Applications
Stranded 1350 aluminum conductors shown in this section of data are classified as follows:
Class A For conductors to be covered with weather-resistant materials and for bare
conductors where greater flexibility is required.
Compact strand conductor for use in bare overhead applications or for use with weather-
resistant coverings or insulations is also available.
Classes refer to stranding and are an indication of relative conductor flexibility, AA being the
least flexible, C the most flexible.
Construction
Aluminum alloy 1350-H19 wires, concentrically stranded.
Specifications
AAC bare conductors meet or exceed the following ASTM specifications :
Notes
Resistance is calculated using ASTM standard increments of stranding and metal
conductivity of 52.5% IACS, AC resistance at 60Hz
Current ratings are based on 75 ºC conductor temperature, 25 ºC ambient, 2ft/s wind,
96/watts/sq.ft sun, .05 coefficients of emissivity and absorption.
4/4/2024 | Page 2 of 2
Specifications
Code Name Cowslip
Size
2000
(AWG or kcmil)
No. of Wires 91
CLASS A
Diameter
Individual 0.1482 Inches
Wire
Diameter
Complete
1.630 Inches
Cable
(O.D.)
Cross
Sectional 1.571 sq.inches
Area
Weight
1877 Lbs
(lb/1000 ft)
Rated
Breaking 32200 Lbs
Strength
Resistance
DC
20 ºC 0.00864 Ω
Per MFT
(ohm)
Resistance
AC
75 ºC 0.0115 Ω
per MFT
(ohm)
Rating 1518 Amps
Standard Package Length (Feet) 4850 ft.
Standard Package Weight (Lbs.) 9100 Lbs
Reel Size RMT 90.45