0 (D
v) IN)
55 (0 v) Link 10Vdc (T50 ) into 29 (D IN)
12 (+24v)
3 (R1 N/C) 32 (D IN)
Analogue Input T53 53 (Ain)
33 (D IN) 32 (D IN)
Running Output 2 (R1 N/O) 20 (0v)
Output Frequency 42 (Aout) 33 (D IN) 54 (Ain)
4-20mA Analogue
Output Frequency3950
(Aout) 1 (R142 (Aout)
COM) Start Signal 18 (D IN) 33 (D IN)
(10V) 55 (0 v)
0-10V Derived from 1k 4-20mA Analogue 19 (D IN)
53 (Ain) 39 (Aout) Link 10Vdc (T50 ) into 50 (10V)
Potentiometer into
3 (R1 N/C) 6 (R2 N/C) Analogue Input T53 27 (D IN)
Input T53 (common 54 (Ain) 53 (Ain)
Output Frequency
Link 10Vdc
42 (Aout) 50 (10V)
Running Output Alarm Output
2 (R1
55 (0N/O)
v)
5 (R2 N/O)
4-20mA Analogue Out5429 (D IN) (T50 ) into
(Ain)
1 (R1 COM) 4 (R23COM)
(R1 N/C) Analogue Input T53 39 (Aout)
32 (D IN) 53 (Ain)
55 (0 v)
Running Output 2 (R1 N/O)
Output Frequency 42 (Aout) 33 (D IN) 54 (Ain)
iv.
4-20mA Analogue CONSTANT CURVE
6 (R2 N/C)MODE - BMS SIGNAL
1 (R1 COM)
3 (R1 N/C)
39 (Aout)
When the Building System is to be used for Output Frequency 42 (Aout)
Running Output 55 (0 v)
Alarm Output 5 (R2Management
N/O) 2 (R1 N/O)
4-20mA Analogue Out 50 (10V)
speed control it 4is(R2necessary
COM)
to disable sensorless control Link 10Vdc (T50 ) into 39 (Aout) 1 (R1 COM)
and provide the unit 3 (R1 N/C) a 0-10VDC speed reference
with Analogue Input T53
6 (R2 N/C) 53 (Ain)
Running Output signal. 2 (R1 N/O) Output 42 (Aout)
Alarm Output 5 (R2 N/O)
12 (+24v) 54 (Ain) Frequency
iv. CONSTANT CURVE MODE - BMS SIGNAL 1 (R1 COM)
3 (R1 N/C)
4-20mA Analogue Out 6 (R2 N/C)
55 (0 v) 39 (Aout)
When the Building Management System is to be used for 20 (0v) 4 (R2 COM) Running Output 2 (R1 N/O)
Alarm Output 5 (R2 N/O)
speed control it is necessary toStart
disable
Signalsensorless control 18 (D IN)
iv constant curve mode – bms signal 6 (R2 N/C)
and provide the unit with a 0-10VDC speed reference 19 (D IN) Output Frequency
1 (R1 COM)
42 (Aout)
4 (R2 COM)
signal. Alarm
iv. Output
CONSTANT CURVE MODE - BMS SIGNAL 4-20mA Analogue Out
5 (R2 N/O) 3 (R1 N/C)
12 (+24v) 27 (D IN) 39 (Aout)
When the Building
4 (R2 COM)
Management System 4.8.4 REMOTE LCP KEYPAD
RunningWIRING
6 (R2 N/C)
Output
29 (D IN) is to be used for 2 (R1 N/O)
When the Building Management System is to be used for speed
20 (0v)
Alarm Output 5 (R2 N/O)
speed control it is18necessary to disable sensorless control
4 .8. 4 remote 4 (R2 COM)lcp keypad wiring1 (R1 COM)
32 (D IN)
iv.control it is necessary BMS (D IN) For large IVS units with remote
3 (R1 N/C)LCP keypad, see wiring
and providetothe
Start Signal
CONSTANT CURVE MODE - disable SIGNAL sensorless control and provide
unit with
19 (D IN) a 0-10VDC speed
33 (D IN) reference arrangement
Running Output below
When the Building Management System is to be used for 2 (R1 N/O)
the unit withsignal. a 0-10vdc speed
speed control it is necessary to disable
reference
sensorless
27 (D IN)
signal.
control 12 (+24v)
4.8.4 REMOTE LCP KEYPAD WIRING 1 (R1 COM) 6 (R2 N/C)
and provide the unit with a 0-10VDC29speed
(D IN) reference 50 (10V) For large
LCP Wiring Design Envelope units with remote lcp
Arrangement keypad, see wiring
signal. 20 (0v)
53 (Ain) Alarm Output
3212
(D(+24v)
IN)
For large IVS units with arrangement
remote
Terminal LCPWire
keypad, below.
Colorsee
6 (R2wiring
N/C)
5 (R2 N/O)
Startfrom
0-10v Signal Signal
BMS 18 (D IN)
54 (Ain)
3320
Input T53 (common
(D(0v)
IN) arrangement below
Alarm Output 5 (R2 N/O) 4 (R2 COM)
18 (D IN)
55 (019
v) (D IN) 1 Green
Start Signal T55)
5019(10V)
(D IN)
lc p
IN) Wiring Arrangement 2
27 (DLCP
w iBrown
ring arr angement4 (R2 COM)
Output Frequency
5327(Ain) 42 (Aout) 4.8.4Red
REMOTE LCP KEYPAD WIRING
Wire Color3
(D IN)
4-20mA Analogue Terminal
29 (D IN)
39 (Aout) 4.8.4 REMOTE LCP KEYPAD WIRING
0-10v Signal from BMS 5429(Ain)
(D IN)
Input T53 (common 32 (D IN) 1 4 Yellow
terminal wire color
5532
(0 (D
v) IN) Green ForLCP
large IVS units with remote LCP keypad, see wiring
T55) For large IVS units with remote
5 keypad,
Black see wiring
33 (D IN)
3 (R133 (D IN) 2
N/C) Brown
arrangement below arrangement
1 below
Green
Output Frequency
Running Output
42 (Aout) 2 (R1 N/O) 6 Orange
4-20mA Analogue
3 Red
3950
(Aout)
(10V)
1 (R1 COM)
LCP
50 (10V) 4 Wiring Arrangement
Yellow
7
LCP Blue
2 Brown
Wiring Arrangement
53 (Ain) 8 Purple
3 (R1 N/C) 6 (R253 (Ain) Terminal
N/C) 5 Wire Color
Black 3 Red
0-10v Signal from BMS 54 (Ain)
Terminal Wire Color
Input T53 (common
Running Output AlarmBMS
0-10v Signal from Output
2 (R1 N/O)
55 (0 v)
5 (R254 (Ain) 6 1
N/O) Green 9
Orange Grey
4 Yellow
T55) Input T53 (common
1 (R1 COM) 4 (R2 COM)
55 (0 v) 72 PageBlue
Brown
16 of 26
1 Green
T55)
42 (Aout) 5 Black
Output Frequency
4-20mA Analogue 6 (R2 N/C)
83 Purple
Red 2 Brown
39 (Aout)
Output Frequency 42 (Aout) 9 4 Yellow
Grey 6 Orange
Alarm Output
4-20mA Analogue
5 (R2 N/O) 3 Red
39 (Aout) 5
4 (R2 COM)
3 (R1 N/C)
Page 16 of 26
Black 7 4 Blue
Yellow
Running Output 2 (R1 N/O) 6 Orange
1 (R1 COM)
8 5 Purple
Black
3 (R1 N/C) 7 Blue
Running Output 2 (R1 N/O) 8 Purple 9 6 Grey
Orange
6 (R2 N/C)
1 (R1 COM) 9
Alarm Output 5 (R2 N/O) Grey 7 Blue
4 (R2 COM)
Page 16 of 26 8 Purple
6 (R2 N/C)
Alarm Output 5 (R2 N/O) 9 Grey
4 (R2 COM)
Page 16 of 26
Design Envelope 4300 & 4380 insta lla t io n &
Vertical In-line Pumping Unit oper ating in struct io n s
21
The Bottom section (c) always shows the state of the inverter in
Status mode.
Status display I:
This read-out state is standard after start-up or initialisation.
Use [info ] to obtain information about the value/measurement
linked to the displayed operating variables (1.1, 1.2, 1.3, 2, and 3).
See the operating variables shown in the display in this illustration.
1.1,1.2 and 1.3 are shown in small size. 2 and 3 are shown in
medium size.
Graphical display:
The lcd-display is back-lit with a total of six alpha-numeric lines.
All data is displayed on the lcp which can show up to five operat-
ing variables while in [Status] mode.
Display lines:
a Status line: Status messages displaying icons
and graphics.
In the example, Speed, Motor current, Motor power and Frequency
b Line 1–2: Operator data lines displaying data and variables
are selected as variables in the first and second lines.1.1, 1.2 and 1.3
de-fined or chosen by the user. By pressing the [Status] key,
are shown in small size. 2 is shown in large size.
up to one extra line can be added.
c Status line: Status messages displaying text.
i nstall a ti o n & Design Envelope 4300 & 4380
o perat i ng i nstr uct i on s Vertical In-line Pumping Unit
22
Display Contrast Adjustment: to Display mode from either the Quick Menu mode, the Main
Press [status] and [] for darker display Menu mode or Alarm mode. Also use the Status key to toggle
single or double read-out mode.
Quick Menu
Allows quick set-up of the inverter by access to a limited number
of parameters. Quick Menu does not include all the parameters
that may need to be changed when utilising Sensorless control and
it is therefore recommended that parameter changes are made in
Main Menu mode.
Main Menu
Is used for programming all parameters.
Press [status] and [] for brighter display
Alarm Log
Displays an Alarm list of the five latest alarms (numbered a1-a5).
5 . 2 indicator lights (leds) To obtain additional details about an alarm, use the arrow keys
to manoeuvre to the alarm number and press OK. Information is
If certain threshold values are exceeded, the alarm and/or warning displayed about the condition of the frequency converter before it
led lights up. A status and alarm text appear on the control panel. enters the alarm mode.
The on led is activated when the frequency converter receives
power from mains voltage, a dc bus terminal, or an external 24 v The Alarm log button on the lcp allows access to both Alarm log
supply. At the same time, the back light is on. and Maintenance log.
Info
Displays information about a command, parameter, or function
in any display window. Info provides detailed information when
needed.
5 .3 control keys
Menu keys
The menu keys are divided into functions. The keys below the dis-
play and indicator lamps are used for parameter set-up, including Navigation keys
choice of display indication during normal operation. The four navigation arrows are used to navigate between the
different choices available in Quick Menu, Main Menu and
Alarm Log. Use the keys to move the cursor.
OK
Is used for choosing a parameter marked by the cursor and for
Status enabling the change of a parameter.
Indicates the status of the frequency converter and/or the motor.
three different readouts can be chosen by pressing the Status key: Operation Keys for local control are found at the bottom of the
five line readouts, four line readouts or Smart Logic Control. control panel.
Use Status for selecting the mode of display or for changing back
Design Envelope 4300 & 4380 insta lla t io n &
Vertical In-line Pumping Unit oper ating in struct io n s
23
Hand On.
Enables control of the pump via the glcp. It is possible to enter Each parameter has a name and number which remain the same
the pump speed data by means of the arrow keys. regardless of the programming mode. In the Main Menu mode, the
parameters are divided into groups. The first digit of the parameter
number (from the left) indicates the parameter group number.
The low water device input must be made for the pump
5 . 4 .1 par ameter selection
to start in either hand mode or auto mode.
In the Main Menu mode, the parameters are divided into groups.
You select a parameter group by means of the navigation keys.
Off
Stops the pump.
The following parameter groups are accessible:
Auto On
group parameter group parameter
Enables the pump to be controlled via the control terminals and/or
no. group no. group
serial communication. When a start signal is applied on the control
terminals the pump will start. 0 Operation/display 13 Smart Logic
1 Load/motor 14 Special functions
For the pump to operate in either Sensorless mode or
2 Brakes 15 fc information
any other automatic control mode it is necessary to
have pressed the [Auto on] button. 3 References/ramps 16 Data readouts
4 Limits/warnings 18 Data readouts 2
Reset
5 Digital in/out 20 Drive closed loop
Is used for resetting the frequency converter after an alarm (trip).
6 Analog in/out 21 Ext. closed loop
8 Com. and options 22 Application functions
5 . 4 progr amming 9 Profibus 23 Time-based functions
10 can Fieldbus 25 Cascade controller
Select the Main Menu mode by pressing the [Main Menu] key.
The below read-out appears on the display. The middle and 11 LonWorks 26 Analog i/0 option
bottom sections on the display show a list of parameter groups mcb 109
which can be chosen by toggling the up and down buttons.
After selecting a parameter group, choose a parameter by means
of the navigation keys.
24
Use the [] [] navigation keys to move the cursor horizontally.
Use the [] [] navigation keys to change the data value. The
up key enlarges the data value, and the down key reduces the
data value. Place the cursor on the value you want to save and
press OK.
Design Envelope 4300 & 4380 insta lla t io n &
Vertical In-line Pumping Unit oper ating in struct io n s
25
6.1 default oper ating mode — quadr atic 6.1.1 settings for quadr atic (control curve)
pressure control pressure control
The default control mode for Design Envelope pumps is Quadratic The design duty head and flow of the pump (provided at time of
Pressure Control where the controller is set to control the speed order) is shown as point A in figure 11 in column 1.
according to a control curve between max and min flow (see
below diagram). It is widely recognised that fitting a differential fig . 12 curve approximation set tings
pressure sensor at the most remote load, across the supply pip-
ing and return piping encompassing the valve and coil set, is the h (head)
benchmark scheme for energy efficiency.
0%
h (head) -81
p22
%
100
a control curve
hdesign
set point q (flow)
p20-21
n des
n r a t -86
ign
p
e
22
d
hmin In order for the controller to determine the true fit and position
p22-87 control curve of the control curve it is necessary to set some specific parameters
with data relating to specific points within the operating range
p22-89 q (flow)
of the pump. There are two ways of programming the parameters
depending on whether the speed at the design duty is known
Design Envelope pumps can replicate this control without the or unknown.
need for the remote sensor. As the flow required by the system is
reduced, the pump automatically reduces the head developed ac- Speed at Required System Design Point is known
cording to the pre-set control curve. (Refer to Figure 11):
It is often found that using a remote differential pressure sensor to 1 Set the design head, hdesign, value in par. 20-21 (Setpoint 1),
sense the pressure across a remote load could theoretically result after setting unit of head in par. 20–12 (Reference/
in loads close to the pump being under-pumped. The situation Feedback unit)
would be where the load at a loop extremity is satisfied and the 2 Set the speed of the pump at design head, hdesign, and design
control valve closes while a load close to the pump needs full flow. flow using par. 22–86 (Speed at Design Point [Hz])
The probability of this occurring is remote but it is possible. One 3 Set the minimum head required, hmin, using par. 22–87
answer to this is to move the sensor closer to the pump (two- (Pressure at No-Flow Speed).
thirds out in the system is a popular recommendation) although 4 Adjust the shape of the control curve if required using par.
physically re-positioning the sensor at commissioning stage can 22–81 as shown in figure 12.
be a costly exercise. With Sensorless pump control it is possible to
replicate the moving of a sensor by increasing the head
setting ‘Hmin’. 6. 2 constant pressure control
26
6. 2 .1 settings for constant pressure 6 The drive on/off status can be read as a dry contact between
control terminals 05 and 06
7 The drive alarm status can be read as a dry contact between
1 To revert to this mode of control simply follow these steps: terminals 01 and 02
Set the design head, hdesign, value in par. 20–21 (Setpoint 1). 8 Terminals 42(+) and 39(-) can provide a 0/4-20mA output which
In the units set in par.20–12 (Reference/feedback unit.) by default is disabled, but can be configured to provide speed
2 Turn off flow compensation by setting par. 22-80 to feedback or sensorless flow
‘Disabled’ [0]
27
28
5 Verify the valve starts to close. 3 All work will be done on low voltage, however, when remov-
ing the controller cover high voltage may be exposed. An
electrician license is required in some areas
6. 4 . 2 ma ximum flow control
This application is not compatible with other set-up switching Design Pressure
Design Flow (Unit
20-21 (Unit specified Set point 1
applications, such as duty / standby control specified in 20-12)
in 20-12)
maximum flow control 40% of maxi- Pressure
22-87 mum system — at No-flow
head speed
head (pressure)
29
30
Note: This application is not compatible with other applications 6. 4 .5 multiple sensor control
that require switching between setups such as Duty/Standby
Application (Single or duty / standby operation)
Personnel requirements This configuration is designed for multi-zone hvac systems
1 Armstrong Tier 3 training or equivalent where [max 2] system differential pressure (dp) feedback
2 Ability to terminate simple control wiring sensors are required for circulating pump speed control and
zone flow stability. The system pump controls will ensure
3 Ability to configure Armstrong controls
each sensor setting is maintained with as little over-pressure
4 All work will be done on low voltage, however, when remov- as feasible
ing the controller cover high voltage may be exposed. An
electrician license is required in some areas
parameter value
parameter
setup 1 setup 2 comments
number
(quadratic) (max flow)
Minimum Minimum flow Operation
13-12.0 —
flow set point value For multi zone, multi set-point control for different pressures,
Pressure at Comparator 2 each set-point must be specified. By selecting Multi set-point
13-12.2 —
minimum flow value minimum, [5], in 20-20 Feedback Function, the ivs102 controller
Selection design will increase the speed of the pump if either of the feedbacks is
Design Minimum flow head (Set-up 1) – below its set-point and decrease the speed of the lowest error
20-21
pressure set point. Min flow set pump if both feedbacks are above their individual set-points
point (Set-up 2)
40% of maxi-
22-87 mum system —
Pressure at Site requirements
No-flow speed
head 1 0-10vdc Pressure Transducers wired though not connected
Flow at De- Flow at Design to the ivs102 controller
22-89 —
sign point point 2 Enough space to remove the ivs102 controller cover safely
Note: pid parameters may require adjusting.
Personnel requirements
Testing 1 Armstrong Tier 3 training or equivalent
1 Adjust system valve to reduce the system flow. 2 Ability to terminate simple control wiring
2 When the system flow reaches the Minimum Design Flow 3 Ability to configure Armstrong controls
in parameter 13-12.1 in setup 1, ensure the ivs102 controller
4 Wiring tools including Torx screw driver set
switches to Setup 2.
5 All work will be done on low voltage, however, when
3 Continue to close the system valves and notice the flow
removing the ivs102 controller cover high voltage may be
remaining constant while the pressure increases.
exposed. Follow and maintain all local safety standards and
4 Open more system valves and notice the flow remains con- regulations
stant and the pressure dropping.
5 When the system pressure has reached the Minimum
Pressure Set point in parameter 13-12.1 in setup 2, ensure the
ivs102 controls switch to setup 1
Design Envelope 4300 & 4380 insta lla t io n &
Vertical In-line Pumping Unit oper ating in struct io n s
31
Wiring the controllers as per the ‘Duty/Standby setup guide’. Wire the
Wire the two Pressure Transducers as shown below. Pressure Transducers as shown in the diagram above. Program
the additional parameters, specified above, to both controllers.
ivs 102 - master ivs 102 - slave
Testing
(+24v dc) 12
{ (+24v dc) 12
{
1 Increasing a sensor set-point and verify the pump increases
(+24v dc) 13 { (+24v dc) 13 {
speed to reach all set-points.
analog in 53 { analog in 53 {
0-10vdc 0-10vdc 2 Decrease all set-points and verify the pump reduces speed
analog in 54 { analog in 54 {
0-10vdc 0-10vdc to cover all set-points.
common { common {
analog in analog in
Supply
Supply
PT2
32
Site requirements 4 All work will be done on low voltage, however, when remov-
Sensor method ing the drive cover high voltage may be exposed. An electri-
Digital Sensor with tools to install cian license is required in some areas
Enough space to remove the ivs102 controller cover safelyely 5 Torx screw driver set
Wiring
Personnel requirements
Sensor method
1 Armstrong Tier 3 training or equivalent
Connect the digital input to Terminal 19. Power can be taken
2 Ability to terminate simple control wiring from Terminal 12 or 13.
3 Ability to configure Armstrong controls
Design Envelope 4300 & 4380 insta lla t io n &
Vertical In-line Pumping Unit oper ating in struct io n s
33
ivs 102 controller Programming such as a system feedback differential pressure sensor register
set-point errors. This set-up in the pump controls will trigger
The controls will already be configured if the pre-heat feature
a standby pump activation, replacing the duty pump, and will
has been ordered. Should the pre-heat feature require remov-
close a dry-contact relay for an alarm, or other purpose, when
ing, the parameters as indicated by the tables below can be
a pre-set sensor reading level is reached. Early warning from
adjusted. Cycle power to the drive after the parameters have
the controls allows system investigation prior to major tenant
been set.
inconveniences.
parameter parameter value
comments Operation
number setup 1 setup 2
The sensor reading is compared with a site dependent con-
1–80 [0] Coast [0] Coast Disable function
stant threshold, programmed in 13-12.0. If the sensor value falls
below that threshold for longer than a delay programmed in
Testing 13.12.1, the pumps alternate.
Manual method
1 When the motor is stopped the text “dc Hold” will appear at Site Requirements
bottom of the lcp keypad screen as shown. 1 Installed sensor with wiring run to the controller
2 If the pre-heat feature is disabled in setup 1the “dc Hold” text 2 Clearance to remove the Master controller cover safely
will not appear
Personnel Requirements
Sensor method 1 Armstrong Tier 3 training or equivalent
1 When the sensor has detected moisture, the setup will be
2 Ability to terminate a sensor’s wiring
changed to 2 which will be indicated in the top right hand
corner of the lcp keypad screen. When the motor is stopped 3 Ability to configure Armstrong controllers
the text “dc Hold” will appear at bottom of the lcp screen 4 Familiarity with array variables
as shown. 5 All work will be done on low voltage, however, when remov-
2 If the pre-heat feature is disabled in setup 2 the “dc Hold” ing the controller cover high voltage will be exposed. In
text will not appear. some areas an Electrician license is required
6 No special tools are required
Wiring
The sensor has to be wired to the Master controller. If you don’t
know which controller is the Master controller, verify the set-
tings of parameters 13-00 to 13-02.
The Master controller is the unit that has the following param-
eters configured as follows:
Applications (Duty / Standby operation only) 13-01 Start event [37] Digital input di32
13-02 Stop event [26] Logic rule 0
This configuration is ideal for,
perhaps, old, retrofit or otherwise duty/standby
1 Connect the sensor to the Master controller terminals
suspect systems which are suscep-
tible to pump and/or piping debris terminal (function)
or air blockages, or even broken supply return sensor type 54 (ai) 12 (24vdc) 55 (com)
pump coupling or shaft. The controls
0-10Vdc pwr + -
may be operating at a high speed; system feedback
sensor
however the system is not being 0/4-20mA 2 wires + -
served and system components, 0/4-20mA 3 wires +/pwr - com
i nstall a ti o n & Design Envelope 4300 & 4380
o perat i ng i nstr uct i on s Vertical In-line Pumping Unit
34
2 Move switch s202 (beside terminal input 54) to on if the Configure these parameters when the controller is running
sensor signal is 4-20mA, or leave it off if it’s 0-10Vdc (Setup 1):
35
4 All work will be done on low voltage, however, when remov- Configure this parameter when the drive is not running
ing the drive cover high voltage may be exposed. In some (Setup 2):
areas an Electrician license is required
5 No special tools are required parameter name suggested value
3–42 Ramp down time 120 sec
Wiring
The contact wires have to be wired to the Master drive. If it’s Testing
unknown which drive is the Master drive, verify the settings of
1 Testing alternation when the sensor value drops.
parameters 13-00 to 13-02.
Recommended method: Close the flow / pressure switch
The Master drive is the unit that has the following parameters
isolation valve slowly until the contact opens.
configured as follows:
Alternate method: Disconnect one of the contact wires from
parameter name value the ivs102 controls (terminals 12 and 19).
13–00 slc Controller Mode [1] On
In both cases the pumping units should alternate after the
13–01 Start Event [37] Digital input di32 number of seconds entered in 13.12.1 and alternate again
13–02 Stop Event [26] Logic rule 0 every [number of seconds entered in 13.20.1]
1 Connect the switch to the Master drive terminals 12 (24Vdc 2 Return everything to normal.
output) and 19 (Digital Input)
3 Force alternations by pressing the ok and Right arrow keys
2 24vdc output provided (Terminal 27) when contact opens simultaneously. Keep in mind this can only be done every
(value entered in 13.20.1) seconds.
Site programming options
Verify that during alternations the contact doesn’t open.
Configure the alternation in the Master drive as per the
table below.
Note: All parameters below are arrays. The index in the array
is the number after the dot. For example 13-10.1 is the second
element of the array parameter 13-10.
i nstall a ti o n & Design Envelope 4300 & 4380
o perat i ng i nstr uct i on s Vertical In-line Pumping Unit
36
After a manual reset using the Reset button on the wa r n i n g /a l a r m 7, dc over voltage:
control panel, the Auto On button must be pressed to If the intermediate circuit voltage exceeds the limit, the inverter
restart the pump. trips after a time.
wa r n i n g /a l a r m 8, dc under voltage:
If an alarm cannot be reset, the reason may be that its cause has If the intermediate circuit voltage (dc) drops below the “voltage
not been rectified, or the alarm is trip-locked (see also table on warning low” limit, the inverter checks if 24 v back-up supply is
following page). connected. If no 24 v backup supply is connected, the inverter
trips after a given time depending on the unit.
Alarms that are trip-locked offer additional protection, means
that the mains supply must be switched off before the alarm can wa r n i n g /a l a r m 9, Inverter overloaded:
be reset. After being switched back on, the inverter is no longer The inverter is about to cut out because of an overload (too
blocked and may be reset as described above once the cause has high current for too long). The counter for electronic, thermal
been rectified. inverter protection gives a warning at 98% and trips at 100%,
while giving an alarm. You cannot reset the inverter until the
Alarms that are not trip-locked can also be reset using the counter is below 90%. The fault is that the inverter is overloaded
automatic reset function in par. 14–20 Reset Mode (Warning: by more than nominal
automatic wake-up is possible!) If a warning and alarm is marked wa r n i n g /a l a r m 10, Motor etr over temperature:
against a code in the table on the following page, this means that According to the electronic thermal protection (etr), the motor is
either a warning occurs before an alarm, or it can be specified too hot. You can choose if you want the inverter to give a warning
whether it is a warning or an alarm that is to be displayed for a or an alarm when the counter reaches 100% in par. 1–90 Motor
given fault. This is possible, for instance, in par. 1–90 Motor Thermal Protection. The fault is that the motor is overloaded by
Thermal Protection. After an alarm or trip, the motor carries on more than nominal current for too long. Check that the motor par.
coasting, and the alarm and warning flash on the inverter. Once 1–24 Motor Current is set correctly.
the problem has been rectified, only the alarm continues flashing.
wa r n i n g /a l a r m 11, Motor thermistor over temp:
The thermistor or the thermistor connection is disconnected. You
7.1 fault messages can choose if you want the inverter to give a warning or an alarm
in par. 1-90 Motor Thermal Protection. Check that the thermistor is
wa r n i n g 1, 10 Volts low: connected correctly between terminal 53 or 54 (analog voltage in-
The 10 v voltage from terminal 50 on the control card is below put) and terminal 50 (+ 10 Volts supply), or between terminal 18 or
10 v. Remove some of the load from terminal 50, as the 10 v supply 19 (digital input pnp only) and terminal 50. If a kty sensor is used,
is over-loaded. Max. 15 ma or minimum 590 Ω. check for correct connection between terminal 54 and 55.
37
38
39
40
41
40 Overload t27
41 Overload t29
42 Overload x30/6-7
47 24v supply low x x x
48 1.8v supply low x x
49 Speed limit
50 ama calibration failed x
51 ama check Unom and Inom x
52 ama low Inom x
53 ama motor too big x
54 ama motor too small x
55 ama parameter out of range x
56 ama interrupted by user x
57 ama timeout x
58 ama internal fault x x
59 Current limit x
60 External interlock
62 Output frequency at maxi- x
mum limit
64 Voltage limit x
65 Control board-over tempera- x x x
ture
66 Heat sink temperature low x
67 Option configuration has x
changed
68 Safe stop activated x
70 Illegal fc configuration
80 Drive initialized to Default x
Value
92 No-flow x x Par. 22-2*
93 Dry pump x x Par. 22-2*
94 End of curve x x Par. 22-5*
95 Broken belt x x Par. 22-6*
96 Start delayed x Par. 22-7*
97 Stop delayed x Par. 22-7*
98 Clock fault x Par. 0-7*
i nstall a ti o n & Design Envelope 4300 & 4380
o perat i ng i nstr uct i on s Vertical In-line Pumping Unit
42
load and 1-22 Motor voltage Motor nameplate volts Motor nameplate volts Motor nameplate volts
motor 1-23 Motor frequency 60 or 50 per nameplate 60 or 50 per nameplate 60 or 50 per nameplate
1-24 Motor current fla per nameplate fla per nameplate fla per nameplate
1-25 Motor nominal speed [rpm] Motor nameplate speed Motor nameplate speed Motor nameplate speed
1-73 Flying start Enabled Enabled Enabled
brakes 2-17 Over-voltage control Enabled Enabled Enabled
3-02 Minimum reference 0 Not used 0
3-03 Maximum reference Hdesign [in unit of mapped perf Not used Max frequency of app (50 or
data] 60Hz)
3-15 Reference 1 source [0] No function [0] No function Analog input 53
reference/
ramps 3-16 Reference 2 source [0] No function [0] No function [0] No function
3-17 Reference 3 source [0] No function [0] No function [0] No function
3-41 Ramp up time Desired ramp time (60s typical) Desired ramp time (60s typical) Desired ramp time (60s typical)
3-42 Ramp down time Desired ramp time (60s typical) Desired ramp time (60s typical) Desired ramp time (60s typical)
4-10 Motor speed direction Clockwise Clockwise Clockwise
4-11 Motor speed low limit [rpm]
4-12 Motor speed low limit [Hz] Min frequency of application Min frequency of application Min frequency of application
limits/
4-13 Motor speed high limit [rpm]
warnings
4-14 Motor speed high limit [Hz] Max frequency of application Max frequency of application Max frequency of application
4-16 Torque limit mode(%) 100 100 100
4-18 Current limit(%) Leave at default (110) or increase if motor has difficulty starting. Do not set beyond s.f.x 100.
5-01 Terminal 27 mode Input Input Input
5-10 Terminal 18 digital input Start Start Start
5-11 Terminal 19 digital input [0] No operation [0] No operation [0] No operation
5-12 Terminal 27 digital input [0] No operation [0] No operation [0] No operation
5-13 Terminal 29 digital input Jog Jog Jog
digital 5-14 Terminal 32 digital input [0] No operation [0] No operation [0] No operation
in/out 5-15 Terminal 33 digital input [0] No operation [0] No operation [0] No operation
5-16 Terminal x30/2 digital input [0] No operation [0] No operation [0] No operation
5-17 Terminal x30/3 digital input [0] No operation [0] No operation [0] No operation
5-18 Terminal x30/4 digital input [0] No operation [0] No operation [0] No operation
5-40 Function relay 1 [0] No operation [0] No operation Alarm
5-40 Function relay 2 [0] No operation [0] No operation Running
Design Envelope 4300 & 4380 insta lla t io n &
Vertical In-line Pumping Unit oper ating in struct io n s
43
b u f fa lo
93 east avenue, north
tonawanda, new york,
u.s.a., 14120 - 6594
+1 7 16 693 8813
d r o i t w i c h s pa
pointon way, stonebridge cross
business park, droitwich spa,
worcestershire,
united kingdom, wr9 0lw
+44 121 550 5333
manchester
wolverton street, manchester
united kingdom, m11 2et
+44 161 223 2223
b a n g a lo r e
#18, lewis workspace, 3 rd floor,
off millers - nandidurga road,
jayamahal cbd, benson town,
bangalore, india 560 046
+91 80 4906 3555
shanghai
unit 903, 888 north sichuan rd.
hongkou district, shanghai
china, 200085
+86 21 5237 0909
beijing
room 1612, nanyin building no. 2
north east thrid ring road
chaoyang district, beijing,
china 100027
+86 21 5237 0909
s ão pau lo
rua josé semião rodrigues
agostinho, 1370 galpão 6 embu
das artes, sao paulo, brazil
+55 11 4785 1330
lyo n
93 rue de la villette
lyon, 69003 france
+33 4 26 83 78 74
dubai
jafza view 19, office 402
p.o.box 18226 jafza,
dubai - united arab emirates
+97 1 4 887 6775
jimbolia
str calea motilor nr. 2c
a r m s t r o n g f lu i d t e c h n o lo g y ®
jimbolia 305400, jud.timis
established 1934 a r m s t r o n g f lu i d t e c h n o lo g y. c o m
romania
+40 256 360 030