SF Guard 12V - 7Ah | VRLA Battery

Applications Specifications
Nominal Voltage 12 V
Number of cells 6
• Uninterruptible Power Supplies (UPS) Design Life 5 years
Length 151.0 mm
• Electric Power Systems (EPS) Width 65.0 mm
Dimensions
Height 93.5 mm
Total Height 101.0 mm
• Emergency backup power supplies Approx. Weight 1.95 kg
20 hours rate (0.35 A, 10.5 V) 7.00 Ah
• Electronic apparatus and equipment Nominal Capacity (25ºC) 10 hours rate (0.65 A, 10.5 V) 6.50 Ah
5 hours rate (1.06 A, 10.5 V) 5.30 Ah
• Communication power supplies 1 hour rate (4.15 A, 9.6 V) 4.15 Ah
Max. Discharge Current (25ºC) 105 A (5s)
Internal Resistance
• DC power supplies 18 mOhms
Fully Charged battery (25ºC)
Self-Discharge 3% of capacity declined per month at 20ºC (average)
• Auto control system Discharge : -20~60ºC
Operating Temperature Range Charge : -10~60ºC
Storage : -20~60ºC
Short Circuit Current 380 A
Cycle use 2.30-2.35 Vpc
MH18852 Maximum charging current 1.8 A
Charge Methods: Temperature compensation -30 mV/ºC
Constant Voltage Charge (25ºC) Standby use 2.23-2.27 Vpc
Temperature compensation -20 mV/ºC

Battery Construction
Component Positive Plate Negative Plate Container Cover Safety Valve Terminal Separator Electrolyte
Raw material Lead dioxide Lead ABS ABS Rubber Copper Fiberglass Sulfuric acid

Dimensions

Temperature Effects on Float Life Self Discharge Characteristics


10 110

100

90
Life (years)

Capacity (%)

2.30V/Cell 80
1
70

60 o
C o
C o
C
50

0.1 10 20 30 40 50 60 40
0 2 4 6 8 10 12 14 16 18 20
Temperature (ºC) Storage Time (Months)

www.systems-sunlight.com
SF Guard 12V - 7Ah | VRLA Battery
Discharge Characteristics (25ºC) Constant Voltage Charging Characteristic (0.25 CA, 25ºC)
Charged
Volume Current Voltage
13.0 (%) (XCA) (V)
140
12.0
120 0.25
Battery Voltage (V)

15.0 Charged Volume


11.0
100 0.20
1.06 A 0.65 A 0.35 A 14.0 Charge Voltage
10.0 1.69 A 80
0.15
21 A 14 A 7 A 4.15 A 13.0
9.0 60
0.10
8.0 40 12.0

20 0.05
0 11.0 Charging Current
0 1 2 3 5 10 20 30 60 2 3 5 10 20 30 0 0
Min H
0 2 4 6 8 10 12 14 16 18 20
Discharge Time Charging Time (hours)

Relationship Between Charging Voltage and Temperature Life Characteristics of Standby Use
120
(V/12V)

(V/CELL)
(V/6V)
(V/8V)

(V/4V)

100
15.6 10.4 7.8 5.2 2.6
Capacity (%) 80
15.0 10.0 7.5 Cyc
5.0 2.5 le U
se
60
14.4 9.6 7.2 4.8 2.4 Testing conditions: floating voltage: 2.27 to 2.30 V/Cell
ambient temperature: 25ºC
Stand 40
13.8 9.2 6.9 4.6 2.3 by Us
e
13.2 8.8 6.6 4.4 2.2 20

0
-10 0 10 20 30 40 50 60 1 2 3
Ambient Temperature (ºC) Life (years)

Cycle Service Life in Relation to Depth of Discharge Temperature Effects on Capacity


120 120

100 100
C
0 .0 5
80 80 0 .1 C
Capacity (%)
Capacity (%)

0.2 C
60 60
100% D.O.D. 50% D.O.D. 30% Depth of discharge
1 .0 C
40 40 2 .0 C
3 .0 C
20 20

0 0
200 400 600 800 1000 1200 1400 -20 -10 0 10 20 30 40 50
Number of Cycles (Cycles) Temperature (ºC)

Constant Current Discharge (Amperes) at 25ºC


End Voltage (Volts/Cell) 5 min 10 min 15 min 30 min 1h 3h 5h 10 h 20 h
1.60 V 28.3 18.1 13.9 8.18 4.15 1.80 1.12 0.68 0.36
1.65 V 26.8 17.3 13.4 7.86 4.05 1.75 1.10 0.67 0.36
1.70 V 25.3 16.4 12.9 7.51 3.93 1.69 1.08 0.66 0.35
1.75 V 23.8 15.5 12.3 7.15 3.79 1.63 1.06 0.65 0.35
1.80 V 22.2 14.6 11.7 6.75 3.64 1.56 1.04 0.64 0.34

Constant Power Discharge (Watts/Cell) at 25ºC


End Voltage (Volts/Cell) 5 min 10 min 15 min 30 min 45 min 1h 2h 3h 5h
1.60 V 51.0 34.5 25.8 14.9 11.20 8.70 4.98 3.50 2.26
1.65 V 48.6 32.8 25.0 14.4 10.80 8.37 4.87 3.41 2.23
1.70 V 46.1 31.1 24.1 13.8 10.40 8.03 4.74 3.32 2.19
1.75 V 43.5 29.4 23.1 13.2 9.98 7.78 4.59 3.22 2.14
1.80 V 40.8 27.6 22.0 12.6 9.55 7.43 4.44 3.11 2.08
(Note) The above characteristics data are average values obtained within three charge/discharge cycles not the mimimum values.