The LFL1.148 and this Data Sheet are intended for use by OEMs which integrate
the burner controls in their products!
Use
Flame supervision is ensured by means of an ionization probe, 1 electrode is used for the
first stage and 1 for the second stage. Changeover takes place automatically after
release of the second fuel valve.
CC1N7454en
Building Technologies Division
20.11.2017
Supplementary documentation
Warning notes
All activities (mounting, installation and service work, etc.) must be performed by
qualified staff
For safety reasons – self-test of the flame supervision circuit, etc. – at least
one controlled shutdown must take place every 24 hours
Before performing any wiring changes in the connection area of the LFL1.148,
completely isolate the unit from the mains supply (all-polar disconnection)
Ensure protection against electric shock hazard by providing adequate protection for
the burner control’s connection terminals
Each time work has been carried out (mounting, installation, service work, etc.),
check to ensure that wiring is in an orderly state and make the safety checks as
described in Commissioning notes
Press the lockout reset button only manually (do not apply a force of more than 10 N)
without using any tools or pointed objects
Do not press the lockout reset button on the unit or the remote lockout reset button
for more than 10 seconds since this would damage the lockout relay inside the unit
Fall or shock can adversely affect the safety functions. Such units must not be put
into operation, even if they do not exhibit any damage
Mounting notes
Ensure that the relevant national safety regulations are complied with
Connect the earthing lug inside the terminal base to burner ground using a screw
with a lockwasher or similar
Installation notes
Always run the high-voltage ignition cables separately while observing the greatest
possible distance to the unit and to other cables
Do not mix up live and neutral conductors
2/11
Compliance with the regulations of the applied directives is verified by the adherence to
the following standards / regulations:
Automatic burner control systems for burners and DIN EN 298
appliances burning gaseous or liquid fuels
Safety and control devices for gas burners and gas burning DIN EN 13611
appliances
Automatic electrical controls for household and similar use DIN EN 60730-2-5
Part 2-5: Particular requirements for automatic electrical
burner control systems
The relevant valid edition of the standards can be found in the declaration of
conformity!
ISO 9001:2008
ISO 14001:2004
OHSAS 18001:2007
China RoHS
Hazardous substances table:
http://www.siemens.com/download?A6V10883536
3/11
The designed lifetime is based on use of the burner controls according to the
manufacturer’s Data Sheet. After reaching the designed lifetime in terms of the number of
burner startup cycles, or the respective time of usage, the burner control is to be replaced
by authorized personnel.
* The designed lifetime is not the warranty time specified in the Terms of Delivery
Disposal notes
The unit contains electrical and electronic components and must not be disposed of
together with domestic waste.
Local and currently valid legislation must be observed.
Mechanical design
The mechanical design of the LFL1.148 corresponds to that of the standard units of the
LFL range (refer to Data Sheet N7451).
4/11
Connection accessories Plug-in base AGM410490550 with Pg11 threads for cable
for medium-capacity entry glands.
burner controls Article no.: BPZ:AGM410490550
Refer to Data Sheet N7230
5/11
For technical data – with the exception of the data listed below and the switching times of
the switching mechanism – refer to Data Sheet N7451.
Warning!
Condensation, formation of ice and ingress of water are not permitted!
If not observed, there is a risk of impairment of safety functions and of
electric shock hazard.
6/11
The pilot flame is supervised by ionization probe (ION1), the main flame by ionization
probe (ION2).
Warning!
On completion of the ignition safety time (TSA), a flame signal must be present
at terminal 23 (ION1). On completion of the second safety time (t9), a flame
signal must also be present at terminal 24 (ION2).
7/11
◄ No start
For example: Start control loop interrupted via actuator (SA)
▼ Abortion of startup sequence because the auxiliary switch in actuator (SA) has
cut the start control loop
▌ Lockout because the flame signal was lost during burner operation
After the reset, the burner control’s switching mechanism first returns to the start position
and then initiates a burner restart.
Connection diagram
LFL1.148 (7)
1 2 3 21 4 12 5 14 6 8 16 18 19 11 15 22 23 24
SB
EK2 W
H
AL R
ION1
GP Z BV1 BV2
Si M1
L ION2
N 7454a04/0204
Connection examples
5 4 12 15 20 11 6 8 2-stage forced draft gas burner without
W
load controller (LR) and without actuator
LP (SA)
R
7454a02/1195
R 7454a03/1195
8/11
SB
1
AS
br1
a b
ar1 I XV ar2
ab a b
ION2
4 12 6 7
22 23 24
W
d1
d2 ION1
x d1 d2
LP
y 22 23 24
R M1 M2 X
N
5 13 14 V
FR
fr1 fr3 fr2
a b b a
XI XIII (1) (1)
XII NTC
b a a b
a b
AR
XIV IV
VII
ar3
a b
br2 V
EK1 VI
L1 II III VIII
E M SM a b
b a a b M
BR ~ IX
A
3 21 2 16 9 10 18 19 15 20 11 8
L Q 6
1 B1
LR
N M 7454a01/0204
1
Y1 Y2
AL Z BV1 BV2
SA
EK2 a z m
M LK
H
N x y
Warning!
Do not press reset bottom (EK) for more than 10 seconds!
Control program
A B C D
SB/
R/W 1
t1 t6
M1 6
7
t7 t3 t20
Z 16
TSA t9
BV1 18
BV2 19
t4 t5
FS1 23
FS2 24
t8 7454d02/0204
9/11
I a 12
b t7 t4 t5 7
II a 19
b 16
III a 9 10
IV b
V a
t8
VI a 20
b t20 11
a
VII b 8
VIII a 18
b
IX a 15
t9
X a 23 24
TSA
XI a
b t10
XII a
b
XIII a
b
XIV a
b
XV a 12
b 7
7454d01/0204
Legend
10/11
LFL1.148
1,5
108,5
123
Plug-in base AGM410490550 /
AGM14.1 7454m04/0305
27,5 27,5
37
7,5
103
2017 Siemens AG Building Technologies Division, Berliner Ring 23, D-76437 Rastatt
Subject to change! 11/11