Packaged Inverter PCTPMT2012
Packaged Inverter PCTPMT2012
PCTPMT2012
Pe r f e c t i n g t h e A i r
Warning • Ask a qualified installer or contractor to install this product. Do not try to install the product yourself. Improper
installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
• Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or contractor to install
those parts and accessories. Use of unauthorised parts and accessories or improper installation of parts and
accessories can result in water or refrigerant leakage, electrical shock, fire or explosion.
• Read the user's manual carefully before using this product. The user's manual provides important safety
instructions and warnings. Be sure to follow these instructions and warnings.
• About harmonics, since this product is equipped with an inverter, harmonics will be generated. If local laws require
the suppression of harmonics on the building, please take harmonic suppression measures on the electrical
Notice equipment side. Please contact your local sales company for details.
DIRECT AIR BLOW DUCT CONNECTION
If you have any enquiries, please contact your local importer, distributor and/or retailer.
FLOOR STANDING TYPE DUCT TYPE OUTDOOR UNIT
Specifications, designs and other content appearing in this brochure are current as of September 2020 but subject to change without notice.
©All rights reserved 09/20 AK COOLING ONLY 50Hz
PCTPMT2012aprv_01_02.pdf 1 10/23/2020 9:29:07 AM
Specifications Page 5
FVGR200PV1(4) FVGR250PV1(4)
DUCT CONNECTION
Specifications Page 5
OUTDOOR UNIT
RZUR200PY1(4) RZUR250PY1(4) RZUR400PY1(4) RZUR500PY1(4)
DUCT TYPE
Specifications Page 6
FDR200PY1(4) FDR250PY1(4) FDR400PY1(4) FDR500PY1(4)
OUTDOOR UNIT
RZUR200PY1(4) RZUR250PY1(4) RZUR400PY1(4) RZUR500PY1(4)
Extended operation range up to 49°C
DIRECT AIR BLOW DUCT CONNECTION
Direct air blow from indoor unit DUCT TYPE Cooling Outdoor temperature (°CDB)
with plenum 10 20 30 40 49°C
- Comfortable factory air conditioning using multiple indoor
Air blow via connected ducts
units installed in accordance with the space. - Comfortable air conditioning of the entire factory by
connecting a blow duct at the top of the indoor unit.
- Installation is next to walls, so units will not affect the
Note: Ducts to be procured locally.
factory layout even if the changes are made.
Note: When outdoor temperature falls below 10℃, the thermostat shuts OFF, the outdoor unit stops, and operation switches from cooling to fan operation.
1 2
PCTPMT2012aprv_03_04.pdf 1 10/23/2020 9:31:49 AM
3 4
PCTPMT2012aprv_05_06.pdf 1 10/23/2020 9:33:55 AM
Specifications
FLOOR STANDING TYPE DUCT TYPE
DIRECT AIR BLOW
Indoor unit FVGR200PV1(4) FVGR250PV1(4) Indoor unit FDR200PY1(4) FDR250PY1(4) FDR400PY1(4) FDR500PY1(4)
Model Name Model Name
Outdoor unit RZUR200PY1(4) RZUR250PY1(4) Outdoor unit RZUR200PY1(4) RZUR250PY1(4) RZUR400PY1(4) RZUR500PY1(4)
Btu/h 68,000 (74,000) 91,000 (96,000) Btu/h 68,000 (74,000) 91,000 (96,000) 136,000 (150,000) 171,000 (176,000)
Cooling capacity*1 (Max.) Cooling capacity*1 (Max.)
kW 20.0 (21.7) 26.7 (28.1) kW 20.0 (21.7) 26.7 (28.1) 40.0 (44.0) 50.0 (51.6)
Power consumption*1 kW 7.25 9.64 Power consumption*1 kW 8.06 10.39 17.86 26.74
Power supply 1 Phase, 220-240 V, 50 Hz Power supply 3 Phase, 380–415 V, 50 Hz
Colour lvory White Colour Galvanized Steel
m3/min 80 m3/min 78 166
Air flow rate (H) Air flow rate (H)
cfm 2,830 cfm 2,750 5,860
Motor output kW 0.245×2 External static pressure*3 Pa 98 147
Indoor unit Fan Indoor unit
Drive Direct Drive 3 Speed Motor output kW 1.5 3.7
Fan
Dimensions (H×W×D) mm 1,870×1,170×510 Drive Belt drive
Machine weight kg 149 Dimensions (H×W×D) mm 500×1,330×850 625×1,980×850
Sound level dB(A) 61 Machine weight kg 108 191
Drain mm PS 1B Internal thread Sound level dB(A) 53 60
Power supply 3 Phase, 380–415 V, 50 Hz Drain mm PS 3/4B Internal thread PS 1B Internal thread
Colour Ivory white Power supply 3 Phase, 380–415 V, 50 Hz
Type Hermetically sealed scroll type Colour Ivory white
Compressor
Motor output kW 3.4×1 4.5×1 Type Hermetically sealed scroll type
Compressor
Air flow rate (H) m3/min 178 Motor output kW 3.4×1 4.5×1 (3.5×1)+(3.5×1) (4.9×1)+(4.2×1)
Outdoor unit Dimensions (H×W×D) mm 1,657×930×765 Air flow rate (H) m3/min 178 257 297
Outdoor unit Dimensions (H×W×D)
Machine weight kg 175 185 mm 1,657×930×765 1,657×1,240×765
Sound level*2 dB(A) 56 57 Machine weight kg 175 185 260 291
Operation range °CDB 10 to 49 Sound level*2 dB(A) 56 57 60 65
Refrigerant charge kg 5.9 6.7 Operation range °CDB 10 to 49
Refrigerant Liquid mm Ø 9.5 (Brazing) Refrigerant charge kg 5.9 6.7 8.2 11.7
Piping Gas mm Ø 19.1 (Brazing) Ø 22.2 (Brazing) Refrigerant Liquid mm Ø 9.5(Brazing) Ø 12.7 (Brazing) Ø 15.9 (Brazing)
Max. piping length m 70 (equivalent length 90 m) Piping Gas mm Ø 19.1 (Brazing) Ø 22.2 (Brazing) Ø 28.6 (Brazing)
Max. level difference m 50 Max. piping length m 70 (equivalent length 90 m)
Max. level difference m 50
Note :
*1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m.
FLOOR STANDING TYPE *2. Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions and oil recovery mode.
When there is concern for noise the surrounding area such as residences, we recommend investigating the installation location and taking soundproofing measures.
DUCT CONNECTION *3. The value is the external static pressure with standard pulley.
Indoor unit FVPR250PY1(4) FVPR400PY1(4) FVPR500PY1(4)
Model Name
Outdoor unit RZUR250PY1(4) RZUR400PY1(4) RZUR500PY1(4)
Option
Btu/h 91,000 (96,000) 136,000 (150,000) 171,000 (176,000)
Cooling capacity*1 (Max.)
kW 26.7 (28.1) 40.0 (44.0) 50.0 (51.6)
Power consumption*1 kW 9.27 17.02 23.26
Power supply 3 Phase, 380–415 V, 50 Hz FLOOR STANDING TYPE
Colour lvory White
Direct Air Blow Duct Connection
m3/min 80 120 162 Option
Air flow rate (H) FVGR-PV1(4) FVPR250PY1(4) FVPR400PY1(4) FVPR500PY1(4)
cfm 2,830 4,240 5,720
Discharge grill plenum chamber (Including pulley and belt) — BPCV10P BPCV16P BPCV20P
External static pressure*3 Pa 147
Indoor unit Filter chamber for clean room — •
Motor output kW 1.5 2.2 3.7
Fan
Drive Belt Drive
Dimensions (H×W×D) mm 1,740×1,170×510 1,870×1,170×720 1,870×1,470×720
Machine weight kg 156 200 250 CONTROL SYSTEM
Sound level dB(A) 61 62 63 Option FVGR-PV1(4) FVPR-PY1(4) FDR-PY1(4)
Drain mm PS 1B Internal thread —
Simplified remote controller BRC2E61
Power supply 3 Phase, 380–415 V, 50 Hz —
Navigator remote controller BRC1E63
Colour Ivory white Wiring adaptor for electrical appendices (Group control adaptor) KRP4AA51 H
Type Hermetically sealed scroll type
Compressor Adaptor for wiring (operation status output) BRP11B61
Motor output kW 4.5×1 (3.5×1)+(3.5×1) (4.9×1)+(4.2×1) Remote sensor (for indoor temperture) BRCS01A-1
Air flow rate (H) m3/min 178 257 297 Mounting plate for adaptor PCB — BRP45A I
Outdoor unit Dimensions (H×W×D) mm 1,657×930×765 1,657×1,240×765
Note :
Machine weight kg 185 260 291 Mounting plate I is necessary for each adaptor marked H.
Sound level*2 dB(A) 57 60 65
Operation range °CDB 10 to 49
Refrigerant charge kg 6.7 8.2 11.7
Refrigerant Liquid mm Ø 9.5 (Brazing) Ø 12.7 (Brazing) Ø 15.9 (Brazing)
Piping Gas mm Ø 22.2 (Brazing) Ø 28.6 (Brazing)
Max. piping length m 70 (equivalent length 90 m)
Max. level difference m 50
Note :
*1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m.
*2. Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions and oil recovery mode.
When there is concern for noise the surrounding area such as residences, we recommend investigating the installation location and taking soundproofing measures.
*3. The value is the external static pressure with standard pulley.
5 6
PCTPMT2012aprv_07_08.pdf 1 10/23/2020 9:38:00 AM
FAN PERFORMANCE
FLOOR STANDING TYPE DUCT TYPE
DUCT CONNECTION
(standard ESP)
0 0 900
68 70 72 74 76 78 80 82 84 86 88 90 92 94 96
rpm
0 0 0 0
Air flow rate (m3/min) 102 106 110 114 118 120 122 126 130 134 140 144 70 72 74 76 78 80 82 84 86 88 90 92 94
4D064265 Air flow rate (m /min) 3 4D064275 Air flow rate (m3/min) A112-24
A106-24
4D064280
30
2B-132-28
External static pressure (Pa)
35 350
2B-180-25
00
2B-125-28
rp
250
m
25 200
20
15 150
2B-250-30
90
900
2B-180-25
0r
rpm
2B-180-28
pm
100
2B-115-28
10 10 100
2B-250-30
5 50 80 800 2B-170-28
rpm
0r
pm 5 50 2B-250-30
0
2B-160-28
0
138 142 146 150 154 158 162 166 170 174 178 182 186 190 194 198
2B-225-25
2B-125-28 Air flow rate (m3/min) 0 0
4D064276B 150 154 158 162 164 166 170 174 178 182 186 190 196 199
7 8
PCTPMT2012aprv_09_10.pdf 1 10/23/2020 9:39:59 AM
Wiring Diagrams
OUTDOOR UNIT
RZUR200PY1(4) RZUR250PY1(4)
3D128846B 3D128847B
9 10
PCTPMT2012aprv_11_12.pdf 1 10/23/2020 9:44:48 AM
RZUR400PY1(4) RZUR200PY1(4)
RZUR500PY1(4) RZUR250PY1(4)
3D130368
RZUR400PY1(4)
RZUR500PY1(4)
2D128848A 3D130373
11 12
PCTPMT2012aprv_13_14.pdf 1 10/23/2020 9:49:55 AM
FVGR200PV1(4) FVPR400PY1(4)
A
FVGR250PV1(4) FVPR500PY1(4) A B C D E F G H J K
B C D
1 Liquid pipe conn. ø 9.52 C1220T brazing FVPR400PY1(4) 1170 477 398 295 344 1187 1170 1144 205 o/ 12.7
2 Gas pipe conn.: FVPR500PY1(4) 1470 558 474 438 407 1487 1470 1444 237 o/ 15.9
ø 19.1 C1220T brazing for FVGR200PV1(4)
E
ø 22.2 C1220T brazing for FVGR250PV1(4) 1 Liquid pipe conn. ( K ) C1220T brazing
3 Upper drain outlet (PS 1B Internal thread) 2 Gas pipe conn. ø 28.6 C1220T brazing
4 Power supply & control wire intake 3 Upper drain outlet (PS 1B Internal thread)
5 Digital remote controller 4 Power supply & control wire intake
5 Digital remote controller
F
G
J
SDR3150202 H SDR3150205
SDR3150203 SDR3150206
DUCT CONNECTION
FVPR250PY1(4)
SDR3150204
13 14
PCTPMT2012aprv_15_16.pdf 1 10/23/2020 9:53:00 AM
FDR200PY1(4) RZUR200PY1(4)
FDR250PY1(4) RZUR250PY1(4)
3D129097 3D129057
FDR400PY1(4) RZUR400PY1(4)
FDR500PY1(4) RZUR500PY1(4)
3D129107 3D129058A
15 16
PCTPMT2012aprv_17_18.pdf 1 10/23/2020 9:56:06 AM
RZUR200PY1(4) / RZUR250PY1(4) / RZUR400PY1(4) / RZUR500PY1(4) (Please refer to engineering databook for other installation patterns.)
10 Front 10 10 Front 10
or more or more or more 20 or more 20 or more or more
500 or more 500 or more
100 or more
Pattern 2 Pattern 2
100 or more
FDR200PY1(4) FDR400PY1(4)
FDR250PY1(4) FDR500PY1(4) Pattern 3 Pattern 3 Wall height unrestricted
Wall height
300 or more unrestricted 300 or more
800 or more
476.5
Pattern 1
800 or more
300 or more 300 or more
800 or more
10 Front 10 10 Front 10
or more 20 or more or more or more 20 or more or more
Provide enough clearance between the unit and Provide enough clearance between the unit and 600 or more 500 or more Front
the surrounding walls to prevent contact. the surrounding walls to prevent contact.
Ceiling surface
Ceiling surface
10 10 300 or more
or more Front 20 or more or more
500 or more 10 10
or more 20 or more or more
720 or more
570 or
more
60 or more
Pattern 2
100 or more 100 or more
50 50
or more Front 100 or more or more
50 100 or more 50
500 or more or more 100 or more or more
Unit : mm
Notes:
1. Heights of walls in case of Patterns 1 and 2:
Front : 1500 mm
Suction side : 500 mm
Side : Height unrestricted.
h2
Installation space to be shown in this drawing is based on the cooling operation at 35 degrees outdoor air temperature.
When the design outdoor air temperature exceeds 35 degrees or the load exceeds maximum ability because of much generation load of heat
in all outdoor unit,take the suction side space more broadly than the space to be shown in this drawing.
1500 mm
Suction
2. If the above wall heights are exceeded then h2/2 and h1/2 should be added to the front and suction side service spaces respectively as shown
h1
Front
Side
in the figure on the right.
3. When installing the units most appropriate pattern should be selected from those shown above in order to obtain the best fit in the space
500 mm
available always bearing in mind the need to leave enough space for a person to pass between units and wall and for the air to circulate
freely.
If more units are to be installed than are catered for in the above patterns
your layout should take account of the possibility of short circuits.
17 4. The units should be installed to leave sufficient space at the front for the on site refrigerant piping work to be carried out comfortably. 18