CLP@ tz
geaynman
20 March 2024 PMc hang Hong ited
xan
EEE est segon
anmienan
AECOM Asia Co. Ltd. Exar cuiing eho
12/F Grand Central Plaza Tower 2 ‘orton Kowleen, Hong Keng
138 Shatin Rural Committee Road Sib sy are ase
Shatin, Hong Kong SB eno weodpcrnne
‘Bit Website mmclppreupcom
Attention: Mr. Dennis Luk
Our ref: WE/L/241664/24-03/SKC/KLN
(Scheme No.: KT-220323)
Please quote our scheme number in response to this letter
Dear Mr. Luk
Revised Transformer Room Layouts for Anderson Road Sites R2-3
The revision of transformer room layouts for the above development has been accomplished.
‘We enclose our Drawing Nos. KT/TR/2023-026A and KT/TR/2023-027A showing the location and
detailed requirements of the proposed transformer room and cable ducts for your action.
You are requested to ensure that the provided transformer room should be complied in all
respects with the drawing enclosed and the requirements as shown on the typical drawings in
accordance with our detailed drawings of COP101 should be fully complied with. No modification
will be acceptable without our prior agreement.
Should you have any queries regarding the above, please contact our Mr. C. H. Ng on telephone
number 2678 3672 or e-mail him at chiho.ng@clp.com.hk .
Yours sincerely
for and on behalf of
CLP Power Hong Kong Limited
S.K. Chow
for Principal Manager - Planning & Design
(East & West Region)
Encl. as stated
ske:flcat
[Tformation Classification: PROPRIETARYNOTES:
1. IF THERE IS A RAMP AT THE PLANT DELIVERY ROUTE,
STRUCTURAL STEEL HAULAGE LUG(S) SHOULD BE
PROVIDED AND MAINTAINED BY CUSTOMER. FOR PLANT
DELIVERY INSIDE TRANSFORMER ROOM, EYE BOLT(S)
SHOULD BE PROVIDED. THE ACTUAL NUMBER(S) AND
LOCATION(S) OF THE HAULAGE LUG(S) AND EYE BOLT(S)
SHOULD BE COORDINATED AT SITE WITH CLP'S ENGINEER,
NO MODIFICATION OF ACB LOCATION(S) WILL BE
ACCEPTABLE WITHOUT CLP PRIOR AGREEMENT.
REMARKS:—
PLANT DELIVERY & BLOCK PLAN PLEASE REFER TO DRG.
NO. KT/TR/2023-027 WITH THE LATEST VERSION.
CUSTOMER'S
SWITCH ROOM
+
2. WERT LEVEL OF TRENCH AT INLET TO BE 10SOrnm MINMUM SELOW PAVEMENT LEVEL FOR HV
‘ABLES AND {080mm BELOW PAVEMENT LEVEL FOR LV CABLES. ALL CABLE TRENCHES TO BE
‘COVERED. WI Smm THICK CHEQUER PLATE & JUNCTIONS WHERE SHOWN CHAMFERED TO BE
{0mm x 150mm. THE CABLE TRENCH OUTLET MUST BE FREE FROM OBSTRUCTION.
STRENGTH OF 30Mpa 6 28°DAYS SHOULD BE 200mm AND TO WTHSTAND A i
[lib ‘OF 7.Skp0 AND THE PLANT LOADS AS SPECIFED. FITS LAD ON. GRADE, THE-SOL,
‘BELOW SHALL BE COMPACTED TO. 95% OF THE MAKMUM DRY DENSITY" DETER IN
‘ACCORDANCE. WI BS. 1377:1880 PART 4,
4. TRANSFORMER ROOM SHALL BE CONSTRUCTED WH RENFORCED CONCRETE OR CONCRETE BLOCK’
(OF 8S GO7S PART A WH A COMPRESSNE STRENGTH OF NOT LESS THAN 20N/ma?.
ERECTON SIAL BE DESGNED TO WTHSTAND A MAKMUM STAT
MIT OF CUSTOMER'S Ly.
‘SWITCHBOARD, ‘SIMILAR TO DRG. NO.
T=COP-10250-D-E33-0102-04-E-A OR
T-COP—10250-D-E33-0102—11—A-A OR
4 X 200 DIA. HOLES FOR MCT
AIR TRUNK TO BE 0.6517
IN CROSS SECTIONAL AREA|
EYE BOLT FOR
UFTING FAN
630 DIA.
EXHAUST FAN
OPEN ACCESS
(NON-COVERED AREA)
EMERGENCY STOP-
PUSH BUTTON FOR
EXHAUST FAN
1000(¥) x 800(H)
STAINLESS STEELY
LouvRE
+198.50
a
‘T-COP=10250-D-£33-0102—12-A
SECTION ALONG 630 DIA. EXHAUST FAN
12014
LAYOUT PLAN OF CUSTOMER'S SWITCH ROOM AT BASEMENT
_ (SECTION ‘A'—"A’_REFER TO
FF ta? 586. K1re/2023—007 wits
THE LATEST VERSION)
oe
500_HIGH MIN. TUNNEL
FLUSH WITH CABLE
TRENCH BOTTOM
(SECTION ‘8'~"8" REFER TO
DRG. KT/TR/2023~027 WITH
THE LATEST VERSION)
Fe
4 X 200 DIA HOLES FOR MCT
CONNECTION, “SIMILAR TO DRG. NO.
‘T=COP—19250-D-£33-0103-04-E-A
4 X 200 DIA. HOLES FOR MCT
CONNECTION, SIMILAR TO DRG. NO.
‘T-COP—10250-D-£33-0103-05-D-A
(2 PLACES)
50 X 20 DEEP RECESS FOR-
Kote
EARTHING CONNECTION IN 3
TRANSFORMERS FOUNDATION
EYE BOLT FOR LV BOARD
INSTALLATION, SIMILAR TO DRG. NO.
T-COP—10280-D-£33-0103-40-A
(2 Places)
ee
1200 DEEP ~
[CABLE TRENCH
Fcapactron |
L
100 X 100mm JUNCTION BOX:
‘AT_2300mm_AFFL WITH 25,
METALLIC CONDUIT UP TO 100
X_ 100mm JUNCTION BOX IN
TRANSFORMER ROOM
4 X 200 DIA. HOLES FOR MCT
CONNECTION, ‘SIMILAR TO DRG. NO.
T-COP—10250-D-E33-0103-04—E-A
800 X 800 SUMP PIT WITH HIGH.
LEVEL WATER DETECTOR, PUMPING
FACILITY AND REMOVABLE CONCRETE
COVERS DETAILS REFER
‘T-COP—10250—D-£33-0106-04-C-A
SUMP PIT
es
‘CONTROL PANEL, e
0 Hace Man, TUNNEL FLusi!
[wn ‘Cabue tenon BOTTOM |
Ir200locee | |
wales |
2600 X 2800 HIGH STAINLESS STEEL
DOOR WITH WICKET AND PANIC BOLT,
‘SIMILAR TO DRG. NO.
T-COP--10250-D-E33-0103-19-G-A
FLOOD GATE FOR DOOR PLEASE REFER:
TO T-COP—10250-D=E33-0112-01-A
1. X #100 UPVC DUCT WITH CONCRETE}
SURROUND IN 1 LAYER (EARTHING
2600 X 2800 HIGH STAINLESS STEEL
DOOR WITHOUT WICKET AND WITHOUT
LOCK, SIMILAR TO DRG. NO.
T=COP—10250-D-E33-0103-21-6-A
‘STRUCTURAL STEEL HAULAGE LUG AT ABOVE FINISH LEVEL:
300mm, 620 MILD STEEL BAR WITH INTERNAL #160 MIN.
FIXING 70 THE EXTERNAL WALL STRUCTURAL ELEMENT WITH
41100 OH PARAPET wa: CONDUCTOR) EXTEND To DRAW PIT
OPEN ACCESS 8 x 0180 eye, DUCTS IN 2, LAYERS
(NON-COVERED AREA) M8," ele JOE ET
Gre eau mere oe a),
'5000kg HORIZONTAL LOAD CAPACITY AT THE END OF A #
180
DELIVERY ACCESS RAMP (1:12 MAX.), PROVIDED AND
MAINTAINED BY THE BUILDING OWNER.
TO DRAW PIT, DETAILS SEE ORG. Nt
T-COP—10250-D-£33-0103-12-G-A)
1500
L-FL00D GATE FOR DOOR PLEASE
REFER TO
T=COP~10250-D-£33—0112-01-A
9630 EXHAUST FAN WITH AIR TRUNK AT
HIGH LEVEL_AND 1000(W) x 800(H)
STAINLESS STEEL LOUVRE AT LOW LEVEL
FLOOD GATE FOR LOUVRE PLEASE REFER
YO T-COP—10250-D-E33-0112-02-A
( PLACES).
‘5200
LAYOUT PLAN OF TRANSFORMER ROOM AT G/F
400 X_100mm JUNCTION
BOX AT 230mm AFL.
WITH 925 METALLIC
CONDUIT DOWN TO 100 x
400mm JUNCTION BOX IN
‘CUSTOMER'S SWITCH ROOM
#80 DRAINAGE Dil. PIPE FLUSH
WITH TRENCH BOTTOM & FALL
To SUMP PIT
PROPOSED LOCATION OF FLOOD GATE
STORAGE FRAME PLEASE REFER TO
T-COP—10250-D-E33-0112-03-A-A
AND THE ACTUAL LOCATION TO BE
‘AGREED WITH CLP's SITE ENGINEER
(3 PLACES)
8 X 6150 UPVC DUCTS IN 2 LAYERS
‘AND ‘1 X #100 UPVC DucT IN 1
LAYER (PILOT/FIBRE_ OPTIC CABLE)
WITH CONCRETE SURROUND EXTEND
TO DRAW PIT,DETAILS SEE DRG. NO.
T=COP—10250-D-E53-0105~i2-6-A
4. X #100 UPVe DUCT wiTH
‘GONGRETE SURROUND IN 1 LAYER
(EARTHING CONDUCTOR) EXTEND To
DRAW PIT
9630 EXHAUST FAN WITH AR TRUNK AT
HIGH LEVEL AND 1000(W) X 800(H)
STAINLESS STEEL LOUVRE AT LOW LEVEL
2600 X 2800 HIGH STAINLESS STEEL
DOOR WITH WICKET AND CLP LOCK,
SIMILAR TO. DRG. NO.
‘T-COP—10250-D-£33-0103-16-G-A SER,
150 X 150 THROUGH WALL OPENING WITH
STAINLESS ‘STEEL COVERS (BOTH INSIDE AND
OUTSIDE) AT HIGH LEVEL FOR TEMPORARY
‘SUPPLY CABLES, SIMILAR TO DRG. NO.
T=COP—10250—D-E33-0103-29-C-A
(Gel). TH REQUREVENT APPLY FOR DOORS, DOOR FRAMES, LOUVRES, RAT GUARDS. TERNAL
[STEELWORK (AR TRUNKING, ANGERS, CHEQUER PLATE, EIC) SHALL BE HOT OP GALVANISED
STEEL TO BS EN 100252004 GRADE’ S275 AND FINSHED WTH ONE COAT OF CALSIA! PLUMBATE
INTEROAL WALL AT 1OQram FROM BOTH SIDES OF ALL DOORS AND AT YCOOmm ABOVE
FNSHED FLOOR LEVEL
+2. THE CUSTOMER'S NSTALLATON INCLUDING THE GENERAL SAFETY REQUREMENTS FOR THE
‘SMICHROOM SHALL COMPLY WITH THE ELECTRICITY ORDNANCE.
5. HOSTING SYSTEM SHALL GE ELECTRCALLY OPERATED. AN EMERGENCY LOWERNG DEVCE WH
HAVONFEEL SHALL BE PROWDED. ELECTHOTTY SUPPLY SHALL BE CONNECTED TO THE
NOLORO'S ESSENTIAL BOARD WITH STANDBY GENERATOR BACK UP.
. THE LAYOUT DRIVING PREPARED FROM BULDNG PLANS SUBMITED. CLP POWER HONG
KONG UMTED MST BE INFORMED IMMEDATELY OF ANY MODFICATONS TO THE BULDING
PLANS WHICH WAY AFFECT THE. DRAWING
5. DOOR CONTACTS SHALL BE WSTALLED FOR ALL WICKET DOORS INSIDE THE TRANSFORMER ROOM.
-EIRE PROTECTION REQUIREMENTS
|. THIS TRANSFORMER ROOM SHALL COMPLY FULLY WIH THE. STANDARD REQUREWENTS OF
HONG KONG FIRE SERVES. DEPARTMENT, FALURE TO COMPLY IN ANY RESPECT MAY RESULT
WA DELAY TO THE PROVSON OF & SUPPLY.
2. THE TRANSFORMER ROOM TO BE COMPLETELY SEPARATED FROM THE REMANOGR. OF THE BULDING
{NO TO BE 2 HOURS FRE RESISTANT PERIOD IN ACCORDANCE WIM 8S 476:1967.
$3. AIL WALL OPENNGS TO LEAD DRECT TO OPEN AR,
4, THE 150mm Hic CONCRETE KERB, AS SHOWN, TO BE CONSTRUCTED BY CUSTOMER AFTER CLP
POWER'S PLANT FAS BEEN INSTALLED AND BEFORE TRANSFORMER ROOM IS ENERGSED.
‘5. MS ROOM IS TO GE PROVED WITH FIRE EXTNGUSHING APPARATUS TO THE SATISFACTION OF
THE ORECTOR OF PRE SERVICES, PORTAELE AS SHON, WL BE PROVDED
{BY CLP POWER. Fx LI. ADDITONAL EQUPMENT, IF ANY, WL GE’ PROMDED 7 CUSTOMER.
6. IE AVTOMATC FRE ALARM NSTALLATON &S REQURED BY THE HONG KONG FRE SERVES
DEPAEMENT, HEAT DETECTION TYPE 1S TO BE PROVDED.
7. MS-ROOM SHALL. BE INCORPORATED IN BULDNG PANS FORMALLY APPROVED BY HONG
‘KONG GOVERNMENT. NOT YET OSTANED, APPROVAL FROM THE BULDING ORDNANCE
DFFice BULDNGS AND LAROS DEPARTMENT SHALL BE" OGTANED.
'. ALL LINNGS FOR ACOUSTIC. AND THERMAL INSULATION PURPOSES iN DUCTINGS AND
‘CONCEALED LOCATIONS SHALL. BE OF CLASS 1 OR 2 RATE OF SURFACE SPREAD OF FLAME.
‘AS PER BRITSH STANDARD 476: PART 7 OR TS INTERNATIONAL EQUNALENT, OR BE BROUGHT
‘UP TO THAT STANDARD BY USE OF AN APPROVED FIRE RETARDANT PRODUCT ACCORDING TO
THE REQUREMENT OF FIRE SERVICES DEPARTMENT.
ELECTRICAL FITTINGS
{ALL METAL WORK MUST BE BONDED TO THE EARTHING TERMINAL AT THE OISTRGUTION
'BORRD WH COPPER CONDUCTOR NOT LESS THAN mm.
‘ALL INTERNAL WRING TO BE PROMDED AND INSTALLED BY CUSTOMER EXCEPT THE AC.
‘SUPPLY SOURCE.
pemenon wer EGR.
5A UGHTING SWITCH WITH PILOT LIGHT
5A, 2-WAY LIGHTING SWITCH WITH PILOT LIGHT
D.P. EXHAUST FAN SWITCH WITH PILOT LIGHT
133A 3 PIN SOCKET OUTLET
139A FUSED SPUR UNIT C/W-D.P, SHITCH
EMERGENCY STOP PUSH BUTTON FOR EXHAUST/FRESH/AKAL FAN
FAN CONTROL PANEL
LY MONITORING PANEL
1.2m TWN LAMPS (TB LED STANDARD TUBE WITH G5 OR G13 BI-PIN
(AP BASE) TO BE FIED ON WALL AT Zim ABOVE FLOOR LEVEL
1.2m TWN LAMPS (8 LED STANDARD TUBE WTH G5 OR G13 BI-PIN
CAP BASE) TO BE SUSPENDED AT 2.8m FROM FLOOR LEVEL
2m TWN IMPS (TB LED STANDARD TUBE WTH G5 OR G13 BI-PWN
CAP BASE) TO BE FED ON WALL AT 2.1m: ABOVE FLOOR LEVEL WTH
ERGENGY Loin UNT
{2m TWH FLUORESCENT LAVPS (TB LED STANDARD TUBE WT GS OR
13 BPN CAP BASE) 10 BE SUSPENDED AT 28m FROM FLOOR LEVEL
WOH EMERGENCY UGHTNG UNIT
BT SIGN BOARO ABOVE DOOR ~ ELECTRICITY SUPPLY TO BE CONNECTED TO
THE LANDLORD'S ESSEMTAL BOARD WITH STANDBY GENERATOR BACK UP
454g 00
BE Bor
YE BOLT FOR SAFETY HARNESS AT 17DOrnm FROM FLOOR LEVEL,
DDETALS SEE DRG. NO. COP—10250-D-E35-O103-37-A
YE BOLT AT HIGH LEVEL/CELING FOR LFTNG FAN
FLOOONG ALARW FLASH UGH
PLASTIC GN STORAGE BOX DETALS SEE ORG. NO,
‘F-00P10250-D-£35-0105-27-8
[METALUC CONDUT STSTEM FOR ACCESS CONTROL SHOULD GE PROMDED
(CHECKED BY:
CHAN KUEN. 05—MAR~2024
DRAWING TITLE :
PROPOSED LAYOUT OF
TRANSFORMER ROOM FOR ARQ
SITE R2-3
SCALE: 1 : 50 (mm) | PROJECT NO. 1220323
DRAWING No..:
KT/TR/2023-026A
PROPRIETARY] ALL RIGHTS RESERVED AND REPRODUCTION IN ANY FORM MUST BE APPROVED BY CLP POWER‘CAPACITY AT THE END OF: A. DELIVERY
\. ACCESS RAMP (T312_MAX.), PROVIDED AND
INTAINED BY THE” BUILD!
/ —~
BLOCK PLAN & DUCTING SYSTEM AT_G/F. sous 1:300]
VEHICULAR 24HRS FREE ACCESS MINIMUM REQUIREMENTS:
LORRY DIMENSION
TURNING RADIUS OF VEHICULAR :
HEADROOM FOR LOADED LORRY MOVEMENT : 4.6M
HEADROOM -FOR UNLOADING AREA
WEIGHT FOR THE LOADED LORRY
WEIGHT FOR THE 2MVA TRANSFORMER
PLANT DELIVERY ACCESS
55M
+ 9000kg
1 SM(W) x 2.8M(H)
:11.5M(L) X 2.7QW)
2 10M
LOADING & UNLOADING AREA
\ Bee ig a HAULAGE LUG AT ABOVE*FINIS!
a
LEVEL 300nh