CSI-91

Non-Combustibility Apparatus
CSI-91 Brochure (Rev 1.1)

Introduction

The CSI-91 is used for determining whether or


not a material will contribute directly to fire
development and is relevant to classification of
all building products (including floorings) or
marine construction material within the
parameters of the test

The CSI-91 provides a means in determining the


non-combustibility performance, under
specified conditions, of homogeneous products
and substantial components of non- Furnace Assembly
homogeneous products.
The Furnace Assembly includes an electrically
The CSI-91 test system includes the Furnace heated ceramic chamber with a insulated safety
Assembly with all features required for heating cover. The single zone furnace has a maximum
of the furnace. This single zone furnace has a operating temperature of 750°C. It has been
maximum operating temperature of 750°C. All designed to be removable for convenience
accessories for sample handling and support of during maintenance and servicing. The furnace
temperature measuring sensors are standard and air flow stabilizer are held in a frame made
features in the CSI-91. This instrument features of stainless steel that acts as a draft shield.
a precision power controller, which controls the
furnace temperature at 750°C, compensating
The specimen holder assembly is supplied
for supply voltage fluctuations and displaying
thermocouple(s) to comply with the required
the Power (watts), voltage (volts) and current
(amps) being supplied to the furnace in real test standards as a standard feature. A viewing
time. mirror is also supplied as standard accessories.
All thermocouples have a disconnect plug for
A computer package with test software and quick and easy maintenance and servicing.
data acquisition hardware is pre-installed,
configured and ready for use. The Test software ✓ Insulated, Alumina Refractory Tube, 75 ID x
is capable of recording all pertinent data and 150 L mm,
observations made by the user during the test ✓ Calibrated furnace thermocouple
process. The data collected is saved and may be ✓ Max Temperature of up to 750 ± 5°C
retrieved and printed in a standard test report ✓ NIST Furnace temperature profile certificate
that meets the below mentioned methods. ✓ Metal Furnace Housing with x2 Stainless
steel guided support brackets and rods
Test Standard ✓ Insulated Safety Cover
✓ Air Flow Stabilizer
✓ ISO 1182 ✓ Draft/Drought Shield
✓ ASTM E136 Method B ✓ Insertion Device (piston type) to assist the
✓ ASTM E2652 operator in lowering and raising the sample
✓ BS 476 Part 4 holder from the furnace with minimal
✓ AS 1530.1 effort.
✓ IMO/FTP Code Part 1
✓ Mirror for safe observation of the sample
during testing

Disclaimer: Product improvement is a continuing goal at CSI. Designs and revisions are subject to change without notice or obligation.
CSI-91 Brochure (Rev 1.1)

✓ Stainless Steel Sample Holder Assembly Computerized Data Acquisition (DAQ) System
with calibrated thermocouples per
specification for Surface and/or Center The CSI-91 Data Acquisition System is offered as
temperature measurements a standard feature. This includes the laptop,
✓ Stainless Steel Base Frame for stable data acquisition hardware and Windows 10 CSI
positioning of furnace software license. It allows the user to perform
✓ Conformance Certificate accurate and repeatable test results,
✓ Operator’s Manual and Software Manual calibration, generate test reports, and much
more.
Operator’s Control Console
The DAQ systems includes all the required data
Dedicated Control Console includes all the acquisition hardware and pre-installed and
controls required to operate the CSI-91. 1.5 kVa configured test software on a CSI supplied
power transformer, programmable Eurotherm laptop.
power controller, cooling fan and switches are
included. The 3 main functions of the software:
The power controller has a range of 0 to 600W
and safety power maximum limit to prevent ✓ Calibration
over temperature. The power controller acts as this function allows the user to set the
a voltage stabilizer and compensates for any parameters for the furnace temperature
supply voltage fluctuations and displays the stabilization and measures the furnace
power, voltage and current being supplied to thermocouple for the stabilization period.
the furnace assembly in real time. This ensures
a constant and reliable test results. ✓ Sample Testing
There is a power adjustment knob that goes This function provides all of the data storage and
from 0 – 100% (0 to 600W) to control the power acquisition, stabilization and test period timing,
output to the furnace. The furnace temperature and other associated tasks for the testing of
is displayed in the test software. materials, The operator inputs the data file
name, sample, pretest comments, and other
pertinent data. After insertion of the sample into
the furnace the user is informed of the
stabilization time, acquisition of the baseline
thermopile reading, insertion of the test sample
and progression through testing period. At the
end of the test run, the user may select to run
another test and use or modify the previous test.

Disclaimer: Product improvement is a continuing goal at CSI. Designs and revisions are subject to change without notice or obligation.
CSI-91 Brochure (Rev 1.1)

Computerized Data Acquisition (DAQ) System

✓ Test Reporting of Data


The test software main menu for test reports
allows the operator to view, print, save raw data
and edit test information Test Results are
available in formats such as:
o Graphical
Allows you to visually observe the graph
produced by the sample during the test
for individual samples or all runs.
o Run Report
Displays the data acquired during the
test of the particular specimen along
with the test information, pre-test, and
after-test comments.
o Test Report
Displays test results for all specimens
tested along with the test information
and pre-test comments.
o Edit
This feature permits the user to modify
text entered during a particular test
session.

Dimensions and Weights

Approx. Physical Weight: 120 lbs (furnace assembly only)


Approx. Physical Dimensions: 17” x 17” x 65H” (furnance assembly only)
Approx. Physical Weight: 65 lbs. (control cabinet only)
Approx. Physical Dimensions: 20” x 17” x 20H” (control cabinet only)
Approx. Shipping Weight: 500 lbs (Complete System)
Approx. Shipping Dimensions: 72” X 30” X 53”H” (Complete System)

Installation Requirements

Electrical Specification: 220 VAC, 50/60 Hz, 1 Ph 10A


Exhaust Blower/Ventilation: To provide ventilation for removal of the heated gases, by-
products and combustion.

Disclaimer: Product improvement is a continuing goal at CSI. Designs and revisions are subject to change without notice or obligation.
� .::.J lnsrru111Pnrs� Inc.
,..�,®Cu5IOl115CiPnliTic

Telephone: l ( 610) 923-6500


Fax: l ( 610) 923-6543
Email: so les@)csi-instruments.com
Website: www.csi-instruments.com
Address: 1125 Conroy Place, Forks Industrial Park IV,
Easton, PA 18040-6656 U.S.A.

Follow Us: 0000 8

With customers worldwide and a strong network of partners and representatives, CSI is one of the premier manufacturers of high technology material
test instrumentation.
CSI has been supplying test instruments and laboratory apparatus to industries, laboratories, government agencies, and universities in this country and
abroad. The knowledge and expertise we have acquired from years of test instrument design, manufacture, and experience in the testing field is
available to serve our valued clients.
Rev 1.0/2019 / CSI and the CSI logo are registered trademarks of Custom Scientific Instruments, Inc. / Due to the CSl's continuous development policy;
technical changes could be made without prior notice.

You might also like