You are on page 1of 7

DRAWING LIST

SYMBOL DESCRIPTION

E000 TITLE PAGE AND DRAWING LIST


E010 LEGEND & SCHEDULES
E100 GROUND FLOOR LIGHTING LAYOUT
E200 GROUND FLOOR POWER & COMMUNICATIONS LAYOUT
E201 ROOF PLAN POWER & COMMUNICATIONS LAYOUT
E300 SINGLE LINE DIAGRAM 1/2
E301 SINGLE LINE DIAGRAM 2/2

CHILD CARE CENTRE


860-864 HIGH STREET EPPING EPPING
ELECTRICAL SERVICES
PROJECT REFERENCE: 4029

PRELIMINARY
NOT FOR
CONSTRUCTION

DRAWING No E000 DATE 23.02.24 REV P1


POWER SECURITY AND ACCESS CONTROL LIGHTING SCHEDULE

COLOUR
SYMBOL DESCRIPTION SUPPLIER CAT. NO. COLOUR SYMBOL DESCRIPTION SUPPLIER CAT. NO. COLOUR REF SYMBOL DESCRIPTION WATTAGE MOUNTING IP RATING SUPPLIER CAT. NO. COLOUR IMAGE
TEMPERATURE

ELECTRICAL DISTRIBUTION BOARD NHP CONCEPT PLUS GREY PROXIMITY CARD READER CETUS/ CETS3 S
Ø137 DIA. FIXED LED DOWNLIGHT C/W WHITE TRIM AND LED
D1 13.4W RECESSED IP44 THORN 4000K 1500-840 HF WHITE
DRIVER, 1511 LUMEN, 60° BEAM ANGLE
RWH
MP-XX METER PANEL. "xx" DENOTES THE PANEL NUMBER. HAGER GREY DOOR MONITORING REED SWITCH.

10A, 240V SWITCHED SINGLE GENERAL PURPOSE OUTLET SEC Ø320 DIA. DIRECT INDIRECT LED LUMINAIRE C/W LED DRIVER,
WHITE SECURITY CONTROL PANEL D2 20W RECESSED IP44 ZUMTOBEL 4000K LANOS S WHITE
1900LUMEN, 60° BEAM ANGLE
CHILD
10A, 240V SWITCHED DOUBLE GENERAL PURPOSE OUTLET HPM PROTECTION WHITE GLASS BREAK DOOR RELEASE PUSH BUTTON. CETUS/ CETS3 S
XLP777ESWE Ø137 DIA. FIXED LED DOWNLIGHT C/W WHITE TRIM AND PHASE CUT 1500-840 HF
1600 10A, 240V SWITCHED DOUBLE GENERAL PURPOSE OUTLET, "1600" DENOTES D3 13.4W RECESSED IP44 THORN 4000K WHITE
WHITE REQUEST TO EXIT DOOR RELEASE PUSH BUTTON. DIMMABLE LED DRIVER, 1511 LUMEN, 60° BEAM ANGLE RWH +
MOUNTING HEIGHT OF 1600mm AFFL
DIMMABLE
10A, 240V SWITCHED DEDICATED SINGLE SOCKET OUTLET ON A DEDICATED PNC
CLIPSAL ICONIC SERIES WHITE PANIC ALARM BUTTON
CIRCUIT BREAKER UNLESS OTHERWISE NOTED INNER RANGE INCEPTION Ø137 DIA. FIXED LED DOWNLIGHT C/W WHITE TRIM AND LED CETUS/ CETS3 S
D4 7W RECESSED IP44 THORN 4000K WHITE
10A, 240V SWITCHED DEDICATED DOUBLE SOCKET OUTLET ON A DEDICATED REFER SPECIFICATIONS FOR FURTHER DETAILS. DRIVER, 800 LUMEN, 60° BEAM ANGLE 800-840 HF RWH
CLIPSAL ICONIC SERIES WHITE 90° INTRUSION DETECTION PIR SENSOR.
CIRCUIT BREAKER UNLESS OTHERWISE NOTED
10A, 240V SINGLE SOCKET OUTLET WITH DOUBLE USB CHARGER. USB-A + PREMIER
CLIPSAL ICONIC SERIES WHITE 360° INTRUSION DETECTION PIR SENSOR. D5 Ø165 DIA. FIXED LED DOWNLIGHT C/W WHITE TRIM, NON-DIMMABLE 18W RECESSED IP64 SAL 3000K WHITE
USB-C S9073TC
10A, 240V DOUBLE SOCKET OUTLET WITH DOUBLE USB CHARGER. USB-A +
CLIPSAL ICONIC SERIES WHITE EXTERNAL STROBE LIGHT + SCREAMER (IP65)
USB-C
SINGLE PHASE HARDWIRED CONNECTION,SWITCHED BY LOCAL ISOLATOR SCRM 1200mm x 300mm LED LUMINAIRE CLEAN ROOM FITTING C/W LED EAGLE EL-CR44L-1115-0
WEATHERSHIELD GREY INTERNAL SCREAMER L1 27W RECESSED IP44 4000K WHITE
SWITCH, RATING DENOTED DRIVER LIGHTING 00

SINGLE PHASE, DIRECT CONNECTION DEDICATED CIRCUIT, 10AMP RATING 50mm WIDE WIRE SUSPENDED LED LINEAR CONTINUOUS
WEATHERSHIELD GREY EXTERNAL AUDIO VISUAL SECURITY ALARM
UNLESS OTHERWISE NOTED. EXTRUSION WITH 90° ANGLE, SUSPENDED AT 2400AFFL, COMPLETE
ICONIC SERIES L2 WITH WHITE DIFFUSER. LENGTHS AS SHOWN ON DRAWING. LED 20W/MTR SUSPENDED IP20 DARKON 4000K SLIM C SUS TBC
CT RAS REMOTE ARMING STATION
APPLIANCE ISOLATOR SWITCH FOR COOKTOP 45AMPS DOUBLE POLE CLIPSAL ITEM No. WHITE DRIVERS TO SUIT LENGTHS. PROVIDE CONNECTORS AND JOINTS &
3041D45-VW SUSPENSION ACCESSORIES, C/W PHASE CUT DIMMABLE DRIVER
THREE PHASE HARDWIRED CONNECTION,SWITCHED BY LOCAL ISOLATOR CCTV CCTV HEAD-END/ NVR
WEATHERSHIELD GREY
SWITCH, RATING DENOTED
PoE CCTV DOME CAMERA (MIN 4MP). PROVIDE CAT6A LED STRIP MOUNTED IN 15MM WIDE PROFILE C/W REMOTE LED SURFACE SUPER MINI
10A, 240V SWITCHED SINGLE CAPTIVE SCREW SOCKET OUTLET ON A L3 16W/MTR IP20 DARKON 4000K -
56 SERIES GREY OUTLET AT EACH CAMERA LOCATION. DRIVER MOUNTED GRAZER SM
DEDICATED CIRCUIT BREAKER UNLESS OTHERWISE NOTED
EXTERNAL WALL MOUNTED CAMERA C/W MOUNTING
WP 10A, 240V SWITCHED SINGLE GENERAL PURPOSE OUTLET, WEATHER PROOF BRACKET (MIN 4MP). PROVIDE CAT6A OUTLET AT EACH
WSC227/1-RG GREY
IP53 RATED. CAMERA LOCATION.
WP ES LED BATTEN LUMINAIRE C/W LED DRIVER WITH INTEGRATED SURFACE CLEVERTRONI MARGO
10A, 240V SWITCHED DOUBLE GENERAL PURPOSE OUTLET, WEATHER PROOF L4 30W IP65 4000K WHITE
WSC227/2-RG GREY ELECTRIC STRIKE DOOR LOCK. PADDE ES2000 OR EQUAL APPROVED OCCUPANCY SENSOR, 1265mmL x 160mmW x 105mmH MOUTNED CS PRO-1200-SN
IP53 RATED.
P EM PADDE Z4 SERIES MONITORED OR EQUAL
SUSPENDED 10A, 240V SWITCHED DOUBLE GENERAL PURPOSE OUTLET ELECTRIC MAGNETIC DOOR LOCK.
APPROVED
WALL
15A, 240V POWER SUPPLY ON A DEDICATED CIRCUIT BREAKER FOR HAND W1 LED WALL LIGHT C/W LED DRIVER 34W IP65 BEGA 3000K 33 243 K3 TBC
HD MOUNTED
DRYER
NBN
ELECTRICAL PIT

SUPPLIE
MSSB MECHANICAL SWITCHBOARD BY MECH TRADE. SYMBOL DESCRIPTION CAT. NO. COLOUR
R
EXTERNAL CARPARK LIGHTING SCHEDULE
SYMO GEN24 NETWORK TERMINATING DEVICE HOUSED IN NBN HOME DISTRIBUTOR
INV SOLAR INVERTER FRONIUS
PLUS 10kW NTD CABINET. COLOUR
PROVIDE DGPO, FIBRE OUTLET AND COMMS PATCH PANEL. REFER TYPICAL REF SYMBOL DESCRIPTION WATTAGE MOUNTING IP RATING SUPPLIER CAT. NO. COLOUR IMAGE
ALL NBN EQUIPMENT SUPPLIED AND TEMPERATURE

PV SOLAR PANEL (1m x 1.7m) NBN DETAILS FOR INFORMATION.


INSTALLED BY NBN Cc.
PCD
COMMUNICATIONS PREMISES CONNECTION DEVICE. REFER 'NBN Co MDU 6m LIGHT POLE GALVENIZED IRON C/W 300mm OUTREACH ADVANCE
SPECIFICATION' FOR DETAILS AND SPATIAL REQUIREMENTS. TAPERED OCTAGONAL
P1 ARM AND SPIGOT TO SUIT THE LIGHT FITTING. (REFER TO - - - LIGHTING (OR - BLACK -
OR EQUIVALENT
DETAILS ON DRAWING E301) EQUIVALENT)

LED POLE MOUNTED LIGHT FITTING (TYPE 2 POLE ADVANCE


LIGHT SWITCHING RETICULATION LP1
DISTRIBUTION)
128W
MOUNTED
IP65
LIGHTING
4000K XSP E22LGI40K BLACK

SYMBOL DESCRIPTION SUPPLIER CAT. NO. COLOUR SYMBOL DESCRIPTION

PE PHOTO ELECTRIC CELL CLIPSAL ICONIC SERIES WHITE LIGHTING SWITCH CIRCUIT, SEE DRAWING FOR CIRCUIT/SWITCH NUMBERS.

EMERGENCY & EXIT SIGN LUMINAIRE SCHEDULE


240V ONE WAY LIGHT SWITCH CLIPSAL ICONIC SERIES WHITE E HD UPVC UNDERGROUND ORANGE ELECTRICAL CONDUIT. SIZE NOTED ON DRAWING

240V PHASE CUT LED DIMMING UNIT AND CONTROL WIRING - PUSH FOR ON/OFF EMERGENCY PHOTOMETRIC
CLIPSAL ICONIC SERIES WHITE C HD UPVC UNDERGROUND WHITE COMMUNICATIONS CONDUIT. SIZE NOTED ON DRAWING REF SYMBOL DESCRIPTION SUPPLIER CAT. No. IMAGE
AND ROTATE TO DIM DOWN AND UP. OPERATION CLASSIFICATIONS

OS1 360° OCCUPANCY SENSOR STEINEL IR QUATTRO HD WHITE LED SELF-CONTAINED, RECESSED MOUNTED EMERGENCY LIGHT COMPLETE WITH LIFELIGHT
DRY FIRE EM1 NON-MAINTAINED C0:D40 C90:D40 CLEVERTRONICS
EMERGENCY BATTERY BACK-UP PACK. CLIFE
OS2 360° OCCUPANCY SENSOR HIGH FREQUENCY STEINEL PRO HF 360 WHITE
31W IP65 LED SURFACE MOUNT EMERGENCY LUMINAIRE BATTEN COMPLETE WITH
SUPPLIE ARGO PRO-1200-SEN-
OS3 CORRIDOR MOTION DETECTOR. STEINEL IS 345 WHITE SYMBOL DESCRIPTION CAT. NO. COLOUR WRAP AROUND DIFFUSER, BATTERY BACK UP, AND ELECTRONIC BALLAST, QUAD C0: D80
R L4/EM SUSTAINED CLEVERTRONICS L10POD- HV (Set to default
OUTPUT 1330mmL x 160mmW x 105mmH WITH INTEGRATED OCCUPANCY SENSOR. C90: D80
Output 2)
ZONE WORKS HIVE MONITORED SYSTEM
OS4 140° CORNER MOUNT OCCUPANCY SENSOR SETINEL IS 140-2 WHITE TO
AS 3786 COMPLIANT PHOTO ELECTRIC TYPE SMOKE ALARM, HARD WIRED, LED SELF-CONTAINED, WALL MOUNTED EXIT SIGN LIGHT FITTING COMPLETE WITH
BROOKS COMPATIBLE WHITE ULTRABLADE PRO
C/W RECHARGEABLE BATTERY EX1 SINGLE/DOUBLE-SIDED RUNNING MAN PICTOGRAM, WITH DIRECTIONAL ARROW AS MAINTAINED C0:E6.3 C90:E6.3 CLEVERTRONICS
WITH RFAP LUBPRO-SM
SHOWN ON LAYOUT, EMERGENCY BATTERY BACK-UP PACK

RFP RESIDENTIAL FIRE ALARM PANEL C/W 2-HR BATTERY BACKUP BROOKS RFP6V2 WHITE LED SELF-CONTAINED, RECESSED MOUNTED EXIT SIGN LIGHT FITTING COMPLETE
ULTRABLADE PRO EXIT
EX2 WITH SINGLE/DOUBLE-SIDED RUNNING MAN PICTOGRAM, WITH DIRECTIONAL MAINTAINED C0:E6.3 C90:D5 CLEVERTRONICS
LUBPRO
TO ARROW AS SHOWN ON LAYOUT, EMERGENCY BATTERY BACK-UP PACK
AS 1603.3 COMPLIANT THERMAL ALARM, HARD WIRED, C/W RECHARGEABLE
BROOKS COMPATIBLE WHITE
COMMUNICATION BATTERY
WITH RFAP

D-CCT DEDICATED CIRCUIT OV OVEN


SYMBOL DESCRIPTION SUPPLIER CAT. NO. COLOUR ACRONYMS
DR DRYER IC ITEMS IN CEILING
n
INTERCOM DW DISH WASHER RH RANGE HOOD
COMMUNICATIONS OUTLET, 'n' DENOTES NUMBER OF OUTLETS. CLIPSAL ICONIC SERIES WHITE AB ABOVE BENCH ES ELECTRIC STRIKE RWP RAINWATER PUMP
SUPPLIE AC AIR-CONDITION UNIT EM ELECTROMAGNETIC LOCK S C/W SHUTTER
REFER TO SYMBOL DESCRIPTION CAT. NO. COLOUR
COMMUNICATIONS RACK, DOUBLE LINE DENOTES FRONT OF RACK. REFER TO SPEC BLACK R AFFL ABOVE FINISHED FLOOR LEVEL
SPEC FIP FIRE INDICATOR PANEL ST SENSOR TAP
CAMXX CAMERA, XX DENOTES CAMERA NUMBER FR FRIDGE / FREEZER SW SERVERY WINDOW
INT/E TBC BY
AUDIO AND COLOUR VISUAL INTERCOM ENTRY STATION. AIPHONE JP-DV CC CHILDCARE
FREE TO AIR TELEVISION SOCKET OUTLET. CLIPSAL ICONIC SERIES WHITE ARCHITECT G-ST GAS SHUT OFF VALVE UB UNDER BENCH
CFM COFFEE MACHINE HD HAND DRYER WAP WIRELESS ACCESS POINT
INT/S TBC BY CT COOK TOP
AUDIO AND COLOUR VISUAL INTERCOM SUB HANDSET (SLAVE) AIPHONE JP-4HD HWS HOT WATER SYSTEM WM WASHING MACHINE
FREE TO AIR ANTENNA ARCHITECT
CU CONDENSING UNIT HWU HOT WATER UNIT WP WEATHERPROOF (MINIMUM IP54)
INT/M TBC BY C/W COMPLETE WITH MP METER PANEL
WAP AUDIO AND COLOUR VISUAL MASTER INTERCOM AIPHONE JP-4MED
SINGLE DATA OUTLET FOR POE WIRELESS ACCESS POINT N/A N/A N/A ARCHITECT DB DISTRIBUTION BOARD

REV AMENDMENTS DATE PM APPROVED


PROJECT
VERIFY ALL DIMENSIONS ON SITE BEFORE
P1 PRELIMINARY ISSUE 23.04.24 BII NTS PRD 4029-E010
COMMENCING ANY WORK OR MAKING ANY SHOP TM Level 1, 76 Munster Terrace
North Melbourne Victoria 3051
CHILD CARE CENTRE SCALE DRAWN CAD FILE

DRAWING. FIGURED DIMENSIONS TO BE USED IN


PREFERENCE TO SCALED DRAWINGS.
THIS DRAWING AT ALL TIMES REMAINS THE
PRELIMINARY Telephone: + 61 3 9328 8088
Facsimile: + 61 3 9328 8966
Email: info@ecmgroup.com.au
Web: www.ecmgroup.com.au
860-864 HIGH STREET EPPING EPPING
DRAWING
SHEET SIZE A1 DESIGNED

DESIGN REVIEW
PRD DATE JUN 2023

COPYRIGHT OF ECM GROUP PTY LTD. THIS DRAWING NOT FOR CONSTRUCTION ELECTRICAL SERVICES CHECKED ECM REF 4029
MUST NOT BE RETAINED, COPIED OR USED WITHOUT ENGINEERING CONSULTING MANAGEMENT
THE WRITTEN AUTHORITY OF ECM GROUP PTY LTD. LEGEND & SCHEDULES DRAWING No E010 REV P1
0 1m 2m 3m 4m 5m 6m 7m 8m 9m 10m SCALE: 1:100
A1
LIGHTING CONCEPT FOR ARCHITECT'S REVIEW

D6 D6 D6 D6 D6
POLE MOUNTED
LIGHTING FOR
W1 CARPARK - TBC

W1 L3
D1 D1 D1 D1

D6 EM1
D1 D1 OS1 D1 D1 LP1 P1

L4
D1
OS2 EM1
OS1

L2
D6
SIMILAR EM1 D4 L4
LIGHTING OS1 L4/EM
CONCEPT
D1 EM1
EM1
EM1 D1
OS2
D4
OS2
SIMILAR D1
W1
D6
LIGHTING
CONCEPT
D4 D4 D4 D4 D4 D4 D4 D2
EX1
OS3 OS3 D2b W1
EX2 EM1 EM1
OS1
ENTRY LOBBY AND
L3 RECEPTION LIGHTING
EX1 D3 D3
L1 D2b

D2 D2 D2 D2a
OS1 EM1

D3 D3
EM1
OS1
D2a

L1 D2 EM1 D2 D2 D1 D1 EM1

D2b
D1 D1
SURFACE MOUNTED CIRCULAR FITTINGS
OS2 Ø500mm, Ø400mm, Ø320mm, MOUNTED IN A
EM1 RANDOM ARRANGEMENT.
EM1 D2a ZUMTOBEL LONOS
L1
D2 D2 D2 D1 D1
EX1 L2 D2
W1 OS2

W1 W1
P1
LP1
D6 D6 D6 D6

POLE MOUNTED
LIGHTING FOR
CARPARK - TBC

SURFACE MOUNTED CIRCULAR FITTINGS


Ø320mm
ZUMTOBEL LONOS

REV AMENDMENTS DATE PM APPROVED


PROJECT
VERIFY ALL DIMENSIONS ON SITE BEFORE
P1 PRELIMINARY ISSUE 23.04.24 BII 1:100 FAS 4029-E100
COMMENCING ANY WORK OR MAKING ANY SHOP TM Level 1, 76 Munster Terrace
North Melbourne Victoria 3051
CHILD CARE CENTRE SCALE DRAWN CAD FILE

DRAWING. FIGURED DIMENSIONS TO BE USED IN


PREFERENCE TO SCALED DRAWINGS.
THIS DRAWING AT ALL TIMES REMAINS THE
PRELIMINARY Telephone: + 61 3 9328 8088
Facsimile: + 61 3 9328 8966
Email: info@ecmgroup.com.au
Web: www.ecmgroup.com.au
860-864 HIGH STREET EPPING EPPING
DRAWING
SHEET SIZE A1 DESIGNED

DESIGN REVIEW
FAS
JAM
DATE JUN 2023

COPYRIGHT OF ECM GROUP PTY LTD. THIS DRAWING NOT FOR CONSTRUCTION ELECTRICAL SERVICES CHECKED KAJ ECM REF 4029
MUST NOT BE RETAINED, COPIED OR USED WITHOUT ENGINEERING CONSULTING MANAGEMENT
THE WRITTEN AUTHORITY OF ECM GROUP PTY LTD. GROUND FLOOR LIGHTING LAYOUT DRAWING No E100 REV P1
0 1m 2m 3m 4m 5m 6m 7m 8m 9m 10m SCALE: 1:100
A1
WP WP WP WP
WP
WP WP
AB

WP

AB

FR

AB
xxA,
WM

POWER AND WAP,IC


DATA TO BE
ADVISED
xxA,
xxA, DW
CL,S
DW
AB

WP

RAS
AB
POWER AND
DATA TO BE
ADVISED
CL,S

EM
WP SCRM
CL,S KP
SEC
DB-CC
INV
AB

USB

E
1500

E
CT
RH WAP,IC S,1500
FR AB

E
WAP,IC

NTD
40A, S,1500 P20 OVERHEAD COMMS CONDUIT
CT TYPICAL

E
32A, ROOM POWER
S,1500

USB,AB
OV FR Ø125 HD UPVC UNDERGROUND CONDUIT
AND DATA AB
NOTES:

CCC
ST UB
FOR REVEIW

E
AB
AB HD PROVIDE Ø125mm UNDERGROUND HD UPVC
FR D1 ELECTRICAL CONDUIT TO THE AUTHORITY PIT. PIT

E
CCC
AB LOCATION IS INDICATIVE ONLY. SUBJECT TO
AUTHORITY OFFER.

E
S,1500
CCC CCC

PCD
MSB CONSISTS OF SUPPLY PROTECTION DEVICE,

E
WP
C D2 CT-METER AND CAPACITY CONTROL DEVICE.
WP C
WP WP C PROVIDE SAFETY BOLLARDS ON CAR PARK SIDE.
C SWITCHBOARD DOORS SHALL NOT BE IMPEDED BY
C
C THE SAFETY BOLLARDS.
C E
C E
C E D2 D3 P20 CONDUIT TO NBN STREET PIT. LOCATION MUST
C E BE CONFIRMED WITH NBN PRIOR TO INSTALLATION.
C E MSB
C E REFER SPECIFICATION FOR NBN APPLICATION AND
E
C E PATHWAY DESIGN DRAWING REQUIREMENTS.
C E
C E
C E D3 FREE STANDING 800W x 800D x 36RU COMMS RACK.
C E
C E
C E
E
C E
C E
C E
C E
C E
C E
E
C E
C E
C E P20 COMMUNICATION CONDUIT TO
Ø125 HD UPVC NBN STREET PIT. FINAL PIT
D3 D1 CONDUIT LOCATION IS TO BE CONFIRMED BY
NBN.

REV AMENDMENTS DATE PM APPROVED


PROJECT
VERIFY ALL DIMENSIONS ON SITE BEFORE
P1 PRELIMINARY ISSUE 23.04.24 BII 1:100 FAS 4029-E200
COMMENCING ANY WORK OR MAKING ANY SHOP TM Level 1, 76 Munster Terrace
North Melbourne Victoria 3051
CHILD CARE CENTRE SCALE DRAWN CAD FILE

DRAWING. FIGURED DIMENSIONS TO BE USED IN


PREFERENCE TO SCALED DRAWINGS.
THIS DRAWING AT ALL TIMES REMAINS THE
PRELIMINARY Telephone: + 61 3 9328 8088
Facsimile: + 61 3 9328 8966
Email: info@ecmgroup.com.au
Web: www.ecmgroup.com.au
860-864 HIGH STREET EPPING EPPING
DRAWING
SHEET SIZE A1 DESIGNED

DESIGN REVIEW
FAS
JAM
DATE JUN 2023

COPYRIGHT OF ECM GROUP PTY LTD. THIS DRAWING NOT FOR CONSTRUCTION ELECTRICAL SERVICES CHECKED KAJ ECM REF 4029
MUST NOT BE RETAINED, COPIED OR USED WITHOUT ENGINEERING CONSULTING MANAGEMENT
THE WRITTEN AUTHORITY OF ECM GROUP PTY LTD. GROUND FLOOR POWER & COMMUNICATIONS LAYOUT DRAWING No E200 REV P1
0 1m 2m 3m 4m 5m 6m 7m 8m 9m 10m SCALE: 1:100
A1
SOLAR PV SYSTEM.
32 x 440W PANELS C/W FRONIUS
SYMO ADVANCED 12kW
INVERTER.

10° 10°
10° 10°

10° 10°
10° 10°

10°
10°

10° 10°
10° 10°

10°

10°

10° 10°
10° 10°
10°
10°

10° 10°
10° 10°

10° 10°
10° 10°

INDICATIVE SOLAR PANEL FRAMING SYSTEM


("DELTA-WING" SYSTEM)

1. DELTA-WING FRAMING SYSTEM FACING EAST-WEST


ORIENTATION.
2. INSTALLATION SHALL BE CARRIED OUT IN ACCORDANCE
WITH THE MANUFACTURER'S SPECIFICATIONS
RECOMMENDATION.

REV AMENDMENTS DATE PM APPROVED


PROJECT
VERIFY ALL DIMENSIONS ON SITE BEFORE
P1 PRELIMINARY ISSUE 23.02.24 BII 1:100 FAS 4029-E200
COMMENCING ANY WORK OR MAKING ANY SHOP TM Level 1, 76 Munster Terrace
North Melbourne Victoria 3051
CHILD CARE CENTRE SCALE DRAWN CAD FILE

DRAWING. FIGURED DIMENSIONS TO BE USED IN


PREFERENCE TO SCALED DRAWINGS.
THIS DRAWING AT ALL TIMES REMAINS THE
PRELIMINARY Telephone: + 61 3 9328 8088
Facsimile: + 61 3 9328 8966
Email: info@ecmgroup.com.au
Web: www.ecmgroup.com.au
860-864 HIGH STREET EPPING EPPING
DRAWING
SHEET SIZE A1 DESIGNED

DESIGN REVIEW
FAS
JAM
DATE JUN 2023

COPYRIGHT OF ECM GROUP PTY LTD. THIS DRAWING NOT FOR CONSTRUCTION ELECTRICAL SERVICES CHECKED KAJ ECM REF 4029
MUST NOT BE RETAINED, COPIED OR USED WITHOUT ENGINEERING CONSULTING MANAGEMENT
THE WRITTEN AUTHORITY OF ECM GROUP PTY LTD. ROOF PLAN POWER & COMMUNICATIONS LAYOUT DRAWING No E201 REV

0 1m 2m 3m 4m 5m 6m 7m 8m 9m 10m SCALE: 1:100


A1
MSB
FORM 3B
IP56, 15kA

CT-CHAMBER METER COMPARTMENT


R W B
10A 10A
10A
FUSE 16A 16A 16A SEE NOTE 1 16A 16A 16A 16A 16A 16A 16A
16A
1. THE LIGHTING LAYOUT

7 DAY, 24HR
TIME CLOCK
BELOW
M BY- T1
TS 7 DAY, 24HR DRAWINGS WILL 1. REFER TO AS2293 TCLK
PASS T1 RCD RCD RCD AUTO TEST RCD RCD RCD RCD
RCD RCD RCD
P/B
365 DAY RCD INDICATE THE NUMBER FOR FURTHER
T2 TIME SWITCH N
N OF TIME SWITCHES DETAILS FOR RELAY T1 TIMER
TIMER T2
REQUIRED. 2 HRS
8 HRS EMERGENCY UVR
90 MIN
LIGHTING CONTROL TIMER /
SUPPLY CAPACITY 2. NCC 2019 -
PHASE FAIL DETECTION RELAY
CIRCUITS
SPD CONTROL DEVICE SPECIFICATION J6 N
SCCD N
FOR CHILD CARE (PAGE 400) CLAUSE 3.
C1 C1 C1
2. AUTOMATIC TESTING C1 C1
C1
160A MCCB THE 8 HR TIMER IS UNIT(ATU) - MANUAL OVERRIDE PUSHBUTTON.
N N
160A 160A N REQUIRED TO ENSURE CLEVERTRONICS PROVIDE LABEL TO INDICATE
FUSE MANUAL MODE AUTOMATIC "BOILING WATER UNIT OVERRIDE FOR
MODEL: EATUPB OR TO NOMINATED B.W.U & AFTER HOURS USE "
DISCONNECTOR SEE NOTE 2 LIGHTING IS TEST UNIT
BELOW APPROVED EQUAL CHILLED WATER UNITS
TO NOMINATED EXTERNAL
AUTOMATICALLY
E
INTERNAL LIGHTING EMERGENCY LIGHTING NOTES:
N LIGHTING CIRCUITS (TIME CLOCK CAR PARK RESET TO TIME NCC 2019 - SPECIFICATION J6 CLAUSE 3(d).
ENTRY CIRCUITS CIRCUITS
M.E.N LINK PLUS PE CELL CONTROL) SWITCH OPERATION. THE 2 HR TIMER IS REQUIRED TO ENSURE MANUAL MODE FOR CONTROL BOILING
LIGHT (QUANTITY AS REQUIRED)
QUANTITY AS REQUIRED WATER UNIT IS AUTOMATICALLY RESET TO TIME CLOCK OPERATION.
EXTERIOR
DETAIL 2
PE CELL DETAIL 3
DETAIL 1 TYPICAL EMERGENCY LIGHTING CONTROLS
UNDERGROUND 4 x 1C TYPICAL BOILING WATER UNIT CONTROLS
CONSUMER MAINS 50mm2 TYPICAL EXTERNAL LIGHTING CONTROLS
CU/XLPE 4 x 1C 50mm2+16mm2 E CU/XLPE
CABLE FROM (UNDERGROUND)
STREET PIT.
LIAISE WITH
SUPPLY
AUTHORITY FOR
EXACT PIT
LOCATION.

DB-CC
IP56, 10kA
NHP
CONCEPT PLUS
160A ISOLATOR

3P 400V 160A 10kA BUSBAR


84 POLE CHASSIS MIN.

10A
63A 20A 20A 20A 20A 20A 20A 20A 20A 32A 32A 32A 40A 40A 20A 20A 40A MCB XX 20A 120A
30mA 30mA 30mA 30mA 30mA 30mA 30mA 30mA 30mA 20A MCB 30mA MCCB 30% SPARE
RCBO RCBO RCBO RCBO RCBO RCBO RCBO RCBO RCBO RCBO
RCD RCD RCD RCD RCD RCD
100kA SURGE
PROTECTOR

RCD RCD RCD RCD RCD RCD RCD RCD RCD RCD RCD RCD
EMERGENCY
SPD LIGHTING
TEST SWITCH
REFER RELAY
DETAIL 2 EXTERNAL Y
LIGHTING CONTROL REFER DETAIL 3
REFER DETAIL 1

1 x 4C 35mm2 CU/XLPE
EMERGENCY LIGHTING WITHIN COT DRYER DRYER
LIGHTING INTERNAL LIGHTING ROOMS OVEN FUTURE EV CHARGING ANY OTHER
VIA TEST EXTERNAL LIGHTING WASHING WASHING FUTURE RAIN COOL ROOM
(QUANTITY AS GENERAL POWER ELECTRIC STATION POWER CIRCUITS
SWITCH INCLUDING CANOPY MACHINE COMBO MACHINE COMBO ELECTRIC HOT BOILING WATER
REQUIRED) CIRCUITS. QUANTITY AS COOKTOP AS NOTED ON
SECURITY LIGHTS (QUANTITY AS WATER UNIT WATER PUMP MSSB
REQUIRED POWER LAYOUT
SYSTEM REQUIRED) UNIT
DRWINGS
(INTERNAL 1 x 4C 10mm2 + E
LIGHTS) CU/PVC

1 x 4C 6mm2 + E 1 x 2C 6mm2 + E 1 x 4C 10mm2 + E 1 x 4C 10mm2 + E


CU/PVC CU/PVC CU/PVC CU/PVC DC DISCONNECTORS AT ENGAGE APPROVED SOLAR SYSTEM
INVERTER. DESIGNER/ INSTALLER TO DESIGN,
DC CABLING SUPPLY AND INSTALL PV CELL
TO SUIT (20 x 440W PANELS) SYSTEM COMPLETE WITH INVERTER
AND ASSOCIATED EQUIPMENTS.
SINGLE LINE DIAGRAM NOTES:
7. PROVIDE CHECK METER (DIGITAL POWER ANALYZER) FOR ALL
1. SUBMIT ALL SWITCHBOARD SHOP DRAWINGS INCLUDING PUBLIC LIGHT & POWER BOARDS FOR LIGHTING, POWER, AIR 3ph SOLAR
INVERTER
CONDITIONING, APPLIANCE POWER, CENTRAL HOT WATER,

QUANTITY AS REQUIRED
SCHEMATIC DIAGRAM AND DISCRIMINATION STUDIES FOR CABLING NOTES: (12.5kW)

PV PANELS STRINGS
APPROVAL PRIOR TO CONSTRUCTION. INTERNAL TRANSPORT AND OTHER ANCILLARY PLANT IN
ACCORDANCE WITH NCC, PART J8.
ALL SUBMAIN CABLE SIZES NOMINATED ON THIS DRAWING ARE SIZED:
2. COORDINATE WITH SUPPLY AUTHORITY FOR MAXIMUM 1. TO ACHIEVE TOTAL SITE MAX. 5% VOLTS-DROP AS REQUIRED BY
PROSPECTIVE FAULT CURRENT BEFORE COMMENCING 8. ALL EXTERNAL COMMUNAL LIGHTING SHALL BE CONTROLLED VIA FRONIUS -
PE CELL AND A TIMER CLOCK. AS3000, ASSUMING FINAL SUBCIRUITS DO NOT EXCEED 2.5%
MANUFACTURE OF MAIN SWITCHBOARD. SYMO 12.5-3-M
VOLTSDROP
2. TO MATCH REQUIRED CIRCUIT BREAKER RATINGS AND ARE
3. ALL MAIN SWITCHBOARDS SHALL REQUIRE APPROVAL FROM A 9. PROVIDE TIME CLOCK CONTROL FOR LOW LEVEL WALL MOUNTED
BASED UPON THE ASSUMPTION THAT ALL CABLES WILL BE:-
LICENSED ELECTRICAL INSPECTOR AND SUPPLY AUTHORITY LIGHTING WITHIN COMMON CORRIDOR AREA. DC DISCONNECTORS AT
SPACED ON CABLE TRAY AND ON WALLS WITHIN THE BUILING EACH STRING
COMPLIANCE TECHNICAL ADVISOR (CTA) PRIOR TO UNDERGROUND OUTSIDE THE BUILDING
10. PROVIDE TOTAL OF 35% SPARE CAPACITY (10% FITTED 25% (WEATHERPROOF)
MANUFACTURING. CONSTRUCTION OF MSB SHALL BE IN 3. TO AVOID DERATING AS PER AS3008.1.1 FIGURE 1 PAGE 22.
ACCORDANCE WITH CURRENT AS3000 RULES, RELEVANT SPARE)
CURRENT VICTORIAN SERVICE INSTALLATION RULES (VSIR) AND IF THE ELECTRICAL TRADE CHOOSES TO INSTALL CABLES THAT
CURRENT ELECTRICAL SAFETY (INSTALLATION) REGULATIONS. GROUND LEVEL
TRIGGER A DERATING FACTOR, THEN INCLUDE TO UPGRADE CABLE
TYPICAL. SIZES/TYPES ACCORDINGLY TO COMPLY WITH AS3000 AND AS3008.1.1 MARKER TAPE
SLOPING GROUND
150mm WIDE
4. PROVIDE ADJUSTABLE CIRCUIT BREAKERS. ELECTRICAL
CONTRACTOR TO COORDINATE TRIP SETTINGS OF CIRCUIT INDICATING "ELECTRIC CABLE
BREAKERS ON SITE SO ALLOCATED MAXIMUM DEMAND IS BURIED BELOW"
GROUND LEVEL
CONTROLLED AND CONFORMS TO SUPPLY AUTHORITY'S 250
CONTRACTUAL AGREEMENT. TYPICAL.
250
5. ALLOW FOR PRESCRIBED AND NON-PRESCRIBED ELECTRICAL
INSPECTION. PROVIDE DISCRIMINATION OF PROTECTIVE DEVICES
IN ACCORDANCE WITH AS3000, SECTION 2. 250
HD UPVC ORANGE 600
ELECTRICAL CONDUIT 600
6. ENSURE MAIN SWITCHBOARD COMPLIES WITH THE NCC
REQUIREMENTS FOR FAULT SEGREGATION OF ESSENTIAL AND
NON-ESSENTIAL SWITCHGEAR.

ELECTRICAL CABLES MARKER TAPE

TYPICAL UNDERGROUND ELECTRICAL CONDUIT INSTALLATION


SCALE: NTS

REV AMENDMENTS DATE PM APPROVED


PROJECT
VERIFY ALL DIMENSIONS ON SITE BEFORE
P1 PRELIMINARY ISSUE 23.02.24 BII 1:100 PRD 4029-E300
COMMENCING ANY WORK OR MAKING ANY SHOP TM Level 1, 76 Munster Terrace
North Melbourne Victoria 3051
CHILD CARE CENTRE SCALE DRAWN CAD FILE

DRAWING. FIGURED DIMENSIONS TO BE USED IN


PREFERENCE TO SCALED DRAWINGS.
THIS DRAWING AT ALL TIMES REMAINS THE
PRELIMINARY Telephone: + 61 3 9328 8088
Facsimile: + 61 3 9328 8966
Email: info@ecmgroup.com.au
Web: www.ecmgroup.com.au
860-864 HIGH STREET EPPING EPPING
DRAWING
SHEET SIZE A1 DESIGNED

DESIGN REVIEW
PRD
KAO
DATE JUN 2023

COPYRIGHT OF ECM GROUP PTY LTD. THIS DRAWING NOT FOR CONSTRUCTION ELECTRICAL SERVICES CHECKED KAO ECM REF 4029
MUST NOT BE RETAINED, COPIED OR USED WITHOUT ENGINEERING CONSULTING MANAGEMENT
THE WRITTEN AUTHORITY OF ECM GROUP PTY LTD. SINGLE LINE DIAGRAM 1/2 DRAWING No E300 REV P1
3 x CAT6 CABLES FROM NDT
CUPBOARD

4-PAIR CAT6 CABLE TO EACH


COMMUNICATIONS NOTES:
1 OUTLET (TYPICAL)
1. RACK LAYOUT IS INDICATIVE. LIAISE WITH CLIENT'S IT REP TO
2 24 PORT PATCH PANEL
RJ45 VOICE & DATA OUTLETS. CARRY OUT THE WORK.

NEUTRAL
3 CABLE MANAGEMENT
REFER TO FLOOR PLAN FOR EXACT
4 24 PORT PATCH PANEL
No. OF OUTLETS 2. STRUCTURED CABLING SYSTEM SHALL BE CAT6 EITHER KRONE, MIN 900mm
5 CABLE MANAGEMENT 16A
6 CCTV PATCH PANEL PANDUIT, SIEMON OR SYSTIMAX MANUFACTURER
CAT6A CABLE TO 100mm
7 CCTV NVR
EACH CAMERA MIN 250mm MIN 250mm
8 3. 36 RU RACK SHALL BE AS FOLLOWING: RCD
OCCUPANCY SENSOR
9 SEVER RACK - 800(W) x 800(D) - HALLAM RACKS OR EQUAL PCD

300mm
16 WAY POWER DISTRIBUTION UNIT
10
QUANTITY AS SHOWN ON DRAWING E200
EACH RACK SHALL COMPLETE WITH FOLLOWING: PCD
11 · 2 x SIDE PANELS ENSURE THAT TURNING OFF 300mm
12 · 1 x BACK DOOR - MESH DOOR THE MANUAL SWITCH DOES
13 ACTIVE EQUIPMENT · 1 x FRONT DOOR - TOUGHENED GLASS NOT LOOSE 230V SUPPLY TO
14

MAX 1500mm
· 2 x ADJUSTABLE SHELVES

MIN 450mm
15 OS1 THE OCCUPANCY SENSOR
16
· 1 x VERTICAL CABLE MANAGER 100mm TO 140mm
LEAD-IN CONDUIT
17
· 1 x POWER DISTRIBUTION UNIT (HORIZONTAL 8 WAY)
COMPLETE WITH AUSTRALIAN STANDARD GPOs. INTERNAL CUSTOMER CONDUIT
18 CCTV SERVER 2x32" MONITORS
19 COMPLETE WITH FOR CCTV · 1 x POWER DISTRIBUTION UNIT (VERTICAL 16 WAY)

LUMINAIRE 1

LUMINAIRE 1
LUMINAIRE n

LUMINAIRE n
20 TRUVISION MONITORING COMPLETE WITH AUSTRALIAN STANDARD GPOs.
21 NAVIGATOR V6.0 · 1 x SET OF CASTORS SWITCH SWITCH
22
OR EQUAL.
· 1 x SET OF LEVELING FEET
GROUP 1 GROUP 2 FINISHED GROUND FINISHED GROUND
23 · 1 X SET OF KEYS FOR ALL DOORS OR FLOOR LEVEL OR FLOOR LEVEL
24
CAPTIVE SOCKET OUTLET 25 AV MATRIX SWITCH
CLIPSAL 56 SERIES. WALL
4. THE FOLLOWING EQUIPMENT SHALL BE SUPPLIED AND
MOUNTED BEHIND THE RACK.
26
AMPLIFIER DENON AVR-X2400H-7.2 INSTALLED: PCD SIDE VIEW PCD FRONT VIEW
20A, 1PH HARDWIRED 27
EXACT LOCATION TO BE · BACKBONE COPPER CABLING LIGHT FITTING QUANTITY AS
CONNECTION TO UPS CONFIRMED ON SITE. 28
29
· 24 PORT PATCH PANELS REQUIRED
(PHASE 1)
· PATCH LEADS AND FLYLEADS (REFER SPECIFICATIONS) PCD AND NDT INSTALLATION DETAIL
15A 15A

30 ACTIVE EQUIPMENT
31 · PATCH MODULAR CORDS
FOYER N.T.S.
32 TYPICAL LIGHTING CONTROL VIA OCCUPANCY
CAPTIVE PLUG 5. PROVIDE VERTICAL AND HORIZONTAL CABLE MANAGEMENT
33 8 WAY POWER DISTRIBUTION UNIT
CLIPSAL 56 SERIES
34 BETWEEN EACH PATCH PANEL.
SENSOR AND MANUAL SWITCH MINIMUM CLEARANCE (MEASURED FROM
OR EQUIVALENT. RACK MOUNTED UPS XXX
35
3KVA APC
OUTER EDGES OF PCD
36 6. PROVIDE ALL COPPER TERMINATION.

ALLOW TO PROVIDE APC XXX · 250 MM FROM FIXED SERVICES, INCLUDING


36RU FREE STANDING 7. ACTIVE EQUIPMENT TO BE SUPPLIED BY CLIENT. CONTRACTOR
SMART-UPS, LINE INTERACTIVE, COMMUNICATIONS RACK PIPES, TAPS AND METERS
3KVA, RACKMOUNT 2U, 230V,
TO INSTALL IN LIAISON WITH CLIENT'S IT MANAGER. · 150 MM CLEARANCE FROM GAS ENCLOSURE
WITHIN STORE ROOM
CEILING SPEAKERS JAMO 2WAY IN CEILING OR COMBINED UTILITY ENCLOSURE
SMT3000RMI2UC ROOF MOUNTED DIGITAL FTA ANTENNA. LOCATE TO SUIT
8" 50W.
QUANTITY AS SHOWN ON DRAWING E200 ROOF STRUCTURE. LOCATE IN OPTIMAL POSITION FOLLOWING · OUTSIDE EXCLUSION ZONES AROUND GAS
SIGNAL STRENGTH AND REVIEW OF ROOF STRUCTURE TO REGULATOR/BOXES AND ENCLOSURES, AND
ARCHITECTS AND STRUCTURAL ENGINEERS APPROVAL. GAS DISCHARGE ZONES
· 1500 MM FROM GAS CYLINDERS
· 150 MM FROM THE CORNER OF THE WALL
· 50 MM FROM AN EXTERIOR STRUCTURE, SUCH
ROOF AS A WINDOW OR BALCONY

DUAL RG6 QUAD SHIELDED


CABLES (TYPICAL PER OUTLET)

240V SIGNAL AMPLIFIER AND


POWER SUPPLY SPLITTER

OUTLETS AS SHOWN ON LAYOUT

TYPICAL FREE TO AIR SCHEMATIC DIAGRAM

REV AMENDMENTS DATE PM APPROVED


PROJECT
VERIFY ALL DIMENSIONS ON SITE BEFORE
P1 PRELIMINARY ISSUE 23.02.24 BII 1:100 PRD 4029-E300
COMMENCING ANY WORK OR MAKING ANY SHOP TM Level 1, 76 Munster Terrace
North Melbourne Victoria 3051
CHILD CARE CENTRE SCALE DRAWN CAD FILE

DRAWING. FIGURED DIMENSIONS TO BE USED IN


PREFERENCE TO SCALED DRAWINGS.
THIS DRAWING AT ALL TIMES REMAINS THE
PRELIMINARY Telephone: + 61 3 9328 8088
Facsimile: + 61 3 9328 8966
Email: info@ecmgroup.com.au
Web: www.ecmgroup.com.au
860-864 HIGH STREET EPPING EPPING
DRAWING
SHEET SIZE A1 DESIGNED

DESIGN REVIEW
PRD
KAO
DATE JUN 2023

COPYRIGHT OF ECM GROUP PTY LTD. THIS DRAWING NOT FOR CONSTRUCTION ELECTRICAL SERVICES CHECKED KAO ECM REF 4029
MUST NOT BE RETAINED, COPIED OR USED WITHOUT ENGINEERING CONSULTING MANAGEMENT
THE WRITTEN AUTHORITY OF ECM GROUP PTY LTD. SINGLE LINE DIAGRAM 2/2 DRAWING No E301 REV P1

You might also like