OCCUPANTS 200
female 1-every 8
= 20,000.00
Using formula
3
V= 15001.13 gallons (1 𝑚 /264 gallons)
3
V= 56.82𝑚
SOIL PIPES
In reference to Max Fajardo Table 5-2 Horizontal Fixture Branch and Stack Pipe, a 150 mm
In reference to table 7-1 Sizes of Sanitary Drain, Under 2% slope, a 100 mm (4” ∅) pipe could
STORM DRAIN
In reference to table 9-2 Sizes of Storm Drain, Under 3% slope, a 510 square mete of roof area
MAIN VENTS
In reference to table 11-1 maximum length permissible length of Vents for soil and waste stacks
in motors, under diameter of vent, 1 100mm (4” ∅) pipe could ventilate 355 fixture units as a
high as 13 meters
BRANCH AND RELIEF VENTS
Based on National Plumbing code of the Philippines, Branch vents shall be the same diameter siz
as the waste pipe and relief cents a circuit vented branch should at least one half diameter of the
soil pipe. Branch vents have 100mm (4” ∅) pipe while relief vents have 100mm (4” ∅) pipe
In reference to Max Fajardo Table 5-2 Horizontal Fixture Branch and stack Pipe, a 50mm (2” ∅)
Pumps
20 mm∅ Tee
20 mm∅ Reducer
IS code, 135 Liters is needed for daily use per person per day.
3 3
Water Formula: 1𝑚 = 1000 L 1 L = 0.001 𝑚
3
Therefore 27000.00 L = 27.00𝑚
3
0.057𝑚 /person 1.2m width/100 persons
3
1.) V=200 persons x 0.057 𝑚 /person
3
V=11.4𝑚
3
2.) W= 200 persons x 0.057𝑚 /person
W= 2.4meters width
3
𝑉 11.4𝑚
L= 𝑊𝐻
= 2.4𝑚 𝑥 1.5𝑚
3.20
TL= 2
+ 3.20
TL - DC = LC