의 신뢰도 향상방안
산업안전보건연구원
안전연구실장/PhD
권혁면
hmkwon@kosha.net
목 차
5. 적용 사례
6. 결론
1
1. Risk Management
1. Risk Management
2
2. What is SIL?
안전시스템 정의
3
SIS 구조의 예
2. What is SIL?
Safety Instrumented System(SIS) 구조
(제어안전시스템)
4
2. What is SIL?
SIL 적용 전
2. What is SIL?
SIL 적용 후
5
2. What is SIL?
SIS 구성부품
Yokogawa / Emerson
ProSafe-RS Process
Management /
DeltaV SLS-1508
Invensys
Triconex /
Tricon
2. What is SIL?
0 No safety requirements
6
3. SIL Procedure
Result SIL
3. SIL Procedure
SIS의 적용 – 신뢰도평가
procedure
Start
대상공정/설비 평가결과
선정 비교/검토
SRS (Safety
공정 Hazard 점검주기/ 설비개선
Requirement 방법개선
분석 및 평가 (필요시)
Spec.)
사고 사고 결과검토 및 비교
발생빈도 평가 파급영향 평가 종합대책 수립
Target SIL 설정 반영
(Safety Integrity Level) CMMS
현재 SIL 평가 END
(Software 사용)
CMMS (Computerized Maintenance Management System)
7
4. SIL Classification
1
2
3
4
4. SIL Classification
Target(Required) SIL 결정
Risk Graph
Risk Matrix
8
4. SIL Classification
4. SIL Classification
양파..방호계층-Onion...Protection Layers
(IEC61511-3 Annex C)
플랜트비상대응 / 주민비상대응
물리적 보호 (Bund wall)
외부 경감 (Relief Valve, Rupture Disk)
자동 제어안전기능 (ESD&FGS)
중요 알람과 수동개입
기본 제어 (DCS)
공정 설계
TT
9
4. SIL Classification
4. SIL Classification
LOPA Procedure
Select SIF
- Establish Design Intent
P&ID, C&E Matrix, HAZOP
List IPL
- Assess IPL Type and IPL Integrity
10
4. SIL Classification
4. SIL Classification
11
4. SIL Classification
Result SIL 결정
4. SIL Classification
SIF : Safety Instrumented Function
(제어안전기능)
Pipe to pipe
Process pipe Process pipe
Logic solver
Vent.
Input Output Air
A
D Protection logic O
Safety
valve
Transmitter
12
4. SIL Classification
Hardware fault tolerance(설비고장허용치)
--- Tables in IEC61508
Table 2 — Hardware safety integrity: Table 3 — Hardware safety integrity:
architectural constraints on type A architectural constraints on type B IEC 61508
safety-related subsystems safety-related subsystems
Safe failure Hardware fault tolerance Safe failure Hardware fault tolerance
fraction fraction
0 1 2 0 1 2
< 60 % SIL1 SIL2 SIL3 < 60 % not allowed SIL1 SIL2
60 % - < 90 % SIL2 SIL3 SIL4 60 % - < 90 % SIL1 SIL2 SIL3
90 % - < 99 % SIL3 SIL4 SIL4 90 % - < 99 % SIL2 SIL3 SIL4
> 99 % SIL3 SIL4 SIL4 > 99 % SIL3 SIL4 SIL4
PC : Proof Test
Coverage
13
4. Functional Safety Management
Override(bypass)
Start-up override(logic solver)
: 제한된 시간 동안만 동작시킬 것 !
Enable Key-switch를 그룹별로 둘 것.
Override On 표시를 그룹별로 둘 것.
다수의 Override를 Reset시킬 General key-
switch를 둘 것.
SIL 결정 예: 누출 허용 위험 발생 확률 : 10-4/year
14
현재의 위험발생확률
15
대안2 (SIL 2의 SIS 추가)
결론