Professional Documents
Culture Documents
در بخش آنالین میتوانید مواردی نظیر انتقال تنظیمات و. در دسترس هستند، تمامی اطالعات قابل ویرایش رله،در حالت آفالین
: به طور کلی موارد در دسترس در این دو حالت به شرح زیر است.خواندن الگها را انجام دهید
The following list provides an overview of the tasks you can deal with, among others, in the offline mode:
• Creating a topology as a single-line configuration
• Incorporating SIPROTEC 5 devices into the topology
• Configuring hardware of a SIPROTEC 5 device
• Defining the functional scope of a SIPROTEC 5 device
• Defining individual function settings
• Routing information
• Editing display pages
• Configuring function charts (CFC)
• Configuring the communication network and setting communication settings
• Displaying saved measured values and indications
• Displaying saved fault records and evaluating them with SIGRA
• Exporting and printing data
• Creating test sequences
The following list provides an overview of the tasks you can deal with, among others, in the online mode:
• Transmitting settings values from DIGSI 5 to the SIPROTEC 5 device
• Transmitting settings values from the SIPROTEC 5 device to DIGSI 5 and saving them in files
• Transmitting indications, measured values, and fault records from the SIPROTEC 5 device to DIGSI 5 and
saving them in files
• Setting limiting values
• Testing SIPROTEC 5 devices and functions
• Controlling equipment
• Initial startup or restart of the SIPROTEC 5 device
• Setting the date and time of the SIPROTEC 5 device
در صورتی که مقدار نامعتبری را، به عنوان مثال. انجام میشودConsistency Check به طور خودکار۵ در نرمافزار دیگزی
مواردی که میتوانند خطاهای مربوط به. هشداری با توضیح مربوطه در این خصوص مشاهده خواهید کرد،برای تنظیمات وارد کنید
: را ایجاد کنند به شرح زیر هستندConsistency
سیگنالها و المانهای گرافیکی استاتیک و داینامیک را نمایش، متن، میتوانند بسته به نوع رله۵ صفحه نمایش رلههای سیپروتک
.دهند
۱۰ این تعداد، یا نسخههای قبلی۹.۴ (در نسخه. صفحه نمایش متفاوت را در این بخش برای رله معرفی کند۳۰ کاربر میتواند تا
.)صفحه نمایش بود
Information درDisplay Page سیگنال باینری اینپوت جدیدی هم در بخش، همزمان با پیکربندی صفحهنمایش۹.۵ از نسخه
. استفاده میشودHMI از این سیگنال ورودی به منظور پیمایش در صفحه نمایش از طریق صفحهنمایش. ایجاد میشودRouting
با کشیدن و رها کردن. توالی آنها را روی صفحهنمایش مشخص میکند،توالی نام صفحهنمایشها در بخش نمایش درختی پروژه
.میتوانید اولویت نمایش صفحهها را تغییر دهید
این امکان وجود دارد تا صفحهنمایشها را به طور مستقیم از بخش Single-Line Configurationایجاد کنید .به این ترتیب
میتوانید برای هر Bayصفحه نمایش جدا ایجاد کنید یا از یک صفحه برای نمایش تمامی Bayها استفاده کنید .با کلیک روی المان
بعد از ایجاد یک خطا ،امکان آن وجود دارد تا رویدادها و مقادیر اندازهگیری به طور خودکار روی صفحهنمایش نشان داده شوند .این
المانها در بخش Fault-Displayپیکربندی میشوند.
در این بخش میتوانید ترتیب نمایش اطالعات را در هر سطر مشخص کنید.
در این بخش المانهای زیر قابل نمایش هستند:
:Pickup Indicationنام فانکشنی که در ابتدا پیکاپ کرده به نمایش درخواهد آمد .عالوه بر این اطالعاتی در خصوص -
فازها و جهت فانکشنی که پیکاپ کرده به نمایش درخواهد آمد.
:Pickup Timeمدت زمان پیکاپی که منجر به خطا شده به نمایش درخواهد آمد. -
: Operation Indicationنام فانکشنی که پس از پیکاپ منجر به خطا شده نمایش داده خواهد شد .عالوه بر ایان ممکن -
است اطالعاتی در خصوص فازها به نمایش درآید.
:Tripping Timeزمان عملکرد مربوط به خطا از ابتدای نقطه شروع خطا (شروع پیکاپ) به نمایش درخواهد آمد. -
:Fault Distanceدر این المان ،میزان فاصله از نقطه بروز خطا به نمایش درخواهد آمد. -
درنظر داشته باشید که میتوانید مشخص کنید ک ه این مقادیر برای هر بار پیکاپ به نمایش درآید یا تنها برای مواردی که در آن
پیکاپ به تریپ منجر میشود نمایش داده شود .این تنظیم در بخش Device Settingانجام میشود.
Information Routing
تخصیص اطالعات و سیگنالها به منبع ( ،)Sourceیا مقصد ( )Destinationدر این بخش انجام میشود .در صورتی که اطالعاتی
را به سورس تخصیص دهید به معنی آن است که رویدادی باعث تریگر کردن این اطالعات خواهد شد .در صورتی که اطالعاتی را
به مقصد اختصاص دهید به معنای آن است که اطالعاتی انتقال یافته یا باعث ایجاد بازخورد خواهد شد.
به عنوان نمونه میتوانید گزینه ) H (Active with voltageیا ) L (Active without voltageرا برای باینری اینپوت انتخاب کنید.
درنظر داشته باشید که مدیریت سیگنالهای انتقالی از طریق DNP3, IEC 60870-5-103- IEC 60870-5-104, Modbus TCP,
Modbus RTU, PROFINET IOو اینترفیسهای حفاظتی از طریق ماتریکس Communication Mappingانجام میشود.
امکان ویرایس لیبلهای ترمینالها LED ،ها و فانکشن کیها در بخش Propertiesدر Information Routingنیست و -
این عمل را میتوانید در بخش ویرایشگر Hardware and Protocolsانجام دهید.
درنظر داشته باشید که در دیگزی ۵به منظور استفاده از یک سیگنال در CFCنیازی به تیک زدن المان مربوط به آن در بخش
Information Routingنخواهید داشت .از همین رو ،المانهایی که مشاهده میکنید در بخش CFCدر Information Routing
تیک خوردهاند تنها برای نمایش استفاده میشوند .همین امر در خصوص ستون Displayنیز صادق است.
در صورتی که سلول انتخابی به رنگ خاکستری است به معنای این است که امکان تخصیص اطالعات به آن وجود دارد .در
صورتی که سلول انتخابی به رنگ خاکستری تیره باشد به معنای عدم امکان تخصیص سیگنال است.
با استفاده از دو المان در باالی صفحه Information Routingامکان فیلتر کردن سیگنالها وجود دارد .در بخش اول ،نمایش به
صورت:
:All Entriesبرای نمایش تمامی موارد ،بدون محدودیت -
:Tripsبرای نمایش سیگنالهایی که به تریپ اختصاص داده شدهاند. -
:Measured and Metered Valuesبرای نمایش مقادیر اندازهگیری (در بخش سورس GOOSE ،و ،CFCهمچنین در -
بخش دستینیشن CFC ،Menus in the Device Display ،Event Log Buffer ،Fault Records ،و )Displayنمایش
داده خواهد شد.
Device I/Oسیگنالهای ورودی و خروجی -
:Configuration of the Menu Levelsبرای نمایش المانها در سطح منوهای رله. -
خواهد بود.
در دسته بندی بعدی ،المانها بر این اساس دستهبندی و فیلتر خواهند شد:
)*( • Routed
)( • Not routed
)*( • Binary I/O routed
)( • Binary I/O not routed
)*( • F-keys routed
)( • F-keys not routed
)*( • LEDs routed
)( • LEDs not routed
از این سیگنال منحصرا برای نمایش موقعیت تپ چنجر در فانکشن Tap Changerاستفاده میشود .این سیگنال میتواند اطالعات
مربوطه را از طریق CFCیا ورودیهای باینری دریافت کند .بسته به تعداد تپهای ترانسفورمر ،سیگنال موقعیت باید به چندین
باینری اختصاص یابد.
. استفاده کنیدNot Routed وX (Routed) برای تخصیص میتوانید از گزینههای
SPS -
. وجود داردSPC در صورتی که سیگنالی توسط کاربر ایجاد شده باشد شرایطی مشابه با
DPC -
در این بخش گزینههای. برای المانهای با بازخورد دو وضعیتی استفاده میشودClose وOpen های دو وضعیتیIndication از
:زیر موجود است
• T (toggle)
When the function key is pressed, the routed single-point indication is generated and stays. When the function key is
pressed once more, the routed single-point indication is canceled.
• P (trigger pulse)
When the function key is pressed, the routed single-point indication is generated and stays. A renewed pressing of the
function key has no effect.
• Not routed
The single-point indication is not routed to the function key.
• T (toggle)
When the function key is pressed, the routed controllable single-point indication is set to On. When the function key is
pressed once more, the routed controllable single-point indication is set to Off.
• On (on)
When the function key is pressed, the routed controllable single-point indication is set to On.
• Off (off)
When the function key is pressed once more, the routed controllable single-point indication is set to Off.
• Not routed
The controllable single-point indication is not routed to the function key
You can route a command with double-point feedback to several function keys. For this, select one of the following
options:
• T (toggle)
When the function key is pressed, the command is sent as an On command. When the function key is pressed once more,
the command is sent as a trip command.
• On (on)
When the function key is pressed, the command is sent as an On command.
• Off (off)
When the function key is pressed once more, the command is sent as a trip command.
Routing a Single-Point Indication (SPS) or a User-defined Marker Command (SPC) to a Binary Output
You can route a single-point indication or a user-defined marker command to several binary outputs. For this, select one
of the following options:
• L (latched)
The single-point indication or the user-defined marker command is stored and routed to the binary output. The relay of
the binary output latches as soon as the single-point indication or the user-defined marker command is pending. Even if
the respective signal is no longer pending, the relay remains latched. You must manually reset the relay on the SIPROTEC
5 device. You find more information about this in the respective device manual.
• U (unlatched)
The single-point indication or the user-defined marker command is not stored and routed to the binary output. The relay
of the binary output latches as soon as the respective signal is pending. As soon as the single-point indication or the user-
defined marker command is no longer pending, the relay also unlatches.
• Not routed
The single-point indication or the user-defined marker command is not routed to the binary output.
Routing a Command with Double-Point Feedback (DPC) or a User-defined Controllable Single-Point Indication
(SPC) to a Binary Output
You can route a command with double-point feedback or a user-defined controllable single-point indication (SPC) to
several binary outputs. For this, select one of the following options:
• On (on)
The command or the controllable single-point indication is routed as an On command to this binary output.
• Off (off)
The command or the controllable single-point indication is routed as a trip command to this binary output.
• BF (command busy flag)
This binary output is specified as a signal relay. The signal relay is controlled as long as the command or the controllable
single-point indication is output. You can route several commands or controllable single-point indications to the same
signal relay and connect this relay, for example, to a control setup.
• CC (common contact)
This binary output is specified as a common contact. You can assign several commands or controllable single-point
indications to a common binary output as a common contact and save binary outputs. Prerequisite is that the signals at
the common contact have the same potential. An application example is a common ground potential.
• Not routed
The command or the controllable single-point indication is not routed to the binary output
هاLED پیکربندی
: های رله میتوانید از سیگنالهای زیر استفاده کنیدLED به منظور پیکربندی
Fault records serve as the destination for a routed signal. The 25.3.2 Information Routing matrix contains the following 2
columns for fault records:
• Signals
Signals routed to this column are recorded in a fault record.
• Trigger
• Signals routed to this column serve as triggers for fault recording. This column is shown, if you have
selected the setting User-defined for the Fault recording parameter. You find this parameter in the fault
recorder settings
• Not routed
The signal is not routed to fault records.
هاLog پیکربندی
را در اینUser log 1, 2 وOperational log, Fault log, Ground Fault log این امکان وجود دارد تا الگهای مختلف شامل
.بخش پیکربندی کنید
:این امکان وجود دارد تا سیگنالهایی به شرح زیر را به الگها اختصاص دهید
. میتوانید آستانه عملکرد هر باینری اینپوت را به طور مجزا تنظیم کنیدProperties در بخش:نکته
CFC (Continuous Function Chart) پیکربندی
. به این منظور انواع مختلف از بلوکها وجود دارند. از بلوکهای فانکشنی پیشفرض استفاده میکنید،CFC به منظور پیکربندی
Each block type has a type definition, which contains the following:
• Type name
The type name describes the function of the block. For example, ADD_R is used for adding values.
• Algorithm
The algorithm is a sequence of instructions for processing a task, for example, adding multiple values.
• Inputs and outputs
Input and output values of the block
Block Instance
A block instance is the use of a block type in the Continuous Function Chart. You can create multiple blocks from a single
block type in consideration of the resource consumption. Each block instance receives a unique name within a CFC. The
block instance inherits the default settings of the block type as a standard, for example, the initial values of the inputs.
During configuration, you have the following possibilities:
• Enter individual initial values
• Change the name of the block instance
• Interconnect the block instances
Flow Model
The execution model describes when and in which order the configured blocks in the Continuous Function Charts are
executed.
2 factors characterize the execution model:
• The task level of the CFC function
• The task sequence of the block within a function
Task Level of the CFC Function
A CFC and its configured CFC functions run on the SIPROTEC 5 device on one of the 4 task levels. Depending on the
selected task level, a CFC is processed event-triggered or cyclically.
You can select between the following task levels:
• High priority Event-triggered
Use this task level for time-critical tasks, for example, if a signal should block a protection function within 2 ms to 3 ms.
Functions on this task level are processed in an event-triggered way with the highest priority. Each change to a logic input
signal is immediately processed. Processing can disrupt the execution of the protection functions and functions on the
Event-triggered task level.
• Event-triggered
Use this task level preferably for logic functions that do not need to be executed with the highest priority. Functions on
the Event-triggered task level are typically processed within a maximum of 5 ms in all devices. For Busbar protection or
Line protection, the functions on the Event-triggered task level are processed within a maximum of 10 ms. But the
protection functions or functions on the High priority Event-triggered task level can disrupt processing.
• Low priority Cyclic-triggered
Use this task level for the processing of measured values. Functions on this task level are processed with low priority
cyclically every 500 ms. This process can be disrupted by protection functions or CFC functions with higher priority.
• Low priority Event-triggered
Use this task level preferably for logic functions that must be executed with lower priority than functions in the Event-
triggered task level. If the available TICKS of the Event-triggered task level are sufficient for the required CFC
functionality, you do not need to use the Low priority Event-triggered task level.
In the Low priority Cyclic-triggered task level, no event-based triggering of the plan execution is done. Siemens does not
recommend using the Low priority Cyclic-triggered task level for the event-based blocks (for example, control blocks)
as the behavior of the blocks may differ in comparison to the other task levels.
All function blocks can be assigned to all task levels. CFC function blocks are always available for all the devices. If enough
TICKS are available, you can create all function plans in the same task level. A TICK is a measure for the performance
requirement of the CFC blocks.
The number of available TICKS per task level is calculated depending on the created device configuration. This calculation
is based on the load model and is described in the Device Manual (chapter Resource-Consumption Supervision).
Siemens recommends creating all selected functions and user-defined signals first and starting the configuration of the
function charts afterwards. Thus, it is possible to calculate a realistic value for the remaining system capacity for function
charts.
With the load model, exceeding the typical response time is avoided by limiting the number of CFC function blocks in the
corresponding task level via the available number of TICKS.
OTE High priority Event-triggered function charts are executed with a higher priority than the other task levels. A
considerably lower number of TICKS is available for this task level than for the other task levels. Siemens recommends
configuring only high-priority logics in this task level and configuring everything else in one of the other task levels
Empty function charts and unused subcharts consume resources and they also contribute to the system resource
consumption. Siemens recommends deleting empty function charts and unused subcharts.
Changing Sequence
Changing the Task Level
If you add a new Continuous Function Chart, also determine a task level for the CFC.
You can change the task level in the properties of the CFC. The CFC can still be visible in the working area. However, the
CFC must not be opened. In this case, use the project tree in order to display the properties.
i NOTE Nested function charts get the same task level as the CFC they are used in. You cannot set the task level of
nested function charts in the Properties tab.
Displaying Properties If the CFC Is Opened
Click in an open area in the CFC.
Open the Inspector window.
Select the Properties tab.
Select the Sequence group
رله شما موجود هستند را مشاهدهCFC میتوانید لیست کاملی از سیگنالها و تنظیماتی که درCross-Reference List در بخش
.کنید
i NOTE The task level for subcharts will be set automatically to the parent chart task level to which it is copied. If for
example, a subchart with the task level Event -triggered is copied to a parent chart with the task level Low priority
Event-triggered, the task level of the subchart is set to Low priority Event-triggered, too.
این امکان وجود دارد تا CFCهای موجود در رله سیپروتک ۴را با استفاده از دیگزی ۴اکسپورت گرفته و وارد نرمافزار دیگزی ۵
کنید.
بنا بر دالیل فنی این امکان وجود دارد که برخی گیتهای منطقی نظیر ANDو ORتعداد ورودی بیشتر از آنچه نیاز است داشته
باشند .این امر ،در عمل تاثیری در اجرای CFCها نخواهد داشت.
از آنجایی که ممکن است رلههای سیپروتک ۵سیگنالهایی متفاوت از رلههای سیپروتک ۴داشته باشند ،کانکشنهایی که به
سیگنالهای بیرون از CFCچارتها وابسته است ممکن است نیاز به ثبت مجدد داشته باشند .به این منظور کافی است کاتالوگ
سیگنالها را از سمت راست بازکرده و المانهای الزم را تنظیم کنید.
برخی از المانهای منطقی نیز در دیگزی ۴و دیگزی ۵متفاوت هستند .در این موارد ،بلوکهای منطقی به صورت باکسهای
خاکستری خواهند بود .با جایگزینی این بلوکهای منطقی با نمونههای صحیح از کتابخانه دیگزی ،۵موارد را مرتفع کنید.
در این مثال خاص ،چارت با عنوان 10s after startدارای بلوکی به عنوان TIMERاست که در دیگزی ۵پشتیبانی نمیشود .از
همین رو باید بلوک یادشده را با بلوکی مشابه از کتابخانه CFCدر دیگزی ۵جایگزین کنید.
معرفی بخش Test Sequence
در این بخش شما میتوانید فانکشنهای حفاظتی را بدون نیاز به دستگاه تستر ،تست کنید .درنظر داشته باشید که تست سکوئنسها
همواره به رله آفالین شما اختصاص داده میشوند.
در بخش Test Sequenceامکان ایجاد موارد زیر را خواهید داشت:
• Set parameters for analog test signals for the phases of each measuring point
• Set values of binary input signals
• Set values for function charts (CFC) input signals
هر تست سکوئنس میتواند تا حداکثر ۲۰استیت را در خود جا دهد .برای هر استیت میتوانید مقادیر مختلفی را تعریف کرده و مدت
زمان خاصی را مشخص کنید .تمامی استیتها در یک فایل با فرمت CSVذخیره میشوند .امکان استفاده از قابلی افزایشی (رمپ) هم
در این بخش وجود دارد.
این امکان وجود دارد تا ۳هارمونیگ را برای هر سیگنال آنالوگ تست ،مشخص کنید .همچنین میتوانید مشخص کنید تا وضعیت
هر باینری اینپوت در هر استیت به چه شکلی باشد .در ادامه میتوانید تنظیمات مربوط به تمامی استیتها را ذخیره کنید.
نرم افزار Siprotec Toolsابزاری بدون نیاز به نصب است تا بتوانید موارد مربوط به رله را بدون نیاز به نرم افزار دیگزی ۵
مدیریت کنید .این نرمافزار از قابلیتهای زیر پشتیبانی میکند:
بارگذاری فایل DAFروی رله به منظور افزایش میزان امتیاز رله -
(برای رلههای بدون پیکربندی که تازه از کارخانه آمدهاند۵ پشتیبانی از تست سختافزاری و وایرینگ رلههای سیپروتک -
برای رلههای با پیکربندی امکان تست باینری. ها وجود داردLED آنالوگها و،امکان تست باینری اینپوتها و اوتپوتها
)اینپوت و اوتپوتها
روی چند رله۵ امکان بارگذاری فایل پیکربندی دیگزی -
الگها و رکوردهای رله،دانلود پیکربندی -
آپلود فیرمویر رله -
دریافت نوتیفیکیشن در خصوص در دسترس بودن نسخههای جدید نرمافزار سیپروتک تولز -
با استفاده از این. امکان دسترسی به مرورگر را دارند۵ درنظر داشته باشید که تمامی اینترفیسهای اترنت در رلههای سیپروتک
: کروم و فایرفاکس میتوانید به المانهای زیر دسترسی داشته باشید، اج، با دسترسی به مرورگرهایی نظیر اکسپلورر،قابلیت
شما را از بارگذاری کامل فایل ستینگ و، المانی کاربردی در زمان تست است زیرا با تغییر ستینگ مورد نظر،قابلیت دوم
. بینیاز میکند،راهاندازی مجدد رله
s.
• Function modes: at one glance it is presented if a function or stage is active or inactive because it is
e.g., switched off, blocked or in test mode. This helps not to forget to activate all relevant functions
and stages.
• Support: creates a device specific log file for analysis by our customer support e.g., in case of
technical problems. With one click you collect all relevant information in only one file. This feature
facilitates and accelerates the communication with our customer support. The file contains internally
logged data but no configuration data.
به منظور فعالسازی قابلیت استفاده از مرورگر ،کافی است روند زیر را طی کنید:
برای هر خطا ،یک فایل با پسوند .inf, .datو .cfgدانلود خواهد شد.
Confirmation IDs
A confirmation ID consists of 6 digits, which you can freely select. For the following areas, you can assign different
confirmation IDs:
• Settings
This confirmation ID allows changing the settings and device mode, loading firmware, setting counter, and deleting logs.
The confirmation ID for this area has the default value 222222.
• Fct.Key/PB operation
This confirmation ID allows operating via function keys and push-buttons only with the confirmation ID of Settings. By
default, the option Fct.Key/PB operation is unchecked. You can activate or deactivate the option only when the option
Settings is enabled. If you change the confirmation ID for the Settings area, then the new confirmation ID is automatically
applicable for the Fct.Key/PB operation area.
• Switching
This confirmation ID allows switching operations. The confirmation ID for this area has the default value 333333.
• Switching/change of interlocking check
This confirmation ID allows switching operations and allows to set the interlocking check on/off for the local switching
operations. The confirmation ID is only visible if a hardware without key switches is used. Switching without interlocking
can be a safety risk and requires precise knowledge of conditions in the substation.
The confirmation ID for this area has the default value 444444.
• Switching/change of switching authority
This confirmation ID allows switching operations and changing the switching authority. The confirmation ID is only
visible if a hardware without key switches is used.
The confirmation ID for this area has the default value 666666.
Connection Password
A connection password ensures authenticated remote access to a SIPROTEC 5 device. The password must meet certain
requirements, including those of the NERC CIP standards. A password must therefore be at least 8 characters long. It must
include at least 1 upper-case letter, 1 lower-case letter, 1 digit, and 1 special character. No connection password is
configured in a SIPROTEC 5 device when it is delivered.
If a password is activated, it must be entered correctly before DIGSI 5 can access the SIPROTEC 5 device. An activated
connection password applies to all interfaces of the SIPROTEC 5 device. Access by plug & play is also protected with the
password. For more information, refer to the chapter Access Control in SIPROTEC 5 in the SIPROTEC 5 Security manual.
Incorrect password entry is logged in the SIPROTEC 5 device. After 3 incorrect password entries, an alarm can be output
via a binary output. The accessing DIGSI 5 is also blocked for further accesses for a few minutes.
در این بخش ،به بررسی روندی خواهیم پرداخت که در قالب آن فایل پروژه به همراه فایل SCDدر اختیار کاربر قرار گرفته و
کاربر باید با اعمال تغییرات مختلف روی رله ،فایل IEC 61850را نیز آپدیت کند.
درنظر داشته باشید به منظور لود کردن تنظیمات روی رله سیپروتک ۵که قرار است از استانداردها و قابلیتهایی نظیر IEC
61850 GOOSEیا MMSاستفاده کند باید فایل لینک شده SCDرا در اختیار داشته باشید .این لینک شدن باید هر زمانی که یک
پروژه برای اولین بار روی کامپیوتر باز میشود یا زمانی که فایل SCDموجود جابهجا شده یا تغییر نام میدهد بررسی شود.
در زمان نصب دیگزی ،۵نرمافزار IEC 61850 System Configuratorهم به طور نرمال نصب خواهد شد.
در زمان ایجاد تغییرات در فایل یا جابهجایی فایل مورد نظر ،آیکونی به شکل زیر به نمایش درآمده و توضیحات مربوط به آن ارائه
خواهد شد:
در این مورد ،همگام سازی اطالعات انجام نشده است .به این منظور باید روند زیر را طی کنید .درنظر داشته باشید که در برخی
موارد ممکن است تغییراتی اعمال نشود اما همچنان روند زیر نیاز است تا اطمینان حاصل شود فایل SCDبه درستی لینک شده است:
در این مرحله IEC61850 System Configurator ،به طور خودکار باز شده و پنجره وضعیت در مقابل شما قرار میگیرد.
اطمینان حاصل کنید که ایمپورت با موفقیت انجام شده و خطایی وجود ندارد.
. را برپایه سرویسهای ابری فراهم کرده استDigital Twin امکان استفاده از ابزاری با عنوان۵ سیپروتک
System requirements
The following hardware and software components are necessary:
• PC/Notebook or Tablet with actual browser (Microsoft Edge, Google Chrome, or Mozilla Firefox)
• Internet connection
• Login SIPROTEC Digital Twin (https://www.siprotec-digitaltwin.siemens.com)
o Siemens ID Registration (for external users)
o An ordered and active license (7XS70*)
Note: The configuration and any necessary changes are made exclusively in the engineering tool DIGSI 5
The following tests are possible:
1. Communication with real, e.g., SIPROTEC 3/4/5/Compact or also third-party devices and virtual devices
2. Ethernet-based communication to control technology (SICAM A8000, PAS, SCC or third-party systems)
3. PQ/PMU functionality with PQ applications SICAM PQS, PQ Analyzer, SIGUARD PDP
4. Connection to the IoT applications SICAM GridEdge and SICAM Dashboard
5. IEC 61850 GOOSE Communication
6. DIGSI 5 Test suite and CFC Online debugging
7. SIPROTEC 5 WebUI (Default https https://172.16.60.60:4443)
8. Cyber Security functionality, e.g., with Radius Server
•…