Professional Documents
Culture Documents
Assessing The Enviromental Performance of Stabilised Rammed Earth Walls Using A Climate Simulation Chamber
Assessing The Enviromental Performance of Stabilised Rammed Earth Walls Using A Climate Simulation Chamber
Abstract
The SHU climatic simulation chamber is a novel piece of apparatus that allows testing of full-sized walls with realistic inner and outer
wall climatic conditions. Four SRE test walls were successfully constructed and tested over four separate regimes to measure physical
properties such as pressure-driven moisture ingress, rate of moisture penetration, and internal/interstitial condensation. The walls far
exceeded a series of cyclic pressure-driven rainfall penetration tests based on BS 4315-2. After 5 days of exposure to static pressure-driven
moisture ingress there was no evidence of moisture penetration or erosion. The embedded sensor array detected no significant increase in
the relative humidity or liquid moisture content inside the test walls, throughout a range of temperature differentials with high levels of
humidity, indicating a negligible risk of internal or interstitial condensation.
r 2005 Elsevier Ltd. All rights reserved.
0360-1323/$ - see front matter r 2005 Elsevier Ltd. All rights reserved.
doi:10.1016/j.buildenv.2005.08.017
ARTICLE IN PRESS
140 M.R. Hall / Building and Environment 42 (2007) 139–145
dry mass of the trapped particles would be indicative of the drop nozzles produced a 1201 flat, fan-shaped spray
level of erosion that occurred due to rainfall. pattern. This gave an efficient distribution of water and
The test run lasted for a total of 5 days followed by a 4 subsequent run-off across the full width of the test wall
week drying period. To start the test, the protective plastic face. The spray nozzles were supplied by a high-pressure
sheets (used during the calibration phase) were removed, potable water supply delivered via a large header tank at a
and the climate side of the chamber was pressurised to pressure of 9 bar (130 PSI). The in-line gate valves
250 N/m2. This is the figure recommended by BS 4315-2: remained connected to act as an emergency shut off valve
1970; it is a static equivalent to strong wind pressure and operated from inside the climate side of the chamber. The
has the effect of exacerbating moisture penetration. The in-line needle valves were removed, however, and a single
rainfall and pressure differential was constantly maintained needle valve was used to regulate the mains water supply
for a cycle of 6 h, after which the pressure and rain are that fed a common rail connecting all four spray nozzles.
turned off for an 18 h drying cycle. This first test cycle The design for this high-pressure rainfall delivery system is
represents day 1, where the entire test programme runs for illustrated in the diagram shown in Fig. 7.
a total of 5 days. The 5-day test methodology was identical to that
The water run-off was collected at the following intervals described in test run 1. It was observed that a flow rate
after the start of each 6 h pressurised rainfall cycle: 10 min, of 0.65 L/min was the minimum rate at which a very good
20, 30, 40, 50, 60, 90, 120, 150, 180, 210, 240, 270, 300, 330, spray pattern could be achieved using this apparatus. The
and 360. That is to say, the readings are taken every 10 min average variation in the delivery rate was 70.04 L/min
for the first hour and then every 30 min for the remaining per wall. During the 6 h daily rainfall period the water run-
5 h. Since the rate of flow is known, the mass of run-off off from each test wall was collected and measured at
water collected over a 1 min period could be calculated as regular intervals.
an effective rate of absorption in ml/m2 min for each of the The water run-off collection data from each of the 5 days
four test walls. Theoretically, the initially dry test wall(s) was plotted against elapsed time on a graph. Even though
should absorb a relatively large amount of water during the the level of variation in water delivery had been much
first hour of exposure, with decreasing amounts of water improved over that of test Run 1, its effects still appeared
absorption as the remainder of the test period proceeds. It to have a significant influence. As one would expect, the
was anticipated that factors such as the total amounts of recorded mass of collected water run-off for each of the test
water absorption, rate of penetration, and the rate of walls was smaller during the early stages of the test and
decreasing absorption over time would be significantly then began to increase back towards the original delivery
affected by the soil type in each of the different rammed rate. To look at this data in isolation, however, would be
earth test walls. misleading since the delivery rates between test walls can
All four test walls ‘passed’ the test with distinction actually vary by up to 70.04 L/min. For each test wall, one
because no signs of water penetration or leakage occurred can calculate the mean absorption rate by deducting the
during the entire 5-day test run. In comparison, a similar collected amount of water run-off, at each time interval,
study was recently performed in the climate chamber on a from the set delivery rate. The mean absorption in each
series of 300 mm thick granite block walls with hydraulic SRE test wall was very low and typically less than 80 ml/
lime mortar, some with the additional application of dense min per wall. Since the typical dry mass for one of these
lime render. Most of the stone test walls began to leak 300 mm thick test walls is 280 kg, the calculated mean
during the first 6 h of exposure to these conditions, and water absorption only represents around 0.01%. It
even those protected by render began to permit water appeared that only a thin outer layer of each wall became
penetration to occur after only a couple of days. On the saturated and in doing so preventing subsequent moisture
SRE test walls, the calculated absorption rates appeared to ingress, i.e. the ‘overcoat’ effect (Fig. 8).
be masked by small, intermittent fluctuations in the rate of
water delivery. As a direct result of these issues, the
calculated data for water absorption in the test walls is
intangible. It was concluded that this particular methodol-
ogy of water delivery was perhaps only suitable for a
qualitative analysis of the time taken for full penetration/
leakage to occur, as specified in BS 4315-2, rather than
attempt to measure the rate of water absorption over time.
Fig. 11. A comparison between the ISA values for SRE test cubes and the
SRE test wall using the 703 mix design.
After the first and second test runs had been completed,
an array of electronic sensors was retrofitted to each of the
four rammed earth test walls. Three different types of
sensors were installed such that the properties of tempera-
ture, relative humidity (RH), and liquid moisture content
could be monitored throughout subsequent test regimes. Fig. 12. A typical temperature depth profile analysis of an SRE test wall
The sensors were embedded by drilling a small hole from during a cyclic pressure-driven rainfall/drying regime.
the inside of the wall to the required depth and then
carefully inserting the sensor using a metal rod marked at
different depths. Once in place the sensor hole was capped Fig. 12, the cooling effects of the rainwater run-off were
and sealed using silicone caulking. In each wall, six type-T cumulative resulting in a gradual reduction in wall core
copper/constantan thermocouples (protected by hollow temperature over the 5-day period. The implications are
plastic tubing) were installed to depths of 25, 50, 75, 100, that potential may arise for interior surface condensation
125, and 150 mm. In addition, armoured thermocouples or the accumulation of interstitial condensation within an
were mounted onto both the internal and external wall SRE wall. This would strongly depend upon the vapour
faces. A single Rotronic RH sensor (encased in a protective permeability of the material, the determination of which
PTFE membrane) was embedded to a depth of 150 mm, would require further research at this stage.
whilst six gold-plated resistance probes (for moisture
content) were embedded to the same depths as the 7. Test run 4: static climate differentials
thermocouples. The sensors were energised, where appro-
priate, using a 5 V DC stabilised supply and logged The effect of temperature differential has been explored
readings every 10 min for the entire 5-day period of test further by creating various fixed temperature and humidity
run 3. gradients across the test walls. This was achieved by
The same methodology for pressure-driven rainfall that maintaining a difference in temperature/humidity between
was used in run 2 was also applied in run 3 using high- the design side and the climate side of the chamber for a
velocity spray nozzles. The target rainfall delivery rate 24 h period. All of this testing was performed in the absence
remained at 0.65 L/min per wall and the applied static of any rainfall or pressure differential. The indoor (design
pressure differential had a force equivalent to 250 N/m2. side) conditions were maintained at 20 1C71 1 and 40%
No changes in liquid moisture content or relative humidity RH 75% to represent a comfortable indoor living
were detected between the depths of 150 and 300 mm environment. The outdoor conditions (climate side) were
(inside face) from the exposed external face. From this we kept at a constantly high level of relative humidity: 75%
may deduce that, under these conditions, the test walls did 75%. This represents a damp outdoor environment that is
not appear to allow the pressure-driven moisture to typical of the inclement British weather.
penetrate as far as 150 mm into the wall. The relative Test run 4 was performed in order to provide additional
humidity recorded at the centre point of each test wall data on the interesting effect of temperature depth profile
typically remained constant with the values observed prior analysis. The test run lasted for a total period of 4 days and
to testing, and ranged between 93% and 94%. included three different outdoor temperature levels.
The observed cooling effect of the surface run-off water On days 1 and 2 the ‘outdoor’ conditions were continu-
(approx. 15 1C) upon the wall surface was significant, and it ously maintained at 8 1C 75% RH, on day 3 they were
affected the wall temperature all the way to the interior maintained at 0 1C 75% RH, and on day 4 they were
surface. The thermal behaviour for each of the test walls maintained at 8 1C 75% RH, during which time snowfall
was observed to be very similar with no significant began to occur. During all 4 days of test run 4 the sensor
differences occurring between soil mix recipes. The initial array was used for recording the performance of the test
temperature of both the internal and external wall faces walls.
was approximately 22 1C, and the temperature of the The temperature depth profiles appeared to be remark-
exposed faces were lowered by the cooling effect of the ably similar to one another and independent of soil type.
water to around 18 1C. The core temperature of each test The typical thermal performance of a test wall can be
wall gradually dropped by up to 1.5 1 (approx. 20.5 1C) represented by the example shown in Fig. 13. No
below the interior wall face temperature during the 6 h significant changes were observed in the relative humidity
period of exposure to rainfall. We can observe from or moisture content resistance probes during run 4. This
ARTICLE IN PRESS
M.R. Hall / Building and Environment 42 (2007) 139–145 145
Acknowledgements
Fig. 13. A typical temperature depth profile analysis of an SRE test wall The author wishes to acknowledge the advice and
during different static temperature and humidity gradients. assistance of laboratory technician Stephen Hetherington
(Sheffield Hallam University) for the experimental work
detailed in this paper.
suggests that no interstitial condensation could be gener-
ated within the confines of this test regime. References